Arif Dyno Trinandatama, Sandy Adyatma. 2018. “Analysis of Loading dan
Maintenance GTT In PT. PLN (Persero) Rayon Sumberpucung Area Malang”. Final Report. Electrical Engineering Program Faculty of Electro Engineering State Polytechnic of Malang. Lecturer: Drs. Awan Setiawan M.MT., MM, Imron Ridzki, ST., MT. Transformer is one of the most important thing in the electrical energy distribution, and because of that transformer management is a must for preventing an operation failure, according to the number of the GTT imposition in Rayon Sumberpucung there are 5 GTT with over 80% loading. And for preventing the operational failure on the transformer, we have to consider the results of the maintenance, tool's suitability, thermovision results, analysis of unbalance load and its loads progression. After doing analysis of maintenance result on transformer L0460 found the amount of insulation resistance under the recommended amount, the amount of their primary-secondary is 50 MΩ, Primary-body 45 MΩ, and secondary-body 20 MΩ. while from the thermovision result on GTT L0460 and GTT L0098 the temperature of the connection is over 50°C. if reviewed from the loading, the loading on all GTT is allowed based on the calculation of long peak load that are allowed, but for the load progression on all GTT is over the standard. Therefore the management step that can be done are transformer mutation, uprating transformer, or adding more additional transformer. Keywords:Loading, maintenance, transformer, transformer management