Building School Specifications:

Concrete:
Using ACI Code
 40mm cover on all sides for the shear reinforcement or 50mm cover for the main
reinforcement
 The yield strength of steel to be used is 414MPa and concrete with 35MPa.
 Using 25mmØ reinforcing bar for main reinforcement and 10mmØ reinforcement
for shear and torsional reinforcement.
Loadings and Analysis
Seismic Load:
 Zone = 0.4
 Rw in both directions = 8.5
 Soil Profile Type = 3
 Near Source Factor (Na = 1.2) (Nv = 1.6)
Wind Load:
 Using ASCE 2002
 Building Category I with an Exposure Category C with Basic Wind Speed of
290kmph and no escarpment is present
Live Load:
 NSCP 2015
 Computer Laboratory= 4.8kPa
 Faculty Offices = 2.4kPa
 Hallways = 3.8kPa
Dead Load:
 NSCP 2015
 Exterior Walls = 200mm thickness and full grout with 16.5kN/cu.m density
 Interior Walls= 100mm thickness and full grout with 16.5kN/cu.m density
 Floors have waterproofing membranes of bituminous gravel-covered
 Floor Finishing of ceramic or quarry tile of 20mm on 13mm mortar bed
 Rigid Insulation for the Classrooms
 Acoustic Fiber Board with Mechanical Duct Allowance
Stair Load:
 Treated as a Hallway with half-weight in kilonewton for the upper beam and lower
beam handling the stairs with 200mm thickness and 300mm thread with 100mm
height.
Beam Deflection:
 Deflection of beams is limited to 25mm
Load Cases:
 USD for the concrete design and ASD for deflect analysis

Building School Specifications:


Concrete:
Using ACI Code
 40mm cover on all sides for the shear reinforcement or 50mm cover for the main
reinforcement
 The yield strength of steel to be used is 414MPa and concrete with 35MPa.
 Using 25mmØ reinforcing bar for main reinforcement and 10mmØ reinforcement
for shear and torsional reinforcement.
Loadings and Analysis
Seismic Load:
 Zone = 0.4
 Rw in both directions = 8.5
 Soil Profile Type = 3
 Near Source Factor (Na = 1.2) (Nv = 1.6)
Wind Load:
 Using ASCE 2002
 Building Category I with an Exposure Category C with Basic Wind Speed of
290kmph and no escarpment is present
Live Load:
 NSCP 2015
 Computer Laboratory= 4.8kPa
 Faculty Offices = 2.4kPa
 Hallways = 3.8kPa
Dead Load:
 NSCP 2015
 Exterior Walls = 200mm thickness and full grout with 16.5kN/cu.m density
 Interior Walls= 100mm thickness and full grout with 16.5kN/cu.m density
 Floors have waterproofing membranes of bituminous gravel-covered
 Floor Finishing of ceramic or quarry tile of 20mm on 13mm mortar bed
 Rigid Insulation for the Classrooms
 Acoustic Fiber Board with Mechanical Duct Allowance
Stair Load:
 Treated as a Hallway with half-weight in kilonewton for the upper beam and lower
beam handling the stairs with 200mm thickness and 300mm thread with 100mm
height.
Beam Deflection:
 Deflection of beams is limited to 25mm
Load Cases:
 USD for the concrete design and ASD for deflect analysis

Building School Specifications:

Concrete:
Using ACI Code
• 40mm cover on all sides for the shear reinforcement or 50mm cover for the main
reinforcement
• The yield strength of steel to be used is 414MPa and concrete with 35MPa.
• Using 25mmØ reinforcing bar for main reinforcement and 10mmØ reinforcement
for shear and torsional reinforcement.
Loadings and Analysis
Seismic Load:
• Zone = 0.4
• Rw in both directions = 8.5
• Soil Profile Type = 3
• Near Source Factor (Na = 1.2) (Nv = 1.6)
Wind Load:
• Using ASCE 2002
• Building Category I with an Exposure Category C with Basic Wind Speed of
290kmph and no escarpment is present
Live Load:
• NSCP 2015
• Computer Laboratory= 4.8kPa
• Faculty Offices = 2.4kPa
• Hallways = 3.8kPa
Dead Load:
• NSCP 2015
• Exterior Walls = 200mm thickness and full grout with 16.5kN/cu.m density
• Interior Walls= 100mm thickness and full grout with 16.5kN/cu.m density
• Floors have waterproofing membranes of bituminous gravel-covered
• Floor Finishing of ceramic or quarry tile of 20mm on 13mm mortar bed
• Rigid Insulation for the Classrooms
• Acoustic Fiber Board with Mechanical Duct Allowance
Stair Load:
• Treated as a Hallway with half-weight in kilonewton for the upper beam and lower
beam handling the stairs with 200mm thickness and 300mm thread with 100mm height.
Beam Deflection:
• Deflection of beams is limited to 25mm
Load Cases:
• USD for the concrete design and ASD for deflect analysis