Anda di halaman 1dari 7

DCS Items required for NODE Extension in existing system cabinet as node 2 , consisting of following items

System Item List


Domain /
SL No. Comp No. / Location Station Desciption Model No.
No.
11 UNIT FCS 0203
1 110 / R1 02 / 03 Node Interface unit ANB10D-410 CU2N
2 110 / R1 02 / 03 Power supply unit for Node PW 481
3 110 / R1 02 / 03 Node bus Interface Module SB401
4 110 / R1 02 / 03 ESB Bus Interface Module EC401-10
5 110 / R1 02 / 03 ESB Bus Cable YCB301-C100
6 110 / R1 02 / 03 8+8 Channel Analog Input/Output Module ( REDUNDANT ) AAB841
7 110 / R1 02 / 03 16 Channel Analog Input Module AAV141
8 204 02 / 03 Marshling cabinet -1200(W)*800(D)*2120(H) WMC12-FERRC
21 UNIT FCS 0204
1 115 / R1 02 / 04 Node Interface unit ANB10D-410 CU2N
2 115 / R1 02 / 04 Power supply unit for Node PW 481
3 115 / R1 02 / 04 Node bus Interface Module SB401
4 115 / R1 02 / 04 ESB Bus Interface Module EC401-10
5 115 / R1 02 / 04 ESB Bus Cable YCB301-C100
6 115 / R1 02 / 04 8+8 Channel Analog Input/Output Module ( REDUNDANT ) AAB841
7 115 / R1 02 / 04 16 Channel Analog Input Module AAV141
8 214 02 / 04 Marshling cabinet -1200(W)*800(D)*2120(H) WMC12-FERRC
Accesories
1 Cable for Analog Input/output card ( AAB841 ) KS1 10*A
2 Cable for Analog Input card ( AAV141 ) KS1 10*A
3 Cable for Digital Input card ( ADV151 ) AKB 331 10*A

Note : These two Nodes will be Installed in the existing system cabinet as second node in FCS 0203 & 0204 respectively
Qty Remarks

1
2
2
2
2
4 2 + 2R
2
As per attached
1 annexure

1
2
2
2
2
4 2 + 2R
2
As per attached
1 annexure

4
4
QTY
Sl.No. ABBREVIATION ITEM DESCRIPTION MAKE/MODEL
FRONT SECTION
01 PT POWER TERMINATORS ( Power TB's) PHOENIX 04
02 MM MINIATURE CIRCUIT BREAKER MERLIN CERIN 02
03 PSU1 & 2 POWER SUPPLY UNIT( 27A, 24V) COSEL 02
04 DRI 1 & 2 DIODE O— RINC M ODULE(SOAMPS) PARAMOUNT 02
05 FM1~2 MINIATURE CIRCUIT BREAKER MERLIN GERIN 02
06 BB1 BUS BAR YIL STD 02
07 FT1 MOTHER BOARD FOR AI/AO SIGNALS MB-AIO16V-KS1 02
08 FT2~3 MOTHER BOARD FOR AI SIGNALS MB-AI16V-KS1 02
09 AT1 ALARM TERMINALS PHOENIX/MTK— P/P 04
10 FFTB1 FUSE TERMINAL BLOKS PHOENIX 24
11 FZ1~4 DISCONNECTING TB'S PHOENIX 200
12 Ec CABINET EARTH 01
13 DSF DOOR SWITCH FRONT 01
14 TLF TUBE LIGHT FRONT PHILIPS 01
15 FAN 1 & 2 COOLING FANS FRONT 02
16 FILTER 1 & 2 AIR FILTER FRONT RITTAL 02
17 Esh SHIELD EARTH YIL STD 02
REAR SECTION
01 BB2 BUS BAR 02
02 FFTB1 FUSE TERMINAL BLOKS PHOENIX 24
03 FT1 TERMINAL BOARD FOR DIGITAL I/P SIGNALS YAED5D 01
04 FR1~32 RELAYS 24v DC , 2 NO & 2 NC IDEC 32
05 TR01~10 TRANSDUSER ( 0-1AMP TO 4-20mA ) ABB 12
06 FFTB2 FUSE TERMINAL BLOKS PHOENIX 100
07 Ec CABINET EARTH STD 01
08 DSR DOOR SWITCH REAR YIL STD 01
09 TLR TUBE LIGHT REAR PHILIPS 01
10 FAN2 COOLING FANS REAR SUNON 02
11 YMRPTB *A POWER TERMIN AL FOR U TILITY SUPPLY 01
12 RCPT RECEPTACLE(240 VAC UPS) ROMA 01
13 PTI &1— PTI POWER TERMIN ATORS(POWER TB's] PHOENIX 08
14 MMI MINIATURE CIRCUIT BREAKER MERLIN GERIN 01
15 FILTER2 AIR FILTER REAR RITTAL 01
16 Esh SHILLD LARTH 01
Note : -1. All the Make/Model of the items described here should be of as described / or better / or as per existing YIL standards
2. Two marshelling cabinet of same specifications are required. Cabinate No. And description of the cabinet are as below...
a. 204F - # Analog Input Cabinet FCS 0203 ( 11 Unit )
204R - # Digital Input Cabinet FCS 0201 ( 11 Unit )
b. 214F - # Ana;og Input Cabinet FCS 0204 ( 21 Unit )
214R - # Digital Input Cabinet FCS 0202 ( 21 Unit )
REMARKS

6A

30A
32A

24V DC WITH LED

16A
24V DC WITH LED

220V DC WITH LED


r existing YIL standards
he cabinet are as below...
PANEL DETAILS

Sl.No. Panel description Standard


1 MAKE RITTAL STANDARDS ( 1200 * 800 * 2120 mm)
2 CONSTRUCTION BENT & BOLTED/WELDED
3 FRAME SHEETSTEEL MATERIAL
4 BASE FRAME 100*50*3.2 mm PLINTH CHANNEL
SPLIT DOORS - 2 mm TH. CRCA SHEET (RITTAL)
SIDE PANEL - 1.6mm TH. CRCA SHEET (RITTAL)
5 SHEET THICKNESS
TOP PANEL - 1.6mm TH. CRCA SHEET (RITTAL)
GLAND PLATES - 3mm TH. CRCA SHEET (RITTAL)
FRAME , FRONT & REAR DOORS , SIDE PANELS - HAVEL'S GREY -
6 COLOUR RAL(7035)
CHANNEL BASE - BLACK
7 CABLE ENTRY BOTTOM
8 GASKET POLYURATHENE GASKETTING
9 REMOVABLE GLAND PLATE 04 NOS
10 SIDE PANELS yes
11 STANDARD HANDLE SYSTEM WITH KEY & LOCK INSERT
12 HYLAM SHEET 5mm
13 PROTECTION GLASS IP54
14 PAINT THICKNESS 65 - 120 MICRONS
15 CRCA COLD ROLLED CLOSE ANNEALED