PROTECTION PRODUCT SOLUTIONS

MICOM ALSTOM P40

PROGRAMMABLE SCHEME LOGIC or alternatively an optional IRIG-B port Disturbance records


Powerful logic available in the 40 series is available for accurate time The internal disturbance recorder will
relays allows the user to customise the synchronisation on all P40 relays. record the sampled values of all
protection and control functions of the Relays can also use an opto input to analogue input variables such as phase
relay. It is also used to program the synchronise the internal clock. currents and voltages where applicable
functionality of the opto-isolated inputs, during a fault. Oscillographic analysis
relay outputs, LED and user alarms. Event records can be performed using the S1 Agile PC
These are generated for status changes tool which will provide the means to
The programmable scheme logic can be to logic inputs and outputs, quickly analyse analogue and digital
used to implement additional supervision modifications to one or more setting signals on the same time scale for
features, such as trip circuit supervision parameters and alarm signals. convenience. (Figure 2 on next page)
or implement complex logic such as All events are time-tagged and stored in Disturbance records can be extracted
frequency restoration schemes. Schemes chronological order in cyclic memory. from the relay via the communication
have been developed capable of These are readily available for viewing ports and saved in the COMTRADE
supervising the trip coil and circuit with on the LCD, or by extraction via the format.
the circuit breaker open or closed. communication ports.

The Px40 gate logic includes OR, AND, Fault records RELAY COMMUNICATIONS
NOT and majority gate functions, with Up to 15 records are supported for As standard, a front communication
the ability to invert the inputs and every fault (5 on some models), with port is available for local access to the
outputs, and provide feedback. A the following information captured: relay. An auxiliary rear communication
number of general purpose logic timers A fault number port is available as an option on relays
are also available as well as those timers The date and time providing easy access to settings,
used to condition the relay contacts. The active setting group records and measurements for
The function that issued the trip protection engineers. A main rear
The system is optimised (event driven) The magnitude of the current/voltage communications port is also available
to ensure that the protection outputs are that gave rise to the trip command for interface to a SCADA system. A
not delayed by the PSL operation. The number of protocols are available as an
programmable scheme logic is Distance to fault calculation is provided option for this purpose, with different
configured using the graphical S1 Agile on most feeder and line protection media such as wired serial, fibre serial,
PC software, as shown in Figure 1. models. RJ45 Ethernet, and fibre Ethernet.

MEASUREMENTS, RECORDING
AND POST FAULT ANALYSIS
Measurement & post fault analysis
The relays are capable of measuring and
storing a wide range of system
quantities such as current, voltage,
frequency, power, distance to fault etc.
depending on the relay functionality.
These measured values can be displayed
on the front LCD display or transferred
locally or remotely per user
requirements.

All event, fault and disturbance records


are time tagged to a resolution of 1ms
using the internal real time clock and are
stored in non-volatile memory. Where
relays are communicating with a SCADA
system, the protocol's telegrams can be
used for external time synchronisation

Figure 1 Programmable logic for Px40