Configuration

10/28/2018 7:43 AM

2206-E13 (TGBF7011U12824X)
Parameter Value
Equipment ID ASIA POWER SYSTEM
Engine Serial Number TGBF7011U12824X
ECM Serial Number 24126123JL
Software Group Part Number 3125950-00
Software Group Release Date JUN08
Software Group Description 2206A TAG2 BSFC

Description Value TT
ECM Identification Parameters
Equipment ID ASIA POWER SYSTEM 0
Engine Serial Number TGBF7011U12824X 1
ECM Serial Number 24126123JL
Software Group Part Number 3125950-00
Software Group Release Date JUN08
Software Group Description 2206A TAG2 BSFC
Selected Engine Rating
Rating Number 1
Rated Frequency 50 Hz
Rated Genset Speed 1500 rpm
Rated Real Genset Power Unavailable Parameter
Rated Apparent Genset Power 400 kVA
Engine Rating Application Type Standby
External Speed Selection Switch Installed Enabled 0
Engine/Gear Parameters
Engine Acceleration Rate 500 rpm/s 0
Droop/Isochronous Switch Installed Disabled 3
Droop/Isochronous Selection Droop
Engine Speed Droop 4.0 % 2

file://C:\ProgramData\Perkins\Electronic Service Tool\temp\STPLReport1.HTM 10/28/2018


Page 2 of 2

Digital Speed Control Installed Installed 0


Speed Control Minimum Speed 125 rpm 0
Speed Control Maximum Speed 125 rpm 0
Digital Speed Control Ramp Rate 10 rpm/s 0
Crank Terminate RPM 400 rpm 0
I/O Configuration Parameters
Desired Speed Input Arrangement 0-5 VDC Input 0
Fuel Enable Input Configuration Switch to Battery + 0
Critical Override Switch Installed Not Installed 0
Emergency Shutdown Override Input Configuration Switch to Ground 0
System Settings
Governor Gain Factor #1 10000
Governor Minimum Stability Factor #1 1049
Governor Maximum Stability Factor #1 3189
Full Load Setting (FLS) -16 0
Full Torque Setting (FTS) 13 0
Passwords
Customer Password 1 ********
Customer Password 2 ********
Security Access Parameters
Total Tattletales 8

file://C:\ProgramData\Perkins\Electronic Service Tool\temp\STPLReport1.HTM 10/28/2018