NRGS 15-1 EN
English
1
Contents
Page
Important Notes
Explanatory Notes
Scope of supply.......................................................................................................................................5
Function..................................................................................................................................................5
Technical Data
NRGS 15-1 ......................................................................................................................................... 6, 7
Name plate / Marking..............................................................................................................................8
Dimensions..............................................................................................................................................9
Design
NRGS 15-1............................................................................................................................................10
Key........................................................................................................................................................12
Functional Elements
NRGS 15-1............................................................................................................................................11
Key........................................................................................................................................................12
Establishing Functions
Selecting function..................................................................................................................................13
Factory setting.......................................................................................................................................14
Cutting electrode tips to length..............................................................................................................14
Establishing functions............................................................................................................................14
Adjusting sensitivity range.....................................................................................................................15
Tools......................................................................................................................................................15
2
Contents - continued -
Page
Installation
Electrical Connection
Commissioning
Malfunctions / Troubleshooting
Fault finding list for troubleshooting.......................................................................................................23
Danger..................................................................................................................................................24
Exchanging the electronic insert............................................................................................................24
Removing and disposing of level switch.................................................................................................24
Note......................................................................................................................................................24
Annex
3
Important Notes
The level switch NRGS 15-1 is designed for detecting and signalling four different liquids levels and
works e.g. in steam boilers and (pressurised) hot-water installations as water level controller with
MIN and MAX alarm.
Safety note
The equipment must only be installed and commissioned by qualified and competent staff.
Retrofitting and maintenance work must only be performed by qualified staff who – through adequate
training – have achieved a recognised level of competence.
Danger
When loosening the level switch steam or hot water might escape. This presents the dan-
ger of severe scalds to the whole body.
It is essential not to mount or dismantle the level switch unless the boiler pressure is
verified to be zero!
The level switch becomes hot during operation. Touching the hot equipment presents the
risk of severe burns to hands and arms. All installation, removal and maintenance work
must only be performed when the system is cold.
The terminal strip of the level switch is live during operation. This presents the danger of
electric shock!
Cut off power supply before mounting, removing or connecting the terminal strips.
The equipment meets the requirements of the Low Voltage Directive 2006/95/EC and the
EMC Directive 2004/108/EC.
According to the European Directive 94/9/EC the equipment must not be used in potentially explosive
areas.
For details on the conformity of our equipment according to the European Directives see our Declaration
of Conformity or our Declaration of Manufacturer.
The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under
www.gestra.de/documents or can be requested from us.
4
Explanatory Notes
Scope of supply
NRGS 15-1
1 Level electrode with four tips
1 Terminal box with integrated level switch
1 Joint ring 33 x 39, form D, DIN 7603, made from 1.4301, bright annealed
1 Installation manual
or
NRGS 15-1
1 Level electrode with four tips
1 Terminal box with integrated level switch and built-in Test and Reset pushbutton
1 Joint ring 33 x 39, form D, DIN 7603, made from 1.4301, bright annealed
1 Installation manual
Function
The level switch NRGS 15-1 is a compact-type system consisting of a level electrode with four tips and
an integrated level switching controller. For the correct functioning of the equipment the water must
have a minimum electrical conductivity of > 0.5 μS/cm at 25 °C.
In the integrated level switch a time-delayed switching channel, an output relay and a signal LED are
assigned to each one of the four electrode tips.
The functions of the switching channels 1 and 4 are fixed, the switching channels 2 and 3 can be
adjusted via code switch to suit individual requirements. The tips of the electrode are cut to length on
site in order to establish the desired switchpoints of the associated switching channels.
The following functions are possible:
n Electrode rod 1 exposed / switching channel 1 energizes relay 1 =
low level 1 with optional performance test and lock-out function
n Electrode rod 2 exposed / switching channel 2 energizes relay 2 = low level 2
n Electrode rod 3 exposed or submerged / switching channel 3 energizes relay 3 =
timed pump control (fill/discharge control)
n Electrode rods 2 and 3 exposed or submerged / switching channel 3 energizes relay 3 =
on/off pump controll (fill/discharge control)
n Electrode rod 4 submerged / switching channel 4 energizes relay 4 = high level
5
Technical Data
NRGS 15-1
Service pressure
PN 25, 25 bar at 224 °C
End connection
Screwed G 1A, ISO 228-1
Materials
Screw-in body: 1.4571, CrNiMoTi17-12-2
Electrode rods: 1.4571, CrNiMoTi17-12-2
Electrode insulation: PTFE
Spacer disc: PTFE
Terminal box: Polycarbonate
Electrode rods
Length supplied: 1000 mm
Diameter: 5 mm
Mains supply
220 – 240 V +10/–15 %, 50/60 Hz
110 – 120 V +10/–15 %, 50/60 Hz (optional)
24 V +10/–15 %, 50/60 Hz (optional)
Power consumption
3 VA
Fuse
External 63 mA, slow-blow at 230 V,
External 125 mA, slow-blow at 115 V,
External 1 A, slow-blow at 24 V.
Response sensitivity (electrical conductivity of water at 25 °C)
> 0,5 ... < 1000 μS/cm or > 10 ... < 10000 μS/cm (switch selectable)
Electrode voltage
20 Vss
Output
Four volt-free relay contacts, 8 A 250 V AC / 30 V DC cos ϕ = 1 (IEC 61810)
Ensure interference suppression by providing contactor with an arc suppressor RC combination.
Energizing /de-energizing delay
Relay 1 and 2: 1s, factory set
Relay 3: 0-30s, adjustable via potentiometer
Relay 4: 3s, factory set
Indicators and adjustors
3 red LEDs to indicate “Low level alarm 1 + 2 / High level”.
1 yellow LED to indicate “Pump ON”.
1 green LED to indicate “Mains supply ON”.
1 ten-pole code switch to select the sensitivity range and to establish the functions.
1 test button in the terminal box to check the function of switching channel 1 (connected to terminals).
1 reset button in the terminal box to reset the lock-out function (connected to terminals).
6
Technical Data - continued -
7
Technical Data - continued -
Vor Öffnen des Deckels, Gerät Vor Öffnen des Deckels, Gerät
freischalten! Betriebsanleitung freischalten! Betriebsanleitung
beachten! beachten!
Safety note
Before removing cover, isolate from Before removing cover, isolate from
power supplies. See installation power supplies. See installation
instructions! instructions!
Avant d'ouvrir le couvercle Avant d'ouvrir le couvercle
dèconnecter complètement l'appareil. dèconnecter complètement l'appareil.
Voir instructions de montage. Voir instructions de montage.
Fig. 1
8
Technical Data - continued -
Dimensions
180
130
b = 60
≈ 355
∅ 42
A
4 3 Screwed G 1A, ISO 228
1000
Fig. 2
9
Design
NRGS 15-1
BB
40
CA E
1 2 3 4
∅ 40
RA 12.5
Screwed
0.5
RA 3.2
50
Fig. 3 Fig. 4
10
Functional Elements
NRGS 15-1
G F
Fig. 5
67 1234 5 H
8 I
O
9
M L K J
Fig. 6
11
Design / Functional Elements - continued -
Key
1 LED 1, red
2 LED 2, red
3 LED 3, yellow
4 LED 4, red
6 Code switch S1
A Sealing
B Thermal insulation
D Joint ring 33 x 39, form D, DIN 7603, made from 1.4301, bright annealed
E Seating surface
F Housing cover
L PE connection
12
Establishing Functions
Selecting function
Vor Einbau und Inbetriebnahme muss festgelegt werden, mit welchen Einstellungen der Niveauschalter
NRGS 15-1 betrieben werden soll.
Es stehen fünf Funktionen zur Verfügung:
Function 1 CodeONswitch S1
ON
1 2 3 4 5 6 7 8 910
Function 2
ON
Electrode rod 1 Low level 1 / burner off with test and reset button ON
1 2 3 4 5 6 7 8 910
Function 3
1 2 3 4 5 6 7 8 910
Function 4
Electrode rod 1 Low level alarm 1 / burner off with test and reset button
Electrode rod 2 Feed pump on (fill control) ON
ON
1 2 3 4 5 6 7 8 910
Function 5 1 2 3 4 5 6 7 8 910
13
Establishing Functions - continued -
Factory setting
The factory setting of level switch NRGS 15-1 without pushbuttons is function 1 and with pushbuttons
is function 2.
The preset time delay for pump control is 5 sec. and the preset sensitivity range is 10 µS/cm.
1. Determine the lengths of the electrode rods as a function of the level-dependent switchpoints
(measured from seating surface E) and enter the data in the table “Functions” (see below).
2. Then cut all electrode tips (see Fig. 3) to the required lengths by using a bolt cutter.
3. Deburr faces of electrode tip ends.
4. Remove approx. 50 mm of the PTFE insulation of the lower end of the electrode rod (see Fig. 3).
Make sure that there is an electrical resistance path of ≥ 14 mm between the electrode tips
5. Arrange PTFE spacer discs so that the cut electrode tips cannot come into contact with each other.
Wire/
Electrode rods Function Length [mm]
connector
1 1
2 2
3 3
4 4
Establishing functions
14
Establishing Functions - continued -
ON
Sensitivity ≥ 10 μS/cm at 25 °C
1 2 3 4 5 6 7 8 910
3. After adjusting the functions replace housing lid F and fasten the cover screws G.
Tools
Bolt cutter
Hacksaw
Flat file, medium cut
Screwdriver for cross head screws, size 2
Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680
15
Installation
We highly recommend that only qualified staff should carry out installation work in accordance with
these installation instructions. The manufacturer expressly rejects any claims for damage caused by
improper installation.
Before installing the electrode cut the electrode rods to length, check the insulation of the PTFE sleeve
(50 mm), see Fig. 3, and establish the functions.
The supplied spacer discs must be slipped over the electrode tips and distributed uniformly to ensure
sufficient spacing between the tips.
1. Check seating surfaces of threads or mounting flange provided on vessel or boiler standpipe (see
Fig. 4). If necessary rework the surfaces according to the specifications indicated in the drawing.
2. Place joint ring D (supplied with the electrode) on the seating surface of the standpipe or flange.
3. Apply a light smear of silicone grease to the electrode thread.
4. Screw electrode into threads or flange provided on vessel (see Fig. 4) and tighten with a 41 mm
open-end spanner. The torque required when cold is 160 Nm.
5. Note that the max. thermal insulation of the boiler around the level switch is 40 mm (see Fig. 3).
Attention
Do not subject the electrode tips to shocks and do not bend the electrode tips when
mounting.
Use only the supplied joint ring D 33 x 39, form D, made from DIN 7603, 1.4301 (bright
annealed). Do not insulate the threads with hemp or PTFE tape!
Do not lag the electrode body above the hexgonal part.
The electrode must only be installed in a vertical position.
The specified torques must be strictly observed.
Note
For the approval of the boiler standpipe (see Fig. 4) the relevant regulations must be
considered.
Carry out the installation work in compliance with the installation examples given in this
installation manual.
Align the terminal box such that the LEDs 1, 2, 3, 4, 5 can be seen by the operator.
1. Undo the cover screws G and remove the housing lid F.
2. Use open-end spanner 18 (19) A. F. to loosen the fixing nut M and turn the terminal box into the
desired direction (cable outlet).
3. Tighten the fixing nut M with a torque of 25 Nm.
4. Replace housing lid F and fasten the cover screws G.
If necessary you can take off the terminal box in order to align the electrode part. The terminal box
must be re-installed after alignment.
16
Installation - continued -
Attention
Close the housing lid F of the terminal box whenever the installation or remvoval work
of the terminal box is interrupted.
Check the seal A for signs of damage. Re-use only undamaged seals.
Tools
Open-end spanner A. F. 41 mm
Open-end spanner A.F. 18 (19) mm
Screwdriver for cross-recess head screws, size 2.5, completely insulated according to VDE 0680
17
Installation - continued -
Examples of Installation
1" 1"
1 1
DN 50 2 DN 50 2
2
3
4
∅ 20
5
7
5
∅ 20
7
8 8
6 9 6 9
0 0
≥ 10
≥ 10
≤ 90° ! !
∅ 20
≤ 90 °
∅ 20
Fig. 7 Fig. 8
Key
Use multi-core flexible control cable (CSA of conductor: 0.75 – 1.5 mm2) for mains and control cables.
1. Undo the cover screws G and remove the housing lid F.
2. Unplug the two-pole terminal strip J and the twelve-pole terminal strip H from the electronic
circuit board.
3. Strip off approx. 40 mm of cable insulation coating and remove approx. 5 mm of conductor end
insulation.
4. Loosen cable glands I and run the mains cables through the lower cable gland I and the control
cables through the upper cable glands I.
5. Connect mains and control cables according to the wiring diagram (inside of housing lid) to the
terminal strips H, J.
6. Plug terminal strips H, J into the electronic circuit board.
7. Seal cable entries by tightening the cable glands I. Use sealing plugs to seal off cable glands I
that are not used.
8. Replace housing lid F and fasten the cover screws G.
Attention
Note that the following basic insulated lines must not be installed in extra-low voltage
areas: mains and control lines.
To prevent the welding together of contacts provide an external slow-blow fuse T 2 A
for the output contacts.
Provide conductivity switch and control circuit with a 2.5 A slow-blow fuse.
Connected contactors must be provided with interference suppressors
(RC combinations) as specified by the manufacturer.
Provide an external slow-blow fuse 63 A (at 230 V) or 125 mA (at 115 V) or 1A (at 24 V)
for the coductivity switch.
For disconnecting the conductivity switch install an easily accessible disconnecting
switch in the close proximity of the equipment (EN 61010-1).
Mark the disconnecting switch as isolating device for the conductivity switch.
Tools
19
Electrical Connection - continued -
Wiring diagram
4
15
4 14
13
12
1
TEST 3 11
2
10
3
RESET 9
4
2 8
7
4
6
3 1 5
Electrode
wires 2 4
1
2
1
PE connection S2
S2 Disconnector
F1
F1 Fuse for level switch
L N
Mains supply
Fig. 9
20
Commissioning
1. Make sure that the level switch is correctly wired in accordance with the wiring diagram
(see Fig. 9).
2. Make sure that the mains voltage agrees with the specification on the name plate.
Danger
The terminal strip of the level switch is live during operation. This presents the danger of
electric shock!
Cut off power supply before opening the housing cover of the level switch!
After removing the housing cover check again that the system is de-energized.
To check the power supply or the correct functioning switch the level switch on again.
This work must only be performed by qualified personnel.
21
Commissioning - continued -
Use the following table as reference when checking the individual switching functions.
Electrode rod 1 = low level 1
Electrode rod 1 emerges Relay 1 is de-energized after 1 sec. LED 1 illuminated
Electrode rod 1 enters the liquid Relay 1 is energized after 1 sec. LED 1 off
Test and lock-out function
Press TEST button Relay 1 is de-energized and locked after 1 sec. LED 1 illuminated
Hold down button RESET for 3 sec. Relay 1 is energized after 1 sec. LED 1 off
Electrode rod 1 emerges Relay 1 is de-energized and locked after 1 sec. LED 1 illuminated
Electrode rod 1 enters the liquid
Relay 1 is energized after 1 sec. LED 1 off
Hold down button RESET for 3 sec.
Electrode rod 2 = low level 2
Electrode rod 2 emerges Relay 2 is de-energized after 1 sec. LED 2 illuminated
Electrode rod 2 enters the liquid Relay 2 is energized after 1 sec. LED 2 off
Electrode rod 4 = high level
Electrode rod 4 enters the liquid Relay 4 is de-energized after 3 sec. LED 4 illuminated
Electrode rod 4 emerges Relay 4 is de-energized after 3 sec. LED 4 off
Electrode rod 3 = timed pump control (fill control)
Electrode rod 3 emerges Relay 3 is energized, pump ON LED 3 illuminated
Relay 3 is de-energized after a preset time delay
Electrode rod 3 enters the liquid LED 3 off
(0 – 30s) = pump OFF
Relay 3 is de-energized too early or too late: Increase or decrease time delay with the aid of the potentiometer
and let electrode tip 3 emerge or enter the liquid again. Repeat the process until you have found
the correct switchpoint for the pump. If 30 sec. time delay is not enough for filling the boiler,
select the operating mode “on-off pump control”.
Electrode rods 2 and 3 = on-off pump control (fill control)
Set potentiometer for time delay to 0 sec.
LEDs 2 and 3 are
Electrode rods 2 and 3 exposed Relay 3 is energized, pump ON
illuminated
Electrode rod 2 enters the liquid LED 2 off
Electrode rod 3 enters the liquid Relay 3 is de-energized = pump OFF LED 3 off
Electrode rods 2 and 3 = on-off pump control (discharge control)
Set potentiometer for time delay to 0 sec.
LED 2 off and
Electrode rods 2 and 3 submerged Relay 3 is energized, pump ON
LED 3 illuminated
Electrode rod 3 emerges LED 3 off
Electrode rod 2 emerges Relay 3 is de-energized = pump OFF LED 2 illuminated
22
Malfunctions / Troubleshooting
Fault: If the electrode is installed inside the boiler: The vent hole in the protection tube does not
exist or is obstructed.
Remedy: Check installation of level switch. Make sure that the level in the protection tube
corresponds to the actual water level (see “Examples of Installation”).
Switchpoint has been reached – incorrect function
Fault: The switching function has not been assigned correctly. The electrode tips have been cut to
the wrong length.
Remedy: Assign the electrode tips correctly and change connections on the electronic circuit board N.
Fault: The switching function does not correspond to the selected function. The code switch has
been set to the wrong value.
Remedy: Set code switch 6 according to the selected function.
If faults occur that are not listed in this installation manual please contact our subsidiary or agency in
your country.
23
Exchanging electronic insert, removing level switch
Danger
When loosening the level switch steam or hot water might escape. This presents the dan-
ger of severe scalds to the whole body.
It is essential not to mount or dismantle the level switch unless the boiler pressure is
verified to be zero!
The level switch becomes hot during operation. Touching the hot equipment presents the
risk of severe burns to hands and arms. All installation, removal and maintenance work
must only be performed when the system is cold.
The terminal strip of the level switch is live during operation. This presents the danger of
electric shock!
Cut off power supply before mounting, removing or connecting the terminal strips.
Before exchanging the electronic insert take the level switch out of service and cut off its power supply.
1. Unscrew the cover screws G and remove the cover F, Fig. 5, 6.
2. Pull the electrode wires off the terminal lugs N on the electronic insert. Unplug all terminal
strips H, J, O.
3. Undo the PE connection L.
4. Unscrew the fixing screws K of the electronic insert and take out the electronic insert. The electronic
insert is available as spare part type NRV 1-47.
5. Install the new electronic insert in reverse order.
Before removing the level switch take it out of service and cut off its power supply.
1. Unscrew the cover screws G and remove the cover F, Fig. 5, 6.
2. Detach the connecting wires from the terminal strips H, J and pull the wires out of the cable
glands.
3. Undo the PE connection L.
4. Before removing the level switch make sure that the equipment is neither hot nor under pressure.
For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal.
Note
When ordering spare parts or replacement equipment please state the material number
indicated on the name plate.
24
Annex
The level switch assigns one switching channel to each electrode tip. The functions of the switching
channels 1 and 4 are fixed, the switching channels 2 and 3 can be adjusted via code switch 6 to suit
individual requirements.
The assigned electrode tip is cut to length on site in order to establish the level-dependent switchpoint
of each individual switching channel.
The code switch can also be used to establish other functions than the ones described in the section
“Establishing
ON Functions”.
ON
Code switch
1 2 34
ON 5 6 7 8 910 Function
ON
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
ON
1 2 3 4 5 6 7 8 910 No TEST button
1 2
ON 3 4 5 6 7 8 910
1 2
ON 3 4 5 6 7 8 910
ON
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910
1 2
ON 3 4 5 6 7 8 910 No RESET button
1 2 3 4 5 6 7 8 910
1 2
ON 3 4 5 6 7 8 910
1 2
ON 3 4 5 6 7 8 910
ON
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910 On-off pump control switched on
1 2
ON 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2
ON 3 4 5 6 7 8 910
1 2
ON 3 4 5 6 7 8 910
ON
1 2
ON
3 4 5 6 7 8 910 Electrode rod 2separated from electrode rod 1
ON
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910
ON
ON
Pump fill control switched on
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910 or
1 2 3 4 5 6 7 8 910
ON
ON Pump discharge control switched on
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910
ON
ON
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
Installation
1 2 3 in
4 5 non-metallic
6 7 8 910 vessel
25
For your notes
26
For your notes
27
GESTRA
GESTRA AG
P. O. Box 10 54 60, D-28054 Bremen
Münchener Str. 77, D-28215 Bremen
Tel. 0049 (0) 421 35 03 - 0
Fax 0049 (0) 421 35 03 - 393
E-Mail gestra.ag@flowserve.com
Web www.gestra.de