CONCEALED HOOK CONNECTORS UV-T / UV-C

GEOMETRY H
Choice of connection system according to the secondary
joist cross section B

SECONDARY JOIST B [mm] SECONDARY JOIST DEPTH H [mm]

300 250 200 150 100 50 0 mm mm 0 200 400 600 800 1000 1200

ALUMINI*
45 80
mm mm

ALUMIDI*
80 100
mm mm

ALUMAXI*
160 432
mm mm

DISC*
80 80
mm mm

UVT3070
45 100
mm mm

UVT4085
70 120
mm mm

UVT60115
80 180
mm mm

UVT60160
100 180
mm mm

UVT60215
100 220
mm mm

UVC60115
80 180
mm mm

UVC60160
100 180
mm mm

UVC60215
100 220
mm mm

* For more details see “WOOD CONNECTORS AND TIMBER PLATES” catalogue

2
STRENGTH
F

Choice of the connection system according to the vertical


component of the shear load

FIELD OF USE CHARACTERISTIC SHEAR STRENGTH Rk [kN]

TIMBER - TIMBER TIMBER - CONCRETE kN 0 50 100 150 200 250 300

ALUMINI* 40
kN

ALUMIDI* 130
kN

ALUMAXI* 320
kN

DISC* 25
kN

UVT3070 10
kN

UVT4085 20
kN

UVT60115 35
kN

UVT60160 50
kN

UVT60215 65
kN

UVC60115 25
kN

UVC60160 30
kN

UVC60215 35
kN

* For more details see “WOOD CONNECTORS AND TIMBER PLATES” catalogue

3
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVT
Concealed hook connector TIMBER - TIMBER
Aluminum three dimensional perforated plate

COMPLETE RANGE
Available in 5 versions, to work with the secondary
beam and load applied.
Resistance over 60 kN

CAN BE DISASSEMBLED
The hook system makes for quick installation and
can easily be removed. Ideal for use in temporary
FIELD OF USE structures
Timber to timber shear joints and
application requiring strength in all
directions SLENDER STRUCTURES
The UVT3070 version is ideal for joining secondary
Solid timber beams of smaller width,
glulam (Glued Laminated starting from a base of 45 mm
Timber)
XLAM (Cross Laminated Timber)
LVL (Laminated Veneer Lumber)
WIND AND EARTHQUAKE
Certified resistance in all load directions, for secure
fastening even in the presence of lateral, axial and
lifting forces

4 UV-T
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

INSTALLATION
Completely concealed, meets fire
resistance requirements. Installed
without cutting, it creates a vent that is
also an attractive architectural detail

ALL DIRECTIONS
The inclined screws inserted in the
secondary beam guarantee resistance
in all directions: vertical, horizontal and
axial. The joint is secure even in the case
of wind and earthquake forces

QUICK ASSEMBLY
Installation is intuitive, easy and fast. The
locking screw impedes unthreading,
guaranteeing resistance even in the
direction opposite to insertion

UV-T 5
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

APPLICATIONS

Secondary beam joint


45 mm x 100 mm with UVT3070

Creation of a temporary pergola

Large structure joints with


UVT60215

RANGE
The range of UV-T concealed connectors for wood-wood joints consists of 5 items, to be selected based on the load acting on the joint and the
dimensions of the secondary beam. Every connector offers different resistance, based on the length of the screws used.
The smallest connector can be used for beams with minimum dimensions of 45 mm x 100 mm. The largest connector offers characteristic
resistance exceeding 60 kN.
Secondary joist
depth [mm]

UVT60215
500
UVT60160
400
UVT60115

UVT4085 300
UVT3070
200

100

0
45 70 80 100 100
Secondary joist [mm] ≈120 ≈160 ≈160 ≈200 ≈240

Characteristic
resistance 6,8 - 9,0 [kN] 18,7 - 21,6 [kN] 28,0 - 36,0 [kN] 28,0 - 47,1 [kN] 37,3 - 62,8 [kN]

6 UV-T
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

CODES AND DIMENSIONS

UV-T
code B [mm] H [mm] s [mm] Ø90° [mm] Ø45° [mm] pcs/box
UVT3070 30 70 16 5 4 25
UVT4085 40 85 16 5 6 25
UVT60115 60 115 16 5 6 25
H
UVT60160 60 160 16 5 6 10
UVT60215 60 215 16 5 6 10
B Screws not included in the box

LBS: 90° SCREWS


code d [mm] L [mm] b [mm] TX pcs/box
PF603550 5 50 46 TX20 200
d
PF603560 5 60 56 TX20 200
b PF603570 5 70 66 TX20 200
L

HBS: 45° SCREWS for UVT3070


code d [mm] L [mm] b [mm] TX pcs/box
HBS450 4 50 30 TX20 200
d HBS470 4 70 40 TX20 200
b
L

VGS: 45° SCREWS for UVT4085 / UVT60115 /


code d [mm] L [mm] b [mm] TX pcs/box
UVT60160 / UVT60215
VGS6100 6 100 88 TX30 100
VGS6160 6 160 148 TX30 100
d
b
L

FASTENERS

MAXIMUM NUMBER OF FASTENERS PER INDIVIDUAL CONNECTOR (total nailing)

code n 90° [pcs - Ø] n 45° [pcs - Ø]


UVT3070 8 - LBS Ø5 6 (+1) - HBS Ø4
90° screws
45° screws UVT4085 11 - LBS Ø5 4 (+1) - VGS Ø6
HBS / VGS
LBS UVT60115 17 - LBS Ø5 6 (+1) - VGS Ø6
UVT60160 25 - LBS Ø5 6 (+1) - VGS Ø6
UVT60215 34 - LBS Ø5 8 (+1) - VGS Ø6

EXTERNAL LOADS MATERIAL AND DURABILTY


UV: aluminum alloy.
To be used in Service class 1 and 2 (EN 1995:2008)
F2

FIELD OF USE
F4
Timber to timber joints
F1
F3 Secondary beam on main beam or column

UV-T 7
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVT3070

MINIMUM DIMENSIONS, WOOD ELEMENTS

main secondary
beam beam UV CONNECTOR 45° SCREWS MAIN BEAM SECONDARY BEAM (1)
BxHxs ØxL BH,MIN GROOVING bJ,MIN hJ,MIN
type
[mm] [mm] [mm] BF [mm] Sf [mm] [mm] [mm]
H HBS Ø4 x 50 45 45 100
UVT3070 30 x 70 x 16 30 16
HBS Ø4 x 70 60 45 115

B s
FASTENERS

MAIN BEAM SECONDARY BEAM


nH,90° nH,45° (3) nJ,90° nJ,45°
type nailing
[pcs - Ø] [pcs - Ø] [pcs - Ø] [pcs - Ø]
total + 6  LBS Ø5 1  HBS Ø4 2  LBS Ø5 6  HBS Ø4
UVT3070
partial (2) 4  LBS Ø5 1  HBS Ø4 2  LBS Ø5 4  HBS Ø4

F2 F2
SF

F4 nH,45°
F4 e nJ,90°
H hj
F1
nH,90°
B=BF ≥10 mm nJ,45°
bj

BH
F3 F3

STATIC CHARACTERISTIC VALUES - TIMBER TO TIMBER JOINT

TOTAL NAILING + PARTIAL NAILING

UVT3070 45° SCREWS 45° SCREWS


HBS Ø4 x 50 HBS Ø4 x 70 HBS Ø4 x 50 HBS Ø4 x 70
[kN] [kN] [kN] [kN]
R1,Rk 1,45 1,45 1,45 1,45
R2,Rk 6,77 9,03 4,51 6,02
LBS Ø5 x 50
R3,Rk 1,13 1,50 1,13 1,50
R4,Rk 1,72 1,81 1,49 1,57
90° SCREWS

R1,Rk 1,76 1,76 1,76 1,76


R2,Rk 6,77 9,03 4,51 6,02
LBS Ø5 x 60
R3,Rk 1,13 1,50 1,13 1,50
R4,Rk 1,72 1,81 1,49 1,57
R1,Rk 2,08 2,08 2,08 2,08
R2,Rk 6,77 9,03 4,51 6,02
LBS Ø5 x 70
R3,Rk 1,13 1,50 1,13 1,50
R4,Rk 1,72 1,81 1,49 1,57

NOTES

(1) The minimum dimensions of the wood elements vary based on changes in the (2) Partial nailing must be performed in accordance with the assembly instructions

direction of the load and must be verified on a case by case basis. shown in the figure and in compliance with ETA.
(3) In the case of F or F loads, the use of a supplementary inclined screw in the
The table shows minimum dimensions to guide the designer when selecting 2 3
the connector. main beam is required, to be inserted after the connector is applied.
Dimensioning and verification of the timber elements must be carried out
separately.

8 UV-T
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVT4085

MINIMUM DIMENSIONS, WOOD ELEMENTS

main secondary
beam beam UV CONNECTOR 45° SCREWS MAIN BEAM SECONDARY BEAM (1)
BxHxs ØxL BH,MIN GROOVING bJ,MIN hJ,MIN
type
[mm] [mm] [mm] BF [mm] Sf [mm] [mm] [mm]
VGS Ø6 x 100 80 70 120
H UVT4085 40 x 85 x 16 40 16
VGS Ø6 x 160 120 70 160

B s FASTENERS

MAIN BEAM SECONDARY BEAM


nH,90° nH,45° (3) nJ,45°
type nailing nJ,90°
[pcs - Ø] [pcs - Ø] [pcs - Ø] [pcs - Ø]
total + 9  LBS Ø5 1  VGS Ø6 2  LBS Ø5 4  VGS Ø6
UVT4085
partial (2) 5 LBS Ø5 1  VGS Ø6 2  LBS Ø5 4  VGS Ø6

F2 F2
SF

F4
F4 e nJ,90°
H hj nH,45°
F1
nJ,45°
nH,90°
B=BF ≥10 mm
bj

BH
F3 F3

STATIC CHARACTERISTIC VALUES - TIMBER TO TIMBER JOINT

TOTAL NAILING + PARTIAL NAILING

UVT4085 45° SCREWS 45° SCREWS


VGS Ø6 x 100 VGS Ø6 x 160 VGS Ø6 x 100 VGS Ø6 x 160
[kN] [kN] [kN] [kN]
R1,Rk 1,45 1,45 1,45 1,45
R2,Rk 18,67 19,22 10,68 10,68
LBS Ø5 x 50
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 1,50 1,50 1,50 1,50
90° SCREWS

R1,Rk 1,76 1,76 1,76 1,76


R2,Rk 18,67 20,40 11,33 11,33
LBS Ø5 x 60
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 1,57 1,57 1,57 1,57
R1,Rk 2,08 2,08 2,08 2,08
R2,Rk 18,67 21,58 11,99 11,99
LBS Ø5 x 70
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 1,64 1,64 1,64 1,57

NOTES

(1) The minimum dimensions of the wood elements vary based on changes in the (2) Partial nailing must be performed in accordance with the assembly instructions

direction of the load and must be verified on a case by case basis. shown in the figure and in compliance with ETA.
(3) In the case of F or F loads, the use of a supplementary inclined screw in the
The table shows minimum dimensions to guide the designer when selecting 2 3
the connector. main beam is required, to be inserted after the connector is applied.
Dimensioning and verification of the timber elements must be carried out
separately.

UV-T 9
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVT60115

MINIMUM DIMENSIONS, WOOD ELEMENTS

main secondary
beam beam UV CONNECTOR 45° SCREWS MAIN BEAM SECONDARY BEAM (1)
BxHxs ØxL BH,MIN GROOVING bJ,MIN hJ,MIN
type
[mm] [mm] [mm] BF [mm] Sf [mm] [mm] [mm]
VGS Ø6 x 100 80 80 180
UVT60115 60 x 115 x 16 60 16
H VGS Ø6 x 160 120 80 220

FASTENERS
B s MAIN BEAM SECONDARY BEAM
nH,90° nH,45° (3) nJ,90° nJ,45°
type nailing
[pcs - Ø] [pcs - Ø] [pcs - Ø] [pcs - Ø]
total + 15  LBS Ø5 1  VGS Ø6 2  LBS Ø5 6  VGS Ø6
UVT60115
partial (2) 8  LBS Ø5 1  VGS Ø6 2  LBS Ø5 4  VGS Ø6

F2 F2
SF

F4
F4 nJ,90°
e
nH,45°
H hj F1

nH,90°

B=BF nJ,45°
≥10 mm

bj
BH
F3 F3

STATIC CHARACTERISTIC VALUES - TIMBER TO TIMBER JOINT

TOTAL NAILING + PARTIAL NAILING

UVT60115 45° SCREWS 45° SCREWS


VGS Ø6 x 100 VGS Ø6 x 160 VGS Ø6 x 100 VGS Ø6 x 160
[kN] [kN] [kN] [kN]
R1,Rk 1,45 1,45 1,45 1,45
R2,Rk 28,00 32,03 17,08 17,08
LBS Ø5 x 50
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 2,59 2,59 2,18 2,18
90° SCREWS

R1,Rk 1,76 1,76 1,76 1,76


R2,Rk 28,00 34,00 18,13 18,13
LBS Ø5 x 60
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 2,70 2,70 2,28 2,28
R1,Rk 2,08 2,08 2,08 2,08
R2,Rk 28,00 35,97 18,67 19,18
LBS Ø5 x 70
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 2,82 2,82 2,38 2,38

NOTES

(1) The minimum dimensions of the wood elements vary based on changes in the (2) Partial nailing must be performed in accordance with the assembly instructions

direction of the load and must be verified on a case by case basis. shown in the figure and in compliance with ETA.
(3) In the case of F or F loads, the use of a supplementary inclined screw in the
The table shows minimum dimensions to guide the designer when selecting 2 3
the connector. main beam is required, to be inserted after the connector is applied.
Dimensioning and verification of the timber elements must be carried out
separately.

10 UV-T
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVT60160

MINIMUM DIMENSIONS, WOOD ELEMENTS

main secondary
beam beam UV CONNECTOR 45° SCREWS MAIN BEAM SECONDARY BEAM (1)
BxHxs ØxL BH,MIN GROOVING bJ,MIN hJ,MIN
type
[mm] [mm] [mm] BF [mm] Sf [mm] [mm] [mm]
VGS Ø6 x 100 80 100 180
UVT60160 60 x 160 x 16 60 16
VGS Ø6 x 160 120 100 220
H

FASTENERS

MAIN BEAM SECONDARY BEAM


nH,90° nH,45° (3) nJ,90° nJ,45°
B s type nailing
[pcs - Ø] [pcs - Ø] [pcs - Ø] [pcs - Ø]
total 21  LBS Ø5 1  VGS Ø6 4  LBS Ø5 6  VGS Ø6
UVT60160
partial (2) 11  LBS Ø5 1  VGS Ø6 4  LBS Ø5 4  VGS Ø6

F2 F2
SF

F4
F4 nJ,90°
e
nH,45°
H hj
F1

nJ,45°
nH,90°
≥10 mm
B=BF
bj
BH
F3 F3

STATIC CHARACTERISTIC VALUES - TIMBER TO TIMBER JOINT

TOTAL NAILING PARTIAL NAILING

UVT60160 45° SCREWS 45° SCREWS


VGS Ø6 x 100 VGS Ø6 x 160 VGS Ø6 x 100 VGS Ø6 x 160
[kN] [kN] [kN] [kN]
R1,Rk 2,90 2,90 2,90 2,90
R2,Rk 28,00 44,85 18,67 23,49
LBS Ø5 x 50
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 3,01 3,01 2,71 2,71
90° SCREWS

R1,Rk 3,53 3,53 3,53 3,53


R2,Rk 28,00 47,09 18,67 24,93
LBS Ø5 x 60
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 3,15 3,15 2,83 2,83
R1,Rk 4,16 4,16 4,16 4,16
R2,Rk 28,00 47,09 18,67 26,38
LBS Ø5 x 70
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 3,28 3,28 2,95 2,95

NOTES

(1) The minimum dimensions of the wood elements vary based on changes in the (2) Partial nailing must be performed in accordance with the assembly instructions

direction of the load and must be verified on a case by case basis. shown in the figure and in compliance with ETA.
(3) In the case of F or F loads, the use of a supplementary inclined screw in the
The table shows minimum dimensions to guide the designer when selecting 2 3
the connector. main beam is required, to be inserted after the connector is applied.
Dimensioning and verification of the timber elements must be carried out
separately.

UV-T 11
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVT60215

MINIMUM DIMENSIONS, WOOD ELEMENTS

main secondary
beam beam UV CONNECTOR 45° SCREWS MAIN BEAM SECONDARY BEAM (1)
BxHxs ØxL BH,MIN GROOVING bJ,MIN hJ,MIN
type
[mm] [mm] [mm] BF [mm] Sf [mm] [mm] [mm]
VGS Ø6 x 100 80 100 220
UVT60215 60 x 215 x 16 60 16
VGS Ø6 x 160 120 100 260

H FASTENERS

MAIN BEAM SECONDARY BEAM


nH,90° nH,45° (3) nJ,90° nJ,45°
type nailing
[pcs - Ø] [pcs- Ø] [pcs - Ø] [pcs - Ø]
total + 30  LBS Ø5 1  VGS Ø6 4  LBS Ø5 8  VGS Ø6
UVT60215
partial (2) 16  LBS Ø5 1  VGS Ø6 4  LBS Ø5 4  VGS Ø6
B s

F2 F2
SF

F4
F4 nJ,90°

e nH45°

H hj
F1
nH,90°
nJ,45°

≥10 mm
B=BF
bj
BH
F3 F3

STATIC CHARACTERISTIC VALUES - TIMBER TO TIMBER JOINT

TOTAL NAILING + PARTIAL NAILING

UVT60215 45° SCREWS 45° SCREWS


VGS Ø6 x 100 VGS Ø6 x 160 VGS Ø6 x 100 VGS Ø6 x 160
[kN] [kN] [kN] [kN]
R1,Rk 2,90 2,90 2,90 2,90
R2,Rk 37,34 62,79 18,67 31,40
LBS Ø5 x 50
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 3,37 3,37 2,78 2,78
90° SCREWS

R1,Rk 3,53 3,53 3,53 3,53


R2,Rk 37,34 62,79 18,67 31,40
LBS Ø5 x 60
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 3,53 3,53 2,90 2,90
R1,Rk 4,16 4,16 4,16 4,16
R2,Rk 37,34 62,79 18,67 31,40
LBS Ø5 x 70
R3,Rk 4,67 7,85 4,67 7,85
R4,Rk 3,68 3,68 3,03 3,03

12 UV-T
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

NOTES

(1) The minimum dimensions of the wood elements vary based on changes in the (2) Partial nailing must be performed in accordance with the assembly instructions

direction of the load and must be verified on a case by case basis. shown in the figure and in compliance with ETA.
(3) In the case of F or F loads, the use of a supplementary inclined screw in the
The table shows minimum dimensions to guide the designer when selecting 2 3
the connector. main beam is required, to be inserted after the connector is applied.
Dimensioning and verification of the timber elements must be carried out
separately.

GENERAL PRINCIPLES

• Characteristic values comply with the EN 1995:2008 standard in accordance • Fixing through full nailing is possible for applications on a beam or partial
with product ETA. nailing for applications on columns. Inclined screws must always be inserted on
• Design values can be obtained from characteristic values as follows: the secondary beam side, in the two upper openings and two lower openings.
• Lateral F4 loads are assumed to act at a distance of e = H / 2 from the centre of
the connector. For different values of “e”, the resistance values can be calculated
in accordance with ETA.
• Coefficients γm and kmod must be taken according to the current Standard. • It is assumed that the main beam is impeded from rotating. In the case the
• For the calculations, a timber density ρk = 350 kg/m3 has been considered. UV connector is installed on only one side of the beam, an eccentric moment,
• Dimensioning and verification of the timber elements must be carried out
separately.
 
Mv = Fd (BH / 2 14 mm) must be considered. The same also applies in the case
of connections on both sides of the main beam when the difference between
• In case of combine loading the following expression shall be satisfied: acting forces is > 20%.

UV-T 13
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

UVC
Concealed hook connector TIMBER - CONCRETE
Aluminum three dimensional perforated plate

TIMBER AND CONCRETE


Joint calculated and certified for fixing of
secondary support beams in concrete (beams or
columns). Also certified for steel supports

CAN BE DISASSEMBLED
The hook system makes for fast installation and
can easily be removed. Ideal for use in temporary
FIELD OF USE structures
Timber to concrete shear joints

solid timber
FAST
Fast assembly even on cement, thanks to the
glulam (Glued Laminated
possibility of pre-assembling the secondary beam
Timber)
element in the workshop
XLAM (Cross Laminated Timber)
LVL (Laminated Veneer Lumber)
LOCKING
Supplementary locking screws included in the
package guarantee resistance to forces moving
from bottom to top

14 UV-C
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

CALCULATION AND CERTIFICATION


Values are calculated and certified for
use on reinforced concrete beams or
columns. Installed without cutting, it
creates a vent that is also an attractive
architectural detail

RAPID FASTENING
Installation on concrete is made easier
through the use of screw-in SKS anchors,
to be quickly and easily dry installed.
Application values for cement have been
calculated and are available

CEMENT AND STEEL


Also certified for applications on steel.
In this case, verification of fixing with
countersunk bolts should be done
separately, based on design choices

UV-C 15
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

CODES AND DIMENSIONS

UV-C
code B [mm] H [mm] s [mm] Øcls [mm] Ø90° [mm] Ø45° [mm] pcs/box
UVC60115 60 115 24 12 5 6 10
UVC60160 60 160 24 12 5 6 10
UVC60215 60 215 24 12 5 6 10
H Fasteners not included in the package

SKS CE: SCREW ANCHORS


COUNTERSUNK
code Ø [mm] L [mm] b [mm] d0cls [mm] Tinst [Nm] TX pcs/box
SKS10100CE 10 100 70 8 50 TX40 50

b
L

LBS: 90° SCREWS


code d [mm] L [mm] b [mm] TX pcs/box
PF603550 5 50 46 TX20 200
d PF603560 5 60 56 TX20 200
PF603570 5 70 66 TX20 200
b
L

VGS: 45° SCREWS


code d [mm] L [mm] b [mm] TX pz/conf
VGS6100 6 100 88 TX30 100
VGS6160 6 160 148 TX30 100
d
b
L

FASTENERS EXTERNAL LOADS MATERIAL AND DURABILTY

UV: aluminum alloy.


To be used in Service class 1 and 2 (EN 1995:2008)
90° screws
LBS
F2

SKS CE FIELD OF USE


45° screws
VGS F1
Timber to concrete joint
F3

16 UV-C
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

STATIC VALUES  TIMBER TO CONCRETE JOINT

UVC60115 UVC60160 UVC60215

concrete secondary concrete secondary concrete secondary


beam / column beam beam / column beam beam / column beam

H
H
H
B s

B s

B s

FASTENERS

UV-C CONNECTOR CONCRETE BEAM / COLUMN WOODEN SECONDARY BEAM


BxHxs nH,90° nJ,90° nJ,45°
type nailing / dowelling
[mm] [pcs - Ø] [pcs - Ø] [pcs - Ø]
UVC60115 60 x 115 x 24 2 - SKS CE Ø10 2 - LBS Ø5 6 - VGS Ø6
UVC60160 60 x 160 x 24 total 2 - SKS CE Ø10 4 - LBS Ø5 6 - VGS Ø6
UVC60215 60 x 215 x 24 3 - SKS CE Ø10 4 - LBS Ø5 8 - VGS Ø6
If it is necessary to impede upward slippage of the connector (e.g. F3 force), two supplemental M6 x 20 screws should be used. The screws and washers are included in the
package.

TIMBER TO CONCRETE JOINT  FASTENING TO BEAM


F2 F2

H
hj
Hcls

B
≥10 mm

bj

Lcls Bcls

CHARACTERISTIC RESISTANCE

R2,k TIMBER R2,k UNCRACKED CONCRETE


fasteners holes Ø5 1 fasteners holes Ø6 1 R2,k timber fasteners holes Ø12 R2,k cls
type
Ø x L [mm] Ø x L [mm] [kN] Ø x L [mm] [kN] γcls
UVC60115 LBS Ø5 x 50 VGS Ø6 x 100 28,00 SKS CE Ø10 x 100 9,78 1,5
UVC60160 LBS Ø5 x 50 VGS Ø6 x 100 28,00 SKS CE Ø10 x 100 12,23 1,5
UVC60215 LBS Ø5 x 50 VGS Ø6 x 100 37,34 SKS CE Ø10 x 100 16,10 1,5

INSTALLATION

UVC CONNECTOR CONCRETE MAIN BEAM WOODEN SECONDARY BEAM 2


BxHxs Bcls,MIN Hcls,MIN C = Cmin bJ,MIN hJ,MIN
type [mm] [mm]
[mm] [mm] [mm] [mm]
UVC60115 60 x 115 x 24 130 200 50 80 180
UVC60160 60 x 160 x 24 140 250 50 100 180
UVC60215 60 x 215 x 24 160 320 50 100 220
The length of the Lcls beam in this calculation configuration, when respecting the distances shown in the table, does not influence the resistance value provided Lcls > 500 mm

UV-C 17
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

TIMBER TO CONCRETE JOINT  FASTENING TO COLUMN


F2 F2

H
hj

B Hcls
≥10 mm

bj

Lcls Bcls

CHARACTERISTIC RESISTANCE

R2,k TIMBER R2,k UNCRACKED CONCRETE


fasteners holes Ø5 1 fasteners holes Ø6 (1) R2,k timber fasteners holes Ø12 R2,k cls
type
Ø x L [mm] Ø x L [mm] [kN] Ø x L [mm] [kN] γcls
UVC60115 LBS Ø5 x 50 VGS Ø6 x 100 28,00 SKS CE Ø10 x 100 17,34 1,5
UVC60160 LBS Ø5 x 50 VGS Ø6 x 100 28,00 SKS CE Ø10 x 100 23,52 1,5
UVC60215 LBS Ø5 x 50 VGS Ø6 x 100 37,34 SKS CE Ø10 x 100 29,07 1,5

INSTALLATION

UVC CONNECTOR CONCRETE COLUMN WOODEN SECONDARY BEAM (2)


BxHxs Bcls,MIN Lcls,MIN C > Ccr bJ,MIN hJ,MIN
type
[mm] [mm] [mm] [mm] [mm] [mm]
UVC60115 60 x 115 x 24 130 200 > 85 80 180
UVC60160 60 x 160 x 24 140 200 > 85 100 180
UVC60215 60 x 215 x 24 160 200 > 85 100 220
The length of the Hcls column in this calculation configuration, when respecting the distances shown in the table, does not influence the resistance value provided Hcls > 1000 mm

GENERAL PRINCIPLES NOTES

• Characteristic values comply with the EN 1995:2008 standard in accordance (1) Use of LBS and VGS screws longer than those in the table is allowed, without it
with product ETA. influencing the overall resistance of the connection (failure on concrete side).
• Design values can be obtained from characteristic values as follows: In this case, installation parameters must be reviewed (wooden secondary
beam).
(2) The minimum dimensions of the wood elements vary based on changes in the

direction of the load and must be verified on a case by case basis. The table
shows minimum dimensions to guide the designer when selecting the
connector.
The coefficients γm and kmod should be taken according to the current
regulations used for the calculation.
The coefficients γcls are provided in the table.
• During the calculation phase a timber density ρk = 350 kg/m3 and a concrete
grade C 25/30 have been considered.
• Dimensioning and verification of timber elements must be carried out
separately.
• Resistance values are valid for the calculation examples defined in the table.
When edge conditions are different (e.g. minimum distances from the edges),
they must be verified by the designer.

18 UV-C
CONCEALED HOOK CONNECTOR UV-T CONCEALED HOOK CONNECTOR UV-C

DIMENSIONING OF ALTERNATIVE ANCHORS


Fixing to concrete using anchors other than those in the table must be verified on the basis of the Fbolt forces that affect the anchors
in question. This can be determined using the kt coefficients.

TRACTION STRESS F1 VERTICAL SHEAR STRESS F2

F2

Fax bolt Fax bolt


F1 Flat bolt
Fax bolt Fax bolt
Flat bolt

nbolt kt kt //
UVC60115 2 0,50 0,299
UVC60160 2 0,50 0,192
UVC60215 3 0,33 0,106

The anchor is satisfactorily verified if project resistance, calculated considering the effects of the group and the geometry of the
UV-C connector, is greater than project stress:

UV-C 19
Rotho Blaas srl - I-39040 Cortaccia (BZ) - Via Dell‘Adige 2/1
01UVTC1EN

Tel. +39 0471 81 84 00 - Fax +39 0471 81 84 84


04 - 17