Anda di halaman 1dari 12

An American National Standard

Designation: F 1696 – 96 (Reapproved 2003)

Standard Test Method for


Energy Performance of Single-Rack Hot Water Sanitizing,
Door-Type Commercial Dishwashing Machines1
This standard is issued under the fixed designation F 1696; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.

1. Scope 2. Referenced Documents


1.1 This test method covers the evaluation of the energy 2.1 ASTM Standards:
consumption of single-rack, hot water sanitizing, door-type F 857 Specification for Hot Water Sanitizing Commercial
commercial dishwashers (hereafter referred to as dishwashers). Dishwashing Machines, Stationary Rack Type2
This includes under the counter single rack, hot water sanitiz- 2.2 NSF Standards:3
ing, door type commercial dishwashing machines. This test NSF, Listings Food Equipment and Related Products, Com-
method excludes single temperature door-type machines. Dish- ponents and Materials
washer tank heaters are evaluated separately from the booster Standard Number 3 Commercial Spray-Type Dishwashing
heater. Dishwashers may have a remote or self-contained Machines
booster heater. This test method does not address cleaning or 2.3 ASHRAE Document:4
sanitizing performance. ASHRAE Guideline 2-1986 (RA90) Engineering Analysis
1.2 The following procedures are included in this test of Experimental Data
method:
1.2.1 Procedures to Confirm Dishwasher is Operating 3. Terminology
Properly Prior to Performance Testing: 3.1 Definitions:
1.2.1.1 Maximum energy input rate of the tank heaters (see 3.1.1 booster heater, n—water heater for taking supply hot
10.2). water (typically 140°F) up to 180°F for sanitizing rinse; the
1.2.1.2 Maximum energy input rate of the booster heater, if booster heater may be separate from dishwasher or integral.
applicable (see 10.3). 3.1.2 dishload, n—a peg type, polypropylene dishrack of a
1.2.1.3 Water consumption calibration (see 10.4). specified weight, loaded with ten 9-in. plates of a specified
1.2.1.4 Booster temperature calibration, if applicable (see weight, used to put a thermal load on the dishwasher during the
10.5). washing energy test.
1.2.1.5 Wash tank temperature calibration (see 10.6). 3.1.3 dishwasher, n—for this test method, a heat-sanitizing
1.2.2 Energy Usage and Cycle Rate Performance Tests: commercial, single rack, door-type dishwasher.
1.2.2.1 Washing energy test (10.7). 3.1.4 uncertainty, n—measure of systematic and precision
1.2.2.2 Tank heater idle energy rate (door(s) open and errors in specified instrumentation or measure of repeatability
door(s) closed) (see 10.8). of a reported test result.
1.2.2.3 Booster idle energy rate, if provided (see 10.9).
1.3 The values stated in inch-pound units are to be regarded 4. Summary of Test Method
as standard. The SI units given in parentheses are for informa- 4.1 The maximum energy input rate of the tank heater and
tion only. the booster heater is determined to check whether the dish-
1.4 This standard does not purport to address all of the washer is operating at the manufacturer’s rated input. If the
safety concerns, if any, associated with its use. It is the measured input rate is not within 5 % of the rated input, all
responsibility of the user of this standard to establish appro- further testing ceases and the manufacturer is contacted. The
priate safety and health practices and determine the applica- manufacturer may make appropriate changes or adjustments to
bility of regulatory limitations prior to use. the dishwasher.

2
Annual Book of ASTM Standards, Vol 15.08.
1 3
This test method is under the jurisdiction of ASTM Committee F26 on Food Available from NSF International, P.O. Box 130140, 789 N. Dixboro Rd., Ann
Service Equipment and is the direct responsibility of Subcommittee F26.01 on Arbor, MI 48113-0140.
4
Cleaning and Sanitation Equipment. Available from American Society of Heating, Refrigerating, and Air-
Current edition approved Sept. 10, 2003. Published September 2003. Originally Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA
approved in 1996. Last previous edition approved in 1996 as F 1696 – 96. 30329.

Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.

1
F 1696 – 96 (2003)
NOTE 1—It is the intent of the testing procedure herein to evaluate the have a resolution of a least 0.01 ft3/(0.0003 m3) and have a
performance of a dishwasher at its rated gas pressure or electric voltage. maximum error of at least 0.01 ft3(0.0003 m3) and have a
If an electric unit is rated dual voltage (that is, designed to operate at either maximum error no greater than 2 % of the measured value.
208 or 240 V with no change in components), the voltage selected by the
manufacturer or tester, or both, shall be reported. If an dishwasher is
6.3 One or Two Steam Flow Meters, for measuring the flow
designed to operate at two voltages without a change in the resistance of of steam to tank heaters and or booster heater. They shall have
the heating elements, the performance of the unit (for example, recovery a resolution of 0.01 ft3 (0.0003 m3) and a maximum uncertainty
time) may differ at the two voltages. of 1 % of the measured value.
4.2 The wash tank and booster temperature are calibrated to 6.4 Pressure Gage, for measuring the pressure of steam to
the manufacturer’s recommendations. steam coils. It shall have a resolution of 0.5 psig (3.4 kPa) and
4.3 The water consumption is adjusted per the manufactur- a maximum uncertainty of 1 % of the measured value.
er’s recommendations. The pressure regulator valve is adjusted 6.5 Canopy Exhaust Hood, mounted in agreement with
to 20 6 1 psi and the water consumption measured. If this is manufacturer’s requirements and operating at a nominal 300 to
not within 60.15 GPM of the NSF rating or the manufacturer’s 500 cfm ventilation rate or in accordance with the manufac-
rating if not listed to NSF standards, then the manufacturer turer’s recommendation, if applicable. Report the ventilation
shall be contacted. rate.
4.4 The tank heater energy rate is determined at idle, that is, 6.6 Pressure Gage, for monitoring natural gas pressure. It
when the tank temperature is being maintained, but no washing shall have a range of 0 to 10 in. H2O (0 to 2.5 kPa), a resolution
is taking place. This test is run both with the door(s) closed and of 0.1 in. H2O (125 Pa), and a maximum uncertainty of 1 % of
with the door(s) left open. the measured value.
4.5 The booster heater idle energy rate is determined. 6.7 Temperature Sensor, for measuring natural gas tempera-
4.6 The dishwasher and booster energy consumption per ture in the range of 50°F to 100°F (10 to 40°C), with a
rack of dishes is determined by washing 10 racks loaded with resolution of 0.5°F (0.3°C) and an uncertainty of 61°F
a specified quantity of dishes. (0.5°C).
6.8 Barometer, for measuring absolute atmospheric pres-
5. Significance and Use sure, to be used for adjustment of measured natural gas volume
to standard conditions. It shall have a resolution of 0.2 in. Hg
5.1 The maximum energy input rate test is used to confirm (670 Pa) and an uncertainty of 0.2 in. Hg (670 Pa).
that the dishwasher is operating at the manufacturer’s rated 6.9 Flow Meter, for measuring water consumption of the
input prior to further testing. This test would also indicate any dishwasher. It shall have a resolution of 0.01 gal (40 mL), and
problems with the electric power supply, gas service pressure, an uncertainty of 0.01 gal (40 mL), at flow rate as low as 0.2
or steam supply flow or pressure. gpm (13 mL/s).
5.2 The tank and booster temperature, as well as water 6.10 Stop Watch, with a 0.1-s resolution.
consumption are adjusted to NSF specifications to ensure that 6.11 Analytical Balance Scale, or equivalent, for measuring
the test is applied to a properly functioning dishwasher. weight of dishes and dish racks used in the dishload energy
5.3 Because much of a dishwasher’s operating period is test. It shall have a resolution of 0.01 lb (5 g) and an
spent in the idle condition, tank heater and booster idle energy uncertainty of 0.01 lb (5 g).
consumption rate is an important part of predicting an end 6.12 Calibrated Exposed Junction Thermocouple Probes,
user’s energy consumption. The test is run with the door(s) with a range from −20°F to 400°F (−30 to 200°C), with a
open and with the door(s) closed, so that the energy use of both resolution of 0.2°F (0.1°C) and an uncertainty of 1.0°F (0.5°C),
end-user behaviors can be characterized. for measuring tank temperature and booster and dishwasher
5.4 A washing energy test generates an energy per rack inlet temperature. Calibrated Type K Z4 GA thermocouple wire
usage. This is useful both as a measure for comparing the with stainless steel sheath and ceramic insulation is the
energy performance of one dishwasher to another and as a recommended choice for booster and dishwasher inlet tempera-
predictor of an end users energy consumption. ture. The thermocouple probe can be fed through a compres-
sion fitting so as to submerse the exposed junction in the
6. Apparatus booster and dishwasher inlets.
6.1 One or Two Wh Meters, for measuring the electrical 6.13 Dishracks, 12, Metro Mdl P2MO, 20 in. by 20 in., peg
energy consumption of the tank heaters, pump motor, and type, commercial, or acceptable equivalent. They shall weigh
booster heater (if applicable), shall have a resolution of at least 4.6 6 0.1 lb and are used in the washing energy test.
10 Wh and a maximum uncertainty no greater than 1.5 % of the 6.14 Plates, 100, 9 in., ceramic-glazed, weighing an average
measured value for any demand greater than 100 W. For any of 1.3 6 0.05 lb each. If plates, meeting this criteria cannot be
demand less than 100 W, the meter shall have a resolution of at obtained, then it will be necessary to acquire saucers, as
least 10 Wh and a maximum uncertainty no greater than 10 %. specified in 6.15. See 9.11 prior to obtaining these plates.
6.2 One or Two Gas Meters, for measuring the gas con-
NOTE 2—Inter-Americant Mdl #1325 are within the specified weight
sumption of tank heater or booster heater, or both, shall have a
range and are inexpensive.
resolution of at least 0.01 ft3(0.0003 m3) and a maximum
uncertainty no greater than 1 % of the measured value for any
demand greater than 2.2 ft3/h (0.06 m3/h). If the meter is used 5
Available from Keystone Restaurant Supply, 491 W. San Carlos St., San Jose,
for measuring the gas consumed by the pilot lights, it shall CA 95110.

2
F 1696 – 96 (2003)
6.15 Saucers, 20, ceramic-glazed, weighing less than 0.5 lb 9.8 Install the flow meter (see 6.9) such that total water flow
each. See 9.11 for an explanation of why these may be to the booster and dishwasher is measured.
required. 9.9 Install a temperature sensor (see 6.12) in the wash tank
6.16 Surface Temperature Thermocouple Probe, for measur- near the thermostat bulb.
ing the plate temperature. Resolution and uncertainty shall be 9.10 Install a temperature sensor (see 6.12) in the dish-
the same as in 6.12. washer rinse water inlet, and in the booster inlet. The sensors
should be installed with the probe immersed in the water.
7. Materials NOTE 3—Install the thermocouple probes described in 6.12 into the
7.1 As specified in 6.13, the dishracks must be made of water inlets for dishwasher rinse and booster. The thermocouple probe
polypropylene. This is required because the test method shall be installed so that the thermocouple is immersed in the incoming
assumes a specific heat of 0.39 Btu/lb°F. One verification that water. A compression fitting should be installed first into the plumbing for
a rack is polypropylene is if it has the recycling symbol 6x5 on both inlets. A junction fitting may be installed in the plumbing line that
would be compatible with the compression fitting.
it (and the letters “PP” below it).
9.11 Preparation of Dish-Loads:
8. Sampling 9.11.1 This section describes preparation of ten dishloads
and two empty racks to be used in the washing energy test.
8.1 Dishwasher—A representative production model shall
9.11.2 An important feature of the washing energy test is
be selected for performance testing.
that every dishwasher is subjected to the same thermal load. To
accomplish this, the tester must control some of the factors that
9. Preparation of Apparatus
affect the thermal load. These factors are:
9.1 Install the dishwasher in accordance with the manufac- 9.11.2.1 the total weight of the dishes,
turer’s instructions under a 3-ft by 3-ft canopy exhaust hood, 9.11.2.2 the weight of the (empty) racks, and
operating at a nominal ventilation rate of 300 to 500 cfm or in 9.11.2.3 the initial temperature of the dishes and racks.
accordance with manufacturer’s recommendation, if appli- 9.11.3 The weight of the racks is specified in 6.13 as 4.6 lb
cable. The associated heating or cooling system shall be or greater. If they weigh more than 4.6 lb, trim away material
capable of maintaining an ambient temperature of 75 6 5°F until they weigh 4.6 6 0.1 lb. To see what parts of the rack are
within the testing environment when the exhaust ventilation not needed for the test and may therefore be trimmed, it may be
system is working and the appliance is being operated. desirable to load the rack as they will be used during the test.
9.2 Install the booster heater (if it is not integral to the The loading is explained in 9.11.4 and 9.11.5.
dishwasher) in accordance with the manufacturer’s recommen- 9.11.4 Prepare ten dishloads as described in this and the
dations. The pipe from the booster outlet to the dishwasher following step (9.11.5). The ten dishloads must have 13.06 0.5
inlet shall be minimized, and shall be wrapped with 1⁄2-in. lb of plates. Ideally, this simply requires ten 9-in. plates. If the
insulation along its entire length. total weight of the ten 9-in. plates does not fall within the
9.3 Connect the booster to a supply of water that is within range, then use the saucers to adjust the total weight. A
63°F of its rated input temperature (not to exceed 140 6 3°F). maximum of two saucers can be added per rack.
9.4 Connect the dishwasher and booster to calibrated energy 9.11.5 Space the plates and saucers evenly on the racks.
test meters. The dishwasher and booster may be monitored as 9.11.6 The bulk temperature of the dishloads must be 75 6
one energy load, but it is preferable to monitor them separately. 2°F. This can be accomplished by storing the dishloads
Separate monitoring will broaden the usefulness of the data and together in a room with an ambient temperature of 75 6 2°F.
enhance the accuracy of the result. Avoid any circumstances that would result in some dishes
9.5 For gas installations, install a pressure regulator (down- being at different temperature from others, such as being stored
stream from the meter) to maintain a constant (manifold) in the air path of an HVAC supply register. Determine the bulk
pressure of gas supplied to the dishwasher and booster heater temperature using a surface temperature probe (6.16), measur-
(if applicable) for all tests. Install instrumentation to record ing the temperature of at least three plates (one front, one
both the pressure and temperature of the gas supplied to the center, and one rear) of each dishrack. Average these tempera-
dishwasher and the barometric pressure during each test so that tures to determine the bulk temperature.
the measured gas flow can be corrected to standard conditions.
9.6 For an electric tank or booster heater, confirm (while the 10. Procedure
elements are energized) that the supply voltage is within 10.1 General:
62.5 % of the operating voltage specified by the manufacturer. 10.1.1 Obtain and record the following for each run of every
If it is not, a voltage regulator may be required during the tests. test (gas and electric units).
Record the test voltage for each test. 10.1.1.1 Voltage while elements are energized, and
9.7 For a gas tank or booster heater, adjust (during maxi- 10.1.1.2 Measured peak input rate during or immediately
mum energy input) the gas supply pressure downstream from prior to test (does not include motor starting load).
the appliance’s pressure regulator to within 62.5 % of the 10.1.2 For dishwashers with a gas-powered tank heater or
operating manifold pressure specified by the manufacturer. booster, the following shall be obtained and recorded for each
Make adjustments to the appliance following the manufactur- run of every test:
er’s recommendations for optimizing combustion, as appli- 10.1.2.1 Higher heating value,
cable. 10.1.2.2 Standard gas conditions for calculation in 11.3,

3
F 1696 – 96 (2003)
10.1.2.3 Measured gas temperature, 10.3.2 Determine the booster maximum energy input rate
10.1.2.4 Measured line gas pressure (before pressure regu- for the dishwasher under test in accordance with 11.4. Report
lator), the measured input rate and confirm that it is within 5 % of the
10.1.2.5 Barometric pressure, and nameplate rated input. If the difference is greater than 5 %,
10.1.2.6 Measured peak input rate during or immediately terminate testing and contact the manufacturer. The manufac-
prior to test. turer may make appropriate changes or adjustments to the
booster.
NOTE 4—For a gas appliance, the quantity of heat (energy) generated 10.4 Dishwasher Water Consumption Calibration:
by the complete combustion of the fuel is known as the heating value, heat
of combustion, or calorific value of that fuel. For natural gas, this heating
10.4.1 Ensure final rinse water is supplied at 20 6 1 psi.
value varies according to the constituents of the gas. It is measured in 10.4.2 Measure water consumption using the flowmeter
Btu/ft3. The heating value should be obtained during testing and used in specified in 6.9 and run the dishwasher through five complete
the determination of the energy input to the appliance. cycles. Determine the average water consumption per rack.
NOTE 5—The preferred method for determining the heating value of 10.4.3 Confirm that the water consumption per rack of
gas supplied to the dishwasher under testing is by using a calorimeter or dishes is within 63 % of the NSF rated water consumption or
gas chromatograph in accordance with accepted laboratory procedures. It the manufacturer’s rating if not listed to NSF standards. If it is
is recommended that all testing be performed with gas with a heating not, testing shall be terminated and the manufacturer contacted.
value between 1000 and 1075 Btu/ft3(37 300 to 40 100 kJ/m3). The use of
“bottle” natural gas with a certified heating value within the specified 1000
The manufacturer may make appropriate changes or adjust-
to 1075 Btu/ft3(37 300 to 40 100 kJ/m3) range is an acceptable alternative. ments to the dishwasher. Record the final water consumption
per rack.
10.1.3 For gas dishwashers, energy calculations shall be in 10.5 Booster Temperature Calibration:
accordance with 11.3. 10.5.1 While monitoring the inlet and outlet temperature of
10.1.4 For dishwashers that use steam coils for tank heat, the booster, initiate a dishwasher cycle every 2 min. Adjust the
the supplied steam pressure, steam temperature at dishwasher booster heater such that the average temperature of water at the
inlet, steam temperature at dishwasher outlet, and average flow dishwasher inlet (measured only during the rinse) is 181 6 1°F.
rate shall be recorded for each run of every test. 10.6 Wash Tank Temperature Calibration:
10.1.5 For each run of every test, confirm that the peak input 10.6.1 Fill the dishwasher tank and activate the tank heaters.
rate is within 65 % of the rated “nameplate” input. If the When the tank heaters cycle off, start the wash pump (door
difference is greater than 5 %, terminate testing and contact the closed) and commence monitoring temperature. Observe the
manufacturer. The manufacturer may make appropriate temperature at which the tank heaters cycle on. Allow the tank
changes or adjustments to the dishwasher. temperature to recover, cycle off, and again observe the
10.2 Tank Heater Maximum Energy Input Rate: cycle-on temperature. Observe the cycle-on temperature a third
10.2.1 Gas Tank Heaters—Fill the dishwasher tank with time and confirm that for each run the cycle-on temperature
706 10°F water, initiate the tank heaters, and when the burners was 151 6 1°F. If it falls outside of this range on any run,
cycle off, immediately drain the tank and proceed with 10.2.2. adjust the thermostat accordingly and repeat the three runs.
NOTE 6—For some gas appliances, the input rate changes as the burner NOTE 7—The wash tank temperature calibration may need to be
orifices heat up from room temperature to operational temperature. changed again during the washing energy test (10.9) to achieve the
Section 10.2.1 is provided to minimize this effect. “ready” temperature required for this test. The reasoning for changing the
wash tank temperature thermostat setting is explained in Note 8. The
10.2.2 Fill the dishwasher tank with 70 6 10°F water, and “ready” temperature is an approximate starting point for the determination
energize the tank heaters. Commence monitoring time and of when to start washing the next dishload. The “ready” temperature is the
energy consumption. When the heaters cycle off, note the time dishwasher tank temperature that is hot enough to start washing the next
and total energy consumption. For electric tank heaters, a direct room temperature dishload and not drop the tank temperature below the
measurement of power may be substituted for the monitoring recommended 151 6 1°F.
of time and energy consumption. 10.7 Washing Energy Performance Test:
10.2.3 Determine the tank heater maximum energy input 10.7.1 This test will require ten dishloads and two empty
rate in accordance with 11.4, for the dishwasher under test. dishracks (as described in Sections 3, 6 and 9). Record the
Report the measured input rate and confirm that it is within 5 % weight of the dishes and the weight of the racks. Record the
of the nameplate rated input. If the difference is greater than make and model of the dishracks and dishes.
5 %, terminate testing and contact the manufacturer. The 10.7.2 The bulk temperature of the dishloads shall be 75 6
manufacturer may make appropriate changes or adjustments to 2°F. Determine the bulk temperature using a surface tempera-
the dishwasher. ture probe (see 6.16) and measure the temperature of at least
10.3 Booster Maximum Energy Input Rate: three plates (one front, one center, and one back). Average
10.3.1 Open the dishwasher drain. Close the door(s) and these temperatures to determine the bulk temperature.
initiate a tank fill. After the booster cycles on, monitor time and 10.7.3 Allow the dishwasher to idle (no washing taking
energy consumption for 10 min. For gas boosters, commence place) for 1 h.
the 10 min monitoring period 15 min after the burners cycle on 10.7.4 Using the surface temperature probe, measure the
(to allow the burners to stabilize). For electric boosters, a direct temperature of a dish in the front, middle, and rear of each
measurement of power may be substituted for the monitoring dishload. Record the average of these temperatures and con-
of time and energy consumption. firm that it is 75 6 2°F.

4
F 1696 – 96 (2003)
10.7.5 After the 1-h idle period, observe the tank heaters Note the minimum tank temperature that occurs during any of
and tank temperature. When the tank temperature is on the rise these dishloads does not have to fall in the range of 151 6 1°F
(tank heaters energized), and the temperature reaches 156°F (that requirement only pertains to the washing of the first
(from now on referred to as the “ready” temperature), start dishload). It does however have to remain above the NSF
washing the first empty dishrack. Immediately after completion required minimum 150°F at all times. If the temperature does
of the cycle, remove the first empty dishrack. Close the door(s), fall below 150°F at any time, increase the “ready” temperature
but not far enough to activate the wash cycle. by 1°F and repeat the test starting at 10.7.1.
NOTE 8—The condition required to start washing the first empty 10.7.9 After removing the last dishload, close the door(s)
dishrack may not occur immediately following the 1-h idle period. For (but not far enough to activate another cycle) and when the
example, when 1 h has elapsed, the tank temperature may already be tank temperature reaches the “ready” temperature, turn off the
above the ready temperature, with the tank heaters already energized. In tank heaters. The last “ready” temperature that signifies the end
this case, allow the elements or burners to cycle off, then on again, and of the washing energy test should be the same “ready”
wait for the temperature to reach the ready temperature. temperature as the tenth dishload’s “ready” temperature (that
NOTE 9—The specification of 156°F as the “ready” temperature is an is, if the tenth dishload’s“ ready” temperature was 155°F after
approximate starting point. It may be different from dishwasher to
the tenth dishload has been washed, wait until the tank
dishwasher and from dishload to dishload, and is precisely determined
though an iterative process. The goal of the iteration is to determine the temperature has recovered to 155°F before ending test).
lowest possible “ready” temperature that does not result in any dishload 10.7.10 Record the final dishwasher and booster energy,
dropping the tank temperature below the NSF required minimum 150°F elapsed time (from start of washing the first dishload to when
(that is, 151 6 1°F). There is one period during the washing energy test the final “ready” temperature is reached in 10.7.9), average
where the lowest tank temperature might occur, that is, during the washing dishwasher inlet temperature, average booster inlet tempera-
of the first dishload. Therefore, this test requires that the tank temperature
ture, minimum tank temperature, and total water consumption,
falls within the range from 151 6 1°F during the first dishload. If it
doesn’t, then the “ready” temperature is adjusted (up, if it fell to below and “ready” temperatures. If at anytime the booster supplying
150°F, down, if it fell to above 152°F), and the test is rerun. The tank the dishwasher does not maintain the average final rinse
heater thermostat may require adjusting up if element(s) or burner(s) cut temperature of 180 6 1°F during washing energy performance
out before the tank temperature reaches the “ready” temperature and down test, the test shall be considered a failure.
if the tank temperature is always above the “ready” temperature. The 10.7.11 In accordance with 11.7, calculate and report the
“ready” temperature may be changed during the test in order to maximize
the cycle rate (racks washed per hour), provided the minimum tank
energy consumed per rack.
temperature meets the qualifications of tank temperature fall to 151 6 1°F 10.8 Closed Door and Open Door Tank Heater Idle Energy
with the first dishload and 151 6 1°F or higher with each subsequent Rate:
dishload. 10.8.1 Allow the dishwasher to fill, and energize the tank
10.7.6 Commence washing the second empty dishrack as heaters.
soon as the same “ready” temperature from the previous empty 10.8.2 With the door(s) closed, allow the dishwasher tank to
rack has been reached. Immediately after completion of the idle for at least two tank heater “on” cycles. Commence
cycle remove the second empty dishrack. Close the door(s), but monitoring elapse time, temperature, and energy consumption
not far enough to activate the wash cycle. When the tank as the tank heater “on” cycles for the second time. Allow the
temperature reaches the “ready” temperature needed to ensure dishwasher to idle for 3 h. Record final time and energy
that the first dishload will cause the tank temperature to fall to consumption.
151 6 1°F, commence washing the first dishload. Commence 10.8.3 Repeat 10.8.1 and 10.8.2, but this time leave the
monitoring time, energy of the dishwasher and the booster, door(s) open.
water consumption, and temperature of the booster inlet, final 10.8.4 Calculate and report the closed door(s) and open
rinse and wash tank. Note the minimum tank temperature door(s) tank heater idle energy rate in accordance with 11.5.
experienced during this washing period. Confirm that, at some 10.9 Booster Idle Energy Rate:
point during this dishload this tank temperature is 151 6 1°F. 10.9.1 Allow the booster to idle (no water drawn from it) for
Remove the dishload when the cycle is complete. Close the a minimum of 1 h. Commence monitoring energy consumption
door(s), but not far enough to activate the wash cycle. and time. Continue for a minimum of 5 h.
10.7.7 If the minimum tank temperature during the washing 10.9.2 Calculate and report the booster heater idle energy
of this first dishload did not fall into the range of 151 6 1°F, rate, in accordance with 11.6.
adjust the“ ready” temperature (up, if it fell to below 150°F,
down, if it fell to above 152°F), and repeat the test, starting at 11. Calculation and Report
10.7.1.
10.7.8 If the minimum tank temperature during the washing 11.1 Test Dishwasher:
of this first dishload did fall into the range of 151 6 1°F, record 11.1.1 Summarize the physical and operating characteristics
the tank temperature and proceed to washing subsequent of the dishwasher using Specification F 857. Describe the
dishloads. When the tank temperature reaches the next “ready” physical and operating characteristics of the booster heater. If
temperature, commence washing the next dishload. Remove needed, describe other design or operating characteristics of
the dishload when the cycle is complete, and leave the door(s) the dishwasher or booster that may facilitate interpretation of
open. Repeat this step eight more times (resulting in a total of the test results.
twelve loads, two with the empty racks and ten with dishloads). 11.2 Apparatus and Procedure:

5
F 1696 – 96 (2003)
11.2.1 Confirm that the testing apparatus conformed to all of 11.5.1 Calculate and report the open door and the closed
the specifications in Section 9. Describe any deviations from door tank heater idle energy rate (Btu/h or kW) based on:
those specifications. Report the ventilation rate. E 3 60
11.2.2 Report the voltage for each test. Eidle rate 5 t (3)
11.2.3 Report the higher heating value of the gas used
where:
during each test for gas booster or tank heaters.
Eidle rate = idle energy rate, Btu/h or kW,
11.3 Gas Energy Calculations: E = energy consumed during the test period, Btu or
11.3.1 For gas dishwashers, add electric energy consump- kWh, and
tion to gas energy for all tests, with the exception of the energy t = test period, min.
input rate test (see 10.2). 11.6 Booster Heater Idle Energy Rate:
11.3.2 Calculate the energy consumed based on: 11.6.1 Calculate and report the booster heater idle energy
Egas 5 V 3 HV (1) rate (Btu/h or kW) based on:
E 3 60
where: Eidle rate 5 t (4)
Egas = energy consumed by the appliance,
HV = higher heating value, where:
= energy content of gas measured at standard condi- Eidle rate = idle energy rate, Btu/h or kW,
tions, Btu/ft3, E = energy consumed during the test period, Btu or
V = actual volume of gas corrected for temperature and kWh, and
pressure at standard conditions, ft3 t = test period, min.
= meas 3 Tcf 3 Pcf 11.7 Washing Energy Test:
11.7.1 Calculate and report each of the following:
where:
11.7.1.1 Dishwasher electric energy per rack (kWh),
Vmeas = measured volume of gas, ft3,
Tcf = temperature correction factor, 11.7.1.2 Booster electric energy per rack, if applicable
= absolute standard gas temperature °R (kWh),
absolute actual gas temperature °R 11.7.1.3 Total electric energy per rack (kWh),
11.7.1.4 Dishwasher gas energy per rack, if applicable
= absolute standard gas temperature °R (Btu),
@gas temp°F 1 459.67#° R 11.7.1.5 Booster gas energy per rack, if applicable (Btu),
11.7.1.6 Total gas energy per rack, if applicable (Btu), and
Pcf = pressure correction factor 11.7.1.7 Cycle rate (racks/hr).
= absolute actual gas pressure psia
11.7.2 Use the following relationship:
absolute standard pressure psia
Etest
Erack 5 10 (5)
= gas gage pressure psig 1 barometric pressure psia
absolute standard pressure psia
where:
NOTE 10—Absolute standard gas temperature and pressure used in this Erack = One of the energy per rack values listed above, and
calculation should be the same values used for determining the higher Etest = Energy consumed during the ten dishload run test,
heating value. PG&E standard conditions are 519.67°R and 14.73 psia. specific to the parameter being expressed (for
11.4 Booster and Tank Heater Energy Input Rate: example, for dishwasher energy per rack,
Etest = the total energy consumed by the dish-
11.4.1 Report the manufacturer’s nameplate energy input
washer during the ten run test).
rate in Btu/h for a gas booster or tank heater and in kW for an
11.7.3 Report the elapsed time for the washing energy test.
electric booster or tank heater.
The elapsed time is measured from the time the dishwasher has
11.4.2 Calculate and report the measured energy input rate commenced washing the first dishload, till the dishwasher tank
(Btu/h or kW) of the booster heater and the tank heaters based temperature has reached the tenth dishload’s ready temperature
on the energy consumed during the period of peak energy input after the last dishload has been removed. Calculate the cycle
according to the following relationship: rate (racks per hour) by dividing ten racks (ten dishloads) by
E 3 60 the elapsed time.
Einput rate 5 t (2)

where: 12. Precision and Bias


Einput rate = measured peak energy input rate, Btu/h or 12.1 Precision:
kW, 12.1.1 Repeatability (within laboratory, same operator and
E = energy consumed during period of peak en- equipment):
ergy input, Btu or kWh, and 12.1.1.1 The repeatability of each reported parameter is
t = period of peak energy input, min. being determined.
11.5 Tank Heater Idle Energy Rate: 12.1.2 Reproducibility (multiple laboratories):

6
F 1696 – 96 (2003)
12.1.2.1 The interlaboratory precision of the procedure in 13. Keywords
this test method for measuring each reported parameter is being
13.1 booster; dishload; dishrack; dishwasher; tank heater
determined.
12.2 Bias:
12.2.1 No statement can be made concerning the bias of the
procedures in this test method because there are no accepted
reference values for the parameters reported.

ANNEX

(Mandatory Information)

A1. PROCEDURE FOR DETERMINING THE UNCERTAINTY IN REPORTED TEST RESULTS

NOTE A1.1—The procedure that follows is based on the method for A1.4.1 Step 1—Calculate the average and the standard
determining the confidence interval for the average of several test results deviation for the test results (energy per rack and cycle rate)
discussed in ASHRAE Guideline 2-1986(RA90). It should only be applied using the results of the first three test runs, as follows:
to test results that have been obtained within the tolerances prescribed in
this test method, (for example, thermocouples calibrated, range was NOTE A1.3—The formulas that follow may be used to calculate the
operating within 5 % of rated input during the test run). average and sample standard deviation. However, it is recommended that
a calculator with statistical function be used. If one is used, be sure to use
A1.1 For the energy per rack (ER) and cycle rate (CR) the sample standard deviation function. Using the population standard
results, the uncertainty in the averages of at least three test runs deviation function will result in an error in the uncertainty. The formula
is reported. For each test run, the uncertainty of the energy per for the average (three test runs) is as follows:
rack and cycle rate shall be no greater than 610 % before any Xa3 5 ~1/3! 3 ~X1 1 X2 1 X3! (A1.1)
of the parameters for that washing energy test run can be
where:
reported. Xa3 = average of results for three test runs, and
X1, X2, X3 = results for each test run.
A1.2 The uncertainty in a reported result is a measure of its The formula for the sample standard deviation (three test runs) is as
precision. If, for example, the cycle rate for the dishwasher is follows:
30 racks/h, the uncertainty shall not be greater than 63 racks/h.
Thus, the true cycle rate is between 27 and 33 racks/h. This S3 5 ~1/=2! 3 =~A3 2 B3! (A1.2)
interval is determined at the 95 % confidence level, which where:
means that there is only a 1 in 20 chance that the true cycle rate S3 = standard deviation of results for three test runs,
could be outside of this interval. A3 = (X1)2 + (X2)2 + (X3)2, and
B3 = (1/3) 3 (X1 + X2 + X3)2.
A1.3 Calculating the uncertainty not only guarantees the NOTE A1.4—The A quantity is the sum of the squares of each test result,
maximum uncertainty in the reported results, but also is used to while the B quantity is the square of the sum of all test results multiplied
by a constant (one third in this case).
determine how many test runs are needed to satisfy this
requirement. The uncertainty is calculated from the standard A1.4.2 Step 2—Calculate the absolute uncertainty in the
deviation of three or more test results and a factor from Table average for each parameter listed in Step 1. Multiply the
A1.1, which lists the number of test results used to calculate the standard deviation calculated in Step 1 by the Uncertainty
average. The percent uncertainty is the ratio of the uncertainty Factor corresponding to three test results from Table A1.1. The
to the average expressed as a percent. formula for the absolute uncertainty (three test runs) is as
follows:
A1.4 Procedure: U 3 5 C3 3 S 3 (A1.3)
NOTE A1.2—See A1.5 for an example of applying this procedure. U3 5 2.48 3 S3

where:
TABLE A1.1 U3 = absolute uncertainty in average for three test runs, and
Test Results, n Uncertainty Factor, Cn C3 = uncertainty factor for three test runs (see Table A1.1).
3 2.48
A1.4.3 Step 3—Calculate the percent uncertainty in each
4 1.59 parameter average using the averages from Step 1 and the
5 1.24 absolute uncertainties from Step 2. The formula for the percent
6 1.05
7 0.92
uncertainty (three test runs) is as follows:
8 0.84 % U3 5 ~U3/Xa3! 3 100 % (A1.4)
9 0.77
10 0.72
where:

7
F 1696 – 96 (2003)

% U3 = percent uncertainty in average for three test runs, Xa4 6 U4 (A1.10)


U3 = absolute uncertainty in average for three test runs, If the percent uncertainty is greater than 610 % for the
and energy per rack or cycle rate, proceed to Step 10.
Xa3 = average of three test runs. A1.4.10 Step 10—The steps required for five or more test
A1.4.4 Step 4—If the percent uncertainty, % U3, is not runs are the same as those described above. More general
greater than 610 % for energy per rack and cycle rate, report formulas are listed below for calculating the average, standard
the average for these parameters along with their correspond- deviation, absolute uncertainty and percent uncertainty. The
ing absolute uncertainty, U3, in the following format: formula for the average (n test runs) is as follows:
Xa3 6 U3 (A1.5) Xan 5 ~1/n! 3 ~X1 1 X2 1 X3 1 X4 1 ... 1 Xn! (A1.11)
If the percent uncertainty is greater than 610 % for energy where:
per rack or cycle rate, proceed to Step 5. n = number of test runs,
A1.4.5 Step 5—Run a fourth test for the energy per rack or Xan = average of results for n test runs,
cycle rate results if the percent uncertainty was greater than and
610 %. X1, X2, X3, X4, ... Xn = results for each test run.
A1.4.6 Step 6—When a fourth test is run for a given energy The formula for the standard deviation (n test runs) is as
per rack and cycle rate, calculate the average and standard follows:
deviation for DER and CR using a calculator or the following Sn 5 ~1/=~n 2 1!! 3 ~=~An 2 Bn!! (A1.12)
formulas: The formula for the average (four test runs) is as
follows: where:
Xa4 5 ~1/4! 3 ~X1 1 X2 1 X3 1 X4! (A1.6) Sn = standard deviation of results for n test runs,
An = (X1)2 + (X2)2 + (X3)2 + (X4)2 + ... + (Xn)2, and
where: Bn = (1/n) 3 (X1 + X2 + X3 + X4 + ... + Xn)2.
Xa4 = average of results for four test runs, and The formula for the absolute uncertainty (n test runs) is as
X1, X2, X3, X4 = results for each test run. follows:
The formula for the standard deviation (four test runs) is as U n 5 Cn 3 S n (A1.13)
follows:
where:
S4 5 ~1/=3! 3 =~A4 2 B4! (A1.7)
Un = absolute uncertainty in average for n test runs, and
where: Cn = uncertainty factor for n test runs (see Table A1.1).
S4 = standard deviation of results for four test runs, The formula for the percent uncertainty (n test runs) is as
A4 = (X1)2 + (X2)2 + (X3)2 + (X4)2, and follows:
B4 = (1/4) 3 (X1 + X2 + X3 + X4)2. % Un 5 ~Un/Xan! 3 100 % (A1.14)
A1.4.7 Step 7—Calculate the absolute uncertainty in the
average for each parameter listed in Step 1. Multiply the where:
standard deviation calculated in Step 6 by the Uncertainty % Un = percent uncertainty in average for n test runs.
Factor for four test results from Table A1.1. The formula for the When the percent uncertainty, % Un, is less than or equal to
absolute uncertainty (four test runs) is as follows: 610 % for the energy per rack and cycle rate, report the
average for these parameters along with their corresponding
U4 5 C4 3 S4 (A1.8)
absolute uncertainty, Un, in the following format:
U4 5 1.59 3 S4
Xan 6 Un
where:
U4 = absolute uncertainty in average for four test runs, and NOTE A1.5—The researcher may compute a test result that deviates
C4 = uncertainty factor for four test runs (see Table A1.1). significantly from the other test results. Such a result should be discarded
A1.4.8 Step 8—Calculate the percent uncertainty in the only if there is some physical evidence that the test run was not performed
parameter averages using the averages from Step 6 and the according to the conditions specified in this test method. For example, a
thermocouple was out of calibration, the dishwasher’s input capacity was
absolute uncertainties from Step 7. The formula for the percent
not within 5 % of the rated input, or the dishrack was not within
uncertainty (four test runs) is as follows: specification. To ensure that all results are obtained under approximately
% U4 5 ~U4/Xa4! 3 100 % (A1.9) the same conditions, it is good practice to monitor those test conditions
specified in this test method.
where:
% U4 = percent uncertainty in average for four test runs, A1.5 Example of Determining Uncertainty in Average Test
U4 = absolute uncertainty in average for four test runs, Result:
and
A1.5.1 Three test runs for the washing energy performance
Xa4 = average of four test runs.
yielded the following cycle rate (CR) results:
A1.4.9 Step 9—If the percent uncertainty, % U4, is not
Test CR, racks/h
greater than 610 % for energy per rack and cycle rate, report Run No. 1 33.8 %
the average for these parameters along with their correspond- Run No. 2 34.1 %
ing absolute uncertainty, U4, in the following format: Run No. 3 31.0 %

8
F 1696 – 96 (2003)
A1.5.2 Step 1—Calculate the average and standard devia-
tion of the three test results for the CR. The average of the three Xa4 = (1/4) 3 (X1 + X2 + X3 + X4)
test results is as follows: Xa4 = (1/4) 3 (33.8 + 34.1 + 31.0 + 32.5)
Xa4 = 32.9 racks/h
The new standard deviation is as follows. First calculate A4
Xa3 = (1/3) 3 (X1 + X2 + X3) and B4:
Xa3 = (1/3) 3 (33.8 + 34.1 + 31.0)
Xa3 = 33.0 racks/h
The standard deviation of the three test results is as follows. A4 = (X1)2 + (X2)2 + (X3)2 + (X4)2
First calculate A3 and B3: A4 = (33.8)2 + (34.1)2 + (31.0)2 + (32.5)
A4 = 4323
B4 = (1/4) 3 [(X1 + X2 + X3 + X4)2]
A3 = (X1)2 + (X2)2 + (X3)2 B4 = (1/4) 3 [(33.8 + 34.1 + 31.0 + 32.5)2]
A3 = (33.8)2 + (34.1)2 + (31.0)2 B4 = 4316
A3 = 3266 The new standard deviation for the CR is as follows:
B3 = (1/3) 3 [(X1 + X2 + X3)2]
B3 = (1/3) 3 [(33.8 + 34.1 + 31.0)2]
B3 = 3260 S4 = (1/ =3! 3 =~4323 2 4316!
The new standard deviation for the CR is as follows: S4 = 1.53 racks/h
A1.5.7 Step 6—Recalculate the absolute uncertainty using
the new standard deviation and uncertainty factor as follows:
S3 = (1/ =2! 3 =~3266 2 3260!
S3 = 1.73 racks/h
A1.5.3 Step 2—Calculate the uncertainty in average as U4 = 1.59 3 S4
follows: U4 = 1.59 3 1.53
U4 = 2.43 racks/h
A1.5.8 Step 7—Recalculate the percent uncertainty using
U3 = 2.48 3 S3 the new average, as follows:
U3 = 2.48 3 1.73
U3 = 4.29 racks/h
A1.5.4 Step 3—Calculate percent uncertainty as follows: % U4 = (U4/Xa4) 3 100 %
%U4 = (2.43/32.9) 3 100 %
% U4 = 7.39 %
% U3 = (U3/Xa3) 3 100 %
A1.5.9 Step 8—Since the percent uncertainty, % U4, is less
%U3 = (4.29/33.0) 3 100 %
% U3 = 13.0 % than 610 %, the average for the CR is reported along with its
corresponding absolute uncertainty, U4, as follows:
A1.5.5 Step 4—Run a fourth test. Since the percent uncer-
tainty for the CR is greater than 610 %, the precision CR: 32.9 6 2.43 racks/h
requirement has not been satisfied. An additional test is run in
an attempt to reduce the uncertainty. The CR from the fourth The CR can be reported assuming that the 610 % precision
test run was 32.5 racks/h. requirement has been met for the corresponding washing
A1.5.6 Step 5—Recalculate the average and standard devia- energy per rack value. The washing energy per rack and its
tion for the CR using the fourth test result. The new average absolute uncertainty can be calculated following the same
CR is as follows: steps.

9
F 1696 – 96 (2003)

APPENDIX

(Nonmandatory Information)

X1. RESULTS REPORTING SHEETS

10
F 1696 – 96 (2003)

11
F 1696 – 96 (2003)

ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.

This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).

12

Anda mungkin juga menyukai