CENTRIFUGAL CHILLER
SKM Centrifugal
R-134a
REFRIGERANT
COP
6.9
1
Chiller SKM Water Cooled Centrifugal
About Us...
INTRODUCTION
S.K.M Air Conditioning LLC is one of the leading manufacturers of HVAC (Heating, Ventilation and Air Conditioning) equipment in the Gulf. It was founded
with a single-minded objective; to meet the growing needs of indoor environment quality in some of the world’s harshest climates. Driven by its mission “Total
Customer Satisfaction”, SKM offers a broad portfolio of premium international quality products that have worked efficiently in various geographic locations.
SKM has provided solutions for many blue chip projects for the companies, organisation and government agencies across the region, to view its major projects
portfolios, please follow the link:
www.skmaircon.com/skm_projects
SKM is the proud winner of Sharjah Economic Excellence Award in the Gold category; it is also the recipient of ISO 9001:2015, ISO 14001:2015 and OHSAS
18001:2007 certifications. Additionally SKM products are certified by internationally recognised testing, and certification bodies such as AHRI Certified Air Cooled
Chilling package, AHRI Certified - Chilled Water / Hot Water Coils, TÜV certified Hygienic Air Handling Units and unitary Packaged Air Conditioners. To know
more about the certifications it received, please follow the link:
www.skmaircon.com/certificates
2
R-134a
R-410A
REFRIGERANT
SKM
Centrifugal
SKM Water Chiller
Centrifugal
Key features:
• High efficiency Chiller with COP up to 6.9 at AHRI conditions. • Cooler & Condenser tubes are triple grooved to
• High Efficiency 2 stage Impeller, with ensure reliability.
dual expansion cycle. Ensures wide
• Environment friendly R-134a
range of operation.
refrigerant.
• Low Noise design with Shroud type
• Built in type oil pump & refrigerant cooled oil cooler.
impeller.
• High-Performance Control Center with 7.5” Color Touch
• Continuous operation from 10%~100%,
Screen
through efficient control of Inlet Guide
• Compatible with most of building management system
Vane & Movable Diffuser.
(BMS) protocols.
efficiency.
• Electronically controlled High and Low
Expansion valves for optimum refrigerant. level
control.
• high-performance “THERMOEXCEL”
heat transfer tubes for both cooler &
condenser.
Motor
High-efficiency motor
Refrigerant cooled system
Economizer
)Ultra High-efficiency model(
3
Fe a tu re s o f th e COP
Ce n tu ry’s Hig h - e ffic ie n c y R - 1 3 4 a Ce n trifu g a l Wa te r Ch ille r h a s
Hig h -e fficie n cy R-13 4kW/RT
Fe aFetuareture effic&rea lizie enBdc&yee2n-esnBrtag gyeees acfits
nvineg thfits a C e n trifu g a l W a te r
r o u g h im p le m e n ta tio n o f a H ig h -
Economizer (Ultra High-efficiency model) 6.9
o m p r e s s o r a n d th e m o s t u p - to - d a teCeh enatut ry’s Hig h - e ffic ie n c y R - 1 3 4 a Ce n trifu g a0.509
Evaporator and Condenser
l Wa te r Ch ille r h a s
Chiller
tra n s fe r tu b e . Cu s to m e r's s a tis fa c tio n w ithSKM
th e p e rfo rm aWater d e d e n eCooled
n cree aanliz r g y s a vin g th r o uCentrifugal
· The newest high-performance heat transfer
tube. g h im p le m e n ta tio n o f a H ig h -
re lia b ility o f th e Ce n tu ry’s Hig h - e ffic ie n c y Ce n trifu g a l Wa te re ffic ie nrchy·aSub-cooling
Ch ille 2s -esatarngeed citosystem
m ps rtae(Condenser)
its s s oars athn ed bthe set sme llin
tus o s tg uCh
p -ille
to -rdoantethhe e a t
tra n s fe r tu b e . Cu s to m e r's s a tis fa c tio n w ith th e p e rfo rm a n c e a n d
Fe a Nomenclature smoea frkHig
tuFerea stuoref th
e t.
th e hHig h -e fficie
-e fficie n cy R-13
n cy R-13 4 a C4ean Ctrifu
e ngtrifu
a l WgreaalialteW r aCte rilleCrh ille r
b ility ohf th e Ce n tu ry’s Hig h - e ffic ie n c y Ce n trifu g a l Wa te r Ch ille r h a s
Ce n tuCe ry’sn tuHig
ry’sh -EnHig h ie- ennffic
viro
e ffic
SKM
c y eieRnn-tac1 y3l-frie
m
Centrifugal
4Ra- 1Ce
Water
n3d4nlyatrifu
Chiller
CCee ngntrifu
atrifu
l Wa ggaatell rWa
Cooling
WCh ateteille
rr ChCr hhille
Capacity
a s mrr ahrk
ille a se t.
COP COP
.VersionNo kW/RT kW/RT
r e a liz e d e n e r g y s a vin g th r o u g h im p le m e n ta tio n o f a H ig h -
6.96.9 0.509
C ENTURY C entrifugal Water C hiller C ooling C apacity (Refer to the Version No.
r e a liz e d e n e r g y s a vin g th r o u g h im p le m e n ta tio )Refer We h a ve s ig n nstandard
ific a o ftoathespecificution)
n tly d Hstandard
e c ig h - specificution(
re a s e d th e a m o u n t o f CO p ro d u c tio n th ro u g h re a liza tio n o f a Hig h -
0.509
2
e ffic ie n c y 2 - s ta g e c o m p r e s s o r a
e ffic ie n c y 2 - s ta g e c o m p r e s s o r a n d the efficmie nocsyt muopd-eton d th e m o s t u p - u c che es safut l a p p lic a tio n o f a re frig e ra n t, R - 1 3 4 a , w h ic h is c o m p le te lyh to
to
l a-ndd as te - d a te Enh eviro
a t n m e n ta l-frie n d ly C e n trifu g a l W a te r C illexinr -
trar ntus fe
b er. tu
Cub se to. Cu
m es r's to ms ea r's tis fas ac tis
tio fa
n cwtio
fre e nw withith
ith th e p ethrfo
ze ro eo zop ne erfo
rm a nrm c e aa nn cde a n d
d e p le tio n p o te n tia l. We h a ve s ig n ific a n tly d e c re a s e d th e a m o u
tra n s fe
re lia bre lia ob fility
ility
STR
Ce
th eoCe
n tu ry’s
f thnetuCe --Hig h
ry’sn tuHig
- e ffic
ry’sh -Hig U
ie n c y R - 1
e ffich ie- enffic
3 4 a Ce1000
n trifu
c y ieCen cnytrifu
g a
Ce ng trifu l Wa te r
a l Wag atel rWa
Ch illeH
Chteille
r h
r Cha s th
r hille
e lo w e s t1to ta l
a s re ha arns eeda itrnits
--
refrig
e d sittaitstusestffic
e ra n V
e mieisn sc io
ta
a stus
y nms orad etel ainnsth
th ea sb eths et sbeellin
dt sesuin
g eCh
dc ue ss gtry.
cllin
illeCh
s fu l aille
r o n thr eo n th
p p lic a tio n
m a rk e t. fre e w ith ze ro o zo n e d e p le tio n p o te n tia l.
m a rk e t. De sig n O p tim iza tioUse n o f Im p e lle r Usin g Nu m e ricaCel An tun ry’s a lysisHigohf- eFlo fficwie nPa
c y ssa
R - 1g3 e4 a Ce n trifu g a l Wa te r Ch ille r h a s th e lo w e
Use Refrigerant : R-134a
We h a ve g re a tly in c re aUs :eUltra
d thHigh
e e efficiency
ffic ie n c Model
y o f th e c o m p re s s o r bRefrigerant : R- 134a
y im p ro vin g th e im p e lle r’s flo w p a s s a g e a n d b y a p p lyin g
Ennviro
En viro m ennmta eron-ta
h ydl-frie
l-frie
d ynna d
m ly
nllydeolypntimCtrifu
ic a C
e High-
Eu:m
ngretrifu lluWgtiomodel
avoefficiency
E : High-efficiency aanmodel
lsteW
U : Ultra High efficiency Model
amtehin urille
p err C
C h ille ritio nsig, wNo
te . rIn a d dDe ne hO p tim
a ve
Marks izadState
u :tilize
Solid tio
a snu poe fr-Im
p re pc ise iollen ra Usin
lu m ingu mNu my eforica
a llo r o ulr A n a lysis
im p e lle r, w h ic h p o s s eWe s sGe s:hStandard-
aa nveid se aigperformance
l n3 D
ific
model
s ah anptly
e thdaet chre a da bs eeedn th c a ereVafu: mllyNo
ore
Marks : Standard
viet wo ef dCOth ro u g h ddue ctatio
ile nd athn aro
lys is o f reitsa sliza
tru c tu re
hoa uvenVFD :fuaVFD
nCO road2s uepcdro roieungchy oreuf gathhliza o mnp roetio
fs sano rHig
obf yahim
-Hig
Starter
We h a ve s ig n ific a n tly d e c re a s e d th e We a m tg Vre
o tly Starter
in
2 p c re th ne ethffic
tio e c tio pro
a n d flo w .
e ffic ie n c y m o d e l a n d s u c c e s s fu l
e s cs tufurel athprop hlic a p p lic a tio n
yd ro - dnyno af ma icrea lly o f a re frig e ra n t, R -
o p timnut,mRre- 1vo3 4luatio 1 3 4 a , w
n sh picehr m h ic h is c o m p le te
, w e- h xi
in u te . In a d dlyitiotonxinly to av
We h a ve a ls o a de offic
p teied na nc yidm e a ol dfloe wl apna sds as guec sc tru u g ah tio
d e ta ile d n u mfrig e ricearal a n a lys is o f CF,Dwflu id floisw cfoorme apcleh te
p a rts
fre
frewep wa sith
a n d c o m b in e d flo
e
s a gze
w ith ze ro o zo n
e throa tomzoa knee udp ethpeleptio
e d e p le tio
a thns po fore
n
tefrig pimo te
p enlletiar, l.w h ic h p o s s e s s e s a n id e a l 3 D s h a p e th a t h a d b e e n c a re fu lly
n tiae ral. n t s u c h a s th e im p e lle r, d iffu s e r, d e - s w irle r, a n d c a s in g .
Feature Ce& nBenefits
Ce n tu ry’s Hig h - e ffic ie n c y R - 1 3 4 a Ce n trifu g a l Wa te r Ch ille r ahnads flo
e loh th
w . w e s t to ta l refrig e ra n t e m is s io n s ra te in th e in d u s try.
w ee slot to
Fe a tu re & B e n e fits
tu ry’s Hig h - e ffic ie n c y R - 1 3 4 a Ce n trifu g a l Wa te r Ch ille r h a s thWe ta l refrig e ra n t e m is s io n s ra te in th e in d u s try.
a ve a ls o a d o p te d a n id e a l flo w p a s s a g e s tru c tu re th ro u g h d e ta ile d
Features of the High-efficiency R-134a Centrifugal a n d c o m b in e d flo w p a s s a g e th a t m a k e u p th e p a th s o f re frig e ra n t s u c h
Water De sig n O p tim iza tio n o f Im p e lle r Usin g Nu m e rica l A n a lysis o f Flo w Pa ssa g e
a C e n trifu g a l WChiller
a teDer C hsig ille nr O p tim M e izarid io ntio
a l S tantico f Im p e lle r Usin g Nu m e rica l A n a lysis o f Flo w Pa ssa g e
P re s s u re Co n to u r
Co m p re s s o r
P e rfo rm a n c e
We h a ve g(1res t Satatly
g e ) in c re a s e d th e e ffic ie n c y o f th e c o m p re s s o r b y im p ro vin g th e im p e lle r ’s flo wP repdaic stiosna g e a n d b y a p p lyin
Wa te r Ch ille r h a s
Fe a tu re & B e n e fits
We h a ve
h
COP
Fe
yd ag tu
ro
re aretlys oinfcth
- d yn a m ic
r e ea sHig
a lly o
e d kW/RT
p tim
th
h -ee efficieffic ienncy c y R-13o f th e4 ac oCmepnretrifu s s o rg ba yl W im ap te ro rvinCgh th illeue rtilize
im p e lle r ’s flo w p a s s a g e a n d b y a p p lyin g
re vo lu tio n s p e r m in u te . In a d d itio n , w e h a ve u tilize d a s udp ae r-s uppree r-
u m re vo lu tio n s p e r m in u te . In a d d itio n , w e h a ve c ispiorenc aisluiomn ina luu mm ina llo
u my fo a llo
r oyufor r o
n ta tio n o f a H ig h -
h yd ro - d6.9 yn a m ic a lly o p tim u m0.509 M e rid io n a l S ta tic
0
04
05
5
Ce nt ur
C e n t u ry
1st Stage
1st Stage
2nd Stage
04
C e n t u ry 05
5
4 To ta l P re s s u re
R-134a
R-410A
REFRIGERANT
2016
2016 _ through
( )_D- major
_( )_D- 17.decrease
17.
7. 4.7. 4. 5:505:50ofPage
Page 7load
7 on the compressor.
• Realized High-efficiency cycle and system through application of a sub-
cooling system and a precise control of expansion valve which carefully This leads to decrease in pressure ratio of the compressor and thus one can
considered the effect of part load. save the cost of power consumption through major decrease of load on the
• The newest and energy-saving high-performance heat transfer tube compressor.
• High-efficiency electric motor. • Heat Transfer Tube for Evaporator “THERMOEXCEL-EKW” In order to
accelerate the boiling process and increase bubble point, a tunnel shall be
Water operated in the lower region of the surface towards the direction of the
Energy
Energy circumference.
savingHigh-performance
saving This allowsHeat
High-performance the Transfer
Heat refrigerant
TransferTube Tube to evaporate quickly and thus
Energy
TheEnergy
The provides complete and continuous boiling
heat
heat saving
saving
transfer
transfer High-performance
ratesHigh-performance
rates ofof the
the evaporator
evaporator and
and HeatHeat Transfer
condenser
condenser Transfer
have
have Tube
been
been Tubeprocess.
significantly
significantly improvedthrough
improved throughthetheuse
useofofaahigh-
high-
performance heattransfer
transfer tube, “THERMOEXCEL.” Asaaresult,
result,condensation
condensationtemperature
temperaturebecomes
becomeshigher,
higher,evaporation
evaporation
er the performance
Also,
heat
the oftube,
Evaporator
“THERMOEXCEL.”
shall
As
perform triple grooving and ridge in
theorder to
Power Consumption
•
••Heat
HeatTransfer
TransferTube
bubblepoint,
bubble
Tubefor
point,aatunnel
forEvaporator
tunnelshall
Evaporator“THERMOEXCEL-EKW”
shallbe beoperated
“THERMOEXCEL-EKW”InInorder
Heat Transfer Tube for Condenser “THERMOEXCEL-CKW” to allow the
operatedininthe thelower
lowerregion
regionofofthe
ordertotoaccelerate
thesurface
acceleratethe
surfacetowardstowardsthe
theboiling
boilingprocess
thedirection
processand
directionofofthe
andincrease
increase
thecircumference.
circumference.
rough • Heat
• Heat
This
bubble
Transfer
bubble
Transfer
point,
point,
Tube Tube
a tunnel
for for
a tunnel
Evaporator
shall
Evaporator
shall
be operated
“THERMOEXCEL-EKW”
be operated
“THERMOEXCEL-EKW”
refrigerant to condense and drip easily, the condenser shall be operated
Thisallows
allowsthe therefrigerant
refrigeranttotoevaporate
evaporatequickly
quicklyand
in the
in the
andthus
lowerlower
region
region
In order
thusprovides
of the
In order
providescomplete
of the
to accelerate
completeand
surface
surface
to accelerate thethe
andcontinuous
towards
boiling
boiling
continuousboiling
towards thethedirection
process
process
andand
boilingprocess.
direction
process.
of the
of the
increase
increase
circumference.
circumference.
Also,the
Also, thecondenser
condensershall shallperform
performdouble
doublegrooving
groovingand andridge
ridgeininorder
ordertotoenhanceenhancethe theheat
heattransfer
transferefficiency
efficiencyofofthe the
ecise in the shape of a Micro-Fin which has a sharp tip. Also, the condenser
ThisThisallows
allows
chilledwater.
chilled
thethe
water. As
refrigerant
refrigerant
Asaaresult,
to evaporate
result,the
to evaporate
theheat
quickly
heattransfer
quickly
andandthusthus
transferperformance
provides
performancehas
providescomplete
hasbeen
complete
beenimproved
andandcontinuous
improvedover
continuous
overthe
boiling
boiling
theprevious
process.
process.
previoussingle
singlegrooving
groovingand and
Also, Also,
thethe
condenser
condenser shall shall
perform
perform double
double grooving
grooving andand
ridge
ridge
in order
in order to enhance
to enhance thetheheatheattransfer
transfer
efficiency
efficiency
of theof the
Feature & perform
shall Benefits
ridgeheattriple grooving and ridge in order to enhance the heat transfer
heattransfer
transfertubes.
tubes.
dered ridge
chilled
chilled
•Heat
water.
HeatTransfer
•ridge
water. As a
TransferTube
Asresult,
a result,
Tubefor
thethe
forCondenser
heatheat
transfer
transfer
Condenser“THERMOEXCEL-CKW”
performance
performance
“THERMOEXCEL-CKW”totoallow
hashasbeen beenimproved
allowthe
improved overover
therefrigerant
thetheprevious
refrigeranttotocondense
previous
single
condenseand
single
grooving
anddrip
grooving
dripeasily,
andand
easily,thethe
efficiency of the cooling water. As a result, the heat transfer rate
ridge
heatheat
condenser
transfer
condensershall
transfer
shallbe
tubes.
tubes.
beoperated
operatedininthe theshape
shapeofofaaMicro-Fin
Micro-Finwhich
whichhas hasaasharp sharptip. tip.Also,
Also,the thecondenser
condensershall shallperform
perform
• Heat
• Heat Transfer
Transfer Tube Tube
for for
Condenser
Condenser “THERMOEXCEL-CKW”
“THERMOEXCEL-CKW” to allow
to allow thethe refrigerant
refrigerant to condense
to condense andand
dripdrip
easily,
easily,
thethe
has been improved over the previous groove and protrusion
doublegrooving
double
condenser
High-efficiency
groovingand
condenser shall
shall
andridge
ridgeininorder
be operated
be operated
ordertotoenhance
in the
in the
shape
enhancethe
shape
theheat
heattransfer
of aofMicro-Fin
a Micro-Fin
transferefficiency
which
which
efficiencyofofthe
hashas a sharpa sharp
thecooling
tip. tip.
coolingwater.
Also,Also,
thethe
water.As
condenser
Asaaresult,
condenser
result,the
shallshall
theheat
perform
heat
perform
e heat Standard High heat transfer tubes.
transferrate
transfer
doubledouble
ratehas
grooving
hasbeen
grooving
beenimproved
andandridge
improvedover
ridge
in order
overthe
in order
theprevious
to enhance
previousgroove
to enhance thethe
grooveand
heatheat
andprotrusion
transfer
protrusionheat
transferefficiency
efficiency
heattransfer
of the
transfertubes.
of the
cooling
tubes.
coolingwater.
water.
As aAsresult,
a result,
thetheheatheat
• Century’s
transfer High-efficiency
transferraterate
hashas
been beenR-134a
improved
improved Centrifugal
overover
thethe Water
previous
previousgroove
groove
andand
protrusion
protrusion heatheattransfer
transfertubes.
tubes.
efficiency Chillers offer the highest efficiency in the industry,
• We have achieved energy saving of 6~8% over the
Power Consumption
Control of Wide Range of Capacities previous 1-stage cycle model by adopting an economizer
based 2-stage compression system.
• High-efficiency Closed Shroud Impeller
Continuous operation is possible from 10%~100% through efficient associated • Realized High-efficiency cycle and system through
application of a sub-cooling system and a precise
control of inlet guide vane, movable diffuser, and hot gas bypass. control of expansion valve which carefully considered
Part load performance
Realization of ais Low
further Noise
improvedProduction
through use of moveable
Systemdesigned the effect of part load.
variable inlet guide vanes. Inlet guide vanes improve performance by throttling • The newest and energy-saving high-performance heat
InternalComposition
Internal
transfer tube
Compositionofofan anOld-model
Old-modelHeat
HeatTransfer
TransferTube
Tube InternalComposition
Internal Compositionof Standard
ofTHERMOEXCEL-EKW,
THERMOEXCEL-EKW, High
CKW
CKW
efficiency
rough refrigerant
R -134agas flow to exactly
centrifugal meetchiller
water part loadhas
requirements
greatly and by pre-rotating
decreased • High-efficiencyInternal
Internal electric motor.
Composition
Composition of anofOld-model
an Old-model
HeatHeat Transfer
Transfer TubeTube Internal
Internal
Composition
Compositionof THERMOEXCEL-EKW,
of THERMOEXCEL-EKW, CKWCKW
as for operates
design whichexceptionally quietly. pressure.
exceeds the atmospheric
and by pre-rotating refrigerant gas for
Realization of a Low Noise Production
operates exceptionally quietly.
System
NoThebleeding devicesrotating
are necessary as the chiller is completely free from the
optimum entry into the impeller. The smoothly rotating Century compressor is inherently06 06
07
0777
smoothly Century compressor is inherently
Century
Century
quietest than other compressor types.
influx of anythan
non condensates, which hastypes.
lowered the chiller’s efficiency in the Safe Performance
07
06 06
7
077 Century
Century
chiller assembly the low speed, direct drive design operates exceptionally quietly.
pressure centrifugal water chillers (R -11, R -123).
R -134a guarantees the chiller’s long life performance as
ler is
sates,
d low- S.K.M Air Conditioning LLC
nce as 5
O p e ra tio n S ta tu s D isp la y C o n v e n ie n t C a p a c ity C o n tro l A la rm Histo ry
Fe a tu re & B e n Chiller
e fits U s e r s m a y g r a p h ic a l l y c h e c k t h e
c h ille r’s o p e ra tio n s ta tu s s u c h a s th e
SKM Water Cooled SCentrifugal
Us e rs m a y e a s ily c on trol th e c a p a c ity
tore u p to 1 2 8 m a lfu nc tioning h
c ontrol va lve m a nu a lly or a u tom a tic a lly. a nd m a y inte rpre t th e c a u s e of a
p r e s s u r e , te m p e r a tu r e , a n d c o n tr o l s toring u p to 8 ope ra tion da ta f
mCentrifugal
o to r’s o p e n in gWater
ra te . Chiller a la rm ite m s w h e n a la rm is trig g
Supportsusing
c aan
u s e Ethernet-based
a y e a s ily c o n tro l th e c a p a c ity th e S tore u pvatolve 1m2a8numa llya lfu Protocol (Option) PC from a
c h ille r’s o p e ra tio n s ta tu s s u c h a s c ontrol or anc tioning
u tom a tic a lly.h a nd m a y inte rpre t th e of a
Modbus
a lve mp rae nu
s s u r e , te m p e r a tu r e , a n d c o n tr o l
a lly or a u tom a tic a lly. a nd m a y inte rpre t th e c a u s e of a s toring u p to 8 ope ra tion da ta f
remoteis location without having to
m o to r’s o p e n in g ra te . a laModbus
rm ite m protocol
s w h e n a laisrm
providedtrig g in standard form to allow users to monitor and
s toring u p to 8 ope ra tion da ta f travelconfigured
or control (modify to the site.
values, remote operation) the chiller’s operation
Convenient Capacity a la rm ite m s w h e n a la rm is trig g and alarm status through RS-485 communication. PC Monitorin
Control
Users may easily control the capacity PC Monitoring (Option)
control valve manually or automatically.
Support Variable
Operator may monitor and or control the chiller installed on the site by using an
Ethernet-based PC from a remote location
communication without having to travel to the site.
Protocol
- Modbus RS485
- Modbus TCP/IP (Option)
- CANopen (Option) Monitorin
(Use
6
• High Oil Temperature Alarm communication.
• Low Oil Temperature Alarm
e fits • Freezing Prevention Alarm R-134a
• High Condenser Pressure Alarm R-410A
REFRIGERANT
g ra pSKM
h ic a- lly d isCentrifugal
Modbus la ys th e c h ille r’s o p e ra tio n s ta tu s , a la rm h is to- ry
pRS485 TouchScreen(support
m a n a g e m e nmodel
t, reofm o te
- Modbus TCP/IP (Option) Ethernet:(Option)
h ic h a llo-wCANopen
s fo r c(Option)
o n ve n ie n t c o n tro l a n d o p e ra tio n . In a d d itio n-, Exclusive
th e P reSoftware
- Ala rm fe a tu re m
(Option)
a n d ta k e a p p ro p ria te m e a s u re s a t th e s a m e tim e .
System Configuration
- MonitoringComputer(User’sPC)
- EthernetCable+ IPAddress
tin g c a n b e c h a n g e d w ith a s in g le to u c h o n th e to u c h s c r e e(User’sScope)n . Th e c o n tr o l c e n te r p
el Water
a s th e Chiller - TouchScreen(support model of Ethernet:
b a s ic o p tio n s w h ile o th e r la n g u a g e s a re a va ila b le p e r o rd e r.
(Option)
- Exclusive Software (Option)
e & B e n e fits
- MonitoringComputer(User’sPC)
C o n tro l C e n te r
trol
- EthernetCable+ IPAddress(User’sScope)
System Configuration
ring System S/W - TouchScreen(support model of Ethernet:
by
to u c h s c re e n g ra p h ic a lly d is p la ys th e c h ille r’s o p e ra tio n s ta tu s , a la rm h is to ry m a n a g e m e n t, re m o te
d o p e ra tio n , w h ic h a llo w s fo r c o n ve n ie n t c o n tro l a n d o p e ra (Option)
tio n . In a d d itio n , th e P re - Ala rm fe a tu re m
m a
m in a te e rro rs a n d ta k e a p p ro p ria te m e a s u re s a t th e s a m e-tim Exclusive
e. Software (Option)
laton g u a g e s e ttin g c a n b e c h a n g e d w ith a s in g le to u c h o n th e to u c h s c r e e n . Th e c o n tr o l c e n te r p
- MonitoringComputer(User’sPC)
h , a n d Ch in e s e a s th e b a s ic o p tio n s w h ile o th e r la n g u a g e s a re a va ila b le p e r o rd e r.
P L C Co n tro lle r Co lo r L CD To u c h S c re e n Dis p la y Win d o w
-PC
EthernetCable+ IPAddress(User’sScope)
Monitoring System S/W
PC Monitoring System S/W
Ethernet
Ethernet
y C o n v e n ie n t C a p a c ity C o n tro l A la rm Histo ry
h e c k th e Us e rs m a y e a s ily c on tro l th e c a p a c ity S tore u p to 1 2 8 m a lfu nc tioning h
c h a s th e c ontrol va lve m a nu a lly or a u tom a tic a lly. a nd m a y inte rpre t th e c a u s e of a
Monitoring Computer
P L C Co n tro lle r
Monitoring Computer
Co lo r Touch
L CD To u c hScreen
S c re e n Dis p la y Win d o w
Touch Screen s toring u p to 8Centrifugal Centrifugal Chiller
d c o n tr o l ope ra tionChiller
da ta f
ring Computer )User’s
(User’s PC)PC( Touch Screen Centrifugal Chiller
a la rm ite m s w h e n a la rm is trig g
ser’s PC)
ta tu s D isp la y C o n v e n ie n t C a p a c ity C o n tro l A la rm Histo ry
r a p h ic a l l y c h e c k t h e Us e rs m a y e a s ily c o n tro l th e c a p a c ity S tore u p to 1 2 8 m a lfu nc tioning h
tio n s ta tu s s u c h a s th e c ontrol va lve m a nu a lly or a u tom a tic a lly. a nd m a y inte rpre t th e c a u s e of a
m p e r a tu r e , a n d c o n tr o l s toring u p to 8 ope ra tion da ta f
n g ra te . a la rm ite m s w h e n a la rm is trig g 08
Century 09
9
Note
1. Fouling Factor for chilled water and cooling water : 0.0001 m2h /kcal. 4. The standard starting method is Solid State .
2. Maximum operational pressure is 10kg/cm2G for chilled water and cooling 5. Product standards and specifications are sub ject to change
water. Higher pressure can also be used. Please contact our company when without notice due to product reform.
the operational pressure exceeds 10kg/cm2G.
3. The standard voltages for the main power are as fol lows. 3ø/60(50)Hz/380V,
440V, 3300V, 6600V
8
R-134a
R-410A
REFRIGERANT
Note
1. Fouling Factor for chilled water and cooling water : 0.0001 m2h /kcal. 4. The standard starting method is Solid State .
2. Maximum operational pressure is 10kg/cm2G for chilled water and cooling 5. Product standards and specifications are sub ject to change
water. Higher pressure can also be used. Please contact our company when without notice due to product reform.
the operational pressure exceeds 10kg/cm2G.
3. The standard voltages for the main power are as fol lows. 3ø/60(50)Hz/380V,
440V, 3300V, 6600V
9
S ta n d a rd OChiller SKM
u tlin e D ra w in g s (TR-U typWater
e) Cooled Centrifugal
S ta n d a rd O u tlin e D ra w in g s (TR-U typ e )
Standard
TR-U Outline
2 0 0 H1~ U6 0 0 H1Drawings (STR-U type)
TR-U 2 0 0 H1~ U6 0 0 H1
STR-U200H1~U600H1
C O O L IN G W A T E R C O O L IN G W A T E R
O UTL E T IN L E T
C O O L IN G W A T E R C O O L IN G W A T E R
O UTL E T IN L E T
C H IL L E D W A T E R
O UTL E T
C H IL L E D W A T E R
O UTL E T
C H IL L E D W A T E R
IN L E T
C H IL L E D W A T E R
IN L E T
C O O L IN G W A T E R IN L E T
C O O L IN G W A T E R IN L E T
C O O L IN G W A T E R O U T L E T
C O O L IN G W A T E R O U T L E T
C H IL L E D W A T E R O U T L E T
C H IL L E D W A T E R O U T L E T
C H IL L E D W A T E R IN L E T
C H IL L E D W A T E R IN L E T
10
C e n t u ry 11 0 1
C e n t u ry 11
10
R-134a
R-410A
REFRIGERANT
SKMModel
Centrifugal
Devision Units 380V (440V) 3,300V 6,600V
OUTPUT kW 130 130 130
F.L.C A 235.2 (203.1] 26.8 13.5
POWERFACTOR % 90.3 91 90
STR-U200H1
EFFICIENCY % 93 93.2 93.5
INPUT kW 139.8 139.5 139
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
OUTPUT kW 190 190 190
F.L.C A 346.8 (299.5] 39.3 19.6
POWERFACTOR % 90 91 91
STR-U300H1
EFFICIENCY % 92.5 93 93
INPUT kW 205.4 204.3 204.3
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
OUTPUT kW 230 230 230
F.L.C A 410.7 (354.7] 47.8 23.9
POWERFACTOR % 91 90.5 90.5
STR-U400H1
EFFICIENCY % 93.5 93 93
INPUT kW 246 247.3 247.3
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
OUTPUT kW 290 290 290
F.L.C A 517.8 (447.2] 60.3 30.1
POWERFACTOR % 91 90.5 90.5
STR-U500H1
EFFICIENCY % 93.5 93 93
INPUT kW 310.2 3118 311.8
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
OUTPUT kW 350 350 350
F.L.C A 635.3 (548.7] 72.8 36.4
POWERFACTOR % 90 90 90
STR-U600H1
EFFICIENCY % 93 93.5 93.5
INPUT kW 376.3 374.3 374.3
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
OUTPUT kW 410 410 410
F.L.C A 741.8 (640.7] 85.7 42.9
POWERFACTOR % 90 90 90
STR-U700H1
EFFICIENCY % 93.3 93 93
INPUT kW 439.4 440.9 440.9
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
OUTPUT kW 460 460 460
F.L.C A 818.7 (707.1] 94.6 47.6
POWERFACTOR % 91.3 91 90.5
STR-U800H1
EFFICIENCY % 93.5 93.5 93.5
INPUT kW 492 4920 492
START METHOD - Soild-State Starter Soild-State Starter Soild-State Starter
11
Chiller SKM Water Cooled Centrifugal
12
R-134a
R-410A
REFRIGERANT
STR-U1350H1
- U1 750H1-- (50Hz)
STR-U1350H1
STR-U1350H1 U1750H1
U1750H1 (50Hz)
(50Hz)
Model
Model Devision
Devision Units
Units 3,300V
3,300V 6,600V
6,600V 11,000V
11,000V
OUTPUT
OUTPUT kW
kW 760
760 760
760 760
760
F.L.C
F.L.C A
A 157.1
157.1 78.1
78.1 46.7
46.7
POWERFACTOR
POWERFACTOR %
% 91
91 91
91 91
91
STR-U1350H1
STR-U1350H1 EFFICIENCY
EFFICIENCY %
% 93
93 93.5
93.5 93.8
93.8
INPUT
INPUT kW
kW 817.2
817.2 812.8
812.8 810.2
810.2
START
START METHOD
METHOD -- Soild-State
Soild-State Starter
Starter Soild-State
Soild-State Starter
Starter Soild-State
Soild-State Starter
Starter
OUTPUT
OUTPUT kW
kW 850
850 850
850 850
850
F.L.C
F.L.C A
A 174.8
174.8 87.4
87.4 52.3
52.3
POWER
POWER FACTOR
FACTOR %
% 91
91 91
91 91
91
STR-U1500H1
STR-U1500H1 EFFICIENCY
EFFICIENCY %
% 93.5
93.5 93.5
93.5 93.8
93.8
INPUT
INPUT kW
kW 909.1
909.1 909.1
909.1 906.2
906.2
START
START METHOD
METHOD -- Soild-State
Soild-State Starter
Starter Soild-State
Soild-State Starter
Starter Soild-State
Soild-State Starter
Starter
OUTPUT
OUTPUT kW
kW 1,000
1,000 1,000
1,000 1,000
1,000
F.L.C
F.L.C A
A 205.6
205.6 102.8
102.8 61.7
61.7
POWERFACTOR
POWERFACTOR %
% 91
91 91
91 91
91
STR-U1750H1
STR-U1750H1 EFFICIENCY
EFFICIENCY %
% 93.5
93.5 93.5
93.5 93.5
93.5
INPUT
INPUT kW
kW 1,069.50
1,069.50 1,069.50
1,069.50 1,069.50
1,069.50
STARTMETHOD
STARTMETHOD -- Soild-State
Soild-State Starter
Starter Soild-State
Soild-State Starter
Starter Soild-State
Soild-State Starter
Starter
13
Chiller SKM Water Cooled Centrifugal
STR-U1350H1~U1750H1(60Hz)
STR-U1350H1
STR-U1350H1 -- U1750H1
U1750H1 (60Hz)
(60Hz)
Model
Model Devision
Devision Units
Units 3,300V
3,300V 6,600V
6,600V 11,000V
11,000V
OUTPUT
OUTPUT kW
kW 760
760 760
760 760
760
F.L.C
F.L.C A
A 155.1
155.1 75.3
75.3 45.9
45.9
POWERFACTOR
POWERFACTOR %
% 91.7
91.7 93.6
93.6 93
93
STR-U1350H1
STR-U1350H1 EFFICIENCY
EFFICIENCY %
% 93.5
93.5 94.3
94.3 93.5
93.5
INPUT
INPUT kW
kW 812.8
812.8 805.9
805.9 812.8
812.8
START
START METHOD
METHOD -- REACTOR
REACTOR STARTING
STARTING AUTO COMPENSATED
AUTO COMPENSATED REACTOR
REACTOR STARTING
STARTING
OUTPUT
OUTPUT kW
kW 850
850 850
850 850
850
F.L.C
F.L.C A
A 173.4
173.4 85
85 51.3
51.3
POWERFACTOR
POWERFACTOR %
% 92.2
92.2 92.8
92.8 93
93
STR-U1500H1
STR-U1500H1 EFFICIENCY
EFFICIENCY %
% 93
93 94.3
94.3 93.5
93.5
INPUT
INPUT kW
kW 914
914 901.4
901.4 909.1
909.1
START
START METHOD
METHOD -- REACTOR
REACTOR STARTING
STARTING AUTO COMPENSATED
AUTO COMPENSATED REACTOR
REACTOR STARTING
STARTING
OUTPUT
OUTPUT kW
kW 1,000
1,000 1,000
1,000 1,000
1,000
F.L.C
F.L.C A
A 206.8
206.8 102.7
102.7 60.4
60.4
POWERFACTOR
POWERFACTOR %
% 90
90 90.3
90.3 93
93
STR-U1750H1
STR-U1750H1 EFFICIENCY
EFFICIENCY %
% 94
94 94.3
94.3 93.5
93.5
INPUT
INPUT kW
kW 1,063.80
1,063.80 1,060.40
1,060.40 1,069.50
1,069.50
START
START METHOD
METHOD -- REACTOR
REACTOR STARTING
STARTING AUTO
AUTO COMPENSATED
COMPENSATED REACTOR
REACTOR STARTING
STARTING
14
R-134a
R-410A
REFRIGERANT
15
Chiller SKM Water Cooled Centrifugal
Note
1. Fouling Factor for chilled water and cooling water : 0.0001 m2h /kcal. 4. The standard starting method is Solid State .
2. Maximum operational pressure is 10kg/cm2G for chilled water and cooling 5. Product standards and specifications are sub ject to change
water. Higher pressure can also be used. Please contact our company when without notice due to product reform.
the operational pressure exceeds 10kg/cm2G.
3. The standard voltages for the main power are as fol lows. 3ø/60(50)Hz/380V,
440V, 3300V, 6600V
16
R-134a
S ta n d a rd O u tlin e D ra w in g s (TR-E typ e ) R-410A
REFRIGERANT
SKM Centrifugal
C O O L IN G W A T E R O U T L E T C O O L IN G W A T E R IN L E T
C O O L IN G W A T E R O U T L E T C O O L IN G W A T E R IN L E T
C H IL L E D W A T E R O U T L E T
C H IL L E D W A T E R O U T L E T
C H IL L E D W A T E R IN L E T
C H IL L E D W A T E R IN L E T
STR-E700H1~E2700H1
TR-E 7 0 0 H1~ E2 7 0 0 H1
TR-E 7 0 0 H1~ E2 7 0 0 H1
C O O L IN G W A T E R IN L E T
C O O L IN G W A T E R O U T L E T
C O O L IN G W A T E R IN L E T
C O O L IN G W A T E R O U T L E T
C H IL L E D W A T E R O U T L E T
C H IL L E D W A T E R O U T L E T
C H IL L E D W A T E R IN L E T
C H IL L E D W A T E R IN L E T
17
Chiller SKM Water Cooled Centrifugal
18
R-134a
R-410A
REFRIGERANT
19
Chiller SKM Water Cooled Centrifugal
20
R-134a
R-410A
REFRIGERANT
21
Chiller SKM Water Cooled Centrifugal
22
R-134a
R-410A
REFRIGERANT
Centrifugal Water Chiller
Electrical Data For High-Efficiency Model
STR-E 2000H1~E 2700H1(60Hz)
STR-E2000H1~E2700H1 (60Hz)
Model Devision Units
6,600V 11,000V 3,300V
SKM Centrifugal
Electrical Specification For High-Efficiency
OUTPUT
F.L.C
kW
1,300
130.4 A
A nd
1,300Standard
78.5
1,300
263.3
STR- POWERFACTOR % 91.4 91.8 93
TR-E(G )2000H1~E(G )2700H1 Type
E2000H1 EFFICIENCY % 94.5 95 93.5 6 0H z
OUTPUTm m
WIRING CV185 × 3
kW CV185 × 3
1,420 (82) × 1 CV70 × 3 CV70 × 3
1,420 (70) × 1 CV35 × 3
1,420 CV35 × 3 (70) × 1
2
STR-E(G) STARTMETHOD
F.L.C 311.2 156.5
A
- Soild-State Starter Soild-State Starter Soild-State Starter 93.6
POWER FACTOR % 92.2 91.7 93.0
2500H1 OUTPUT kW 1,670 1,67094.5 1,670
EFFICIENCY % 94.5 93.5
INPUT F.L.C kW A 1,640.2 334.6 169.31,640.2 100.8 1,657.8
START METHOD - REACTOR STARTING AUTO COMPENSATED STARTING REACTOR STARTING
STR- POWERFACTOR
WIRING mm CV120 ×% 92.1 (82) × 2
3 (2 Line) CV120 × 3 (2 Line)
2
CV120 × 3 91.3CV120 × 3 (82) × 1 93
CV50 × 3 CV50 × 3 (70) × 1
E2700H1 EFFICIENCY
OUTPUT kW % 1,670 94.8 94.5 1,670 93.5 1,670
F.L.C A 334.6 169.3 100.8
POWER INPUT kW 92.11,761.60 1,767.20 1,786.10
STR-E(G)
FACTOR % 91.3 93.0
2700H1
STARTMETHOD
EFFICIENCY % - Soild-State
94.8 Starter Soild-State Starter
94.5 Soild-State Starter 93.5
INPUT kW 1,761.6 1,767.2 1,786.1
START METHOD - REACTOR STARTING AUTO COMPENSATED STARTING REACTOR STARTING
Electric Wire
FIELD WIRING CONNECTIONS IN ACCORDANCE WITH THE WIRING DIAGRAMS AND
APPLICABLE ELECTRICAL CORDS. TABLE SHOWS THE ARRANGEMENT OF ELECTRICAL
PIPING AND WIRING.
23
a y-O u t Fo r SChiller
ta rte r Pa n e l D im SKM
e n sioWater
n Cooled Centrifugal
Starter Panel
S TAR TE R P AN E L S IZE
M ODE L P OW E R S OUR CE A B C R E M AR K S
TR - U, E , 2 0 0 H1 ~6 0 0 H1 3 8 0 V,4 4 0 V Solid State Starter 800 1 ,0 0 0 2 ,3 5 0 S TAN DAR D
24
R-134a
R-410A
REFRIGERANT
Standard Features:
25
Chiller SKM Water Cooled Centrifugal
Scope of supply for standard centrifugal High-Tech Control Center with Controller.
:chillers 7.5” color LCD touch screen graphically displays the chiller’s operation
status, alarm history management, remote control, and scheduled operation,
Factory assembled, single piece, liquid chiller with compressor, motor, which allows for convenient control and operation
lubrication system, cooler, condenser, initial oil and refrigerant(R-134a)
operating charge, micro-processor control system, and documentation Operation Status Display: Users may graphically check the chiller’s operation
required prior to start-up. status. Alarm History: Store up to 128 malfunctioning histories
Economizer:
Ultra-high efficiency chiller (STR-U200H1 ~ 2,700H1) will be with inter-stage
economizer to improve the efficiency.
26
R-134a
R-410A
REFRIGERANT
NOTES
SKM Centrifugal
27
Chiller SKM Water Cooled Centrifugal