OPU 8810 NORCONTROL Automation AS

'Fable 4-6 Channel Input Parameter Select Codes when C = 0 (Analog Input) with manual scaling

This is only possible when OC=7 and F=O or F=l!


SELECT PARAhETER TYPE EXAMPLE VALUES COMMENTS
CODE

P Parameter Value Measured value for the Cannot be altered


selected channel
C Channel Type 0 (= analog input)

F Scaling Factor 0 or 1 Use CH, CL, CM and


TH,TL,TM.
L Not used

d OPU alarm delay 3 (= 3 seconds)

I OPU alarm Inhibit P (= Passive)


(by another channel)

OC OPU Configuration 7 Used to group related


signals

db deadband 5 Defined change before


logging

CA CAlibration FALSE FALSE = normal


TRUE = calibration
CH Counts High 4000

CL Counts Low 200

a TH Technical High + 150


TL Technical Low - 75
CM Counts M e d i u d i d d l e 2100 Only for F = l

TM Technical MediumlTvIiddle 0 Only for F = l

AC Actual Counts MMX Read only!

DP Dot Point 0-4 Position of period


(dot) in the numbers

Note: With CH the printer will printout the TH value.


With CL the printer will printout the TL value.
With CM the printer will printout the IU value.