SPP Pumps, Inc.

2905 Pacific Drive Norcross, GA 30071 Telephone: 1-770-409-3280 Fax: 1- 770-409-3290

Pump Performance Curve – Test Results

CLIENT/PURCHASER Dragados Offshore De Mexico SA

PROJECT CA-KU-A1 Platform de Compression

CLIENT ORDER NO 85024 / 91021 /CAK-0055

TAG NO.S GA-9001 & GA-9001R

SPP JOB NO US1823002

We are pleased to provide the attached firewater pump no.2 test data (GA-9001R) for your approval.

During pump performance test, it was noted that the pump is consuming slightly higher power than originally
anticipated.

In accordance to project specification 85024-EPI-H-0009_B, 6.1.3, the diesel engine must have a power at
least 20% above the maximum power required by the pump at the speed regime.

The peak power absorbed by the pump is 419.29kW

The net (site) diesel engine nameplate power (de-rated for site conditions) is 485kW

SPP Pumps would advise that as the engine is fully FM Approved (as with all FM approved diesel engines), its
nameplate power (485kw) is 10% less than the actual engine maximum rating.

This effectively means that the current engine maximum power (485 x 1.10 = 533kW) is 27% higher than the
peak power absorbed by the pump (533/419.29 = 27%)

We hope this is acceptable and look forward to receiving your approval of this test data

Our policy is one of continuous improvement and we reserve the right to alter specifications of our products at any time without giving notice.
SPP Pumps Inc
2905 Pacific Drive, Norcross, GA, USA, 30071

TEST CURVE Serial No 1823030/2/B ( Test No 1


Pump Type: GH20F2X Nom. Speed: 1760 rpm
Branches : x 300
Head m
210.00

400
200.00

350
190.00

300
180.00

250
170.00

Efficiency%
200
160.00

150
150.00

100
140.00 80

50
130.00 70

120.000 60

110.00 50

100.00 1 40

90.00 30

80.00 20

70.00 10
Power
kW
600
60.00 0

Max engine rating = 533.5 kW


500
50.00

400
40.00

300
30.00

200
20.00

100
10.00

0.000
0
0.00 20
10.00 40
20.00 60
30.00 80
40.00 100
50.00 120
60.00 140
70.00 160
80.00 180
90.00 200
100.00 220
110.00 240
120.00 260
130.00 280
140.00 300
150.00 320
160.00
Flow l/s
Customer: DRAGADOS DE MEXICO SA
Cust. Order No.
Cust. Item No.
Tested by: Steve Turley
Date: 4/11/2019
PUMP TEST CERTIFICATE Sales Order No 1823030 Pump Type GH20F2X
SPP Pumps Inc Line No 2 Serial No 1823030/2/B (USA-01-18-7955)
2905 Pacific Drive Test No 1
Norcross, GA 30071 Type of test: Production Test Page 1 of 3
Nominal Inlet Dia.: Nominal Outlet Dia.: 300 No. of Stages: 3
Customer: DRAGADOS DE MEXICO SA Cust. Order No:
Application COMPRRESSION PLATFORM CA-KU-A1 (PEMEX) Cust. Item No:
Other Job Data:
Job Liquid: SEAWATER Impeller Details: Test Conditions:
Density kg/m3 1020 Stage 1/1/1900 Stage 3-Feb Test Location:
Viscosity cSt Hyd. Design X Hyd. Design F Rig Type: Open
Liq. Temp degC Figure No. 2 Figure No. 2 Test Liquid: Water
Site Duty Additional Duties Test Duty D1 370 D1 360 Liq Temp degC 0
1 2 D3 D3 SG 1
Speed rpm: 1760.00 1760.00 1760.00 D4 D4 Amb Temp 0
Flow l/s 192.28 286.91 192.28 D5 D5 Bar. Pressure mbar
Head m 141.17 91.76 141.17 E 7.5 E 7.5 Inlet Pipe dia
Efficiency %: T 24 T 7 Outlet pipe dia mm 300
Power kW T1 24 T1 10
NPSH m R R Outlet gauge datum mm 1600
Driver: R1 R1 Inlet sub Yes
Type Electric Motor L L Instruments:
Test Motor M11 Ref. No. Units
Manufacturer MATHER & PLATT Flow Meter F31 l/s
Type 725963
Serial No 725963 Outlet Head P7-F1-TEST m
Rated Output 260 Wattmeter LV CON P kW
Volts 415 Voltmeter LV CON V V
F.L. Amps 440 Ammeter LV CON A A
Phase/Freq. 3/50 Hydrostatic Test Press: bar PF Meter None
F.L. Speed 1450 Freq Meter None
TAD Code: E Tachometer SPP630278 rpm
Test Standard: ANSI/HI 14.6 Gr1U Mandatory Guarantees - (Flow and Head)
Additional Specifications: Pump peak power to allow for minimum 20% power reserves on engine's maximum rating.
Additional Requirements: Pump peak power to allow for minimum 10% power reserves on engine's UL/FM nameplate rating.
Tested by: Steve Turley Witnessed by:
for: Certified : Test Date: 4/11/2019
PUMP TEST CERTIFICATE Sales Order No 1823030 Pump Type GH20F2X
SPP Pumps Inc Line No 2 Serial No 1823030/2/B (USA-01-18-7955)
2905 Pacific Drive Test No 1
Norcross, GA 30071 Type of test: Production Test Page 2 of 3
Nominal Inlet Dia.: Nominal Outlet Dia.: 300 No. of Stages: 3
Customer: DRAGADOS DE MEXICO SA Cust. Order No:
Application COMPRRESSION PLATFO Cust. Item No:

1 2 3 4 5 6 7 8

Flow l/s 157.60 237.00 197.00 167.00 152.00 80.40 43.20 0.00

Outlet Head m 98.00 73.70 86.90 95.10 100.10 112.60 118.00 126.60
Velocity Head Corr. m 0.25 0.57 0.40 0.28 0.24 0.07 0.02 0.00
Gauge Position Corr. m 1.60 1.60 1.60 1.60 1.60 1.60 1.60 1.60
Head Loss m 0.78 1.76 1.22 0.88 0.72 0.20 0.06 0.00

Total Head m 100.63 77.64 90.11 97.86 102.66 114.47 119.68 128.20

Volts V 408.00 410.00 410.00 409.00 410.00 410.00 409.00 412.00


Amps A 390.00 397.00 398.50 391.00 286.00 331.00 302.00 291.00
Power factor
Frequency
Motor Input kW 246.60 251.30 251.80 247.50 244.90 208.90 189.40 183.00
Motor Output kW 230.49 234.83 235.29 231.32 228.92 195.42 177.08 171.03
Drive Loss kW 9.95 10.13 10.15 9.98 9.89 8.51 7.76 7.51

Pump Power Input kW 220.54 224.70 225.14 221.34 219.03 186.90 169.32 163.52

Shaft Speed rpm 1442 1442 1440 1442 1443 1447 1450 1452

Data translated to 1760.00 rpm and duty S.G.


Flow l/s 192.36 289.26 240.78 203.83 185.39 97.79 52.44 0.00
Total Head m 149.91 115.65 134.61 145.78 152.72 169.35 176.32 188.36
Power Abs SG 1. kW 400.99 408.55 411.07 402.44 397.42 336.32 302.79 291.22
Power Abs SG 1.02 kW 409.01 416.72 419.29 410.49 405.37 343.05 308.85 297.04

Pump Efficiency % 70.52 80.30 77.33 72.41 69.87 48.29 29.94 0.00
PUMP TEST CERTIFICATE Sales Order No 1823030 Pump Type GH20F2X
SPP Pumps Limited Line No 2 Serial No 1823030/2/B (USA-01-18-7955)
Crucible Close, Mushet Industrial Park, Coleford, Test No 1
Gloucestershire, GL16 8PS Type of test: Production Test Page 3 of 3
Nominal Inlet Dia.: Nominal Outlet Dia.: 300 No. of Stages: 3
Customer: DRAGADOS DE MEXICO SA Cust. Order No:
Application COMPRRESSION PLATFORM CA-KU-A1 (PEMEX) Cust. Item No:

Pre-Test Comments Post-Test Comments

* Peak pump power as tested is 419.29 Kw.


* FM approved engines max HP rating is 10% more than
nameplate rating.
* Pump peak HP is 28% less than engine max hp rating.
- Maximum engine rating = FM nameplate rating * 1.1
= 485 * 1.1
= 533.5 Kw
- Margin over max engine rating = 533.5 / 419.29 Kw
= 27%