Medium Voltage Products

TJO 6
Outdoor voltage transformers

The TJO 6 single-pole insulated voltage transformers


are cast in outdoor epoxy resin and designed mainly
for insulation voltages up to 25 kV. Alternative insulation
voltages are available to special order. Standard
transformers incorporate an overvoltage factor
of 1.9 x Un/8 hrs.

Description Parameters
One outlet of the primary winding, including its terminal, is insu- Rated primary voltages 1)
[kV] 10:√3; 15:√3; 20:√3; 22:√3
lated from earth at the rated insulation value. The other outlet of Rated secondary voltages 1) 2)
[V] 100:√3 V; 110:√3 V
the primary winding, together with its terminal, is earthed during Rated voltages for open-delta [V] 100:3; 110:3
operation. Most transformers are equipped with two secondary connection 1)

windings, the first is for either measuring or protection purposes, Rated frequency [Hz] 50; 60
the other connects into an open-delta configuration in a three- Highest voltage for equipment [kV] up to 25
phase system. One terminal of each secondary winding and one Rated power-frequency withstand [kV] up to 50
of the open-delta connected terminals must be earthed during voltage (r.m.s.), 1 min.
transformer operation. Rated lightning impulse withstand [kV] up to 125
The secondary windings are led out into a cast-type second- voltage (peak)
ary terminal board covered with a sealed cover. Max. rated burden/classes [VA/cl] 50/0.2; 100/0.5; 150/1
– measurement winding
The transformer body is fixed by four screws, the bolted Max. rated burden/classes [VA/cl] up to 200/3P or 6P
earthing clamp is located on the transformer base plate. – residual winding
For ease of handling and assembly, the transformer is sup- 1)
Other voltages can also be supplied on request.
plied with four suspension lugs fixed to the base frame. 2)
Accuracy classes 0.2; 0.5; 1 (measurement winding) or 3P; 6P (protection winding).

By special order, the transformer can also be provided with


primary winding designed for two different primary voltages
(with secondary side changeover switch).

The transformers are designed and manufactured to conform


with the requirements and recommendations of the following
standards: IEC, VDE, ANSI, BS, GOST, ČSN and PN-EN.
Dimensions
410 330 creepage distance: 1250 mm
M10

26
D

542
516
rating
plate P

90

3405PL401-W1-en. Edition 12.2010


4x 14 35
300
340

D (1:1)
300
130

M6 P 2xM6

67
P21

108
180

60
30

M12 50
14

Labelling of the voltage transformer outlets

A (M) N (O) A (M) N (O) A (M) B (N) A (M) B (N)

a n a1 a2 n a b a1 a2 b
(m) (o) (m1) (m2) (o) (m) (n) (m1) (m2) (n)

a) Single-pole insulated b) Single-pole insulated c) Double-pole insulated d) Double-pole insulated


transformer transformer with a tap transformer transformer with a tap

A (M) N (O) A (M) N (O) A (M) N (O)

1a 1n 2a 2n a n da dn a1 a2 n da1 da2 dn
(1m) (1o) (2m) (2o) (m) (o) (r) (s) (m1) (m2) (o) (r1) (r2) (s)

e) Single-pole insulated transformer with f) Single-pole insulated transformer with g) Single-pole insulated transformer with two
two secondary windings two secondary windings, one of which is secondary, tapped, windings, one of which
the auxiliary (residual) winding is the auxiliary (residual) winding

For more information please contact: We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB Sp. z o.o. does not accept any responsibility
ABB Sp. z o.o. whatsoever for potential errors or possible lack of information in this document.
Branch in Przasnysz We reserve all rights in this document and in the subject matter and illustrations
59 Leszno Str. contained therein. Any reproduction, disclosure to third parties or utilization of its
06-300 Przasnysz contents – in whole or in parts – is forbidden without prior written consent of
ABB Sp. z o.o.
Phone: +48 29 75 33 000
Fax: +48 29 75 33 327 © Copyright 2010 ABB
All rights reserved
www.abb.pl