Product leaflet

Current transformer LVB/IMT 40.5 - 550 kV


Reliable and safe outdoor instrument transformers

Current transformer LVB/IMT product range


is based on top core design. It is an oil-paper
insulated type with a metallic expansion
bellow. The products are mainly used for
outdoor installations. It is a reliable product
with minimum maintenance and suitable for
wide range of environmental conditions.

Features
Designed and tested in accordance with latest IEC specification
High accuracy and reliable design
Safe sealing slows the aging process and extends product life
Corrosion resistance: stainless steel expansion bellows and cast
aluminum oil tank and basement.

Benefits
Easy installation and commissioning
Maximum reliability and minimal maintenance
Suitable for wide range of environmental conditions
Good seismic performance

Technical data
Type LVB-40.5 LVB-126 LVB-252 IMT-550
Highest voltage kV 40.5 126 252 550
2 50-2 2000, 2 50-2 2000, 2 50-2 2000, 2 50-2 2000,
Rated current A
100-4000 100-4000 100-4000 100-4000
Short-time thermal current kA/s 31.5/1- 50/3 31.5/1- 50/3 50-63/3 50-63/3
Rated dynamic current kA 80-125 80-125 80-160 125-160
Rated insulation level kV 40.5/95/200 126/230/550 252/460/1050 550/740/1300/1675
Dielectric dissipation factor \ 0.005 0.005 0.005 0.004
Rated sencondary current A 1, 5
Rated frequency Hz 50/60
Measurement and protection IEC 61869-2: 0.1, 0.2S, 0.5S, 0.2, 0.5/5P, 5PR, 10P, 10PR, PX, PXR, TPZ, TPX, TPY
\
accuracy class IEEE C57.13: 0.15, 0.15S, 0.3, 0.6, 1.2/C100, C200, C400, C800, X
Rated burden and instrument
\ 1-200 VA, Fs 5
security factor of measuring class
Rated burden and accuracy
\ 1-200 VA, 5P10-5P40/10P10-10P40
limit factor of protective class
Insulator creepage distance mm/kV 25, 31

Other standard/regulation and values on request


Dimensions
LVB-40.5 LVB-126 LVB-252 IMT-550
1675 2375 3790 6950
A
-- -- -- 6190
1125 1825 3080 5920
B
-- -- -- 5220
C 220 220 285 400
D 475 475 600 600
E 20 20 24 28

Copyright 2015 ABB. All rights reserved.


Note: Above are typical dimensions, dimensions may adjust upon varies rating and configuration.
All dimensions are in mm.

IMT-550
1
2

P2 P1

C
2GSE000003-Rev.A, en 2015-10
4

LVB-252
1
2
3

20
A
P2 P1

20
5

B
LVB-126 4
1
2
20

3
LVB-40.5
A

P2 P1
20

1
5
2
B

4
3
A 20
B 20

P2 P1
5
A 20

4
B 20

6
5
6 6 6 7
7 7 7
8
C
C

8 8
C

8
C

D D 4 E D D 4 E D D 4 E D D 4 E

No. 1 2 3 4 5 6 7 8
Oil-level Primary Secondary
Name Expander Shell Bushing Nameplate Base
indicator terminal terminal box

For more information please contact: Note: We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the agreed particulars
shall prevail. ABB does not accept any responsibility whatsoever for potential errors or
ABB Jiangsu Jingke Instrument Transformer Co., Ltd. possible lack of information in this document

No.9 Gucheng Road, Su-Su Industrial Park, We reserve all rights in this document and in the subject matter and illustrations
Suqian, Jiangsu Province, 223800, P.R. China contained therein. Any reproduction, disclosure to third parties or utilization of its content
- in whole or in parts - is forbidden without ABB's prior written consent.
Tel: +86 527 8288 0886
Fax: +86 527 8288 0868