Anda di halaman 1dari 158

Lionel Ng, LPBS - Low Voltage Products

Welcome To ABB
Technical Sharing Session

© ABB Group
September 24, 2013 | Slide 1
MV & LV Transformer Substations
Theory & Short Circuit Calculation

© ABB Group
September 24, 2013 | Slide 2
Contents

 General information on MV/LV transformer substations


 Calculation of short-circuit currents
 Choice of protection and control devices
 Example of study of a MV/LV network
General Information
MV/LV Transformer Substations

 The electrical substations can be divided into


 public substations
 belong to the electricity utility
 supply private users in AC single-phase or three-phase current
(230V and 400V)
 urban type in bricks
 rural type installed externally directly on the MV pylon
 private substations
 belong to the user
 civil users (schools, hospitals, etc.) and industrial users
 are mostly located in the same rooms of the factory
General Information
MV/LV Transformer Substations
 Typical structure of a substation
where the switching apparatus of
the utility is installed.

where the measuring units


are located

contains the transformer and


the MV and LV switching
apparatus
General Information
MV/LV Transformer Substations
 Most common management methods

Substation with a single transformer


General Information
MV/LV Transformer Substations

 Most common management methods

It is possible to use the


Emax with a wire interlock
(mechanical interlock)
between two CBs

Substation with two transformers


(one as a spare for the other)
General Information
MV/LV Transformer Substations

 Most common management methods

two transformers which operate


in parallel on the same busbar
General Information
MV/LV Transformer Substations

 Most common management methods

It is possible to use the


Emax with a wire interlock
(mechanical interlock)
between three CBs

two transformers which operate simultaneously on


two separate half-busbars
General Information
MV/LV Transformer Substations

 MV/LV transformers
 is the most important part of the transformer substation
 single transformer for low powers (up to 630kVA - 800kVA)
 several units in parallel for higher powers (1000kVA - 2500kVA)
 type of cooling system
 air
 oil
 most used
 AN cooling with natural air circulation
 ONAN cooling with natural oil and air circulation types
General Information
MV/LV Transformer Substations

 MV/LV transformers

ONAN transformer containing more than 500 kg of oil (> 800kVA)


General Information
MV/LV Transformer Substations

 MV/LV transformers
 one single trafo or two trafos in parallel?

750M 750M
U VA U VA

1600kVA
800kVA 800kVA
6%
4% 4%
400V 400V

37 kA 55kA
General Information
MV/LV Transformer Substations

 Management philosophy for the protections


 L1 trip
 ensured service continuity
General Information
MV/LV Transformer Substations

 Management philosophy for the protections


 ILV1 and CLV trip
 power supply is maintained to the half-busbar

trip

trip
General Information
MV/LV Transformer Substations
 Management philosophy for the protections
 IMV1 and ILV1 trip to isolate the trafo affected by the fault
 ensured service continuity
 a logic for the disconnection of non-priority loads should be
foreseen
General Information
MV/LV Transformer Substations
 Management philosophy for the protections
 IMV1 trip, ILV1 trip for pulling
 service continuity of the whole plant
 a logic for the disconnection of non-priority loads should be
foreseen
General Information
MV/LV Transformer Substations
 LV protection devices

L function protection against


overload
General Information
MV/LV Transformer Substations
 LV protection devices

S function protection against


delayed short-circuit
General Information
MV/LV Transformer Substations
 LV protection devices

I function protection
against instantaneous
short-circuit
General Information
MV/LV Transformer Substations
 LV protection devices

G function protection
against earth-fault
MV/LV Transformer Substations
Calculation of Short Circuit Currents

 IEC 60909-0 (CEI 11-25)


 Short-circuit:
 “Accidental or intentional conductive path between two or more
conductive parts forcing the electric potential differences between
these conductive parts to be equal or close to zero”
 Short-circuit current:
 “Overcurrent resulting from a short-circuit in an electric system”
MV/LV Transformer Substations
Calculation of Short Circuit Currents

 Main components involved in a short-circuit calculation


 Distribution networks
 Generators
 Transformers
 Asynchronous motors
 Cables
 Each component of the network is replaced by its
relevant impedance
U

Zknet ZcMV ZTR ZcLV


MV/LV Transformer Substations
Calculation of Short Circuit Currents

 The equivalent network is solved according to standard


electrotechnical rules (circuits in series / in parallel)
Zkne ZcM ZT ZcLV
t V R

Un

Ik
Un
Ik 
3  Z knet  Z cMV  Z TR  Z cLV 
MV/LV Transformer Substations
Calculation of Short Circuit Currents

 Distribution network
 it is necessary to know the network short-circuit power
 from 250MVA to 500MVA Un  30kV
 from 700MVA to 1500MVA Un > 30kV
 according to IEC 60076-5

Un2 Un
Z knet  
Sknet 3  Iknet
MV/LV Transformer Substations
Calculation of Short Circuit Currents

 Generators
 it is necessary to know
 rated apparent power Sn
 rated voltage Un
 subtransient reactance x”d
 from 10% to 20% smooth rotor (isotropic machines)
 from 15% to 30% salient pole rotor (anisotropic machines)

" 2
x U
X "d  d  n
100 Sn
MV/LV Transformer Substations
Calculation of Short Circuit Currents

 Transformer
 it is necessary to know
 rated apparent power Sn
 primary rated voltage voltage U1n
 secondary rated voltage U2n
 short-circuit voltage uk% from 4% to 8%
 according to IEC 60076-5

uk % U22n
Z TR  
100 Sn
MV/LV Transformer Substations
Calculation of Short Circuit Currents

 Asynchronous motors
 In case of short-circuit it functions as a
generator with a x”d from 20% to 25%
 a current equal to 4-6 times the In can be
assumed as contribution to the short-circuit
 the minimum criteria for taking into
consideration the phenomenon

 (Ik shortcircuit without motor contribution)


MV/LV Transformer Substations
Calculation of Short Circuit Currents
 Example
Sk = 500 MVA U
UMV= 20 kV

ZcMV = 0.01 

Sn = 400 kVA
U= 20/0.4 kV
uk% = 4 %

ZcLV = 0.06 
MV/LV Transformer Substations
Calculation of Short Circuit Currents
 Example
U Sk = 500
MVA
UMV= 20 kV Zu = 0.32
m
Z u20kV 
U2

20  103 2

 0.8
Sk 500  106 
Z u400V  Z u20kV 
400
2

 3.2  104 
200002
MV/LV Transformer Substations
Calculation of Short Circuit Currents
 Example
U
Zu = 0.32 m

Z cMV 400V  Z cMV 20kV 


400
2

 4  106  ZcMV = 0.01 


200002 ZcMV = 410-3 m
MV/LV Transformer Substations
Calculation of Short Circuit Currents
 Example
U
Zu = 0.32 m

ZT 
2
uk % UnLV

4

400  0.016
2

100 Sn 100 400  103 ZcMV = 410-3 m

Sn = 400 kVA
U= 20/0.4 kV ZT = 0.016 
uk% = 4 %
MV/LV Transformer Substations
Calculation of Short Circuit Currents
 Example U
Zu = 0.32 m

ZcMV = 410-3 m

ZT = 16 m

ZcLV = 0.61 m
ZcLV = 0.61
m
MV/LV Transformer Substations
Calculation of Short Circuit Currents
 Example U Sk = 500
MVA Zu = 0.32 m
UMV= 20 kV

ZcMV = 410-3 m

ZT = 16 m
Un
Ik   14.1kA
3  Z u  Z cMV  Z T 

Un ZcLV = 0.61 m
Ik   13.6kA
3  Z u  Z cMV  Z T  Z cLV 
Un = 400 V
MV & LV Transformer Substations
General Information about Circuit
Breakers
© ABB Group
September 24, 2013 | Slide 34
MV/LV Transformer Substations
IEC Standard Definition of Circuit Breakers

Definitions
 Circuit-breaker: a mechanical switching device capable of making,
carrying and breaking currents under normal circuit conditions and
also making, carrying for a specified time, and breaking currents
under specified abnormal circuit conditions such as those of
overload or short-circuit (IEC 60947-1 def. 2.2.11)
MV/LV Transformer Substations
IEC Standard Definition of Circuit Breakers

Definitions
 Moulded case CB: a circuit-breaker having a supporting
housing of moulding insulating material forming an
integral part of the circuit-breaker (Isomax / Tmax /
Formula)
 Air CB: a circuit-breaker in which the contacts open and
close in air at atmospheric pressure (Emax)
MV/LV Transformer Substations
IEC Standard Definition of Circuit Breakers

Definitions
 Current-limiting circuit-breaker: a circuit-breaker with a
break-time short enough to prevent the short-circuit
current reaching its peak value (IEC 60947-2 def. 2.3)
MV/LV Transformer Substations
Current-Limiting Circuit Breakers
I

Prospective
peak value
Limited
peak
value
t
Prospective short-
Specific let-through circuit current
Limited short-circuit
energy (I2t)
current
MV/LV Transformer Substations
Current-Limiting Circuit Breakers Ip

Icc
Prospecti
ve peak
I2t
Limited value
peak
value
Prospective short-
t
Specific let-through circuit current
energy Limited short-
circuit current
Icc

go
MV/LV Transformer Substations
Current-Limiting Circuit Breakers
Curva di limitazione

Ip
1E5kA

T2L160 In160 A

1E4kA 40 kA

1E3kA
Prospective
peak value
84 kA
100kA

16 kA
10kA

1kA Limited peak


value
1E-2kA 0.1kA 1kA 10kA
Irms 40 kA
MV/LV Transformer Substations
Selection of Protective Devices
 Generalities about the main electrical parameters

 Rated operational voltage Ue: the value of voltage which


determines the application and to which all the other
parameters are referred to

 Rated uninterrupted current Iu: the value of current which the


device is able to carry for an indefinite time. It defines the size
of the CB

 Rated current In: the value of current which characterizes the


protection release installed. Is often related to the rated
current of the load protected
MV/LV Transformer Substations
Selection of Protective Devices

 Generalities about the main electrical parameters


 Rated ultimate short-circuit breaking capacity Icu: it is the
r.m.s. value of the symmetrical component of the short-circuit
current which the circuit-breaker is able to break (test cycle O-
t-CO)
 Rated service short-circuit breaking capacity Ics: it is the r.m.s.
value of the symmetrical component of the shortcircuit current
which the circuit-breaker is able to break (O-t-CO-t-CO)

T5N400 PR221DS-LS/I In 320

Icu
MV/LV Transformer Substations
Selection of Protective Devices

Ultimate Short-Circuit Breaking Capacity (Icu):


breaking capacity for which the prescribed conditions
according to a specified test sequence do not include
the capability of the CB to carry its rated current
continuously

- test sequence: O - 3 min - CO


- dielectric withstand at 2 x Ue
- verification of overload release at 2.5 x I1
MV/LV Transformer Substations
Selection of Protective Devices
Service Short-Circuit Breaking Capacity (ICS):
breaking capacity for which the prescribed conditions
according to a specified test sequence include the
capability of the CB to carry its rated current continuously

- test sequence: O - 3 min - CO - 3 min – CO


(25%-50%-75%-100% of Icu)

- operational performance capability: (5% of N°operating cycle


for operational performance capability- table 8 60947-2)
- dielectric withstand at 2 x Ue
- verification of temperature rise at Iu (the temperature doesn‟t
exceed the limits of table 7 60947-2)
- verification of overload release at 1.45 x I1
MV/LV Transformer Substations
Selection of Protective Devices
 Generalities about the main electrical parameters
 Rated short-circuit making capacity Icm: it is the maximum
prospective peak current which the circuit-breaker must be
able to make
 Icm=n x Icu

T5N400 PR221DS-LS/I In 320

Icu 36kA Icm 75.6 kA @415V


MV/LV Transformer Substations
Selection of Protective Devices

 Generalities about the main electrical parameters

 Rated short-time withstand current Icw: it is the r.m.s. value of


the alternate current component which the circuit-breaker is
able to withstand without damages for a determined time,
preferred values being 1s and 3 s

 Defined for category B only


MV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices

 Generalities about the main electrical parameters


 Don‟t forget
 Ue  Un
 Icu or Ics  Ik
 Icm  Ip

Ue, Icu, Ics, Icm?


MV/LV Transformer Substations
Selection of Protective Devices

 Protection of feeders
 against overload In
 Ib ≤ In or I1 ≤ Iz

 against short-circuit Iz S
 I2t ≤ k2S2

Ib
MV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices
MV/LV Transformer Substations
Selection of Protective Devices

 Protection of generators
 Ingen ≤ I1
 I3 or I2 ≤ 2.5-4 x Ingen
G
MV/LV Transformer Substations
Selection of Protective Devices

 Protection of transformers
 InT ≤ I1
 Upstream CB
 I3 or I2  Iinrush
MV/LV Transformer Substations
Example of an MV/LV Network
20kV

 Steps
 determining the short-circuit
currents
 choosing the CB
 setting of the MV overcurrent
protection …
 setting of the LV overcurrent
protection …

400V
MV/LV Transformer Substations
Example of an MV/LV Network
20kV

400V
MV/LV Transformer Substations
Example of an MV/LV Network
20kV

400V
Low voltage selectivity
with ABB circuit breakers
Selectivity definitions and Standards
© ABB Group
September 24, 2013 | Slide 57
Agenda
Low voltage selectivity with ABB circuit breakers

 Definitions and Standards


 Selectivity techniques
 Back-up protection
Introduction
What is selectivity?
A is the supply side circuit
Selectivity (or discrimination) breaker (or upstream)

is a type of coordination of two or


more protective devices in series.

Selectivity is done between


one circuit breaker on the supply side
and one circuit breaker, or more than
one, on the load side.

B and C are the load side circuit


breakers (or downstream)
Introduction
Protection system philosophy
 Reduce the stress and prevent damage
 Minimize the area and the duration of
power loss

DAMAGE REDUCTION FAULT CONTINUITY OF SERVICE

 Better selectivity  Fast fault elimination


Main purposes of coordination
Selectivity purpose
Selective coordination among devices
is fundamental for economical and technical reasons
It is studied in order to:
 rapidly identify the area involved in the problem;
 bound the effects of a fault by excluding just the affected zone of the
network;
 preserve the continuity of service and good power quality to the sound
parts of the network;
 provide a quick and precise identification of the fault to the personnel in
charge of maintenance or to management system, in order to restore
the service as rapidly as possible;
 achieve a valid compromise between reliability, simplicity and cost
effectiveness.
Standards definition
Selectivity
The definition of selectivity

IEC 60947-1 Standard: “Low voltage equipment IEC 60947-1


Part 1: General rules for low voltage equipment” def. 2.5.23

“Trip selectivity (for overcurrent) is a coordination between the


operating characteristics of two or more overcurrent protection
devices, so that, when an overcurrent within established limits
occurs, the device destined to operate within those limits trips
whereas the others do not trip”
Overcurrent selectivity
Example

In occurrence of a fault
(an overload or a short circuit)

if selectivity is provided

only the downstream circuit


breaker opens.
Overcurrent selectivity
Example

In occurrence of a fault
(an overload or a short circuit)

if selectivity is not provided

both the upstream and the


downstream circuit breakers
could open

All the system is out of service!


Standards definition
Partial and total selectivity

IEC 60947-2
def. 2.17.2 - 2.17.3

A and B connected in series:

partial selectivity and total selectivity.


Standards definition
Partial selectivity
“Partial selectivity is an overcurrent selectivity where, in the
presence of two protection devices against overcurrent in series,
the load side protection device carries out the protection up to a
given level of overcurrent, without making the other device trip.”

B opens only according to fault current


lower than a certain current value;
Is is the ultimate
values equal or greater than Is
selectivity
value!
will give the trip of both A and B.
Is = ImA
Standards definition
Total selectivity
“Total selectivity is an overcurrent selectivity where, in the
presence of two protection devices against overcurrent in series,
the load side protection device carries out the protection without
making the other device trip.”

Only B trips for every current value


lower or equal to the maximum
B A short-circuit current.
Is = Ik
Standards definition
Partial and total selectivity
Upstream circuit breaker A
T4N 250 PR221DS In = 250 (Icu = 36kA)
Downstream circuit breaker B
S 294 C100 (Icu = 15kA)
Selectivity analysis
Time-current curves
 Overload zone

Thermal protection
L protection

Time-current selectivity

 Short-circuit zone

Magnetic protection
S, D, I and EF protections

Current, time, energy, zone,


directional, zone directional selectivity
Selectivity analysis
Real currents
Real currents circulating through the circuit breakers

A I> A I> A I> I>

B I> B I> I> I> B I> I> I>

IA = IB IA = IB + Iloads IA = (IB + Iloads) / 2

tA tA
tB tA
tB
tB

IA=IB IB IA IA IB
Agenda
Low voltage selectivity with ABB circuit breakers

 Definitions and Standards


 Selectivity techniques
 Back-up protection

© ABB Group, BU Breakers and Switches


September 24, 2013 | Slide 71
Introduction
Selectivity techniques

 Current selectivity
 Time selectivity
 Energy selectivity
 Zone (logical) selectivity

© ABB Group, BU Breakers and Switches


September 24, 2013 | Slide 72
Current selectivity
Base concept
 Current selectivity: closer to the power supply
the fault point is, higher the fault current is
3kA
 In order to guarantee selectivity,
the protections must be set to different
values of current thresholds

1kA
tA  The ultimate selectivity value
tA is equal to the instantaneous trip threshold
B A of the upstream protection device
Ultimate
selectivity
value
tB  Other methods are needed to have a total
selectivity
ImB ImA
Current selectivity
Example

Circuit breaker A will be set to a value which does not


trip for faults which occur on the load side of B.
(I3Amin >1kA)

Circuit breaker B will be set to trip for faults which


occur on its load side (I3Bmax < 1kA)

104s

103s Is Is = I3Amin
102s A

10s
Here the selectivity is a total selectivity,
1s

10-1s
B because it is guaranteed up to the maximum
10-2s
value of the short-circuit current, 1kA.
0.1kA 1kA 3kA 10kA
Current selectivity
Plus and minus

Plus
Easy to be realized
Economic
Instantaneous

CURRENT SELECTIVITY
Minus
Selectivity is often only partial
Current thresholds rise very quickly
Time selectivity
Base concept
 Time selectivity is based on a trip delay of the upstream
circuit breaker, so to let to the downstream protection the
time suitable to trip

 Setting strategy:
progressively increase the
B A
trip delays getting closer to
the power supply source

 On the supply side


the S function is required
Time selectivity
Example
A will be set with the current threshold I2
adjusted so as not to create trip overlapping
and with a trip time t2 adjusted so that
B always clears the fault before A

B will be set with an instantaneous trip


against short-circuit
I
k
104s
Is The ultimate selectivity value is:
103s

102s
I2 Is = IcwA (if function I = OFF)
B
10s

1s
Is = I3minA (if function I = ON)
t2
10-1s

10-2s
0.1kA 1kA 10kA 100kA
Time selectivity
Example
Which is the problem of time selectivity?

In the case of fault occurring at the busbars,


circuit breaker A takes a delayed trip time t2
I
k

104s
The network must withstand high values of
103s
let-through energy!
102s

10s
B
If there are many hierarchical levels, the
1s
t2
progressive delays could be significant!
10-1s

10-2s
0.1kA 1kA 10kA 100kA
Time selectivity
Plus and minus

Plus
Economic solution
Easy to be realized

TIME SELECTIVITY
Minus
Quick rise of setting levels
High values of let-through energy
Energy selectivity
Base concept

 Energy selectivity is based on the current-


limiting characteristics of some circuit breakers
104s

103s

A
102s

10s

1s
B
10-1s

10-2s

Current-limiting circuit breaker


0.1kA 1kA 10kA
has an extremely fast trip time,
 The ultimate current short enough to prevent the
selectivity values current from reaching its peak
is given by the
manufacturer
(Coordination tables)
Energy selectivity
Example

104s

103s Is = 20kA
A

102s
B
Circuit breaker A conditions:
10s
I3=OFF
1s

10-1s
S as for time selectivity
10-2s
0.1kA 1kA 10kA
Energy selectivity
Plus and minus

PLUS
High selectivity values
Reduced tripping times
Low stress and network disturbance

ENERGY SELECTIVITY
MINUS
Increasing of circuit breakers size
Zone selectivity
Base concept
 Zone selectivity is an evolution of the time
selectivity, obtained by means of a electrical
interlock between devices
locking
signal

 The circuit breaker which detects a fault


communicates this to the one on the supply side,
sending a locking signal

 Only the downstream circuit breaker opens,


Fault
with no need to increase the intentional time
delay
Zone selectivity
Example
Zone 1

A
A Does Not Open
B Does Not Open
Zone 2

B C Opens
Zone 3

C
Zone selectivity
Specifications
Zone selectivity needs:
 a shielded twisted pair cable

Zone 1
 an external source of 24V
 dedicated trip units

Zone 2
 PR223EF for Tmax T4, T5 and T6
 PR332/P for Tmax T7 and T8
 PR122/P and PR123/P for Emax

Zone 3
 PR332/P and PR333/P for X1

 Is up to 100kA for Tmax


 Is up to Icw for Emax
 It is possible to obtain zone selectivity between Tmax and Emax
Zone selectivity
Plus and minus

PLUS
Trip times reduced
Low thermal and dynamic stress
High number of hierarchical levels
Can be made between same size circuit breakers

ZONE SELECTIVITY
MINUS
Cost and complexity of the installation
Additional wiring and components
Agenda
Low voltage selectivity with ABB circuit breakers

 Definitions and Standards


 Selectivity techniques
 Back-up protection

© ABB Group, BU Breakers and Switches


September 24, 2013 | Slide 87
Back-up protection
What is back-up protection?

Back-up protection (or cascading)

is a type of coordination of two protective


devices in series which is done in electrical
installations where continuous operation is
not an essential requirement.

Back-up protection
excludes the use
of selectivity!!!
Back-up protection
Standards definition

The definition of back-up is given by the

IEC 60947-1 Standard: “Low voltage equipment IEC 60947-1


Part 1: General rules for low voltage equipment” def. 2.5.24

“Back-up is a coordination of two overcurrent protective


devices in series, where the protective device on the supply
side, with or without the assistance of the other protective
device, trips first in order to prevents any excessive stress on
downstream devices”.
Back-up protection
Base concept

 Back-up is used by those who need


to contain the plant costs

 The use of a current-limiting circuit


breaker on the supply side
permits the installation of lower performance
circuit breakers on the load side

 Both the continuity of service and the selectivity are sacrificed


Back-up protection
Application example

T4L 250

Ik = 100 kA
Icu (T4L+T1N) = 100kA

T4L 250 T4L 250 T4L 250 Icu = 120kA

T1N 160 T1N 160 T1N 160 Icu = 36kA


Back-up protection tables
Back-up protection
Application example

T4L 250

Icu (T4L+T1N) = 100kA


B C D

Ik = 100kA Ik = 100kA General power supply


T1N 160 T1N 160 T1N 160 is always lost
Back-up protection
Plus and minus

Plus
Economic solution
Quick tripping times

BACK-UP PROTECTION
Minus
No selectivity
Low power quality
Example of Selectivity
~
T5H 630A 70kA
Incoming = T5H 630A (70kA
rating) Outgoing = T3N 160A
(36kA rating)
Results: The co-ordination T3N 160A 36kA
resulted in a conditional short-
circuit of 65kA for the T3 mccb!
Iz
The discrimination is up to 20kA.

65kA
Example of Selectivity
Discrimination
Example of Selectivity
Back-Up
Example of Selectivity
Meaning of Selectivity Value

T5H 70kA
T5H 70kA
T3N 36kA

T3N 36kA

Fault level at Y is 20kA


Y is 20kA
Example of Selectivity
Meaning of Selectivity Value

T5H 70kA
T5H
T3N 20kA

T3N 36kA
Example of Selectivity
Meaning of Selectivity Value

T5H T3N T5H 70kA

5kA fault ON Trip

T3N 36kA

5kA
Example of Selectivity
Meaning of Selectivity Value

T5H T3N T5H 70kA

5kA fault ON Trip


10kA fault ON Trip
T3N 36kA

10kA
Example of Selectivity
Meaning of Selectivity Value

T5H T3N T5H 70kA

5kA fault ON Trip


10kA fault ON Trip
20kA fault Trip Trip
T3N 36kA

20kA
Example of Selectivity
Meaning of Selectivity Value

T5H T3N T5H 70kA

5kA fault ON Trip


10kA fault ON Trip
20kA fault Trip Trip T3N 36kA
36kA fault Trip Trip 36kA
Example of Selectivity
Meaning of Selectivity Value

T5H T3N T5H 70kA

5kA fault ON Trip


10kA fault ON Trip
20kA fault Trip Trip T3N 36kA
65kA
36kA fault Trip Trip
65kA fault Trip Trip
MV/LV Transformer Substations
Selection of Protective & Control Devices
 Motor co-ordination
 ABB offers co-ordination tables
MV/LV Transformer Substations
Selection of Protective & Control Devices
 Co-ordination between CBs and switch-disconnectors

400V

T2S160

T1D160
DOC
Electrical Installation Calculation and
Dimensioning
© ABB Group
September 24, 2013 | Slide 107
Contents

Introduction
 Aim of the application
 Target users
 Products managed

How it works
 Features

 Support Tools
 ABB Software Desktop
 Assistance
 How to obtain the software
DOC
Introduction

© ABB Group
September 24, 2013 | Slide 109
Aim of the application

 DOC is the software for Electrical Installations Calculation


and Dimensioning
Introduction
Aim of the application
Target users  Draw single-line diagrams
Product managed

How it works  Perform electrical calculation according to the


Features
Standards
Support Tools
ASD
Assistance
 Choose the correct switching and protecting devices
How to obtain the
software
(MV and lv devices)
 Set the trip units and check for discrimination
 Prepare a complete project documentation
Target user

 DOC is complete and precise, but smart and flexible and


can be used from everyone interested in calculating
Introduction
Aim of the application electrical installation or part of them
Target users
Product managed
 Consultants
How it works
Features
 Electrical Engineers
Support Tools
ASD
Assistance
 Panel builders
How to obtain the
software  Installers
Product managed

 DOC allows and the selection of a wide range of ABB


Products
Introduction
Aim of the application
Target users  Medium Voltage products
Product managed

How it works  Low Voltage products


Features

Support Tools
 Motors
ASD
Assistance
How to obtain the
 Transformers
software
Product managed

 Low Voltage Products


Introduction  Air Circuit- Breakers
Aim of the application
Target users  New Emax
Product managed

How it works  Emax


Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  Molded Case Circuit Breakers
Aim of the application
Target users  Tmax
Product managed

How it works  Isomax


Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  Miniature Circuit Breakers
Aim of the application
Target users  System PRO M
Product managed

How it works  System PRO M Compact


Features
 S800
Support Tools
ASD  Smissline
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  RCCBs
Aim of the application
Target users  System PRO M
Product managed

How it works  System PRO M Compact


Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  Fuses
Aim of the application
Target users  OFAX
Product managed

How it works  OFASB


Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  Switch Fuses
Aim of the application
Target users  E930
Product managed

How it works  OESA


Features
 OS
Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  Disconnectors
Aim of the application
Target users  New Emax MS
Product managed

How it works  Emax MS


Features
 Tmax D
Support Tools
ASD  Isomax D
Assistance
How to obtain the  OT
software
 OETL
 E200
Product managed

 Low Voltage Products


Introduction  Contactors
Aim of the application
Target users  A
Product managed

How it works  AF
Features
 EN
Support Tools
ASD  ESB
Assistance
How to obtain the  E250
software
 E259
 E260
Product managed

 Low Voltage Products


Introduction  Manual Motor Starter
Aim of the application
Target users  MS116, MS325, MS450, MS495, MS496
Product managed

How it works  MO325, MO450, MO495, MO496 , MO497


Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Low Voltage Products


Introduction  Thermal Overload
Aim of the application
Target users  TAxxDU, ExxDU
Product managed

How it works  UMC-22


Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Medium Voltage Products


Introduction  Circuit breaker
Aim of the application
Target users  Secondary distribution SF6 and Vacuum up to 24kV 630A 16kA
Product managed

How it works  Primary distribution SF6 and Vacuum up to 36kV 3150A 50kA
Features

Support Tools
ASD
Assistance
How to obtain the
software
Product managed

 Medium Voltage Products


Introduction  Circuit breaker
Aim of the application
Target users
Product managed
 REF542Plus/DK

How it works  PR521/DK


Features
 PR521/P (50-51)
Support Tools
ASD  PR521/P (50-51-51N)
Assistance
How to obtain the  REF542Plus
software

 REF610
 REJ525
 PR512/P (50-51)
 PR512/P (50-51-50N-51N)
 PR512/PD
Product managed

 Medium Voltage Products


Introduction  Disconnectors
Aim of the application
Target users  SHS2/A
Product managed

How it works  SHS2/I


Features
 SHS2/IB
Support Tools
ASD  SHS2/IF
Assistance
How to obtain the  SHS2/N-I
software

 Earth Disconnectors
Product managed

 Medium Voltage Products


Introduction  Switch Disconnectors
Aim of the application
Target users  SHS2/T1
Product managed

How it works  SHS2/T1M


Features
 SHS2/T2
Support Tools
ASD  SHS2/T2F
Assistance
How to obtain the  SHS2/T2M
software
 SHS2/T2MF
 SHS2/N-T1
 SHS2/N-T1M
 SHS2/N-T2
 SHS2/N-T2F
 SHS2/N-T2M
 SHS2/N-T2MF
Product managed

 Medium Voltage Products


Introduction  General Purpose Fuses
Aim of the application
Target users
Product managed
 CEF 7.2kV 200A

How it works  CEF 12kV 125A


Features
 CEF 17.5kV 100A
Support Tools
ASD
Assistance  CEF 24kV 80A
How to obtain the
software
 Motor Fuses
 CEM 7.2kV 315A

 CEM 12kV 100A


Product managed

 Medium Voltage Products


Introduction  Cables
Aim of the application
Target users
Product managed
 Sized according to
the ABB
How it works
Features “XLPE Cable Systems
Support Tools
Users Guide"
ASD
Assistance
How to obtain the
software
Product managed

 Other Products
Introduction  Motors
Aim of the application
Target users
Product managed  M2xxx
How it works
Features  M3xxx
Support Tools
ASD
 Transformers
Assistance
How to obtain the
software
 Oil Distribution Transformers
 RESIBLOC
How
DOC it works
How it Works
Features - Professional and Light Profiles

 DOC can be used with 2 different profiles


Introduction  Depending on the user needs and skills it can be recommended to use
Aim of the application
Target users the Light Profile which hides the advanced and complex features
Product managed

How it works  DOC Light is for ...


Features
 ... first time, unskilled DOC users
Support Tools
ASD  ... installers – panel builders
Assistance
How to obtain the
who need a simple tool to draw
software and verify small networks

 DOC Professional is for ...


 ... skilled DOC users

 ... customers working on industrial


applications

 ... engineering companies –


OEM‟s looking for a powerful
calculation and design tool
Features - Single line diagram drawing

 Different layout available:


Introduction  Blank Page
Aim of the application
Target users  More flexible
Product managed
 Allows representing rings and meshes
How it works
Features  Main project data available beside the objects

Support Tools
ASD
Assistance
How to obtain the
software

 Column Page
 Faster and easier drawing
 Main project data available in the grid
Features - Single line diagram drawing

 Different ways to draw the symbols:


Introduction  By Single Objects
Aim of the application
Target users  More flexible
Product managed
 Allows representing rings and meshes
How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

 By Macros
 Faster and easier drawing

 Note: it is possible to use Single Objects


and Macros independently from the layout
Features - Single line diagram drawing

 When using the Column layout, Objects are numbered by Page &
Introduction
Column
Aim of the application
Target users
Product managed
 All the object in the same feeder have the same number
How it works
Features
 I.e: Page =1, Column=3 leads to QF1.3+ WC1.3 +L1.3
Support Tools
ASD
Assistance
How to obtain the
software
Features - Single line diagram drawing

 It is possible to draw one scheme on more than one page


Introduction  Use the „Add Sheet‟ and „Change layout‟ commands to prepare new empty
Aim of the application
Target users pages
Product managed

How it works  Use the Cross References to connect two objects


Features

Support Tools
 Use the „Previous/Next Sheet‟ commands to turn the pages
ASD
Assistance
How to obtain the
software
Features - Plant General Properties Window

 This window is shown when starting a new project. Set all the options
carefully to spare time when drawing and calculating the electrical
Introduction
Aim of the application installation
Target users
Product managed
 Main options:
How it works  Power supply definition
Features  Voltage level
 Default distribution system
Support Tools
ASD  Default number of phases
Assistance  Method for SC calculations
How to obtain the  Method for cable sizing
software
 Options for addressing the device
selection
Features - Suggested Workflow

 A toolbar on the right side of the working area suggests the preferred
way to develop a project with DOC
Introduction
Aim of the application
Target users
Product managed

How it works
Features  MV diagram drawing
Support Tools  LV diagram drawing
ASD
Assistance  Calculation and automatic project dimensioning
How to obtain the
software  Protection and discrimination verification thru the curves
 Auxiliaries scheme drawing
 Switchboard configuration
 Printouts
Features - MV Diagram Drawing

 The Medium Voltage section of the project can be drawn by the Macros
of the typical units of the Unimix switchboard or by Objects for more
Introduction
Aim of the application flexibility
Target users
Product managed
 To pass to the Low Voltage section it is necessary to use the
How it works
Features transformers (when a low voltage section is not needed, the drawing
Support Tools
can be completed with MV Loads or Motors)
ASD
Assistance
How to obtain the
software
Features - Lv Diagram Drawing

 The Low Voltage section of the project can be drawn by the Macros or
by Objects for more flexibility
Introduction
Aim of the application
Target users  The Macros available represents the most common Objects
Product managed
combinations; not available combinations can be realized using the
How it works
Features Objects
Power Supply
Support Tools  1 Macro = 1 Feeder = Many
ASD
Assistance
How to obtain the
single objects Switchboard Arrival
software
 I.e.: CB+Cable+Load
Sub-Switchboard
 I.e.: Fuse+Cable+Load

 Faster drawing Interlock graphical representation

 Pop-up window
Feeders

 When drawing a feeder it is


Motor Coordination
possible to insert the main

data making the drawing phase faster


Features - Calculation and automatic dimensioning

 Load-Flow
Introduction  DOC can calculate the current distribution, the voltage profile
Aim of the application
Target users and the voltage drop profile in load condition considering:
Product managed
 Section with different number of phases
How it works
Features
 Unbalanced loads (automatic balance is optional)
Support Tools  Transformer Voltage Regulator
ASD
Assistance
How to obtain the  Cable dimensioning
software
 Presence of meshes
 More distribution systems
Features - Calculation and automatic dimensioning

 Cable dimensioning
Introduction  Given the power required by the loads and the motors, DOC is
Aim of the application
Target users able to size the cables in an iterative process bringing to the
Product managed
section optimization and the current profile calculation
How it works
Features
 DOC implements several calculation methods
Support Tools
ASD  IEC 60364
Assistance
How to obtain the  CEI 64-8 Italian standard
software
 VDE 298 German standard
 NFC 15-100 French standard
 UNE 20460 Spanish standard
 IEC 60092 (for naval installation)
Features - Calculation and automatic dimensioning

 Short Circuit
Introduction  DOC can calculate the maximum and minimum short
Aim of the application
Target users circuit currents, with or without the motor contribution,
Product managed
for symmetrical and non-symmetrical faults, for different
How it works
Features times
Support Tools
ASD
 DOC implements several calculation methods
Assistance
How to obtain the  IEC 60909 LV\MV network, AC, 50-60Hz
software

 IEC 60363 Naval


ABB SACE – A Division of ABB S.p.A., MK-TO, 2009 June
 NFC 15-100 French national standard
 Symmetrical components method
Features - Calculation and automatic dimensioning

 Configuration Management
Introduction
Aim of the application  In DOC it is possible to
Target users
Product managed simulate different
How it works scenarios for the electrical
Features
installation defining the
Support Tools
ASD
open/closed position for
Assistance
How to obtain the
the switching and
software
protecting devices
 The calculation are
performed in the worst
condition
Features - Calculation and automatic dimensioning

 Devices Selection
Introduction  The calculation leads to an automatic proposal for all
Aim of the application
Target users the devices drawn in the scheme
Product managed

How it works  When more than one product is technically suitable,


Features
DOC proposes the basic one
Support Tools
ASD
Assistance
 It is possible to change the solution proposed by DOC
How to obtain the
software
and to lock the user choice thanks to the padlocks
present in all the selection windows
Features - Calculation and automatic dimensioning

 DOC gives the possibility to perform the temperature rise-


assessment according to IEC 60890 in a early stage of the
Introduction
Aim of the application installation design
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software
Features - Curves

 With DOC it is possible to manage


Introduction  Time-current diagrams for the devices present in the scheme
Aim of the application
Target users
Product managed  Set the thermomagnetic and electronic trip units
How it works
Features  Realize discrimination studies involving MV and LV devices
Support Tools
ASD
 Verify the cable protection Time-Current curve LLL

Assistance
How to obtain the
software 1E4s

1E3s

100s

10s

1s -TM1

-QF2, HD4/UniMix-R 24.06.12 P230, REF542Plus/DK


0.1s

-QF5, E4S 4000 PR121-LI 4000A


1E-2s

1E-2kA 0.1kA 1kA 10kA 100kA


Features – Switchboard configuration

 With DOC it is now possible to configure switchboard:


 By using a Wizar configuration: three steps guide procedure to create a
switchboard.

 By using a toolbar on the left side of working area:


 Insert and move column, Kit and device

 Tracking busbar system and temperature rise assessment

 Layer management (door, panel and plate layer, show hide busbars)

 Modify switchboard dimension

 Smart commands (switchboard table, labels, accessories)


Features - Project documentation

 Different reports sections allows the creation of a unique file


documenting the project
Introduction
Aim of the application
Target users  The report sections can be added/removed according to the needs
Product managed
 Calculation hypothesis
How it works
Features
 Short circuit calculations
Support Tools  Cable Protections
ASD
Assistance
How to obtain the  MV / LV devices list and settings
software

 Export in MS Excel is available


 The report language can be different from the current language
Support
DOC Tools
Support Tools
ABB Software Desktop

 ABB Software Desktop (ASD)


Introduction
Aim of the application
Target users
Product managed
 ASD is automatically installed with the first installed software
How it works
Features
 ASD functionalities:
Support Tools
ASD
 Allows to run the software
Assistance
How to obtain the
 Manage the language
software
 Registration
 Software upgrade
 Contact Software Support
ABB Software Desktop

 Registration
Introduction  Visit www.bol.it.abb.com
Aim of the application
Target users
Product managed
 Click on Profile Management
How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Starting on a New
Project
The Single Line Diagram

© ABB Group
September 24, 2013 | Slide 152
ABB Software Desktop

 Registration
Introduction  Click on New User
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Starting on a New
Project
The Single Line Diagram

© ABB Group
September 24, 2013 | Slide 153
ABB Software Desktop

 Registration
Introduction  Click on Subscribe
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Starting on a New
Project
The Single Line Diagram

© ABB Group
September 24, 2013 | Slide 154
ABB Software Desktop

 Registration
Introduction
Aim of the application
Target users
Product managed
 After registering via internet ,
How it works
you will receive immediately
Features
an e-mail with ID and PSW
Support Tools to access the Upgrade
ASD
Assistance Service
How to obtain the
software

 Use them to check for


available Upgrades before
starting using the Software
ABB Software Desktop

 Upgrade DOC via internet


Introduction
Aim of the application
Target users  Use The Automatic Upgrade
Product managed
Service allows you to
How it works
Features
maintain the software
aligned to the latest
Support Tools
ASD improvements delivered
Assistance
How to obtain the from ABB SACE them to
software
check for available
Upgrades before starting
using the Software
Assistance

 How to contact us – Software support


Introduction
Aim of the application
Ask the ABB SACE Software Assistance for any question you may
Target users
Product managed
have regarding the software tools
How it works  Email
Features

Support Tools  software.tools@it.abb.com


ASD
Assistance
How to obtain the  Call Center
software

 +39 035 395 570


 On line
 http://www.bol.it.abb.com
How to obtain the software

 Refer to the ABB Local Sales Organization for a free copy of the
Introduction
software
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Anda mungkin juga menyukai