Anda di halaman 1dari 8

1ZSC000562-AAV en, Rev.

Tap-changers for power transformers


Product guide
Vacuum on-load tap-changers

Our new generation of tap-changers utilize the most recent from developing technical solutions. ABB offers a full range of
vacuum interrupter technology. This design philosophy allows products for both high voltage and low voltage regulation. Our
the arcs during load commutations to occur in vacuum tap-changers are paired with robust, dependable motor drives
interrupters and not in the tap-changer oil. This greatly that are configurable to meet a wide range of environmental
reduces the need for maintenance and creates the potential conditions and customer specifications. From the compact
for using environmental-friendly insulating fluids. Final product BUL and versatile BUE for in-tank tap changers to the digitally
dependability is ensured through extensive testing beyond controlled SMD with integrated Tap Logic Monitoring System
international standards combined with decades of experience (TLMS) for the type VRLTC tap-changer.

On-load tap-changer, type VRLTC On-load tap-changer, type VUBB

2 Tap-changers for power transformers | 1ZSC000562-AAV en, Rev. 3


Type VRLTC Type VUBB Type VUCG Type VUCL
Application Single unit: three-phase star point, and three-phase Single unit: single-phase and three-phase star point
fully insulated Multiple units: three-phase fully insulated
Maximum rated through-current
Three-phase star point 2000 A 600 A 800 A 1300 A
Three-phase fully insulated 2000 A 600 A 1800 A 1300 A
Highest rated lightning impulse/ 200 kV / 70 kV 380 kV / 140 kV 1050 kV / 460 kV 1175 kV / 510 kV
power frequency withstand to earth
Highest system voltage 34.5 kV 76 kV 300 kV 362 kV
Maximum rated phase step voltage 500 V 1600 V 3500 V 4500 V
Maximum number of operating
positions
Linear 17 10 22 22
With change-over selector 33 19 35 35
Technology: Vacuum reactance Vacuum resistive Vacuum resistive Vacuum resistive

On-load tap-changer, type VUCG On-load tap-changer, type VUCL

1ZSC000562-AAV en , Rev. 3 | Tap-changers for power transformers 3


Conventional on-load tap-changers

Unsurpassed simplicity, convenient accessibility and Our tap-changers are matched with trustworthy, rugged
no requirements for special tools is the hallmark of our motor drives that are configurable to meet a wide range of
conventional tap-changers. ABB‘s customer-focused design environmental conditions and customer specifications. From
philosophy has stood the test of time for over 100 years and the compact BUL and versatile BUE for in-tank tap changer
resulted in designs with fewer parts and lower maintenance models to the fully integrated BUF for the type UZ on-tank
costs. In addition to increased reliability, tap-changers with tap-changer.
fewer parts allow for considerable reduction in size and cost.

On-load tap-changer, type UZ On-load tap-changer, type UBB

4 Tap-changers for power transformers | 1ZSC000562-AAV en, Rev. 3


Type UZ Type UBB Type UCG Type UCL Type UCC/UCD
Application Single unit: three-phase star point, and Single unit: single-phase and three-phase star point
three-phase fully insulated Multiple units: three-phase fully insulated
Maximum rated through-current
Three-phase star point 600 A 500 A 600 A 900 A 1600 A
Three-phase fully insulated 600 A 500 A 1500 A 2400 A 1600 A
Highest rated lightning impulse/ 650 kV / 275 kV 350 kV / 140 kV 1050 kV / 460 kV 1175 kV / 510 kV 1050 kV / 460 kV
power frequency withstand to earth
Highest system voltage 145 kV 76 kV 300 kV 362 kV 300 kV
Maximum rated phase step voltage 2000 V 1500 V 3500 V 4500 V 5000 V
Maximum number of operating
positions
Linear 17 14 22 22 18
With change-over selector 33 27 35 35 35

On-load tap-changer, type UCG On-load tap-changer, type UCL On-load tap-changer, type UCC

1ZSC000562-AAV en , Rev. 3 | Tap-changers for power transformers 5


De-energized tap-changers

Our designs are proven solutions with decades of successful energized tap changers available in the market. Both bridging
field experience. Their simplicity and ease of installation make and linear options are available with ratings up to 4000 A and
ABB‘s de-energized tap-changers the preferred solution 1050 kV BIL. And, with little to no required maintenance, our
by transformer manufacturers worldwide. Multiple deck designs have proven to be an ideal solution to both utility and
arrangements make our designs the most space saving de- industrial customers.

Type DTU Type DTL Type DTW


Maximum rated through-current 1500 A (500 A per deck) 2000 A (1000 A per deck) 4000 A (1000 A per deck)
Highest rated lightning impulse / 650 kV / 275 kV 650 kV / 275 kV 1050 kV / 460 kV
power frequency withstand to ground
or between phases
Lightning impulse / power frequency 650 kV / 275 kV 140 kV / 50 kV 400 kV / 130 kV
withstand between adjacent contacts
Maximum number of operating 7 7 6
positions

De-energized tap-changer, type DTU De-energized tap-changer, type DTL De-energized tap-changer, type DTW

6 Tap-changers for power transformers | 1ZSC000562-AAV en, Rev. 3


Life cycle support

We are committed to stand behind our products for as long as they are in operation. Product support, documentation and
training is therefore essential. This includes immediate availability of parts for all models, 24-hour access to support personnel
and the existence of a global reporting network.

Some of our UC tap-changer types are possible to upgrade without the need to rebuild; they can be upgraded with vacuum
technology as quickly and as easily as performing a normal overhaul. In many cases this makes it possible to increase the tap-
changers nominal load and at the same time benefit from all the advantages associated with vacuum technology.

1ZSC000562-AAV en , Rev. 3 | Tap-changers for power transformers 7


Contact us

ABB AB Note

© Copyright 2015 ABB, All rights reserved. 1ZSC000562-AAV en, Rev. 3, 2015-10-30
Components
SE-771 80 Ludvika, Sweden We reserve the right to make technical changes or modify the
Phone: +46 240 78 20 00 contents of this document without prior notice. With regard
Fax: +46 240 121 57 to purchase orders, the agreed particulars shall prevail. ABB
E-Mail: sales@se.abb.com does not accept any responsibility whatsoever for potential
errors or possible lack of information in this document.
ABB Inc.
1133 South Cavalier Drive We reserve all rights in this document and in the subject mat-
Alamo, Tennesseee 38001, USA ter and illustrations contained therein. Any reproduction, dis-
Phone: +1 800 955 8399 closure to third parties or utilization of its content – in whole
+1 731 696 5561 or in parts – is forbidden without ABB’s prior written consent.