Cp- is an Inspection Call No.

AMA/PESCO/610-09 dated 10-06-2013 the inspection of following material offered by


M/S A.M. Associates Lahore against PESCO P.O. No. 9983-89 dated 04-02-2013 (Cp-1)
The status of P.O. is as under:-
SR.NO DESCRIPTION QTY. ON ORDER ALREADY ACCEPTED QTY. NOW OFFERED
1. L.T. Steel Structures 30’-8”
19375Nos 12000 1000 Nos
(Sr. Nos 12001 to 13000)

The inspection of material was carried out by the undersigned on _____________________ at manufacturers premises
According to WAPDA specification DDS-78:2008 (amended to date) following samples tests were performed.

A- ON COMPLETE STRUCTURES
i) Visual inspection.
ii) Verification of Dimension and weight.
iii) Transverse Load Test.
B- ON MEMBERS.
i) Tensile Strength and Elongation
ii) Bend Test
ii) Galvanizing test (Wt. of zinc coating test, Uniformity & Adherence).

Structures were checked visually and dimensionally as per Wapda Specification DDS-78:2008 and found the values within
specified tolerance limit Cp- LT Steel Structures were randomly picked from offered lot and subjected to transverse load.
The testing was performed at manufacturer’s premises & found the values within specified tolerance. Cp-

Weighing of LT Structures was carried out and found the weight within specified tolerance. (Cp-

Samples for mechanical and wt. of zinc coating tests were collected from transverse load tested structure.
These samples were sent to M/S PSQCA Lab Lahore for testing. Reports are placed at Cp-
Following tests were carried out, their specified and observed values are tabulated below:-

SR NO. TESTS CARRIED OUT SPECIFIED VALUE OBSERVED VALUES


MANUFACTURER PREMISES
1. Dimensions Manufacturer Premises Within specified Tolerance limits
As per drawing approved Cp-
By CE(D&S)

2- Weight 130 Kg + 3% 128 - 130-Kg (Cp-


126.53-134.35 Kgs
3- Transverse Load Test Min 610 Kg (-5%) Collapsed at 780,805,745-Kg (Cp-

4- (MECHANICAL TEST)
a) Yield Strength 25 Kg/mm2 (Min) (30.3 – 33.9) kg/mm2
b) Tensile Strength 40 – 56 Kg/mm2 (50.9 – 53.4) kg/mm2
c) Elongation Thickness 3/16(min.15%) (20.3 – 22.7) %(Cp-
1/8 (min. 12.5%) No crack was found bending at 180(Cp-
d) Bend test No crack bending at 180
5- (GALVANIZING TEST)
INDIVIDUAL AVERAGE
Weight of Zinc coating 550 gm/m2 610 gm/m2 742 – 984 gm/m2 (Cp-
There should be no copper deposit

No Pealing or flaking of zinc


Uniformity coating was No copper deposit was observed.
observed
Adherence Test report is placed at Cp-

All samples have qualified the above specified tests satisfactorily

Punching of P.O. No., Purchaser name, manufacturer name, transverse load and mentioning of weight with Ink on
each L.T. Structures has been done.

100% material sealed with Wapda Lead Impression No. MI-543


NOTE: Inspection charges @ 0.5% of the cost of material costing Rs. 178335/- were recovered from the firm vide Challan
No. 20911 NBP LDA Plaza Branch Lahore dated 17-05-2013 (Cp-187)

As material has qualified all specified tests carried out in accordance with the relevant standard / specification / special
conditions and no deviation has been noticed, as such approval may please be accorded for acceptance of the following
material offered by M/s A.M. Associates Lahore against PESCO P.O.

L.T. Steel Structure 30-8” = 1000 Nos


(Sr. No. 12001 to 13000)

(ENGR: KHALID MEHMOOD)


ADDL: DIRECTOR-06 (MI) NTDC
ADDL: C.E. (MI)-II
The report submitted by Engr: Khalid Mehmood Addl: Dir-06 from NP____ to NP______ alongwith relevant data / documents has
been examined & found in order. It is recommended to accord approval for acceptance of:-

L.T. Steel Structure 30-8” = 1000 Nos


(Sr. No. 12001 to 13000)

From M/S A.M. Associates Lahore for PESCO Ltd. Peshawar please.

(ENGR: MUHAMMAD ARSHAD SALEEM UPPAL)


ADDL: C.E. (MI)-II NTDC LAHORE
C.E.(MI) NTDC
SUBJECT: INSPECTION OF LT STEEL STRUCTURE 30’-8”

Cp-04 is an Inspection Call No. AR/2011/2102 dated 21-03-2011 for the inspection of following
material offered by M/S Ajmer Engg: Electric Works Lahore against QESCO P.O. No. 1039 dated 11-
03-2011 (Cp-1)
The status of P.O. is as under:-
SR. DESCRIPTION QTY. ON ALREADY QTY. NOW
NO ORDER ACCEPTED OFFERED
1. L.T. Steel Structures 30’-8” 1050 Nos Nil 1050 Nos
(Sr. Nos 001 to 1050)

The prototype approval of L.T. Steel Structures 30-8 has been accorded by CE(D&S) vide letter No.
229-33/CEDS/HYD-67 dated 12-01-2011 (Cp-2)

The inspection of material was carried out by undersigned on _____________________ at


manufacturers premises According to WAPDA specification DDS-78:2008 (amended to date) following
samples tests were performed.

A- ON COMPLETE STRUCTURES
i) Visual inspection.
ii) Verification of Dimension and weight.
iii) Transverse Load Test.
B- ON MEMBERS.
iii) Tensile Strength and Elongation
iv) Bend Test
ii) Galvanizing test (Wt. of zinc coating test, Uniformity &
Adherence).

Structures were checked visually and dimensionally as per Wapda Specification DDS-78:2008 and
found the values within specified tolerance limit Cp-5. LT Steel Structures were randomly picked from
offered lot and subjected to transverse load. The testing was performed at manufacturer’s premises &
found the values within specified tolerance Cp-7-10.

Weighing of LT Structures was carried out and found the weight within specified tolerance(Cp- 6)

Samples for mechanical and wt. of zinc coating test were collected from transverse load tested structure.
These samples were sent to M/S PSQCA Lab Lahore for testing. Test report is placed at Cp-15-16

Following tests were carried out, their specified and observed values are tabulated below:-

SR.
TESTS CARRIED OUT SPECIFIED VALUE OBSERVED VALUES
NO.
MANUFACTURER PREMISES
1. Dimensions Manufacturer Premises Within specified Tolerance limits
As per drawing approved Cp-5
By CE(D&S)
2- Weight 130 Kg + 3% 127 - 131-Kg Cp-6
126.53-134.35 Kgs
3- Transverse Load Test Min 610 Kg (-10%) Collapsed at 755,709,795,788-Kg
Cp-7-10
4- (MECHANICAL TEST)
e) Yield Strength 25 Kg/mm2 (Min) 32.3– 34.8-kg/mm2
f) Tensile 40 – 56 Kg/mm2 52.2 – 54.7-kg/mm2
Strength Thickness 3/16(min.15%) 22.2 – 24.7-%(Cp-16)
g) Elongation 1/8 (min. 12.5%)
No crack bending at 180 No crack was found bending at
h) Bend test 180(Cp-16)
5- (GALVANIZING TEST)
INDIVIDUAL AVERAGE
Weight of Zinc coating 550 gm/m2 610 gm/m2 856 – 1072gm/m2 (Cp-15)
There should be no copper deposit
Uniformity No Pealing or flaking of zinc No copper deposit was
observed. (Cp-15)
Adherence coating was observed
Test report is placed at Cp-15

All samples have qualified the above specified tests satisfactorily

Punching of P.O. No., Purchaser name, manufacturer name, transverse load and mentioning of weight
with Ink on each L.T. Structures has been done.

100% material sealed with Wapda Lead Impression No. MI-367

NOTE: Inspection charges @ 0.5% of the cost of material costing Rs.56112/- were recovered from the
firm vide Challan No. 15160 NBP LDA Plaza Branch Lahore dated 12-04-2011 (Cp-13)

As material has qualified all specified tests carried out in accordance with the relevant standard /
specification / special conditions and no deviation has been noticed, as such approval may please be
accorded for acceptance of the following material offered by M/s Ajmer Engg: Electric Works Lahore
against QESCO Purchase order.

L.T. Steel Structure 30-8” = 1050 Nos


(Sr. No. 001 to 1050)

(ENGR: KHALID MAHMOOD)


DY:DIRECTOR-07
DIRECTOR(MI)-II
The report submitted by Engr: Khalid Mahmood DD-07 from NP____ to NP______ alongwith relevant
data / documents has been examined & found in order. It is recommended to accord approval for
acceptance of:-

L.T. Steel Structure 30-8” = 1050 Nos


(Sr. No. 001 to 1050)

From M/S Ajmer Engg: Electric Works Lahore for QESCO Ltd. Quetta please.

(ENGR: SYED ASGHAR IMAM RIZVI)


DIRECTOR(MI)-II
CE(MI) NTDC
Cp- is an Inspection Call No. AMA/SEPCO/I.C/2012/127 dated 17-12-2012 the inspection of following material offered by
M/S A.M. Associates Lahore against SEPCO P.O. No. 09/151 dated 14-12-12(Cp-1)
The status of P.O. is as under:-
SR.NO DESCRIPTION QTY. ON ORDER ALREADY ACCEPTED QTY. NOW OFFERED
1. L.T. Steel Structures 30’-8”
1000 Nos NIL 1000 Nos
(Sr. Nos 001 to 1000)

The inspection of material was carried out by the undersigned on _19,20 & 21-12-2012 at manufacturers premises
According to WAPDA specification DDS-78:2008 (amended to date) following samples tests were performed.

A- ON COMPLETE STRUCTURES
i) Visual inspection.
ii) Verification of Dimension and weight.
iii) Transverse Load Test.
B- ON MEMBERS.
v) Tensile Strength and Elongation
vi) Bend Test
ii) Galvanizing test (Wt. of zinc coating test, Uniformity & Adherence).

Structures were checked visually and dimensionally as per Wapda Specification DDS-78:2008 and found the values within
specified tolerance limit Cp- 12-21 LT Steel Structures were randomly picked from offered lot and subjected to transverse load.
The testing was performed at manufacturer’s premises & found the values within specified tolerance. Cp-9-11

Weighing of LT Structures was carried out and found the weight within specified tolerance (Cp- 08

Samples for mechanical and wt. of zinc coating tests were collected from transverse load tested structure.
These samples were sent to M/S PSQCA Lab Lahore for testing. Report are placed at Cp-25&26

Following tests were carried out, their specified and observed values are tabulated below:-

SR NO. TESTS CARRIED OUT SPECIFIED VALUE OBSERVED VALUES


MANUFACTURER PREMISES
1. Dimensions Manufacturer Premises Within specified Tolerance limits
As per drawing approved Cp-12-21
By CE(D&S)

2- Weight 130 Kg + 3% 128 – 131Kg (Cp-8)


126.53-134.35 Kgs

3- Transverse Load Test Min 610 Kg (-5%) Collapsed at 780,785,795-Kg (Cp-9-11)

4- (MECHANICAL TEST)
i) Yield Strength 25 Kg/mm2 (Min) (31.7 – 34.8) kg/mm2
j) Tensile Strength 40 – 56 Kg/mm2 (51.8 – 54.9) kg/mm2
k) Elongation Thickness 3/16(min.15%) (22.8 – 25.1) %(Cp-26)
1/8 (min. 12.5%)
l) Bend test No crack bending at 180 No crack was found bending at 180
(Cp-26)
5- (GALVANIZING TEST)
INDIVIDUAL AVERAGE
Weight of Zinc coating 550 gm/m2 610 gm/m2 861 - 1281gm/m2 (Cp-25)
There should be no copper deposit

No Pealing or flaking of zinc


Uniformity coating was No copper deposit was observed.
observed
Adherence Test report is placed at Cp-25

All samples have qualified the above specified tests satisfactorily

Punching of P.O. No., Purchaser name, manufacturer name, transverse load and mentioning of weight with Ink on
each L.T. Structures has been done.

100% material sealed with Wapda Lead Impression No. MI-367


NOTE: Inspection charges @ 0.5% of the cost of material costing Rs.58445/- were recovered from the firm vide
Challan No. 19739 NBP LDA Plaza Branch Lahore dated 26-12-2012 (Cp-23)
As material has qualified all specified tests carried out in accordance with the relevant standard / specification / special
conditions and no deviation has been noticed, as such approval may please be accorded for acceptance of the following
material offered by M/s A.M. Associates Lahore against SEPCO P.O.

L.T. Steel Structure 30-8” = 1000 Nos


(Sr. No. 001 to 1000)

(ENGR: KHALID MEHMOOD)


ADDL. DIRECTOR-06
ADDL. CHIEF ENGINEER (MI)-II
The report submitted by Engr: Khalid Mehmood Addl. Director-06 from NP____ to NP______ alongwith relevant data /
documents has been examined & found in order. It is recommended to accord approval for acceptance of:-

L.T. Steel Structure 30-8” = 1000 Nos


(Sr. No. 001 to 1000)

From M/S A.M. Associates Lahore for SEPCO Ltd. Sukkur please.

(ENGR: MUAHMMAD ARHSAD SALEEM UPPAL)


ADDL.CHIEF ENGINEER-II (MI)

CE(MI) NTDC
Cp-261 is an Inspection Call No. AMA/I.C/PESCO/201325-09 dated 25-07-2013 the inspection of following material offered
by M/S A.M. Associates Lahore against PESCO P.O. No. 9983-89 dated 04-02-2013 (Cp-206/4)
The status of P.O. is as under:-
SR.NO DESCRIPTION QTY. ON ORDER ALREADY ACCEPTED QTY. NOW OFFERED
1. L.T. Steel Structures 30’-8”
19375Nos 15000 Nos. 1000 Nos.
(Sr. Nos. 15001 to 16000)

PROTOTYPE APPROVAL.
Prototype approval for L.T Steel structure 30’.8’’ has been approved by C.E (D & S) approval placed at (Cp-206/2)

The inspection of material was carried out by the undersigned on 30 & 31-7-13 & 1-8-13 at manufacturer’s premises According
to WAPDA specification DDS-78:2008 (amended to date) following samples tests were performed.

A- ON COMPLETE STRUCTURES
i) Visual inspection.
ii) Verification of Dimension and weight.
iii) Transverse Load Test.
B- ON MEMBERS.
vii) Tensile Strength and Elongation
viii) Bend Test
ii) Galvanizing test (Wt. of zinc coating test, Uniformity & Adherence).

Structures checked visually and dimensionally as per WAPDA Specification DDS-78:2008(amended to date) and approved
drawing, values were found within specified tolerance limit (Cp- 267 to 277) Three Nos. LT Steel Structures were randomly
picked from offered lot and subjected to transverse load test at manufacturer’s premises & found the values within specified
tolerance limit (Cp-264 to 266). Weighing of LT Structures was carried out and found the weight within specified tolerance.
(Cp-263)

Samples for mechanical and wt. of zinc coating tests were collected from transverse load tested structures. These samples
were sent to M/S PSQCA Lab Lahore for testing. Test report is placed at (Cp- 280 to 281)
Following tests were carried out, their specified and observed values are tabulated below:-

SR NO. TESTS CARRIED OUT SPECIFIED VALUE OBSERVED VALUES


MANUFACTURER PREMISES
1. Dimensions Manufacturer Premises Within specified Tolerance limits
As per drawing approved (Cp-267-276)
By CE(D&S)

2- Weight 130 Kg + 3% 128 - 130-Kg (Cp-263)


126.53-134.35 Kgs
3- Transverse Load Test Min 610 Kg (-10%) Collapsed at 805,780,750-Kg (Cp-264-266)

4- (MECHANICAL TEST)
a) Yield Strength 25 Kg/mm2 (Min) (29.2 – 33.3) kg/mm2
b) Tensile Strength 40 – 56 Kg/mm2 (49.3 – 52.7) kg/mm2
c) Elongation Thickness 3/16(min.15%) (20.7 – 23.7) %(Cp-280)
1/8 (min. 12.5%)
d) Bend test No crack should found on No crack was found on bending at 180⁰
bending at 180⁰ (Cp-280)
5- (GALVANIZING TEST)
INDIVIDUAL AVERAGE
Weight of Zinc coating 550 gm/m2 610 gm/m2 731 – 964 gm/m2 (Cp-280)
There should be no copper deposit
Uniformity No copper deposit was observed.
No Pealing or flaking of zinc coating

Adherence No Pealing or flaking of zinc coating was observed


(Cp-280)

All samples have qualified the above specified tests satisfactorily

TYPE TEST.
The type test (transverse load test) for the calendar year 2013 will be performed jointly with rep. of C.E (D&S)
during current month.

INSPECTION FEE
Inspection fee deposited by firm and Bank Challan receipt placed at (Cp-239)
Punching of P.O. No., Purchaser name, manufacturer name, transverse load and mentioning of weight with Ink on
each L.T. Structures has been done.
Undersigned verified that 100% material is available and sealed with WAPDA Lead Impression No. MI-543

As material has qualified all specified tests carried out in accordance with the relevant standard / specification / special
conditions and no deviation has been noticed, as such approval may please be accorded for acceptance of the following
material offered by M/s A.M. Associates Lahore against PESCO P.O.

L.T. Steel Structure 30-8” = 1000 Nos. (One Thousand Nos.)


(Sr. No. 15001 to 16000)

(ENGR: KHALID MEHMOOD)


ADDL: DIRECTOR-06 (MI) NTDC
DIRECTOR-II (MI)
The report submitted by Engr: Khalid Mehmood Addl. Director-06 from NP____ to NP______ alongwith relevant data /
documents has been examined & found in order. It is recommended to accord approval for acceptance of:-

L.T. Steel Structure 30-8” = 1000 Nos. (One Thousand Nos.)


(Sr. No. 15001 to 16000)

From M/S A.M. Associates Lahore for PESCO Ltd. Peshawar please.

(ENGR: BASHIR AHMED BHATTI)


DIRECTOR-II (MI) NTDC LAHORE
C.E.(MI) NTDC