ELECTRICAL POWER-General
The Electrical System consists of three separate subsystems:
• DC (Direct Current):
28 VDC from Starter/Generators,
24 VDC from Batteries.
• AC (Alternating Current), constant frequency:
115 VAC (400 Hz) single-phase from Static Inverters,
26 VAC (400 Hz) single-phase from Static Inverters.
• ACW (Alternating Current Wild), variable frequency:
115 / 200 VAC (341 - 488 Hz) three-phase from ACW Generators (frequency depends on Np).
Note: ACW generation is basically used for the De-icing and Heating Systems, and electro-hydraulic Pumps.
ACW and DC feeders run in the wing leading edge and under the ceiling roof to the Electrical Racks.
DC generation by main and emergency Batteries is normally utilized to provide stored energy during normal ground operations, and in
flight in the event of a total loss of the DC Primary Generation System.
A Transformer Rectifier Unit (TRU) transforms ACW into DC for emergency purposes.
TRAINING PURPOSES ONLY
The electrical components are located in the Electrical Racks, except for Batteries which are located on the floor of the Avionics Racks.
TRAINING PURPOSES ONLY
The AC-DC or ACW-HYD electrical page presents the main basic information concerning the electrical systems on the Multi Function
Display.
And another circuit breakers are located behind the First Officer on several panels.
Electrical system indications are located on Main Electrical Power Control Panel and on Multi Function displays (AC/DC electrical SD
page).
The "DC GEN" pushbutton controls the energization of associated generator and the resetting of the protection system after failure:
• ON: (pushbutton depressed without lighting), the associated generator is energized and the associated generator contactor
closes if the network electrical parameters are normal.
On MFD, state 1 is displayed.
ISSUE 01 REV 00 PAGE 6
24 – ELECTRICAL POWER
ENGINEERING TRAINING CENTRE ATR 72 – 212A MAINTENANCE TRAINING MANUAL
The "FAULT" light of the "DC GEN" pushbutton illuminates amber and the CCAS is activated in case of:
• A protection trip is initiated by the associated GCU. If it is caused by an under speed generator, the reset will be automatic. In
other cases, a manual reset has to be performed.
• An opening of a generator contactor except if the pushbutton is selected OFF. In both cases, the BUS TIE CONTACTOR closes
and the affected DC BUS is automatically supplied from the remaining generator.
On MFD, state 2 is displayed.
The "OFF" light of the "DC GEN" pushbutton illuminates white when the pushbutton is released and the associated generator is de-
energized and associated contactor is open.
On MFD, state 3 is displayed.
TRAINING PURPOSES ONLY
The "EXT PWR" pushbutton controls the Ground Power Unit (GPU):
• No lights: (pushbutton released) when GPU is not connected.
On MFD, no information is displayed.
• AVAIL: Illuminates green when conditions of the DC external power connection are met.
On MFD, state 1 is displayed.
• ON: Illuminates cyan and allows connecting the DC external power when the BAT toggle switch is selected "ON" with the "EXT
PWR" pushbutton depressed.
On MFD, state 2 is displayed.
TRAINING PURPOSES ONLY
• ON: Illuminates cyan when the BAT toggle switch is selected "ON" with the "EXT PWR" pushbutton depressed but without
external power connected.
On MFD, state 3 is displayed.
This green symbol is displayed at exit of corresponding DC Source or AC Source:
• At the top of the DC external power label, when the external power supplies network.
• At the top of the connected DC generator label, when the corresponding generator supplies network.
• At the top of the connected inverter label, when the corresponding inverter supplies its busses.
The "BTC" guarded pushbutton controls the DC Bus Tie Contactor (BTC) which, when it is closed, connects both main DC BUSSES:
• NORM: (pushbutton released), the BPCU automatically controls the DC BTC:
• In normal condition with both generators running, the BTC is open allowing isolated operation of both generators circuits.
TRAINING PURPOSES ONLY
The "DC BUS OFF" caution light is blank, when the associated main DC BUS is supplied.
On MFD, state 1 is displayed.
The "DC BUS OFF" caution light illuminates amber, when the associated main DC BUS is not supplied. Additionally, if one DC BUS is
"OFF" the CCAS will be also activated.
On MFD, state 2 is displayed.
TRAINING PURPOSES ONLY
The "DC SVCE / UTLY BUS" pushbutton controls connection / disconnection of the DC SVCE BUS and both UTLY BUSSES to
associated main DC BUSSES:
• NORM: (pushbutton depressed without lighting), the DC SVCE BUS and both UTLY BUSSES are available unless a load shed
signal is provided by the BPCU.
On MFD, state 1 is displayed.
• SHED: Illuminates amber and the CCAS is activated when a load shed condition controlled by the BPCU is present and at least
one DC UTLY BUS is disconnected from associated main DC BUS.
On MFD, state 2 is displayed.
The "DC SVCE / UTLY BUS" pushbutton controls connection / disconnection of the DC SVCE BUS and both UTLY BUSSES to
associated main DC BUSSES:
• NORM: (pushbutton depressed without lighting), the DC SVCE BUS and both UTLY BUSSES are available unless a load shed
signal is provided by the BPCU.
On MFD, state 1 is displayed.
TRAINING PURPOSES ONLY
Note: The DC SVCE BUS can be connected to DC BUS 1 or to external power (in accordance with DC network configuration).
The "DC SVCE / UTLY BUS" pushbutton controls connection / disconnection of the DC SVCE BUS and both UTLY BUSSES to
associated main DC BUSSES:
• When only DC SVCE BUS is not supplied, on MFD state 2 is displayed.
Note: Additionally, the associated SHED light is illuminated on the attendant's panel.
On MFD, State 1 is displayed when the DC Emergency bus voltage is greater than 18V.
On MFD, State 2 is displayed when the DC Emergency bus voltage is lower than 18V.
TRAINING PURPOSES ONLY
The "STBY BUS" pushbutton controls the transfer of DC standby bus and Inverter 1 from HOT MAIN BAT BUS to HOT EMER BAT
BUS:
• NORM: (pushbutton released without lighting), the DC standby bus and Inverter 1 are supplied from HOT EMER BAT BUS or
HOT MAIN BAT BUS (in accordance with DC network configuration).
On MFD, State 1 is displayed.
TRAINING PURPOSES ONLY
• The "UND/V" light illuminates amber when the MAIN BAT is discharging (DC STBY BUS below 19.5 volts).
On MFD, State 2 is displayed.
Note: If the DC Standby bus voltage is lower than 18V the rectangle changes also to amber.
• The "OVRD" light illuminates white when the pushbutton is depressed to transfer STBY BUSSES (DC and AC through INV 1) to
EMER BAT.
On MFD, State 3 is displayed.
On MFD, State 1 is displayed when the DC Essential bus voltage is greater than 18V.
On MFD, State 2 is displayed when the DC Essential bus voltage is lower than 18V.
ISSUE 01 REV 00 PAGE 15
24 – ELECTRICAL POWER
ENGINEERING TRAINING CENTRE ATR 72 – 212A MAINTENANCE TRAINING MANUAL
On MFD, State 1 is displayed when the corresponding DC HOT BUS voltage is greater than 18V with the "OVRD" position not
selected.
• ON: With batteries only (without EXT PWR, DC GEN or TRU):
ESS BUS, STBY BUSSES (DC and AC through INV1) are supplied from HOT MAIN BAT BUS,
EMER BUS is supplied from the HOT EMER BAT BUS.
On MFD, State 2 is displayed when the corresponding DC HOT BUS voltage is lower than 18V.
Note: When DC HOT BUS voltage is invalid, the readout is replaced by two amber dashes at the left of the V unit label.
ISSUE 01 REV 00 PAGE 16
24 – ELECTRICAL POWER
ENGINEERING TRAINING CENTRE ATR 72 – 212A MAINTENANCE TRAINING MANUAL
• OVRD: ensures busses are supplied by their respective battery in case of dual DC GEN loss. This position is protected by a
toggle guard.
• ON or OVRD: with TRU connected (Dual DC GEN loss). The TRU supplies ESS BUS, EMER BUS and STBY BUSSES (DC and
AC through INV 1).
On MFD, State 3 is displayed when the corresponding DC HOT BUS voltage is greater than 18V with the "OVRD" position
selected.
The "BAT TIE" caution light illuminates amber when associated battery is discharging:
• Right arrow illuminates amber when the DC ESS BUS is supplied from the MAIN BAT.
• Left arrow illuminates amber when the DC EMER BUS is supplied from the EMER BAT.
On MFD, the corresponding amber arrow is displayed.
TRAINING PURPOSES ONLY
The "BAT CHG" pushbutton controls the associated Battery Charge Contactor (BCC) operation:
• ON: (pushbutton depressed without lighting), the MFC controls the contactor which is closed in normal operation.
TRAINING PURPOSES ONLY
The "BAT CHG" pushbutton controls the associated Battery Charge Contactor (BCC) operation which opens in case of:
• Thermal runaway of the battery.
• Under voltage of the DC MAIN BUS (< 25 volts).
• Start sequence is initiated (in this case, both BCC are open, and will close when start rotary selector leaves "START" or
"CRANK" position).
• A selected "OVRD" position with the BAT toggle switch.
ISSUE 01 REV 00 PAGE 18
24 – ELECTRICAL POWER
ENGINEERING TRAINING CENTRE ATR 72 – 212A MAINTENANCE TRAINING MANUAL
The "AC BUS OFF" caution light is blank when the associated main AC BUS is supplied.
On MFD, State 1 is displayed.
The "AC BUS OFF" caution light illuminates amber when the associated AC BUS is not supplied.
Additionally, if one AC BUS is "OFF" the CCAS will be also activated.
On MFD, State 2 is displayed.
"INV FAULT" caution lights are extinguished when associated inverters are in normal condition.
On MFD, State 1 is displayed.
The "INV FAULT" caution light illuminates amber and the CCAS is activated when an under / over voltage is detected at the output of
the associated inverter. This may be caused by an inverter failure or a power supply loss.
On MFD, State 2 is displayed.
TRAINING PURPOSES ONLY
The "BTC" guarded pushbutton controls the AC Bus Tie Relay (BTR) which, when it is closed, connects both main AC BUSSES:
• NORM: (pushbutton released) the Multi Function Computer (MFC) controls the AC BTR:
In normal condition, with both inverters running, the AC BTR is open allowing dependant operation of both inverter
circuits.
On MFD, no information is displayed.
• In case of inverter failure, the AC BTR is automatically closed and the corresponding "INV FAULT" light illuminates. Its
TRAINING PURPOSES ONLY
associated AC BUSSES are supplied by the remaining valid inverter on the network.
On MFD, State 1 is displayed.
• ISOL: (pushbutton depressed), the AC BTR is open and the "ISOL" light illuminates white.
Note: AC 1 and 2 BUSSES are isolated. DC 1 and 2 BUSSES are isolated.
On MFD, State 1 is displayed.
The "BAT AMP" ammeter indicates the charge (CH) / discharge (DCH) current of the selected battery.
The "EMER/MAIN BAT SEL" selector allows verification of amperage in the selected battery.
The "GND SERVICE BUS" membrane key controls the supply of the DC SVCE BUS:
• ON: (pushbutton depressed), the ON light is illuminated green when DC SVCE BUS is energized.
• SHED: illuminates amber when the DC SVCE BUS is not supply:
TRAINING PURPOSES ONLY
Electrical system indications are located on the ACW Electrical Power Control Panel and on the Multi Function displays (ACW /
Hydraulic SD page).
TRAINING PURPOSES ONLY
The "ACW GEN" pushbutton controls the energization of the associated generator and the resetting of the protection system after
failure:
• ON: (pushbutton depressed without lighting), the associated generator is energized and the associated generator contactor
closes if the network electrical parameters are normal.
On MFD, state 1 is displayed.
• The "FAULT" light of the "ACW GEN" pushbutton illuminates amber, and the CCAS is activated in case of:
A protection trip is initiated by the associated GCU. If it is caused by an under speed generator, the reset will be
automatic. In other cases, a manual reset has to be performed.
An opening of a generator contactor except if pushbutton is selected "OFF".
Note: - In both cases, the BTC's are closed and affected ACW BUS is automatically supplied from the remaining generator. The
light extinguishes and the fault circuit is reset when the pushbutton is cycled to the out position.
Additionally, the BPCU sheds the ACW SVCE BUS as soon as one generator is off line.
On MFD, state 2 is displayed.
• The "OFF" light of the "ACW GEN" pushbutton illuminates white, when the pushbutton is released and the associated generator
is de-energized and associated contactor is open.
On MFD, state 3 is displayed.
The "ACW BUS OFF" caution light is blank, when the associated main ACW BUS is normally supplied.
On MFD, state 1 is displayed.
The "ACW BUS OFF" caution light illuminates amber, when the associated main ACW BUS is not supplied. If one ACW BUS is OFF the
CCAS will be also activated.
Note: When the ACW BUS 1 is OFF the ACW SVCE BUS is shedded.
The "BTC" guarded pushbutton controls ACW Bus Tie Contactors (BTC1 and BTC2) which, when they are closed, connect both main
ACW BUSSES in parallel:
• NORM: (pushbutton released), automatically the BPCU controls ACW BTCs: In normal condition with both generators running,
TRAINING PURPOSES ONLY
The "BTC" guarded pushbutton controls ACW Bus Tie Contactors (BTC1 and BTC2):
• NORM: (pushbutton released), automatically the BPCU controls ACW BTCs: In case of external power operation or single
generation running, BTCs are automatically closed and the green flow bar is illuminated and affected ACW BUS is supplied
through BTCs closure.
On MFD, state 2 is displayed.
ISSUE 01 REV 00 PAGE 25
24 – ELECTRICAL POWER
ENGINEERING TRAINING CENTRE ATR 72 – 212A MAINTENANCE TRAINING MANUAL
The "BTC" guarded pushbutton controls ACW Bus Tie Contactors (BTC1 and BTC2):
• ISOL: (pushbutton pressed in), BTCs are open and the "ISOL" light illuminates white.
On MFD, state 3 is displayed.
The "EXT PWR" pushbutton controls the power via the Bus Power Control Unit (BPCU) which provides protection for:
• voltage limits, • open phase,
• phase sequence, • overload.
• frequency limits,
• AVAIL: (pushbutton released), illuminates green when the above conditions are in the correct status, then the external power can
be used.
On MFD, state 1 is displayed.
The "TRU" pushbutton controls connection / disconnection of the Transformer Rectifier Unit (TRU):
• NORM: (pushbutton released without lighting) the TRU is not connected to ACW BUS 2.
TRAINING PURPOSES ONLY
• The "ON" light on the "TRU" pushbutton illuminates white when the pushbutton is pressed in with the TRU connected to ACW
BUS 2. The arrow illuminates amber when supply of DC EMER BUS, DC STBY BUS, INV 1 and DC ESS BUS from TRU is
effective.
On MFD, state 3 is displayed.
ISSUE 01 REV 00 PAGE 27
24 – ELECTRICAL POWER
ENGINEERING TRAINING CENTRE ATR 72 – 212A MAINTENANCE TRAINING MANUAL
• The "ON" light on the "TRU" pushbutton illuminates white when the pushbutton is pressed in with the TRU connected to ACW
BUS 2, but the TRU is failed.
On MFD, state 4 is displayed.
The "TRU" pushbutton controls disconnection of the Transformer Rectifier Unit (TRU):
• NORM: (pushbutton released), normally the TRU is not connected anymore to the ACW BUS 2, but it still continues to supply DC
EMER BUS, DC STBY BUS, INV 1 and DC ESS BUS. The arrow remains illuminate amber.
On MFD, state 5 is displayed when the TRU remains supplied from ACW BUS 2 due to 93PA contacts welded.
• The "ON" light on the "TRU" pushbutton illuminates white when the pushbutton is pressed in, but the TRU is not supplied by
ACW BUS 2.
On MFD, state 6 is displayed.
TRAINING PURPOSES ONLY
The "GND SERVICE BUS" membrane key controls the supply of the ACW SVCE BUS:
• ON: (pushbutton depressed), the ON light is illuminated green when ACW SVCE BUS is energized.
TRAINING PURPOSES ONLY
Electrical system indications are given on the left maintenance panel, and on the right maintenance panel.
The electrical system failure codes can be read through the Multifunction Control Display Unit (MCDU).
The "ROTARY SELECTOR" allows for selected sources to display relevant current parameters on corresponding indicators.
The "DC VOLTAGE INDICATOR" indicates the voltage of sources selected by the rotary selector. Normal reading is:
• for battery without load = 25 to 28 volts,
• for battery under load = 23 to 28 volts.
The "DC CURRENT INDICATOR" indicates the current generated by selected sources. Normal reading for each generator is: less than
300 A.
The "AC LOAD INDICATOR" indicates in hundred percent the load of selected AC source. Normal reading is below 0.5 (= 250VA) of
Current Nominal (In = 500VA).
The "FREQUENCY INDICATOR" indicates frequency, in Hz, of selected AC source. Normal reading is: 400 Hz ± 5 Hz.
The "AC VOLTAGE INDICATOR" indicates voltage on selected AC source. Normal reading is: 115 V ± 4 V.
A bite loaded magnetic indicator on the RH Maintenance Panel turns amber when an electrical system failure has been recorded and
dedicated to the maintenance operator.
On ground, the Multifunction Control Display Unit (MCDU) permits to access to MFC memory. Electrical system failure codes can be
read in Miscellaneous 1 page of the MCDU.
TRAINING PURPOSES ONLY
The "ROTARY SELECTOR" allows for selected sources to display relevant current parameters on corresponding indicators.
The "AC LOAD INDICATOR" indicates in hundred percent the load of selected ACW source. The normal reading is below 0.5 (= 10
KVA) of Intensity nominal (In = 20KVA).
TRAINING PURPOSES ONLY
The "FREQUENCY INDICATOR" indicates frequency, in Hz, of selected GEN source (ACW 1 or ACW 2). The reading depends of the
flight phase situation and of NP value in percent.
The "AC VOLTAGE INDICATOR" indicates voltage on selected GEN source (ACW 1 or ACW 2). The normal reading is: 115 V ± 4 V.
The guarded "ACW BTC OPNG" toggle switch is used to open the corresponding ACW Bus Tie Contactor (BTC 1 or BTC 2) during
maintenance action.
ISSUE 01 REV 00 PAGE 32