PROFIBUS-DP

SIMATIC ET 200S Distributed I/O Devices


SSI module
PROFIBUS-DP

■ Overview
• Single-channel module for • Can be plugged into terminal
ST70499z
connecting SSI encoders to module TM-E 1 ) with automat-
ET 200S ic coding
• For position detection and • Fast mode for high-speed ac-
easy positioning tasks quisition of encoder values,
for example, for drive controls
• With two comparison func-
tions with comparison values • Module replacement during
that can be specified (stand- operation with voltage ap-
ard mode) plied ("hot swapping") is pos-
sible
• With digital input for latching
actual values (standard • Easy parameterization
mode) without additional software

■ Application
The SSI module enables SSI There are two operating modes: • Fast mode with time-opti-
encoder values to be acquired mized encoder value transfer
• Standard mode with latch
for position detection and easy
and comparison functions
positioning tasks.

■ Design
The mechanical characteristics • 1 red LED for displaying • 1 green LED for displaying
of the SSI module are: faults (group fault) the status of the integrated
digital input
• Compact design: • 2 green LEDs to display the
The compact module is only encoder direction of rotation • 1 green LED for displaying
15 mm wide and contains: – Forwards: LED UP the status of comparator
– Backwards: LED DN No. 1

■ Operation
• Actual value acquisition • Latching actual values • Status indication and diag-
(standard+fast): (standard): nostics (standard+fast):
The module acquires the ac- The actual value is latched on Errors in position detection
tual values of the SSI encod- the rising edge of the digital and in the status of the com-
ers (13, 12, 25 bits) and input; the frozen value is also parison function are indicated
makes them available to the available at the DP interface via LEDs and supplied to the
higher-level master to the master master
• Comparison function • Power supply for the encod-
(standard): er (standard+fast):
The actual value is compared The encoder is supplied via
with two comparison values the SSI module
supplied by the master; the
results are indicated on the
interface to the master

■ Functions
• Acquisition of the actual val- • Data transmission rate adjust- • Comparison function:
ues of an SSI encoder (13, able: Comparison of the actual val-
21, 25 bits) 125 kHz, 250 kHz, 500 kHz, ue with two comparison val-
1 MHz, 2 MHz ues.
• Gray-code/BCD conversion,
adaptation of the direction of • Monoflop time (dead time be- • Latch function:
rotation, actual value normali- tween the transmission of two Active on the rising or falling
zation parameterizable actual values from the encod- edge of the digital input; the
er) adjustable: currently acquired position
16 µs, 32 µs, 48 µs, 64 µs encoder status is latched

■ Parameterization
Parameters are assigned using The data record is transferred
STEP 7 or COM PROFIBUS and on power-up. Special software
standardized GSD files. is not necessary.

1) For selection of the appropriate TM-E, see the configuring aids.

1/252 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
SSI module

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
SSI module A 6ES7 138-4DB00-0AB0 250 1
for connecting SSI encoders to ET 200S
Accessories
Inscription sheet in A4 format
• petrol A 6ES7 193-4BH00-0AA0 251 1
• red A 6ES7 193-4BD00-0AA0 251 1
• yellow A 6ES7 193-4BB00-0AA0 251 1
• light beige A 6ES7 193-4BA00-0AA0 251 1

■ Connection diagram
SSI module

1 SSI

SF

7 IN

2;6 L+
1 D
D
5
SSI
4 C
8 C
3 M

X 2
3 4

UP DN
CMP 7
G_IK10_deP0075s

6ES7
138-4DB00-0AB0

Siemens NS K · 2002 1/253


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
SSI module

■ Technical data
Channel number 1
Counting range ±31 bit
Connectable encoders • SSI encoder 13, 21, 25 bit
• Gray-code, BCD
Baudrate to encoder Setting range: 125 kHz, 250 kHz, 500 kHz, 1 MHz, 2 MHz
Monoflop time Setting range: 16/32/48/64 µs
Power supply for encoders via SSI module: L+ –0.8 V, 500 mA, short-circuit proof
Cable length for encoder 320 m for 125 kHz
160 m for 250 kHz
60 m for 500 kHz
20 m for 1 MHz
8 m for 2 MHz
Number of digital inputs 1
Input voltage in V DC 24, –15 % ... +20 %
• for "1" signal in V typ. DC –30 ... + 30
• for "0" signal in V DC 11 ... + 30
Input current in mA
• for "1" signal 9
• for "0" signal Closed-circuit current ≤ 2
Input delay in µs max. 300
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Cable length in m
• unshielded 32
• shielded 600
Actual value acquisition Cyclic transfer of the current actual value to the master in 500 µs cycle
Comparison function, Comparison of the actual value with up to two comparison values.
e.g. for easy positioning tasks Transfer of the comparison value from the master.
Indication of the comparison result to the master
Freeze functions, Latching the actual value on
e.g. for length measurement, distance measurement • a rising edge
• a falling edge
• a rising and falling edge of the digital input.
Transfer of the frozen actual value to the master
Adaptation of direction of rotation Adaptation of the counting direction of the encoder and of the SSI module for
allows low-cost, non-programmable encoders to be used • counting in the same direction
• counting in the opposite direction
Actual value normalization Automatic suppression of non-relevant bits
Monitoring function Indication of short-circuit of encoder supply; transmission error, wire-break
Parameters 16 bytes

1/254 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
2PULSE pulse generator
Actuator-Sensor-Interface

■ Overview
2-channel pulse generator and
2Pulsez
timer module for ET 200S
• For controlling final control el-
ements, valves, heating ele-
ments etc. by means of any of
the following:
• Pulse-width modulation,
pulse trains, pulse sequenc-
es, time-limited permanent
signals on a 24 V output

■ Application
The pulse generator and timer elements for proportioning/fill- • Food processing • Plastics
module ET 200S 2PULSE are ing and for repositioning or con-
• Pharmaceuticals • Ceramics
used for controlling valves, final trolling, for example, in the fol-
control elements, heating lowing industrial sectors: • Chemicals
(paints/coatings)

■ Design
• Single-width module • 2 channels each with • LEDs: – 1 LED per DO for status in-
(15 mm) – 1 digital output DC 24 V – 1 LED per DI for status in- dication
– 1 digital input DC 24 V dication – 1 LED for group fault

■ Operation
Depending on the parameter- The output values are specified as required, either by the user Both channels can be operat-
ized operating mode, the mod- by the user programme, activa- programme or the digital input ed mutually independently.
ule generates signals and pulse tion is performed of the channel.
trains independently of the mas-
ter CPU and outputs them on the
digital output.

■ Functions
• Max. output frequency "PWM" operating mode "Pulse sequence" operating "ON/OFF delay"
2.5 kHz (pulse width modulation) mode operating mode
• Max. output current 2 A • A pulse-width modulated sig- • A number of pulses that can • A signal that is applied to the
nal sequence is output on the be specified by the user is 24 V digital input is output on
• Time setting range 200 µs to
24 V digital input. The period output on a 24 V digital out- the 24 V digital output with an
60 s
duration is parameterized. It put. The period duration is ON/OFF delay.
"Pulse output" operating mode can be changed via the user parameterized. It can be
An ON delay (active for the
programme. The mark/space changed via the user pro-
• A pulse is output once on a rising edge) and an OFF de-
ratio is specified by the PLC gramme. An ON delay can be
24 V digital output. The pulse lay (active for the falling
programme. An ON delay parameterized.
duration is specified by the edge) can be parameterized.
can be parameterized.
user programme. An ON • Pulse output starts when an
Both values can be changed
delay can be parameterized • Pulse width modulation starts interface bit is set (after the
via the user programme.
and can be changed via the when an interface bit is set ON delay has elapsed) and
user programme. (after the ON delay has ends when the specified
elapsed) and ends when this number of pulses has been
• Pulse output starts when an
bit is reset. Alternatively, output on the DO or before-
interface bit is set (after the
pulse output can be control- hand if the bit is reset.
ON delay has elapsed). Alter-
led by using the digital input Alternatively, pulse output
natively, pulse output can be
as a HW gate. can be started by using the
enabled/disabled by using
digital input as a HW gate.
the digital input as a HW
gate.

■ Parameterization
Parameters are assigned and standardized GSD files.
using STEP 7, Version 5.1 SP1
and higher or COM PROFIBUS

Siemens NS K · 2002 1/255


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
2PULSE pulse generator

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
Pulse generator and timer module 2PULSE A 6ES7 138-4DD00-0AB0 250 1
for ET 200S
Accessories
Inscription sheet in A4 format
• petrol A 6ES7 193-4BH00-0AA0 251 1
• red A 6ES7 193-4BD00-0AA0 251 1
• yellow A 6ES7 193-4BB00-0AA0 251 1
• light beige A 6ES7 193-4BA00-0AA0 251 1

■ Technical data
Dimensions and weights
Dimensions (W × H × D) in mm 15 × 81 × 52
Weight in g approx. 40
Number of channels 2
Voltages, currents, potentials
Rated load voltage L+ in V (from power module) DC 24
• Polarity reversal protection yes
Isolation
• between the channels no
• between the channels and the backplane bus yes
Permissible potential difference
• between different electric circuits in V DC 75, AC 60
Isolation tested at DC 500 V
Encoder supply
• Output voltage in V L+ -0.8
• Output current in mA max. 500, short-circuit proof
Supply current in mA
• from backplane bus max. 10
• from load voltage L+ (or load) max. 40
Power loss in W typ. 1.8
Digital inputs
Input voltage in V
• Rated value DC 24
• for "1" signal 11 ... 30
• for "0" signal –30 ... +5
Input current in mA
• for "1" signal, typ. 9
Minimum pulse time or pause time in µs 25
Response time in µs max. 100
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Connection of 2-wire BEROs possible
• Permissible residual current in mA max. 2
Cable length, shielded in m max. 100

1/256 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
2PULSE pulse generator

■ Technical data
Digital outputs
Output voltage
• for "1" signal min. L+ –1 V
Output current
• for "1" signal
– Rated value 2A
– Permissible range 7 mA ... 2 A
• for "0" signal (residual current) max. 0.5 mA
Minimum pulse duration in µs 200
Accuracy ± (pulse duration x 100 ppm)
± 100 µs
Output delay (for resistive load) in µs
• for "0" to "1" max. 100
• for "1" to "0" max. 200
Lamp load in W max. 10
Activation of a digital input yes
Switching frequency
• for resistive load in kHz 2.5
• for inductive load in Hz max. 2
• for lamp load in Hz max. 10
Inductive switch-off voltage is limited (internally) to L+ - (50 V ... 65 V)
Short-circuit protection of the output yes
• Response threshold in A typ. 10
Cable lengths in m
• unshielded 600
• shielded 1000

Siemens NS K · 2002 1/257


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1STEP step module
Actuator-Sensor-Interface

■ Overview
• Single-channel module for • External stop with/without
St70595z
ET 200S for controlled posi- ramp via digital input
tioning of a stepper motor
• Status display and fault indi-
• Operating modes: Reference cation via LEDs:
point approach and incre- Errors in positioning and the
mental traverse statuses are displayed via
LEDs and at the interface to
• Connection of power sections
the master
with pulse/direction interface
via 5 V difference signals

■ Application
The stepper module 1STEP per- In conjunction with
mits simple positioning tasks FM STEPDRIVE and
with stepper motor axes. SIMOSTEP stepper motors,
complete stepper motor axes
can be equipped.

■ Design
The mechanical characteristics – 2 green LEDs for displaying • Easy installation: • User-friendly wiring:
of the stepper module 1STEP the status of the digital in- The stepper module is easy The stepper module 1STEP is
are: puts to install and deinstall, as are wired up using the screw-
– 1 green LED for displaying all other ET 200S modules. type or spring-loaded termi-
• Compact design;
the status "Ready for posi- nals on the front. When the
the stepper module is single-
tioning commands" module is replaced, the wir-
width (15 mm) and contains:
– 1 green LED for displaying ing remains intact and can be
– 1 red LED for displaying
the status "Positioning now" used directly for the new
faults (group fault)
module.

■ Operation
• Basic parameterization: – Parameterization tasks for • Positioning the stepper mo- • Starting/stopping positioning
By transferring a parameter setting/changing the basic tor: tasks, reading out status in-
set from a GSD file on power- parameters The direction signal and puls- formation into the PROFIBUS
up – Positioning tasks for speci- es are transferred to a step- master:
fying the positioning pa- per motor power section as Starting of traversing tasks
• Interface to the higher-level
rameters before traversing specified by a higher-level and reading out the status in-
PROFIBUS master:
the axes; in the "Reference PLC formation by the PROFIBUS
A distinction is made be-
point approach" and "Incre- – The direction signal deter- master via interface bits.
tween parameterization and
mental traverse" operating mines the traversing direc- Traversing movements can
positioning tasks
modes tion either be stopped via a high-
– The number of pulses out- er-level PLC or via an on-
put determines the travers- board input
ing distance
– The frequency of the pulses
determines the traversing
speed

■ Functions
• Reference point approach: • Stop:
Synchronization of the axis Either via the PROFIBUS
master or via onboard inputs
• Incremental traverse:
The axis is traversed by a • Parameter change
specified distance

■ Parameterization
Configuration/parameterization Selected parameters can also For quick and easy start-up of
is performed using STEP 7 or be changed by the higher-level the stepper module, the GSD
COM PROFIBUS and a stand- PLC. file included in STEP 7 or
ardized GSD file. COM PROFIBUS is executable.

1/258 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1STEP step module

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
1STEP step module A 6ES7 138-4DC00-0AB0 250 1
for simple positioning tasks with stepper motor axes
SIMOSTEP stepper motors see ST 70 Catalogue
Power section for stepper motors FM STEPDRIVE see ST 70 Catalogue
Accessories
Inscription sheet in A4 format
• petrol A 6ES7 193-4BH00-0AA0 251 1
• red A 6ES7 193-4BD00-0AA0 251 1
• yellow A 6ES7 193-4BB00-0AA0 251 1
• light beige A 6ES7 193-4BA00-0AA0 251 1

■ Technical data
Rated input voltage in V DC 24
Number of stepper motor channels 1
Power losses in W 1.5
Dimensions (W × H × D) in mm 15 × 81 × 52
Weight in g approx. 40
Interface to motor power section
Difference signals acc. to RS 422
for pulses (PULSE, PULSE) and
direction (DIR, DIR)
Cable length, shielded in m max. 100, twisted-pair cable
Number of digital inputs 2
Function
• REF input Reference cam
• DI input Pulse inhibit or external stop
Input voltage in V
• Rated value DC 24 –15% / + 20%
• for "1" signal DC 11 ... 30
• for "0" signal DC -30 ... +5
Input current in mA
• for "1" signal, typ. 9
• for "0" signal Closed-circuit current ≤ 2
Input delay in µs
• "0" to "1" max. 300
• "1" to "0" 300
Repetition frequency in kHz max. 1
Connection of 2-wire BEROs yes
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Cable length in m
• unshielded 600
• shielded 1000

Siemens NS K · 2002 1/259


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1 POS SSI/digital positioning module
Actuator-Sensor-Interface

■ Overview
• Single-channel positioning
POSz
module for ET 200S
• For controlled positioning with
the help of digital outputs ac-
cording to the rapid traverse/
creep feed principle
• For absolute encoders with
SSI interfaces

■ Application
The ET 200S 1Pos SSI / Digital The 1 Pos SSI / Digital module • Plastics
is a single-channel positioning can be used in
• Ceramics
module for positioning dis-
• Conveyor systems
placement axes and simple op- • Paper processing
erating axes. Absolute value • Food processing
• Packaging machines
encoders with an SSI interface
• Pharmaceuticals
can be connected.

■ Design
• Double-width module – 3 digital outputs • LEDs: • Easy installation:
(30 mm) DC 24 V for outputting the – 3 LEDs for displaying the The module is easily installed
control signals for the drive status of the DIs and deinstalled in the same
• 1 channel with
– 3 digital inputs – 3 LEDs for indicating the manner as any other ET 200S
– 1 actual-value acquisition
DC 24 V for reference point status of the module: module.
for SSI encoders
approach and as a HW limit Actual value rising, actual
switch value falling, positioning
mode
– 1 LED for group fault

■ Operation
Controlled positioning with the • Once a target position has • When the limit point is Inputs for HW limit switches en-
help of 3 digital outputs been specified, the rapid reached, the drive is sure that an emergencs stop
traverse is started. switched off. takes place when the operating
• Before starting the traverse,
range is exited.
the switching difference and • When the switching point is
limit difference are parame- reached, changeover to
terized once only. creep feed takes place.

■ Functions
• Jog: • Relative traverse: • Parameter change during • Selection of the value re-
The control signals are speci- The axis is traversed by a rel- normal operation: turned in the checkback in-
fied directly by the user pro- ative distance For the parameters switching terface apart from the actual
gramme and the module sim- difference, limit difference, value:
• Latch function:
ply executes them encoder adjustment The possibilities are distance
The actual value is saved by
to go, actual speed, addition-
• Absolute traverse: setting a digital input
al error information or certain
Traversal of the axis to an ab-
parameters.
solute specified position

■ Parameterization
Parameterization is performed The GSD files are already exe-
using STEP 7 Version 5.1 SP1 cutable to support rapid start-
and higher or COM PROFIBUS up.
and standardized GSD files.

1/260 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1 POS SSI/digital positioning module

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
1POS SSI/digital positioning module A 6ES7 138-4DH00-0AB0 250 1
for controlled positioning for absolute encoders with an
SSI interface

■ Technical data
Rated input voltage in V DC 24
Dimensions and weight
Dimensions (W x H x D) in mm 30 x 81 x 52
Weight in g approx. 40
Voltages, currents, potentials
Rated load voltage L+ in V DC 24
• Range in V 20.4 ... 28.8
• Polarity reversal protection yes
Isolation
• between I/O and bus yes
Encoder supply
Output voltage in V L+ -0.8
Output current in mA max. 500, short-circuit proof
Supply current in mA
• from backplane bus max. 10
• from load voltage L+ (or load) max. 50
Power loss in W typ. 1
Digital inputs
Input voltage in V
Rated value DC 24
• for "0" signal –30 ... +5
• for "1" signal 11 ... 30
Input current in mA
• for "0" signal ≤ 2 (perm. residual current)
• for "1" signal 9 (typ.)
Minimum pulse width 500 µs
Connection of a two-wire BERO, Type 2 possible
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Cable length in m 32
Digital outputs
Output voltage in V
Rated value DC 24
• for "0" signal ≤3
• for "1" signal ≥ L+ -1
Output current
• "0" signal (residual current) in mA ≤3
• "1" signal (perm. range) 7 ... 0.6 A
Switching frequency in µs 500
• Resistive load in Hz 100
• Inductive load in Hz 2
• Lamp load in Hz ≤ 10
Output delay (resistive load) possible
• "0" signal in µs max. 200
• "1" signal in ms max. 1.3
Short-circuit protection of the output yes
Response threshold in A 0.7 ... 1.8
Inductive erasing yes; L+ - (55 ... 60 V)
Activation of a digital input yes
Cable lengths in m
• unshielded 600
• shielded 1000

Siemens NS K · 2002 1/261


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1 POS SSI/digital positioning module

■ Technical data
SSI encoder signals
Position sensing Absolute
Difference signals for SSI data and SSI clock acc. to RS 422
Data transfer rate and cable lengths for 125 kHz max. 320 m
(shielded twisted-pair cable) for 250 kHz max. 160 m
for 500 kHz max. 60 m
for 1 MHz max. 20 m
for 2 MHz max. 8 m
Status, alarms, diagnostics
Status display, actual value rising LED UP (green)
Status display, actual value falling LED DN (green)
Status display, positioning mode LED POS (green)
Status display, DI LED 9 (green)
Status display, DI LED 13 (green)
Status display, DI LED 14 (green)
Diagnostic functions LED SF (red)
Fault indication on the module yes
Refresh rate for checkback signals in ms 2
Module replacement
• During operation of the IM-DP yes
• With normal voltage applied yes

1/262 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1 POS Inc/digital positioning module
Actuator-Sensor-Interface

■ Overview
• Single-channel positioning
POS_Incz
module for ET 200S
• For controlled positioning with
the help of digital outputs ac-
cording to the rapid traverse/
creep feed principle
• With actual position sensing
for incremental encoder acc.
to RS 422

■ Application
Positioning of displacement ax- • Food processing • Plastics • Paper processing
es and simple operating axes
• Pharmaceuticals • Ceramics • Packaging machines

■ Design
• Double-width module – three 24 V DOs for output- • Seven LEDs: • Easy installation:
(30 mm) ting the control signals for – 3 LEDs for displaying the The module is easily installed
the drive status of the DIs and deinstalled in the same
• 1 channel with
– three 24 V DIs for reference – 3 LEDs for indicating the manner as any other ET 200S
– 1 encoder acquisition for
point approach and as a status of the module: module.
incremental encoder to
HW limit switch Actual value rising, actual
RS 422
value falling, positioning
mode
– 1 LED for group fault dis-
play

■ Operation
Controlled positioning with the • Once a target position has • When the limit point is Inputs for HW limit switches en-
help of 3 digital outputs been specified, the rapid reached, the drive is sure that an emergency stop
traverse is started. switched off. takes place when the operating
• Before starting the traverse,
range is excited.
the switching difference and • When the switching point is
limit difference are parame- reached, changeover to
terized once only. creep feed takes place.

■ Functions
• Jog: • Relative traverse: • Reference point approach: • Selection of the value re-
The control signals are speci- The axis is traversed by a rel- For synchronization after turned in the checkback in-
fied directly by the user pro- ative distance switching on the PLC or dur- terface apart from the actual
gramme and the module sim- ing normal operation value:
• Latch function:
ply executes them The possibilities are distance
The actual value is saved by • Parameter change during
to go, actual speed, addition-
• Absolute traverse: setting a digital input normal operation:
al error information or certain
Traversal of the axis to an ab- For the parameters switching
parameters.
solute specified position difference, limit difference

■ Parameterization
Parameterization is performed The GSD files are already exe-
using STEP 7 Version 5.1 SP1 cutable to support rapid start-
and higher or COM PROFIBUS up.
and standardized GSD files.

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
1POS Inc/digital positioning module A 6ES7 138-4DG00-0AB0 250 1
for controlled positioning for incremental encoders acc.
to RS 422

Siemens NS K · 2002 1/263


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1 POS Inc/digital positioning module

■ Technical data
Module 1 POS Inc / digital high feature
Rated input voltage in V DC 24
Dimensions and weight
Dimensions (W x H x D) in mm 30 x 81 x 52
Weight in g approx. 80
Voltages, currents, potentials
Rated load voltage L+ in V DC 24
• Range in V 20.4 ... 28.8
• Polarity reversal protection yes
Isolation
• between I/O and bus yes
Encoder supply
Output voltage in V L+ -0.8
Output current in mA max. 500, short-circuit proof
Supply current in mA
• from backplane bus max. 10
• from load voltage L+ (or load) max. 50
Power loss in W typ. 1
Digital inputs
Input voltage in V
Rated value DC 24
• for "0" signal -30 ... +5
• for "1" signal 11 ... 30
Input current in mA
• for "0" signal ≤ 2 (perm. residual current)
• for "1" signal 9 (typ.)
Minimum pulse width in µs 500
Connection of a two-wire BERO, Type 2 possible
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Cable length in m 32
Digital outputs
Output voltage in V
Rated value DC 24
• for "0" signal ≤3
• for "1" signal ≥ L+ -1
Output current
• "0" signal (residual current) in mA ≤3
• "1" signal (perm. range) 7 ... 0.6 A
Switching rate in µs 500
• Resistive load in Hz 100
• Inductive load in Hz 2
• Lamp load in Hz ≤ 10
Output delay (resistive load) possible
• "0" signal in µs max. 200
• "1" signal in ms max. 1.3
Short-circuit protection of the output yes
Response threshold in A 0.7 ... 1.8
Inductive erasing yes; L+ - (55 ... 60 V)
Activation of a digital input yes
Cable lengths in m
• unshielded 600
• shielded 1000

1/264 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1 POS Inc/digital positioning module

■ Technical data
SSI encoder signals
Position sensing Absolute
Difference signals for SSI data and SSI clock acc. to RS 422
Data transfer rate and cable lengths for 125 kHz max. 320 m
(shielded twisted-pair cable) for 250 kHz max. 160 m
for 500 kHz max. 60 m
for 1 MHz max. 20 m
for 2 MHz max. 8 m
Status, alarms, diagnostics
Status display, actual value rising LED UP (green)
Status display, actual value falling LED DN (green)
Status display, positioning mode LED POS (green)
Status display, DI LED 9 (green)
Status display, DI LED 13 (green)
Status display, DI LED 14 (green)
Diagnostic functions LED SF (red)
Fault indication on the module yes
Refresh rate for checkback signals in ms 2
Module replacement
• During operation of the IM-DP yes
• With normal voltage applied yes

Siemens NS K · 2002 1/265


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 24 V/100 kHz counter module
Actuator-Sensor-Interface

■ Overview
• Single-channel intelligent • Can be plugged into terminal
ST70493z
counter module for universal module TM-E 1) with automat-
counting and time-oriented ic coding
measuring tasks
• Module replacement during
• For direct connection of 24 V operation with voltage ap-
incremental encoders or initi- plied ("hot swapping") is pos-
ators sible
• Comparison function using • Easy parameterization
comparison values that can without additional software
be specified
• Integrated digital output for
outputting the response when
the comparison value is
achieved

■ Application
The ET 200S 1COUNT 24 V/ • Assembly and handling • Production machines • Packaging machines
100 kHz is used for counting equipment
• Wood and paper machines • Glass and ceramics industry
and measurement tasks (length,
• Rubber and plastics ma-
frequency, speed and period • Textile machines
chines
duration measurement) in

■ Design
• Single-width module – 1 green LED for displaying • Mounting: • The following terminal mod-
(15 mm) the status of the integrated The counter module is easily ules can be used:
digital input or output installed and deinstalled in – TM-E15S24-01
• LEDs:
– 1 red LED for group error the same manner as any oth- – TM-E15C24-01
– 2 green LEDs to display the
indication er ET 200S module with per- – TM-E15S26-A1
counting direction
manent wiring without the – TM-E15C26-A1
(Up: LED UP; • Connections (encoder and
need for special tools.
Down: LED DN) DI/DO) via terminal module

■ Operation
The counter module 1COUNT There are six possible operating modes:
acquires pulses from Operating mode Description
• 24 V incremental encoders, Continuous counting Once the gate has been enabled, continuous counting takes place
• distance encoders and from the start value between the lower and upper count limits
• initiators One-shot counting When the gate is enabled, counting takes place in accordance
with the counting direction once only from the start value as far as
in response to directly connect- the upper or lower limit value.
able gating signals. The coun-
ter module compares the count • Main counting direction Up:
with the specified comparison from 0 as far as the parameterized end value
values in both count directions. • Main counting direction Down:
The reaction can be output to from the parameterized start value to 0
the process in two different Periodic counting When the gate is enabled, counting takes place in accordance
ways: with the main counting direction periodically from the start value
• Directly via the integrated within the parameterized counting range.
digital output on the counter • Main counting direction Up:
module Periodically from 0 as far as the parameterized limit value –1
• Via the integrated backplane • Main counting direction Down:
bus: The counter module Periodically from the parameterized start value to 1
sends status information to
the CPU Frequency measurement Once the gate has been enabled, all pulses that are received in a
parameterizable time window are counted and the frequency is de-
termined.
Speed measurement Once the gate has been enabled, all pulses that are received in a
parameterizable time window are counted and the speed is deter-
mined.
Period measurement Once the gate has been enabled, all pulses that are received in a
parameterizable time window are counted and the period duration
is determined.

1) For selection of the appropriate TM-E, see the project planning aids.

1/266 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 24 V/100 kHz counter module
Actuator-Sensor-Interface

■ Operation
In the event of CPU failure, the Function Description
following alternatives are availa- Abort The outputs are switched off immediately and the counting/meas-
ble: uring process is aborted.
Continue The module continues to count/measure as before.
Substitute values The current counting/measuring procedure is aborted. The module
switches the parameterized substitute value to the output.
Hold last value The current counting/measuring procedure is aborted. The output
of the module is frozen in the state in which it was immediately be-
fore aborting.

■ Functions
• 1 channel for Up and Down • Gate control via level on digit- • Output signal (24 V level), • Latch function:
counting; 32 bits al input (HW gate) as well as controlled via the compari- The actual count value is
software activation (SW gate) son function: saved by setting the digital
• Counting frequency up to
– as a permanent signal from input
100 kHz • Loading the counter with a
the comparison value to the
defined start value • Synchronization:
• Counting range ±31 bits count limit
once only or periodic syn-
• Comparison function using – as a permanent signal be-
• Continuous, one-shot or peri- chronization with simultane-
comparison values that can tween comparison value 1
odic counting ous loading of the counter
be specified and comparison value 2
with the load value
• 1, 2 or 4-fold evaluation
• Reaction on reaching a com-
• Connectable incremental en- parison value or on range
coders: overshoot
24 V encoders or initiators

■ Parameterization
Parameterization is performed PROFIBUS and standardized The GSD file is already executa-
using STEP 7, Version V5.0 and GSD files. ble to support rapid start-up.
higher Servicepack 3 or COM

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
1COUNT 24 V/100 kHz Counter module A 6ES7 138-4DA02-0AB0 250 1
for universal counting and measuring tasks with
ET 200S
Accessories
Inscription sheet in A4 format
• petrol A 6ES7 193-4BH00-0AA0 251 1
• red A 6ES7 193-4BD00-0AA0 251 1
• yellow A 6ES7 193-4BB00-0AA0 251 1
• light beige A 6ES7 193-4BA00-0AA0 251 1

Siemens NS K · 2002 1/267


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 24 V/100 kHz counter module

■ Technical data
Number of channels 1
Parameter length 16 bytes
Rated load voltage L+ in V DC 24
• Range in V 20.4 ... 28.8
• Polarity reversal protection yes
Isolation
• between the backplane bus and the counter function yes
• between the counter function and the load voltage no
Encoder supply
• Output voltage L+ (–0.8 V)
• Output current in mA max. 500, short-circuit proof
Current consumption
• from backplane bus in mA max. 10
• from load voltage L+ (without load) in mA max. 42
• Power loss of the electronic module in W typ. 1
Counting signals and digital input
Isolation no, only from shield
Input voltage in V
• Rated value DC 24
• for "0" signal –30 ... 5
• for "1" signal 11 ... 30
Input current in mA
• for "0" signal ≤ 2 (closed-circuit current)
• for "1" signal typ. 9
Minimum pulse width (max. counting frequency)
• Filter On ≥ 25 µs (20 kHz)
• Filter Off ≥ 2.5 µs (200 kHz)
Connection of a two-wire BERO, Type 2 possible
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Cable length, shielded yes
• Filter 200 kHz in m 50
• Filter 20 kHz in m 100
Digital output
Number 1
Output voltage in V
• Rated value DC 24
• for "0" signal ≤3
• for "1" signal ≥ L+ (–1)
Output current
• "0" signal (residual current) in mA ≤ 0.5
• for "1" signal
– Permissible range 5 mA to 2 A
– Rated value in A 2 (40 °C); 1 (50 °C); 0.5 (60 °C)
Switching frequency in Hz
• with resistive load 100
• with inductive load 2
• with lamp load ≤ 10
Lamp load in W ≤ 10
Output delay (resistive load) in µs 100
Short-circuit protection of the output yes
Response threshold in A 2.6 to 4
Inductive erasing yes; L+ (50 ... 60 V)
Activation of a digital input yes
Cable lengths in m
• unshielded 600
• shielded 1000

1/268 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 24 V/100 kHz counter module

■ Technical data
Status, diagnostics
Status display, digital input DI LED 8 (green)
Status display, digital output DO LED 4 (green)
Count change Up LED UP (green)
Count change Down LED DN (green)
Fault indication LED SF (red)
on the electronic module
Diagnostic functions yes
Measuring ranges
max. measuring range
• Frequency measurement 0.1 Hz ... 100 kHz
• Speed measurement 1 rpm ... 25,000 rpm
• Period measurement 10 µs ... 120 s
Replacement of the electronic module
• During operation of the IM-DP possible
• With normal voltage applied possible
Parameters for counting modes
Group diagnostics disable/enable
Response to CPU/master STOP Switch off DO1/"Continue" mode/
DO1 connect substitute value/DO1 hold last value
Encoder parameters
• Signal evaluation A*, B* Pulse and direction/shaft encoder once/twice/four times
Encoder and input filter
• Counter input (Track A*) 2.5 µs (200 kHz)/25 µs (20 kHz)
• for direction input (Track B*) 2.5 µs (200 kHz)/25 µs (20 kHz)
• for digital input 2.5 µs (200 kHz)/25 µs (20 kHz)
Sensor A*, B*, DI 24 V P-switch, opposing pulse/24 V M switch
Direction input B* normal/inverted
Output parameters
• Function of DO1 Output/switch on at count
≥ Comparison value/switch on at count
≤ Comparison value/pulse when comparison value reached/
switch at comparison values
• Function of DO2 Output/switch on at count
≥ Comparison value/switch on at count
≤ Comparison value/pulse when comparison value reached
• Substitute value DO1 0/1
• Diagnostics DO1 Off/On
• Hysteresis DO1, DO2 0 ... 255
• Pulse duration (ms) DO1, DO2 0 ... 255
Operating mode
• Counting mode Countinuous counting/One-shot counting/Periodic counting
• Gate function Abort counting/Interrupt counting
• Digital input normal/inverted
• Function DI Input/HW gate/latch and retrigger on positive edge/
synchronization on positive edge
• Synchronization once only/periodic
• Main counting direction none/Up/Down
• Upper counting limit 2 to 7FFF FFFF
Note:
Default settings for parameters are underlined.

Siemens NS K · 2002 1/269


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 24 V/100 kHz counter module

■ Technical data
Parameters for measuring modes
Group diagnostics disable/enable
Response to CPU/master STOP Switch off DO1/"Continue" mode/
DO1 connect substitute value/DO1 hold last value
Encoder parameters
• Signal evaluation A*, B* Pulse and direction/shaft encoder once
Encoder and input filter
• Counter input (Track A*) 2.5 µs (200 kHz)/25 µs (20 kHz)
• for direction input (Track B*) 2.5 µs (200 kHz)/25 µs (20 kHz)
• for digital input 2.5 µs (200 kHz)/25 µs (20 kHz)
Sensor A*, B*, DI 24 V P-switch, opposing pulse/
24 V M switch
Direction input B* normal/inverted
Output parameters
• Diagnostics DO1 Off/On
• Function of DO1 Output/outside limits/
below lower limit/
above upper limit
• Substitute value DO1 0/1
Operating mode
• Measuring mode Frequency measurement/
Speed measurement/
Time period measurement
• Function of DI Input/HW gate
• Digital input DI normal/inverted
• Lower limit 0 ... fmax -1 or Tmax-1 or nmax-1
• Upper limit 1 ... fmax or Tmax or nmax
• Integration time (n* 10 ms) 1 ... 10 ... 1000/12000
• Encoder pulses per revolution 1 ... 65535
• Parameter length 16 bytes
Module width in mm 15
Weight in g approx. 40
Note:
Default settings for parameters are underlined.

■ Connection diagram
1COUNT 24 V/100 kHzCounter module

1 Count
24V/100kHz
SF

1 B*
5 A*
OUT
4
8 IN

3;7
M
2;6
L+

X 2
3 4

UPX DN
4 8
G_IK10_deP0076s

6ES7
138-4DA00-0AB0

1/270 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 5 V/500 kHz counter module
Actuator-Sensor-Interface

■ Overview
• Single-channel intelligent • Can be plugged into terminal
Count5Vz
counter module for universal module TM-E 1) with automat-
counting and time-oriented ic coding
measuring tasks
• Module replacement during
• For direct connection of 5 V operation with voltage ap-
incremental encoders plied ("hot swapping") is pos-
(RS 422) sible
• Comparison function using • Easy parameterization
comparison values that can without additional software
be specified
• Two integrated digital out-
puts for outputting the re-
sponse when the compari-
son value is achieved

■ Application
The ET 200S 1COUNT 5 V/ • Assembly and handling • Production machines • Packaging machines
500 kHz can be used for count- equipment
• Wood and paper machines • Glass and ceramics industry
ing and measurement tasks
• Rubber and plastics ma-
(length, frequency, speed and • Textile machines
chines
period duration measurement) in

■ Design
The module is 30 mm wide and – Count up: LED UP The counter module is easily in- The following terminal modules
contains: – Count down: LED DN stalled and deinstalled in the can be used:
– Synchronization LED SYN same manner as any other ET
• 1 red LED for displaying • TM-E 30S44-01 or
200S module with permanent
faults (group fault) • 1 green LED for displaying
wiring without the need for spe- • TM-E 30C44-01
the status of the digital input
• 2 green LEDs to display the cial tools.
or output
counting direction

■ Operation
The counter module 1COUNT There are six possible operating modes:
5 V/500 kHz acquires pulses Operating mode Description
from 5 V incremental encoders
(RS 422) in accordance with di- Continuous counting Once the gate has been enabled, continuous counting takes place
rectly connectable gate signals. from the start value between the lower and upper count limits
The counter module compares One-shot counting When the gate is enabled, counting takes place in accordance
the count with the specified with the counting direction once only from the start value as far as
comparison values in both the upper or lower limit value.
count directions. • Main counting direction Up:
The reaction can be output to from 0 as far as the parameterized end value
the process in two different • Main counting direction Down:
ways: from the parameterized start value to 0
• Directly via the integrated Periodic counting When the gate is enabled, counting takes place in accordance
digital output on the counter with the main counting direction periodically from the start value
module within the parameterized counting range.
• Via the integrated backplane • Main counting direction Up:
bus: The counter module Periodically from 0 as far as the parameterized limit value –1
sends status information to
the CPU • Main counting direction Down:
Periodically from the parameterized start value to 1
frequency measurement Once the gate has been enabled, all pulses that are received in a
parameterizable time window are counted and the frequency is de-
termined.
speed measurement Once the gate has been enabled, all pulses that are received in a
parameterizable time window are counted and the speed is deter-
mined.
period measurement Once the gate has been enabled, all pulses that are received in a
parameterizable time window are counted and the period duration
is determined.

1) For selection of the appropriate TM-E, see the project planning aids.

Siemens NS K · 2002 1/271


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 5 V/500 kHz counter module
Actuator-Sensor-Interface

■ Operation
In the event of CPU failure, the Function Description
following alternatives are availa- Abort The outputs are switched off immediately and the counting/meas-
ble: uring process is aborted.
Continue The module continues to count/measure as before.
Substitute values The current counting/measuring procedure is aborted. The module
switches the parameterized substitute value to the output.
Hold last value The current counting/measuring procedure is aborted. The output
of the module is frozen in the state in which it was immediately be-
fore aborting.

■ Functions
• 1 channel for Up and Down • Gate control via level on digit- • Output signal (24 V level), • Latch function:
counting; 32 bits al input (HW gate) as well as controlled via the compari- The actual count value is
software activation (SW gate) son function: saved by setting the digital
• Counting frequency up to
– as a permanent signal from input
500 kHz • Loading the counter with a
the comparison value to the
defined start value • Synchronization
• Counting range ±31 bits count limit
once only or periodic syn-
• Comparison function using – as a permanent signal be-
• Continuous, one-shot or peri- chronization with simultane-
comparison values that can tween comparison value 1
odic counting ous loading of the counter
be specified and comparison value 2
with the load value
• 1, 2 or 4-fold evaluation
• Reaction on reaching a com-
• 5 V (RS 422) incremental en- parison value or on range
coder can be connected overshoot

■ Parameterization
Parameterization is performed or COM PROFIBUS and stand- The GSD file is already executa-
using STEP 7, Version V5.1 and ardized GSD files. ble to support rapid start-up.
higher Servicepack 1

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
1COUNT 5 V/500 kHzCounter module A 6ES7 138-4DA01-0AB0 250 1
for universal counting and measuring tasks with
ET 200S
Accessories
Inscription sheet in A4 format
• petrol A 6ES7 193-4BH00-0AA0 251 1
• red A 6ES7 193-4BD00-0AA0 251 1
• yellow A 6ES7 193-4BB00-0AA0 251 1
• light beige A 6ES7 193-4BA00-0AA0 251 1

1/272 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 5 V/500 kHz counter module

■ Technical data
Number of channels 1
Parameter length 16 bytes
Rated load voltage L+ in V DC 24
• Range in V 20.4 ... 28.8
• Polarity reversal protection yes
Isolation
• between the backplane bus and the counter function yes
• between the counter function and the load voltage no
Encoder supply
• Output voltage L+ (–0.8 V)
• Output current max.
Current consumption
• from backplane bus in mA max. 10
• from load voltage L+ (without load) in mA max. 42
• Power loss of the electronic module in W typ. 2
Track signals A; not A; B; not B
Zero point signals N; not N
Input signal
• Differential input voltage in V 1 ... 10
• Input frequency in kHz max. 500
Encoder supply in V DC 24 via the module
Cable length in m max. 100
Digital input
Isolation no, only from shield
Input voltage in V
• Rated value DC 24
• for "0" signal –30 ... 5
• for "1" signal 11 ... 30
Input current in mA
• for "0" signal ≤ 2 (closed-circuit current)
• for "1" signal, typ. 9
Minimum pulse width 2.5 µs
Connection of a two-wire BERO, Type 2 possible
Input characteristic curve acc. to IEC 1131, Part 2, Type 2
Cable length, shielded in m 50
Digital outputs
Number 2
Output voltage in V
• Rated value DC 24
• for "0" signal ≤3
• for "1" signal ≥ L+ (–1)
Output current
• "0" signal (residual current) in mA ≤ 0.5
• for "1" signal
– Permissible range 5 mA ... 2.4 A
– Rated value in A 2
Switching frequency in Hz
• with resistive load 100
• with inductive load 2
• with lamp load ≤ 10
Lamp load in W ≤ 10
Output delay (resistive load) in µs 100
Short-circuit protection of the output yes
Response threshold in A 2.6 ... 4
Inductive erasing yes; L+ (50 ... 60 V)
Activation of a digital input yes
Cable lengths in m
• unshielded 600
• shielded 1000

Siemens NS K · 2002 1/273


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 5 V/500 kHz counter module

■ Technical data
Status, diagnostics
Status display, digital input DI LED 16 (green)
Status display, digital output DO1 LED 9 (green)
Status display, digital output DO2 LED 13 (green)
Count change Up LED UP (green)
Count change Down LED DN (green)
Synchronization LED SYN (green)
Fault indication on the electronic module LED SF (red)
Diagnostics information yes
Measuring ranges
max. measuring range
• Frequency measurement 0.1 Hz ... 500 kHz
• Speed measurement in rpm 1 ... 25,000
• period measurement 10 µs ... 120 s
Replacement of the electronic module
• During operation of the IM-DP possible
• With normal voltage applied possible
Parameters for counting modes
Group diagnostics disable/enable
Response to CPU/master STOP Switch off DO/"Continue" mode/
DO connect substitute value/DO hold last value
Encoder parameters
• Signal evaluation A, B Shaft encoder once/twice/four times
Encoder and input filter
• Diagnostics A and B Off/On
• Diagnostics N Off/On
• Direction input B* normal/inverted
Output parameters
• Function of DO1 Output/switch on at count
≥ Comparison value/switch on at count
≤ Comparison value/pulse when comparison value reached/
switch at comparison values
• Function of DO2 Output/switch on at count
≥ Comparison value/switch on at count
≤ Comparison value/pulse when comparison value reached
• Substitute value DO1 0/1
• Substitute value DO2 0/1
• Diagnostics DO1 Off/On
• Diagnostics DO2 Off/On
• Hysteresis DO1, DO2 0 to 255
• Pulse duration (ms) DO1, DO2 0 to 255
Operating mode
• Counting mode Countinuous counting/One-shot counting/Periodic counting
• Gate function Abort counting/Interrupt counting
• Digital input normal/inverted
• Function DI Input/HW gate/latch and retrigger with a positive edge/
synchronization on positive edge/latch on positive edge/
HW enable for synchronization
• Synchronization once only/periodic
• Main counting direction none/Up/Down
• Upper counting limit 2 ... 7FFF FFFF
Note:
Default settings for parameters are underlined.

1/274 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1COUNT 5 V/500 kHz counter module

■ Technical data
Parameters for measuring modes
Group diagnostics disable/enable
Response to CPU/master STOP Switch off DO/
"Continue" mode/
DO connect substitute value/
DO hold last value
Encoder parameters
Encoder and input filter
• Diagnostics A and B Off/On
• Diagnostics N Off/On
• Direction input B normal/inverted
Output parameters
• Diagnostics DO1 Off/On
• Diagnostics DO2 Off/On
• Function of DO1 Output/outside limits/
below lower limit/
above upper limit
• Substitute value DO1 0/1
Operating mode
• Measuring mode Frequency measurement/
Speed measurement/
Time period measurement
• Function of DI Input/HW gate
• Digital input DI normal/inverted
• Lower limit 0 ... fmax -1 or Tmax-1 or nmax-1
• Upper limit 1 ... fmax or Tmax or nmax
• Integration time (n* 10 ms) 1 ... 10 ... 1000/12000
• Encoder pulses per revolution 1 ... 65535
• Parameter length 16 bytes
Module width in mm 30
Weight in g approx. 65
Note:
Default settings for parameters are underlined.

■ Connection diagram
1COUNT 5 V/500 kHz Counter module

1 Count
24V/100kHz
SF

1 B*
5 A*
OUT
4
8 IN

3;7
M
2;6
L+

X 2
3 4

UPX DN
4 8
G_IK10_deP0076s

6ES7
138-4DA00-0AB0

Siemens NS K · 2002 1/275


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1SI interface module
Actuator-Sensor-Interface

■ Overview
• Single-channel module for • Parameterization via
Seriell_ssz
serial data transfer via point- GSD file or STEP 7
to-point link (V5.1 or higher)
• RS 232C, RS 422, RS 485
• 2 variants
– ASCII and 3964(R) protocol
– Modbus and USS protocol

■ Application
• Connection of SIMATIC S5 to • Connection of MOBY identifi- • Interfacing to PCs • Connection of non-Siemens
ET 200S via 3964(R) proto- cation systems PLC systems
• Connection of barcode read-
cols
• Connection of drives ers/scanners and other data
• Connection of BDE terminals (e.g. SIMOVERT, SIMOREG, acquisition units
and operator panels MICROMASTER)

■ Design
The mechanical characteristics • 1 green LED "TX" The interface module 1SI is The interface module 1SI is
of the interface module 1S1 are: for displaying the status easily installed and deinstalled wired up using the terminals of
"Send data" in the same manner as any oth- the terminal module (screw-
The interface module is single-
er ET 200S module. type or spring-loaded). When
width (15 mm) and contains: • 1 green LED "RX"
the module is replaced, the wir-
for displaying the status "Re-
• 1 red LED for displaying ing remains intact and can be
ceive data"
faults (group fault) used directly for the new mod-
ule of the same type.

■ Operation
• The parameterization data is the data from the 1SI module • Sending data • Receiving data
transferred when the 1SI are sent to the serial interface The module P_SEND is called The module P_RCV is called
module is powered up. or in which format the data to transfer data from a data to store data received from
On system start-up, the pa- from the 1SI module are ex- block of the S7 to the 1SI the 1SI module in a data
rameterization data that pected at the serial interface module for transmission to block of S7.
specify the exact transmis- (selected protocol, baudrate, the partner
sion parameters are trans- data flow control, character
ferred from the PROFIBUS format, etc.)
master to the 1SI module.
They specify in which format

■ Functions
• ASCII protocol The handshake signals of the • 3964(R) protocol • Modbus protocol
for interfacing to non-Sie- interface can be scanned and for interfacing to Siemens de-
• USS protocol
mens systems with simple controlled by the user pro- vices or non-Siemens compo-
transmission protocols, e.g. gramme. nents via the standardized
protocols with start and end and open Siemens protocol
characters or protocols with 3964(R)
block check characters.

■ Parameterization
Parameterization is performed
using STEP 7 (V5.1 or higher) or
a standardized GSD file.

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
1SI interface module
• ASCII and 3964(R) protocol A 6ES7 138-4DF00-0AB0 250 1
• Modbus and USS protocol A 6ES7 138-4DF10-0AB0 250 1

1/276 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
1SI interface module

■ Technical data
General data
Number of interfaces 1
Rated input voltage in V DC 24
Current input from backplane bus in mA
• 24 V typ. 40
• 3.3 V max. 10
Power loss in W typ. 0.85
LEDs
• Green TxD (transmitting)
RxD (receiving)
• Red SF (system error)
Integrated protocol driver ASCII, 3964(R)
Transmission rates (parameterizable)
• 3964(R), half-duplex 110, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bits/s
• ASCII, full-duplex 110, 300, 1200, 2400, 4800, 9600, 19200, 38400 bits/s
Character frame (parameterizable)
• Bits per character frame 10 or 11
• Bits per character 7 or 8
• Number of start/stop bits 1 or 2
• Parity None, uneven, even, any
No. of bytes per PLC programme cycle in bytes
• Receive direction 13
• Send direction 14
Memory requirement of the standard blocks
P_SEND, P_RCV in S7-CPU in bytes 2700
RS 232C interface
• RS 232C signals 8: TxD, RxD, TRS, CTS, DTR, DSR, DCD, PE
• Electrical isolation from internal ET 200S power supply yes
• Max. cable length in m (shielded) 15
RS 422/485 interface
• RS 422 signals 5: TxD(A), RxD(A), TxD(B), RxD(B), PE
• RS 485 signals 3: R/T(A), R/T(B), PE
• Electrical isolation from internal ET 200S power supply yes
• Max. cable length in m (shielded) 1200
Permissible ambient conditions in °C
• Operating temperature 0 ... +60
• Transport and storage temperature°C –40 ... +70

■ Connection diagram
ET 200S 1SI

SERIAL
INTERFACE
SF

RS232 MODE
1 TXD
2 RTS
3 DTR
4 DCD
5 RXD
6 CTS
7 DSR
8 PE

RS422 MODE
1 TXD (B)
2 TXD (A)
5 RXD (B)
6 RXD (A)
8 PE

RS485 MODE
1 T/RXD (A)
2 T/RXD (B)
5 PE

X 2
3 4

TX RX
G_IK10_deP0130s

6ES7
138-4DF00-0AB0

Siemens NS K · 2002 1/277


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
Terminal modules
for power and electronics modules
Actuator-Sensor-Interface

■ Overview
• Mechanical modules for car- • Replaceable terminal box (al-
ST70490z
rying the electronic modules so from the middle of the sta-
tion network)
• For constructing the perma-
nent wiring via the self-as- • Automatic coding of the elec-
sembling voltage bus tronics modules TM-E TM-P
for electronic for power
• Positive-locking connection • Self-assembling shielding of modules modules
technique to ensure en- the backplane bus for high
hanced vibration resistance data security
of up to 5 g
• Opportunity for colour cod-
• Different variants for carrying ing the terminals and identify-
power modules and electron- ing the slot numbers
ics modules

■ Application
Terminal modules are purely The rugged construction and for the continuous supply of • Terminal modules for elec-
mechanical components used positively locking connection light barriers or PE conduc- tronics modules (TM-E); TM-E
for installing ET 200S. They car- technique supports implemen- tors. Power modules are modules carry electronic
ry the electronics modules and tation under harsh industrial plugged into TM-P modules modules (inputs/outputs,
motor starters. The modules are conditions. (e.g. vibration for voltage monitoring and technology modules). Un-
automatically coded. strength up to 5 g). fuse protection. used signal leads from anti-
valent signal encoders can
Self-assembling voltage bus in- The terminal modules are avail- TM-P modules can be imple-
also be connected.
tegrated into the terminal mod- able in various different vari- mented any number of times
ules, motor starters with com- ants: at any location within
munications capability and their ET 200S . This allows the size
• Terminal modules for TM-P
self-assembling 40 A power of a potential group to be in-
power modules: For infeed of
bus considerably reduce the dividually determined. The
load/encoder voltage onto
wiring overheads and the con- first module following the IM
two self-assembling voltage
trol cabinet space needed. Self- 151 is always a TM-P with a
buses. A third voltage bus
assembling shielding of the plugged-in power module.
(AUX1, max. 230 V) can be
backplane bus increases the
used, for example,
data security.

■ Design
Design comprising terminal module and electronics module
ST70z

+ =

TM-P TM-E • Direct connection of antiva-


lent signal encoders without
• Connection via screw-type or • Connection via screw-type or
additional modular terminal
spring-loaded terminals spring-loaded terminals
blocks
• With or without terminal ac- • With or without terminal ac-
cess to AUX1 rail cess to AUX1 rail
• With or without interruption of • 2-, 3- or 4-wire
the AUX1 rail connection technique
• Light coloured enclosure for
visual distinction

1/278 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
Terminal modules
for power and electronics modules

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
TM-P terminal modules for PM-E power modules
TM-P15S23-A1 A 6ES7 193-4CC20-0AA0 250 1
2 × 3 terminals, terminal access to AUX1 rail, AUX1
connected through to the left, screw-type terminals
TM-P15C23-A1 A 6ES7 193-4CC30-0AA0 250 1
2 × 3 terminals, terminal access to AUX1 rail, AUX1
connected through to the left, spring-loaded terminals
TM-P15S23-A0 A 6ES7 193-4CD20-0AA0 250 1
2 × 3 terminals, terminal access to AUX1 rail, AUX1
interrupted to the left, screw-type terminals
TM-P15C23-A0 A 6ES7 193-4CD30-0AA0 250 1
2 × 3 terminals, terminal access to AUX1 rail, AUX1
interrupted to the left, spring-loaded terminals
TM-P15S22-01 A 6ES7 193-4CE00-0AA0 250 1
2 × 2 terminals, no terminal access to AUX1 rail, AUX1
connected through to the left, screw-type terminals
TM-P15C22-01 A 6ES7 193-4CE10-0AA0 250 1
2 × 2 terminals, no terminal access to AUX1 rail, AUX1
connected through to the left, spring-loaded terminals
TM-E terminal modules for electronic modules 1)
TM-E15S24-A1 1 packg.
2 × 4 terminals, terminal access to AUX1 rail, AUX1 A 6ES7 193-4CA20-0AA0 250 5
connected through to the left, screw-type terminals
TM-E15C24-A1 1 packg.
2 × 4 terminals, terminal access to AUX1 rail, AUX1 A 6ES7 193-4CA30-0AA0 250 5
connected through to the left, spring-loaded terminals
TM-E15S24-01 1 packg.
2 × 4 terminals, no terminal access to AUX1 rail, AUX1 A 6ES7 193-4CB20-0AA0 250 5
connected through to the left, screw-type terminals
TM-E15C24-01 1 packg.
2 × 4 terminals, no terminal access to AUX1 rail, AUX1 A 6ES7 193-4CB30-0AA0 250 5
connected through to the left, spring-loaded terminals
TM-E15S23-01 1 packg.
2 × 3 terminals, no terminal access to AUX1 rail, AUX1 A 6ES7 193-4CB00-0AA0 250 5
connected through to the left, screw-type terminals
TM-E15C23-01 1 packg.
2 × 3 terminals, no terminal access to AUX1 rail, AUX1 A 6ES7 193-4CB10-0AA0 250 5
connected through to the left, spring-loaded terminals
TM-E15S26-A1 1 packg.
2 × 6 terminals, terminal access to AUX1 rail, AUX1 A 6ES7 193-4CA40-0AA0 250 5
connected through to the left, screw-type terminals
TM-E15C26-A1 1 packg.
2 × 6 terminals, terminal access to AUX1 rail, AUX1 A 6ES7 193-4CA50-0AA0 250 5
connected through to the left, spring-loaded terminals
TM-E30S44-01 A 6ES7 193-4CG20-0AA0 250 1
4 × 4 terminals, no terminal access to AUX1 rail, AUX1
connected through to the left, screw-type terminals
TM-E30C44-01 A 6ES7 193-4CG30-0AA0 250 1
4 × 4 terminals, no terminal access to AUX1 rail, AUX1
connected through to the left, spring-loaded terminals

1) For selection of the appropriate TM-E and TM-P, see the configuring aids (see Page 1/218).

Siemens NS K · 2002 1/279


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
Terminal modules
for power and electronics modules

■ Selection and ordering data


Design DT Order No. Price PG Pack

1 unit Unit
Accessories for shield attachment
Shield attachment 1 packg.
for plugging into TM-E and TM-P A 6ES7 193-4GA00-0AA0 251 5

Shield terminals 1 packg.


for busbar 3 × 10 mm A 6ES7 193-4GB00-0AA0 251 5
Earth connection terminal A 8WA2 868 102 1
for conductor cross-sections up to 25 mm2
Busbars 3 × 10 mm A 8WA2 842 102 1
10 units of 1 m
Accessories for inscription
Inscription sheet in A4 format, perforated
10 sheets of 60 strips each,
can be used for electronics modules, power modules
and motor starters
+ 20 strips, can be used for IM 151
• petrol 1 set
A 6ES7 193-4BH00-0AA0 251 1 set
• red 1 set
A 6ES7 193-4BD00-0AA0 251 1 set
• yellow 1 set
A 6ES7 193-4BB00-0AA0 251 1 set
• light beige 1 set
A 6ES7 193-4BA00-0AA0 251 1 set
Accessories for coding
Colour coding plates 1 set
for TM-P, TM-E; A 6ES7 193-4LA10-0AA0 251 1 set
200 units per colour;
light beige, yellow-green, red, brown, blue, turquoise
Labeling plates, with inscription
• 200 units for slot numbering 1 set
(1 to 20) 10 × A 8WA8 861-0AB 102 1 set
• 200 units for slot numbering 1 set
(1 to 40) 5 × A 8WA8 861-0AC 102 1 set
• 200 units for slot numbering 1 set
(1 to 64) 1 ×, A 8WA8 861-0DA 102 1 set
(1 to 68) 2 ×
Labeling plates, without inscription
• 200 units for slot numbering 1 set
A 8WA8 848-2AY 102 1 set

1/280 Siemens NS K · 2002


PROFIBUS-DP
SIMATIC ET 200S Distributed I/O Devices
Terminal modules
for power and electronics modules

■ Dimension drawings
Dimension drawings of terminal module with an electronics module plugged in

66,5

Support for
sectional rail

132

65,5

67
15

66,5

Support for
sectional rail

119,5

53

67
15