DOOR SIZE NO. NO. LOCKS METAL GAGE 1. SHEET METAL DUCT SEALANT
2. 24 GAGE (MIN.) G.I. ASTM 653 DUCT SHEET METAL LINEAR GRILLE CEILING DIFFUSERS
(MM) HINGES FRAME DOOR BACK TO BE OF ALL STEEL CONSTRUCTION
(MM) (MM) (MM) 3. INSULATION ADHESIVE (NO AIR GAPS)
AND INSTALLED IN ACCORDANCE
350 X 350 2 1-S 0.70 0.55 0.55 4. DUCT INSULATION WITH MANUFACTURER'S
500 Pa 1"THK AEROFLEX OR ARMAFLEX CONCRETE SLAB INSTRUCTIONS
406 X 508 2 2-S 0.85 0.70 0.55 5. SHEET METAL STRAPS 1m SPACING
STATIC AND LESS 610 X 610 3 2-S 0.85 0.85 0.55 LOCK
350 X 350 2 1-S 0.85 0.85 0.55 TYPE 1
750 Pa EXPANSION HANGER ROD
406 X 508 2 1 - S, 1 - T, 1 - B 1.00 1.00 0.55 BOLT 12 MM DIA. MIN. STEEL
STATIC 610 X 610 3 2 - S, 1 - T, 1 - B 1.00 1.00 0.70 BEAM
SASH LOCK WASHER
32 MM
350 X 350 2 1 - S, 1 - T, 1 - B 1.00 1.00 0.55 BOTTOM CHORD
BEAM
1000 Pa OR STEEL JOIST
406 X 508 3 2 - S, 1 - T, 1 - B 1.00 1.31 0.70 AIR DUCT HANGER ROD
CLAMP
AND 2000 Pa 610 X 610 3 2 - S, 2 - T, 2 - B 1.31 1.31 0.70
S = SIDE OPPOSITE HINGES, T = TOP, B = BOTTOM
VIEW PROT CONCRETE
NOTE : CONSTRUCTION AND AIRTIGHTNESS MUST BE SUITABLE FOR THE DUCT NUT SLAB
STEEL ANGLE
PRESSURE CLASS USED. IF SPECIFIED LOCK
32 MM
32 MM
TYPE 2 FRAME 2 VARIES
FRAME 3 4 3. HANGER ROD SHALL CONFORM WITH SMACNA 5TH EDITION, TABLE 5-1.
HINGE POS. 3 DUCT
PANEL IS DUCT GAGE (MIN.) 3
WITH SCREWS AT 203mm MAX. SPACING 1 2
A DUCT ACCESS DOORS AND PANELS DETAIL B APPLICATION METHOD FOR DUCT INSULATION C DUCT HANGER DETAIL D DOUBLE DEFLECTOR LINEAR DIFFUSER DETAIL
ME 03 SCALE NTS SCALE NTS SCALE NTS SCALE NTS
ME 03 ME 03 ME 03
TYPICAL MASONRY
EXPANSION BOLT SUPPLY OR
INLET DUCT CONNECTIONS CAUSING INLET SPIN RETURN DUCT
FULL THREADED
CONCRETE SLAB ROD DUCT
SUPPORT
SUPPORT FROM ROOF
ANGLE BAR
IN AN APPROVE MANNER DUCT SUPPORT
PAINTED ROUND
BAR
STEEL DUCT STEEL DUCT
CONNECTOR CONNECTOR
DUCT INSULATION ISOLATORS DUCT INSULATION, MIN. R-VALUE
TURNING THERMAL BLANKET OF 3.5 hr-ft 2-°F
TURNING VANES CERAMIC RUBBER
DUCT VANES INSULATION NOTE:
EXTERNAL DUCT INSULATION NOT SHOWN
LOCKING NUT FOR CLARITY. SEE SPECIFICATIONS AND
GENEARAL NOTES FOR TYPE.
HANGER RODS
IMPELLER
300 METAL FRAME AROUND DIFFUSER
IMPELLER
SUPPORT NUT ROTATION ROTATION RUBBER-IN-SHEAR SPRING TYPE FIRE RATED 600
CEILING (SEE
ANGLE BAR ARCH'L. DWGS.) FUSIBLE VOLUME CEILING DIFFUSERS
DUCT SUPPORT ADJUSTMENT/FIRE TO BE OF ALL
HANGER WIRE FASTENED DAMPER ASSEMBLY STEEL CONSTRUCTION
TO BUILDING STRUCTURE (COMBINATION AND INSTALLED
TO SUPPORT ALL FOUR IN ACCORDANCE
CORNERS OF CEILING CEILING RADIATION
DIFFUSERS DAMPER AND WITH MANUFACTURER'S
BALANCING DAMPER) INSTRUCTIONS
E TRAPEZE SUPPORT F TURNING VANE DETAIL G VIBRATION ISOLATORS DETAIL H FIRE RATED INSTALLATION DETAIL
SCALE NTS SCALE NTS SCALE NTS
ME 03 ME 03 ME 03 ME 03 SCALE NTS
UP TO2"48"
NON-ASBESTOS DAMPER ROD STOPPER
FABRIC W/ INSULATION SHEETMETAL SELF-
TAPPING SCREW
U-STRAP (TYP.) SPLITTER DAMPER
MACHINE BOLT
A10
DUCT REDUCER
STEEL ANGLE
COLLAR (TYP.)
CONNECTOR
AVAILBLE
FLEXIBLE DUCT
A1
2"
EQUIPMENT
CASING OR WITH A MAXIMUM CONCENTRIC TRANSITION A1
UP TO2"48"
DUCT LINER MIXING BOX LENGTH OF 1 METER
FROM SUPPLY AIR DUCT SUPPLY AIR DUCT
TO PLENUM BOX AIR FLOW
DUCT 5" MIN.
LBRY
INDICATED ON DRAWINGS
A10
FLEXIBLE DUCT CONNECTION
AVAILBLE
PLENUM RTR BRX
BOX FIBERGLASS INSULATION
2"
RECTANGULAR-T0-ROUND TRANSITION
NON-CONCENTRIC TRANSITION A1
CEILING
ISOMETRIC DETAILED
FORMULA : CONVERT RECTANGULAR DUCT TO ROUND DUCT
De = 1.30 (a x b )0.625 / ( a + b ) 0.25
CEILING DIFFUSER, SEE PLANS FOR Where : * De = Equivalent Diameter, mm
BRANCH TAKE OFF LOCATIONS, AND FOR SIZING * a = Length of major side, mm
TDC / FLANGE TYPE DUCT CONNECTION * b = Length od minor side, mm
6mmØ DAMPER ROD
I DUCT CONNECTION DETAIL J BRANCH TAKE OFF DETAIL K FLEXIBLE DUCT TAKE OFF DETAIL L RECTANGULAR TO ROUND TRANSITION DETAIL
SCALE NTS
ME 03 SCALE NTS
ME 03 SCALE NTS
ME 03 SCALE NTS ME 03