Anda di halaman 1dari 2

Table 5.

1: 132/33 KV Khulna Central Grid Substation


SL. Items Voltage Level Description
No
1 Name of Substation 132/33 KV 132/33 KV Khulna Central grid Substation

2 Date of Commissioning 132 KV 1984

3 Capacity of Substation 132 KV 144/92 MVA (3*48/64 MVA)

4 Substation Maximum 132 KV 102MW (13/08/2015)


Demand
5 132KV Feeders 132 KV 09 (Nine) Nos.
• Central- Goalpara(OH) 1 & 2
• Central- Khulna South (OH) 1& 2
• Central-Noapara (OH) 1& 2
• Central- KPCL 2,115MW(UC)
• Central- NWPGCL- 1,2 225MW(UC)
6 33KV Feeders 33KV 12 (Twelve) Nos.

7 Power Station Connected 132KV 02 Nos. (03 Feeders), KPCL & NWPGCL

8 Power Transformer 132/33 KV 03 (Three) Nos.

9 Auxiliary Transformer 132 KV 01 (One) No.


(33/0.4 KV,200KVA)
10 Bus bar 132 KV Main and Transfer Bus. 795 MCM Double
Conductor, Capacity: 1600 Amps
11 Circuit Breaker 132 KV 13 (Thirteen) Nos.
10(Ten) Nos. SF6 Gas, Spring Operated
02(Two) Nos. SF6 Gas, Pneumatic Operated
01(One) Nos. SF6 Gas, Hydraulic Operated
33KV 05 (Five) Nos.
03(Three) Nos. Vacuum, Spring Operated
02(Two) Nos. SF6 Gas, Spring Operated
12 Current Transformer 132KV 10 (Ten) Set.

13 Potential Transformer 132 KV 13 (Thirteen) Set.

14 Isolator (DS) 132 KV 40 (Forty) Set.

15 Earth Switch (ES) 132 KV 06 (Six) Set.


16 Lighting Arrester 132 KV 12 (twelve) Set.

17 Fire Fighting Equipment 132 KV 09 (Nine) Nos. (Kgs. Date:- 13/06/2019)

18 Battery & Battery Charger 110 Volt • 02 (Two) Set (Xinxing, China) 80 AH
• 01(One) Set (HBL nife, India) 105 AH
• 01 (One) Set (Volta, Bangladesh) 200 AH
48 Volt • 02 (Two) Set (Xinxing , China) 80 AH
• 01 (One) Set (Volta, Bangladesh) 200 AH
19 Communication ➢ BTCL
➢ IP
➢ ATS
➢ Carrier
➢ Internet
20 Total Area 132KV 11 Acre

21 CC/IP Camera 04 (Four) Nos.

22 Capacitor Bank 33 KV 05 Units (5 MVAR/Units)

23 SCADA Equipment 48 Volts ❖ 02 (Two) Nos. RTU


❖ 02(Two) Nos. FOX
❖ 01 (One) No Mux. (OSN)
24 Carrier Equipment 48 Volts ❖ 02 (Two) Nos. ETI-21
❖ 02(Two) Nos. ETL-500
❖ 01(One) Sopho (Ex-Change)
25 Asset ➢ 132/33 KV & 33/11 KV Control Room
➢ Indoor 33 KV Capacitor Bank
➢ Manosi-1250 Sft (2 Storied, 04 Units )
➢ Moloti- 750 Sft (2 Storied, 04 Unit)
➢ Rupasi- 550 Sft (4 Storied, 08 Unit)
➢ Ansar Bank
➢ Mosque
26 Manpower 132KV 14 (Fourteen) Persons
Officers 09 (Nine) Person’s
Staff 05(Five) Person’s
27 Security 132KV 10(Ten) Nos. Ansar (Without Arm’s)
PC. APC. 02(Two) Person’s
Ansar Guard 08 (Eight) Person’s

Anda mungkin juga menyukai