EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The drain pipe trap shall have a water seal height equal to or larger
SAES-K-001
A7 than the fan's External Static Pressure (ESP) but not less than 50
Para 5.3.4.2d
mm (2").
The drain pipe shall discharge to the nearest floor drain, in SAES-K-001
A8
accordance with the requirements of ASHRAE Equipment Handbook. Para 5.3.4.2e
Page 1 of 2
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Fan Coil Installation SAIC-K-4040 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
REMARKS:
REFERENCE DOCUMENTS:
SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 5 July, 2009 Design and Installation of Heating, Ventilating and Air
conditioning Systems 5 December 2012