SAUDI ARAMCO INSPECTION CHECKLIST
Fan Coil Installation SAIC-K-4040 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Floor Mounted Fan Coil Units shall be mounted (unless it is wall


mounted) on a concrete housekeeping pad, at a minimum of 100 mm SAES-K-001
A1
(4") above the floor or a minimum of 150 mm (6") above unpaved Para 5.1.1
ground as applicable.

Fan Coil Units shall be installed at the location indicated on the


drawings and in accordance with details of mounting, with vibration SAES-K-001
A2
isolation as required by the Design Specification and in accordance Para 5.1.7
with manufacturer's recommendation.

Evaporators of floor mounted Fan Coil units shall be mounted a


SAES-K-001
A3 minimum of 150 mm (6 inch) off the floor, to allow room for
Para 5.3.4.1
condensate trap.

Equipment clearance shall be provided with a minimum of 1 m


clearance on each side of equipment with openable panel or SAES-K-001
A4
controls, unless equipment manufacturer requires greater Para 5.1.4
clearances. Adequate space shall be provided for coil removal

All HVAC Equipment shall be properly grounded in accordance with SAES-K-001


A5
NFPA 70, National Electrical Code. Para 5.1.8
Vibration isolators shall be provided between Fan Coil Units and SAES-K-001
A6
foundations to minimize transmitted vibration. Para 4.8.14.1

The drain pipe trap shall have a water seal height equal to or larger
SAES-K-001
A7 than the fan's External Static Pressure (ESP) but not less than 50
Para 5.3.4.2d
mm (2").

The drain pipe shall discharge to the nearest floor drain, in SAES-K-001
A8
accordance with the requirements of ASHRAE Equipment Handbook. Para 5.3.4.2e

HVAC system shall be inspected in accordance with the


SAES-K-001
A9 requirements of 27-SAIP-01,"HVAC Inspection Requirements" prior
Para 5.5.2
to start-up.

Page 1 of 2
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Fan Coil Installation SAIC-K-4040 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

REMARKS:

REFERENCE DOCUMENTS:
SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 5 July, 2009 Design and Installation of Heating, Ventilating and Air
conditioning Systems 5 December 2012

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 2

Anda mungkin juga menyukai