In recent years a very large number of UT inspections have been performed to detect wall thickness reduction of
feed water pipe, etc. These inspections are accompanied by heat insulation removal and restoration work through-
out the inspection range. In order to enable efficient execution of such a great number of tests, a new method of pipe
damage detection and monitoring has been developed which makes it possible to inspect a long range of pipe with
one sensor, using the ultrasonic characteristics of so-called "guided wave." This new technique has drastically re-
duces the work of heat insulation removal, scaffolding and restoration. This method has also made it possible to
reduce inspection work itself. This report introduces the results of some pipe damage detection tests performed
using the method described above and shows an outline of the application of the system to a thermal power plant.
Transducer system
PC
Fig. 1 System of guided wave pipe inspection and monitoring Fig. 2 Image of iceberg whole picture
This system is composed of a sensor comprising pieces of magnetstrictive screening by G-Monitor
strip of Ni, etc. and coils, a transducer system and a PC for controls.
. Inspection can be implemented over a long range In case of stepped section change
Transmission
Inspection of a 5 - 15m range is possible. Generated
Sensor installed in a position with scaffolding is wave wave 1 Acoustic impedance Z
(ultrasonic wave propagation resistance)
capable of covering positions without scaffolding.
= A (section area) (density)
Use for primary damage screening
(sound velocity)
. Detailed inspection to be performed by UT inspection.
Sensor can be set up easily A2 2 Ultrasonic wave reflection ratio: R
. One sensor can be installed in 90minutes.
Environmental protection taken into consideration
Reflection A 1 Z 2
wave Z1
R=
Reflection wave
=
Z 1-Z 2
Generated wave Z 1+Z 2
One sensor is capable of covering a wide range, A: Medium section area
reducing work of heat insulation and waste materials. Z: Acoustic impedance
MHI is now applying for a patent for this system. In case of gradual change The reflection ratio of guided wave
Generated Transmission changes in response to change in
wave wave the section area.
When wall thickness is reduced, the
reflection ratio takes a positive value.
Pipe wound with When it is increased, the ratio takes
pieces of strip of a negative value.
Fe-Co, etc. Reflection Reflection wave shifts 180 deg.
A1 A2
Z1 wave upon Z2 to reverse the amplitude.
defect detection
Notch like defect (depth 3.0mm x 3 positions; section loss ratio 10.8%) Measurement result
Reflection from sensor
Gradual thickness reduction 2 Sensor A B-side end surface Notch
(length 200mm x 3 points) like
0.08 defect
Pipe dimension: 114.3 x t 6 Gradual thickness
Amplitude (V)
0.04 reduction 1
The echo amplitude of the cut point is 0.05 V, The amplitude will be attenuated 15% by elbow transmission
which is twice the noise level. (circumferential weld 1 circumferential weld 2).
Circumferential Circumferential
In the case of straight pipe, a cut of 1.6% weld 2 weld 1
in section loss ratio can be detected. Sensor
Sensor 0.5
0.4
Initial noise
Amplitude (V)
Fig. 7 Defect detection limit in straight pipe Fig. 8 Elbow section attenuation measurement result
Notch-like cut flaw of 1.6% in section loss ratio can be detected. Guided wave is attenuated 15% by elbow transmission.
Not measurable
(Dead zone: 1m)
Not measurable Not measurable
(From orifice onwards) (Echo noise)
Measurable Measurable Measurable
Note 1
Note 1 Note 1
Flow Guided wave Guided wave
Detectability is reduced
Orifice Sensor Reducer due to attenuation caused
by elbow transmission.
U-rod (Support) (Note 2) Elbow
Takashi Kuroishi Akira Shiibashi Nobuhiko Nishimura Fumitoshi Sakata Hirotoshi Matsumoto Kiyotaka Aoki