P124/EN T/E44
Technical Guide
Technical Guide P124/EN T/E44
Safety instructions
Introduction Chapter 1
SAFETY SECTION
Pxxx/EN SS/G11
1. INTRODUCTION 3
BLANK PAGE
Pxxx/EN SS/G11
1. INTRODUCTION
This guide and the relevant equipment documentation provide full information on safe
handling, commissioning and testing of this equipment. This Safety Guide also includes
descriptions of equipment label markings.
Documentation for equipment ordered from Schneider Electric is despatched separately from
manufactured goods and may not be received at the same time. Therefore this guide is
provided to ensure that printed information which may be present on the equipment is fully
understood by the recipient.
The technical data in this safety guide is typical only, see the technical data section of the
relevant product publication(s) for data specific to a particular equipment.
Before carrying out any work on the equipment the user should be familiar with the
contents of this Safety Guide and the ratings on the equipment’s rating label.
Reference should be made to the external connection diagram before the equipment is
installed, commissioned or serviced.
Language specific, self-adhesive User Interface labels are provided in a bag for some
equipment.
• Are familiar with the installation, commissioning, and operation of the equipment and
of the system to which it is being connected;
• Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorised to energize and de-energize equipment and
to isolate, ground, and label it;
• Are trained in the care and use of safety apparatus in accordance with safety
engineering practices;
To ensure that wires are correctly terminated the correct crimp terminal and tool
for the wire size should be used.
The equipment must be connected in accordance with the appropriate connection
diagram.
Protection Class I Equipment
- Before energizing the equipment it must be earthed using the protective
conductor terminal, if provided, or the appropriate termination of the
supply plug in the case of plug connected equipment.
- The protective conductor (earth) connection must not be removed since
the protection against electric shock provided by the equipment would be
lost.
- When the protective (earth) conductor terminal (PCT) is also used to
terminate cable screens, etc., it is essential that the integrity of the
protective (earth) conductor is checked after the addition or removal of
such functional earth connections. For M4 stud PCTs the integrity of the
protective (earth) connections should be ensured by use of a locknut or
similar.
The recommended minimum protective conductor (earth) wire size is 2.5 mm²
(3.3 mm² for North America) unless otherwise stated in the technical data section
of the equipment documentation, or otherwise required by local or country wiring
regulations.
The protective conductor (earth) connection must be low-inductance and as short
as possible.
All connections to the equipment must have a defined potential. Connections that
are pre-wired, but not used, should preferably be grounded when binary inputs
and output relays are isolated. When binary inputs and output relays are
connected to common potential, the pre-wired but unused connections should be
connected to the common potential of the grouped connections.
Before energizing the equipment, the following should be checked:
- Voltage rating/polarity (rating label/equipment documentation),
- CT circuit rating (rating label) and integrity of connections,
- Protective fuse rating,
- Integrity of the protective conductor (earth) connection (where
applicable),
- Voltage and current rating of external wiring, applicable to the application.
Accidental touching of exposed terminals
If working in an area of restricted space, such as a cubicle, where there is a risk of
electric shock due to accidental touching of terminals which do not comply with
IP20 rating, then a suitable protective barrier should be provided.
Equipment use
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Removal of the equipment front panel/cover
Removal of the equipment front panel/cover may expose hazardous live parts,
which must not be touched until the electrical power is removed.
Pxxx/EN SS/G11
6.4 Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet or housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of
protection IP54 (dust and splashing water protected).
Pollution Degree - Pollution Degree 2 Compliance is demonstrated by reference
Altitude - Operation up to 2000m to safety standards.
IEC 60255-27:2005
EN 60255-27: 2006
Technical Guide P124/EN T01/B44
MiCOM P124
CHAPTER 1
Introduction
Technical Guide P124/EN T01/B44
Introduction CHAPTER 1
MiCOM P124 Page 1/6
CONTENT
1. INTRODUCTION 3
4. MAIN FUNCTIONS 5
P124/EN T01/B44 Technical Guide
CHAPTER 1 Introduction
Page 2/6 MiCOM P124
PAGE BLANCHE
Technical Guide P124/EN T01/B44
Introduction CHAPTER 1
MiCOM P124 Page 3/6
1. INTRODUCTION
The overcurrent relays of the MiCOM P124 series are Schneider Electric™s self- and
dual-powered relays. The MiCOM P124 series are designed to control, protect and
supervise industrial plants as well as public distribution systems and substations and
do not require an external power supply. They may also be used as backup to
distance protection relays in electrical transmission networks.
4. MAIN FUNCTIONS
The following table shows the functions available in the various models of the
MiCOM P124 of relays.
SELF-POWERED DUAL-POWERED
Type
(Order code Vaux = S) (Order code Vaux = A, F, or M)
Protection functions
Non-directional three-phase X X
overcurrent (50/51)
Non-directional earth fault overcurrent X X
(50N/51N)
Instantaneous thresholds X X
Thermal overload (49) X X
Negative sequence overcurrent (46) X
Undercurrent (37) X (note 1)
Circuit breaker failure (50 BF) X
Cold load pickup X (note 1)
Broken conductor detection X
Blocking logic X (note 1)
Relay selective scheme logic X (note 1)
Output relays latching (86) X (note 1)
Fail-safe operation X
Autorecloser option (79) X (note 1)
Ancillary functions
Dual power supply (Vaux + CT) X
Output for striker X X
Trip changeover output relay for CB X X
coil
Healthy LED 1 led (note 2) 1 led (note 2)
Other LEDs No 3 + 4 programmable
Magnetic flag for trip information 1 1
4 magnetic flags option No option 4 programmable
Setting groups 1 2
Measurements (true RMS values) X X
Current maximum and average values X X
Fault records X (note 4) X
Event records X (note 1)
Disturbance records X (note 1)
Circuit breaker supervision X
Communication RS485 rear port Not applicable X
Communication RS232 front port X (note 3) X (note 3)
P124/EN T01/B44 Technical Guide
CHAPTER 1 Introduction
Page 6/6 MiCOM P124
MiCOM P124
CHAPTER 2
Handling, Installation and Case
Dimensions
Technical Guide P124/EN T02/C44
Handling, installation and CHAPTER 2
case dimensions Page 1/8
MiCOM P124
CONTENT
1. GENERAL CONSIDERATIONS 3
1.1 Receipt of relays 3
1.2 Electrostatic discharge (ESD) 3
3. RELAY MOUNTING 5
4. UNPACKING 5
5. STORAGE 5
6. CASE DIMENSIONS 6
P124/EN T02/C44 Technical Guide
CHAPTER 2 Handling, installation and
case dimensions
Page 2/8 MiCOM P124
BLANK PAGE
Technical Guide P124/EN T02/C44
Handling, installation and CHAPTER 2
case dimensions Page 3/8
MiCOM P124
1. GENERAL CONSIDERATIONS
1.1 Receipt of relays
Protective relays, although generally of robust construction, require careful treatment
prior to installation on site. Upon receipt, relays should be examined immediately to
ensure no damage has been sustained in transit. If damage has been sustained
during transit a claim should be made to the transport contractor and
Schneider Electric should be promptly notified.
Relays that are supplied unmounted and not intended for immediate installation
should be returned to their protective polythene bags.
1.2 Electrostatic discharge (ESD)
The relays use components that are sensitive to electrostatic discharges.
The electronic circuits are well protected by the metal case and the internal module
should not be withdrawn unnecessarily. When handling the module outside its case,
care should be taken to avoid contact with components and electrical connections. If
removed from the case for storage, the module should be placed in an electrically
conducting antistatic bag.
There are no setting adjustments within the module and it is advised that it is not
unnecessarily disassembled. Although the printed circuit boards are plugged
together, the connectors are a manufacturing aid and not intended for frequent
dismantling; in fact considerable effort may be required to separate them. Touching
the printed circuit board should be avoided, since complementary metal oxide
semiconductors (CMOS) are used, which can be damaged by static electricity
discharged from the body.
P124/EN T02/C44 Technical Guide
CHAPTER 2 Handling, installation and
case dimensions
Page 4/8 MiCOM P124
3. RELAY MOUNTING
Relays are dispatched either individually or as part of a panel/rack assembly.
If an MMLG test block is to be included it should be positioned at the right-hand side
of the assembly (viewed from the front). Modules should remain protected by their
metal case during assembly into a panel or rack.
For individually mounted relays an outline diagram is supplied in section 6 of this
chapter showing the panel cut-outs and hole centres.
4. UNPACKING
Care must be taken when unpacking and installing the relays so that none of the
parts is damaged or the settings altered. Relays must only be handled by skilled
persons. The installation should be clean, dry and reasonably free from dust and
excessive vibration. The site should be well lit to facilitate inspection. Relays that have
been removed from their cases should not be left in situations where they are
exposed to dust or damp. This particularly applies to installations which are being
carried out at the same time as construction work.
5. STORAGE
If relays are not to be installed immediately upon receipt they should be stored in a
place free from dust and moisture in their original cartons. Where de-humidifier bags
have been included in the packing they should be retained. The action of the de-
humidifier crystals will be impaired if the bag has been exposed to ambient
conditions and may be restored by gently heating the bag for about an hour, prior to
replacing it in the carton.
Dust which collects on a carton may, on subsequent unpacking, find its way into the
relay; in damp conditions the carton and packing may become impregnated with
moisture and the de-humifier will lose its efficiency.
Storage temperature : –25°C to +70°C.
P124/EN T02/C44 Technical Guide
CHAPTER 2 Handling, installation and
case dimensions
Page 6/8 MiCOM P124
6. CASE DIMENSIONS
MiCOM P124 relays are available in a 4U metal case for panel or flush mounting.
Weight : about 2.9 Kg
External size : Height Case 152 mm
Front panel 177 mm
Width Case 148,1 mm
Front panel 155 mm
Depth Case 140,8 mm
Front panel + case 166 mm
129.6 10.2
4 holes Ø 3.4
103.6 23.2
148.1
Flush mounting
+ 0.8
(Top) 150 0
4 holes Ø 4.4
MiCOM P124
Trip
IA = 214A
Trip
Alarm
Flush mounting
10
(Front) (Right)
Technical Guide P124/EN T02/C44
Handling, installation and CHAPTER 2
case dimensions Page 7/8
MiCOM P124
BLANK PAGE
Technical Guide P124/EN T31/B44
MiCOM P124
CHAPTER 3-1
User Guide
P124 Self-powered Relay
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 1/24
CONTENT
2. USER INTERFACE 5
2.1 Front panel display and keypad 5
2.1.1 The display 5
2.1.2 Keypad 5
2.2 Front panel LED and magnetic flag 6
2.3 The two areas under the top and bottom flaps 6
2.4 The battery box 6
2.5 Description of the MiCOM P124 self-powered front panel 7
2.5.1 LEDs 7
2.5.2 Magnetic flag 7
3. MENUS 8
3.1 Default display 8
3.2 Access to the menu 8
3.3 Password 8
3.3.1 Password protection 8
3.3.2 Entering the password 8
3.3.3 Changing the password 9
3.4 ALARM display 9
3.4.1 Electrical system ALARMS 9
3.4.2 Relay Hardware or Software ALARMS 10
3.5 Menu contents 11
3.5.1 O.P. Parameters menu 12
3.5.2 CONFIGURATION Menu 13
3.5.3 MEASUREMENTS Menu 14
3.5.4 PROTECTION Menu 15
3.5.4.1 [50/51] Phase OC sub-menu 15
3.5.4.2 [50N/51N] E/Gnd sub-menu 17
3.5.4.3 [49] Therm OL sub-menu 19
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 2/24 MiCOM P124
4. WIRING 23
4.1 Current inputs (measurement) 23
4.2 Output relays 23
4.3 Striker output 24
4.4 RS 232 Front Communication port 24
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 3/24
39 +
Striker output
41 –
P124
Auxiliary supply
44
RL1 42
40
P124
Auxiliary supply
2. USER INTERFACE
The MiCOM P124 relay front panel serves as an interface between the user and the
protection relay. It enables the user to enter relay settings, display the measured
values, alarms and display clearly the various actions carried out by MiCOM P124
relay.
The front panel of the relay consists of three separate sections:
− The LCD display and the keypad,
− The LED's
− The two zones under the upper and lower flaps.
The battery box (accessory):
Associated with the MiCOM P124 relays, the battery box MiCOM E1 can be used to
allow the user to access the menu when there is no line current (circuit breaker open).
2.1 Front panel display and keypad
2.1.1 The display
The front panel of the MiCOM P124 relays caries a liquid crystal display (LCD) on
which data such as settings, measured values and alarms can be viewed. The data is
accessed through a menu system.
The liquid crystal display has two lines each with sixteen characters. A back-light is
activated when any key is pressed and will remain lit for five minutes after the last key
press. This allows the display to be read in most lighting conditions.
NOTA : IN ORDER TO SAVE ENERGY, THE LCD IS BACKLIT ONLY
WHEN THERE IS AT LEAST ONE PHASE CURRENT ABOVE 0.5 In.
2.1.2 Keypad
The keypad has seven keys divided into two groups :
Two keys situated immediately under the screen (keys ! and ").
Five main keys situated at the middle of the front face are for programming.
The two keys ! and " are dedicated for reading and acknowledging the alarms. So
as to display successive alarms, press on key ". The alarms are presented in reverse
order for their detection (the most recent first, the oldest last). So as to acknowledge
the alarms, the user can either acknowledge each alarm using ! or go to the end of
the ALARM menu and carry out a general acknowledgement.
NOTA : NO PASSWORD IS REQUIRED TO ACKNOWLEDGE ALARMS.
The five keys situated in the middle of the MiCOM front panel are dedicated to
setting the relay.
The # $ % & keys make it possible to move in the direction indicated to the various
levels of the menus.
The ' key validates a choice or value (modification of settings).
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 6/24 MiCOM P124
Battery box
To MiCOM P124
RS 232
Input for
external supply
12Vcc – 24Vcc
2 x 16 character
backlit display
2 tactile buttons
to view and Magnetic flag for
acknowledge trip indication
alarms and
indications
Retractable flaps
allowing to
Healthy LED remove the
active part of the
relay
3. MENUS
The menu of the MiCOM P124 relays is organised into main and sub menus.
3.1 Default display
By default, the value of the current IA is continuously displayed.
As soon as an alarm is generated by the MiCOM relay, that information is
considered as priority and replaces the default value.
3.2 Access to the menu
Complete menu access is performed by manipulation of the keys # $ % &.
The general arrangement of the menus is shown in figure 3.
Reading of parameters and measurements is possible without entering the password.
Modification of the parameters requires entering the password.
Should an error be made in entering a parameter, press ! to cancel.
Except for reading and cancelling, the keys ! and " are inactive.
NOTA : The letter P is displayed at the botton-right of each first (main
menu) and second menu level when the password is entered.
This password remains active for 5 minutes of keypad inactivity.
3.3 Password
3.3.1 Password protection
Password protection is applicable to the relay settings, especially to the selection of
the various thresholds, time delays, communication parameters, allocation of inputs
and outputs relays.
The password consists of four alphabetical capital characters. When leaving the
factory, the password is AAAA. The user can define his own combination of
characters. Should the password be lost or forgotten, the modification of the stored
parameters of the relay is prohibited. It is then necessary to contact the manufacturer
or his agent by specifying the serial number of the relay so as to receive a stand-by
password specific to the relay concerned.
3.3.2 Entering the password
The input of the password is requested as soon as a modification of a parameter is
made for any one of the menus or sub-menus. The user enters for each of the 4
characters/letters and validates the entire password with '.
After 5 seconds, the display returns to the point of the preceding menu.
If no action is taken on the keypad for 5 minutes, the password is deactivated. A new
request shall be associated with any subsequent parameter modification.
NOTE : WHILE THE PASSWORD IS ACTIVE, IT IS NOT POSSIBLE TO
DOWNLOAD A SETTING FILE FROM THE PC SETTING
SOFTWARE MiCOM S1.
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 9/24
DEFAULT DISPLAY
OP PARAMETERS
IA = 1245 A
CONFIGURATION
MEASUREMENTS
PROTECTION
AUTOMAT.CTRL
RECORDS
Relay Status = 1 Displays the state of the trip logic output. (RL1)
0 - state 0 : output relay inactive
- state 1 : output relay active
NOTA : The Watch-dog output (RL0) is not display in the
output status menu.
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 13/24
Line CT primary = Display of the primary ratio of the phase CT. The value
1000 consists of 4 digits: Minimum 1, Maximum 9999.
Press ' to modify this value and use # $ % & to display
the new primary phase CT ratio. Enable your choice using
' at the end of selection
E/Gnd CT primary = Display of the primary ratio of the earth CT. The consist of 4
1000 digits : Minimum 1, Maximum 9999.
Press ' to modify this value and use # $ % & to display
the new primary earth CT ratio. Enable your choice using '
at the end of selection.
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 14/24 MiCOM P124
IA= Display the A phase current (True RMS value) taking into
257.05 A account the phase CT ratio (CONFIGURATION/CT RATIO
sub-menu).
IB= Display the B phase current (True RMS value) taking into
258.80 A account the phase CT ratio (CONFIGURATION/CT RATIO
sub-menu)
IC= Display the C phase current (True RMS value) taking into
257.50 A account the phase CT ratio (CONFIGURATION/CT RATIO
sub-menu).
IN= Display the earth current (True RMS value) taking into
20.00 A account the earth CT ratio (CONFIGURATION/CT RATIO
sub-menu).
Max. & Average. I Allows the user to clear the maximum (peak) and average
RST = [C] (rolling) memorised values of the current.
To clear these values, press !.
Max. IA Rms = Display the peak value for phase A. The value is the true
350 A RMS maximum value.
Max. IB Rms = Display the peak value for phase B. The value is the true
0.00 A RMS maximum value.
Max. IC Rms = Display the peak value for phase C. The value is the true
0.00 A RMS maximum value.
Average. IA Rms = Display the rolling value for phase A. The value is the true
150 A RMS average value.
Average. IB Rms = Display the rolling value for phase B. The value is the true
148 A RMS average value.
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 15/24
Average. IC Rms = Display the rolling value for phase C. The value is the true
153 A RMS average value.
I> ? Selection of the first phase threshold (I>). Select Yes or No.
Yes If the user enters I>(Yes), the following menu is displayed.
If the user enters I> (No), go to I>> menu.
Delay Type Selection of the I> time delay type threshold. Select (DMT
DMT for definite time, IDMT for inverse time curves, RI for the
electromechanical inverse time curve).
tl > Selection of the I> time delay. Select the time delay from 0
100 ms to 180 s using # and enable your choice using '.
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 16/24 MiCOM P124
Delay Type Display the I> inverse time delay (IEC or IEEE/ANSI curves).
IDMT
Idmt = Selection of the I> curve. Select from IEC SI, IEC STI, IEC VI,
IEC SI IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI, IEEE EI using
# and enable your choice using the key '
Tms = Select the curve TMS value. Select from 0.025 to 1.5 using
0.025 # and enable your choice using '
tI >> Selection of the second threshold I>> time delay. Select the
300 ms time delay from 0 to 180 s using # and enable your choice
using '.
tI >>> Selection of the third threshold I>>> time delay. Select the
110 ms time delay from 0 to 180 s using # and enable your choice
using '.
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 17/24
le> ? Selection of the first earth threshold (Ie>). Select Yes or No.
Yes If the user enters Ie>(Yes), the following menu is displayed.
User enters > (No), go to Ie>> menu.
Delay Type Selection of the Ie> threshold time delay type. Select (DMT
DMT for definite time, IDMT for inverse time curves, RI for the
electromechanical inverse time curve) using # and enable
your choice using '.
t le> Selection of the Ie> time delay. Select the time delay from 0
100 ms to 180 s using # and enable your choice using '.
Delay Type Display of the Ie> inverse time delay (IEC or IEEE/ANSI
DMT curves).
Idmt Selection of the Ie> curve. Select from IEC SI, IEC STI, IEC
IEC SI VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI, IEEE EI
using # and enable your choice using the key '.
Tms Selection of the selected curve Tms value. Select from 0.025
0.025 to 1.5 using # and enable your choice using '.
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 18/24 MiCOM P124
Trip tI > = Allocation of the first phase time delay overcurrent threshold
Yes (tI>) to the trip output relay and/or the striker (select Yes or
No). If the user validates Yes, the trip output relay (RL1) shall
be activated at the end of the time delay tI>. If the user
validates No, the trip output relay (RL1) shall never be
activated, even at the end of the time delay tI>.
Trip tI >>> Allocation to the third phase time delay overcurrent threshold
Yes (tI>>>) to the trip output.
Select Yes or No.
Trip tIe > Allocation of the first earth time delay overcurrent threshold
Yes (tIe>) to the trip output.
Select Yes or No.
Trip tIe >> Allocation of the second earth time delay overcurrent
Yes threshold (tIe>>) to the trip output.
Select Yes or No.
Trip tIe >>> Allocation of the third earth time delay overcurrent threshold
Yes (tIe>>>) to the trip output.
Select Yes or No.
Record Number Selection of the Fault record number (by selecting either 1, 2,
4 3, 4 or 5) to be displayed.
To modify this fault record number, press ' then using #
enter the required number.
Validate your choice using '.
Faulted Phase Display the faulty phase for the chosen fault record. (NONE,
Phase A phase A, B, C, EARTH, AB, AC, BC, or ABC).
Threshold Display the origin of the fault that as generated the trip
I>> order.
Magnitude Display the magnitude of the faulty current. This value is the
1200 A 50/60 Hz amplitude.
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 22/24 MiCOM P124
Time Window = Display of the time window during which the mean and
5 mn maximum current values are stored.
To change this value, press the ' key.
This window can be set with the following values: 5mn,
10mn, 15mn, 30mn or 60mn.
Press the ' key to confirm the setting.
Technical Guide P124/EN T31/B44
User Guide CHAPTER 3-1
MiCOM P124 Page 23/24
4. WIRING
The external connection diagrams of MiCOM P124 are provided in APPENDIX 1 to
this document.
4.1 Current inputs (measurement)
The MiCOM P124 relays have 4 analogue inputs (3 phase current inputs and 1 earth
current input). The rated current value of these measurement inputs is either 1A or 5A
(must be specified on order).
The rated current is indicated on the front panel of the relay, behind the top flap.
WARNING: THE CONNECTION OF THE EARTH CURRENT INPUT MAY DIFFER
DEPENDING ON WHETHER IT IS CONNECTED TO A CORE BALANCED CT
OR TO A SUMMATION OF THE 3 PHASE CTS.
Connection to 3 phase CTs and 1 core balanced CT:
Generally, when the relay is used with three phase CTs and one core balanced CT,
there is not need to power the relay through the earth channel.
In this case, the core balanced CT can be connected to terminals 47 and 48.
For some phase to earth faults, when some specific cores are used, it can be possible
that the fault does not generate a current high enough* to power the relay from only
one phase circuit. It will then be necessary to connect the core TC to terminals 55
and 56 in order to power the relay through the earth circuit as well.
*reminder: the MiCOM P124 relay is self-powered from a 0.2 In current on at least
one phase.
Connection to 3 phase CTs:
In this case the earth current is derived from the summation of the 3 phase currents.
It is not necessary to power the relay via the earth circuit. The summation of the 3 CTs
must be connected to terminals 47 and 48.
Connection to 2 phase CTs and 1 core balanced CT:
In this case it is necessary to power the relay through the earth circuit. The core
balanced CT must be connected to terminals 55 and 56.
4.2 Output relays
Two output relays are available on the self-powered model:
• One trip relay (RL1) with a C/O contact (1 common, 1 normally open, 1 normally
closed)
• One watchdog relay (RL0) with a C/O contact (1 common, 1 normally open, 1
normally closed)
WARNING : IN ORDER TO SAVE ENERGY, THE WATCHDOG RELAY IS USED ONLY
WHEN THERE IS A 0.4 IN CURRENT ON AT LEAST ONE PHASE. IT IS DE-
ENERGISED BELOW THAT CURRENT LEVEL OR WHEN A SOFTWARE OR
HARDWARE FAULT IS PRESENT.
P124/EN T31/B44 Technical Guide
CHAPTER 3-1 User Guide
Page 24/24 MiCOM P124
In cases where the battery box MiCOM E1 is used to power the P124 relay, it is
placed between the PC and the P124 relay.
Technical Guide P124/EN T32/B44
MiCOM P124
CHAPTER 3-2
Menu Content
MiCOM P124 Self-powered
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT.
OP PARAMETERS CONFIGURATION MEASUREMENTS PROTECTION RECORD
CTRL
Menu content
MiCOM P124
Technical Guide
K= K
Max IC Rms
0.1 0.1 MiCOM P124 S
0.02 A
BLANK PAGE
Technical Guide P124/EN T41/B44
MiCOM P124
CHAPTER 4-1
User Guide
P124 Dual-Powered Relay
Technical Guide P124/EN T41/B44
User Guide CHAPTER 4-1
MiCOM P124 Page 1/68
CONTENT
2. USER INTERFACE 7
2.1 The LCD display and the keypad 7
2.1.1 The LCD display 7
2.1.2 Keypad 7
2.2 Front panel LED and magnetic flag 8
2.3 The two areas under the top and bottom flaps 8
2.4 The battery box 9
2.5 Description of the MiCOM P124 dual-powered front panel 10
2.5.1 Leds 10
2.5.2 Magnetic flags 11
2.5.3 Battery backup 11
3. MENUS 12
3.1 Default display 12
3.2 Access to the menu 12
3.3 Password 12
3.3.1 Password protection 12
3.3.2 Entering the password 12
3.3.3 Changing the password 13
3.4 ALARM display 13
3.4.1 Electrical system ALARMS 13
3.4.2 Relay Hardware or Software ALARMS 16
3.5 Contenu du menu 17
3.5.1 OP. PARAMETERS Menu 19
3.5.2 CONFIGURATION Menu 21
3.5.2.1 DISPLAY sub-menu 21
3.5.2.2 CT RATIO sub-menu 22
3.5.2.3 RL1 Output Relay sub-menu 22
3.5.2.4 Led 5 to 8 configuration sub-menus 23
3.5.2.5 Group Select sub-menu 26
3.5.2.6 Alarms sub-menu 27
P124/EN T41/B44 Technical Guide
CHAPTER 4-1 User Guide
Page 2/68 MiCOM P124
4. WIRING 66
4.1 Current inputs (measurement) 66
4.2 Output relays 66
4.3 Striker output 67
4.4 RS232 front communication port 67
4.5 Auxiliary supply 67
4.6 Logic inputs 68
4.7 RS485 rear communication port 68
P124/EN T41/B44 Technical Guide
CHAPTER 4-1 User Guide
Page 4/68 MiCOM P124
BLANK PAGE
Technical Guide P124/EN T41/B44
User Guide CHAPTER 4-1
MiCOM P124 Page 5/68
39 +
Striker output
41 –
P124
RL1 42
40
P124
Auxiliary supply
2. USER INTERFACE
The MiCOM P124 relay front panel serves as an interface between the user and the
protection relay. It enables the user to enter relay settings, display the measured
values, alarms and display clearly the various actions carried out by MiCOM P124
relay.
The front panel of the relay consists of three separate sections:
− The LCD display and the keypad,
− The Led's
− The two zones under the upper and lower flaps.
The battery box (accessory):
Associated with the MiCOM P124 relays, the battery box MiCOM E1 can be used to
allow the user to access the menu when there is no line current (circuit breaker open).
2.1 The LCD display and the keypad
2.1.1 The LCD display
The front panel of the MiCOM P124 relays caries a liquid crystal display (LCD) on
which data such as settings, measured values and alarms can be viewed. The data is
accessed through a menu system.
The liquid crystal display has two lines each with sixteen characters. A back-light is
activated when any key is pressed and will remain lit for five minutes after the last key
press. This allows the display to be read in most lighting conditions.
NOTA : IN CASE OF AUXILIARY POWER SUPPLY FAILURE AND IN
ORDER TO SAVE ENERGY, THE LCD IS BACKLIT ONLY WHEN
THERE IS AT LEAST ONE PHASE CURRENT ABOVE 0.5 IN.
2.1.2 Keypad
The keypad has seven keys divided into two groups :
Two keys situated immediately under the screen (keys ! and ").
Five main keys situated at the middle of the front face are for programming.
The two keys ! and " are dedicated for reading and acknowledging the alarms. So
as to display successive alarms, press on key ". The alarms are presented in reverse
order for their detection (the most recent first, the oldest last). So as to acknowledge
the alarms, the user can either acknowledge each alarm using ! or go to the end of
the ALARM menu and carry out a general acknowledgement.
NOTA : NO PASSWORD IS REQUIRED TO ACKNOWLEDGE ALARMS.
P124/EN T41/B44 Technical Guide
CHAPTER 4-1 User Guide
Page 8/68 MiCOM P124
The five keys situated in the middle of the MiCOM front panel are dedicated to set
the relay.
The keys make it possible to move in the direction indicated to the various
levels of the menus.
The key validates a choice or value (modification of settings).
2.2 Front panel LED and magnetic flag
Height LEDS and up to 5 magnetic flags are available for the dual-powered version
of the P124 relay.
The default corresponding labels on the front panel are in the English language but
the user is provided with a set of French stickers.
2.3 The two areas under the top and bottom flaps
Under the upper flap, a label identifies the relay according to its model (ordering
code) and series number. This information defines the product uniquely and
specifically.
In making all requests for information from Schneider Electric After Sales Department,
please quote these two numbers.
Information indicated in the lower portion of this label covers the auxiliary supply
voltage, the nominal earth current value and the rated current (1A or 5A).
Under the lower flap, a RS232 port is available to download a new version of the
protection software, as well as the settings created in a dedicated PC software
MiCOM S1. The same software allows to view all the relays internal data
(measurements, events…).
In case of auxiliary power supply failure and when there is no line current from the
CTs (circuit breaker open), the user can view or modify the settings by powering the
MiCOM P124 relay with the battery box MiCOM E1 connected to the RS232 port.
The withdrawability of the MiCOM active part (chassis) from the case is effected by
opening the two flaps, then with a 3mm screwdriver, turn the extractor situated under
the upper flap, and pull using the two slots situated behind these flaps.
Technical Guide P124/EN T41/B44
User Guide CHAPTER 4-1
MiCOM P124 Page 9/68
Battery box
To MiCOM P124
RS 232
Input for
external supply
12Vcc – 24Vcc
2 x 16 character
backlit LCD display
Removable flaps
Trip LED
Alarm LED to extract the
Warning LED active part
Healthy LED
4 programmable LEDs
Pile RS 232
3. MENUS
The menu of the MiCOM P124 relays is organised into main and sub menus.
3.1 Default display
By default, the current value (selected phase or earth) is continuously displayed.
As soon as an alarm is generated by the MiCOM relay, that information is
considered as priority and replaces the default value.
The default display choice is made in the CONFIGURATION/Display menu.
3.2 Access to the menu
Complete menu access is performed by manipulation of the keys # $ % &.
The general arrangement of the menus is shown in figure 3.
Reading of parameters and measurements is possible without entering the password.
Modification of the parameters requires entering the password.
Should an error be made in entering a parameter, press ! to cancel.
Except for reading and cancelling, the keys ! and " are inactive.
NOTA : The letter P is displayed when the password is entered.
If no key is pushed during 5 minutes, the password becomes inactive.
3.3 Password
3.3.1 Password protection
Password protection is applicable to the relay settings, especially to the selection of
the various thresholds, time delays, communication parameters, allocation of inputs
and outputs relays.
The password consists of four alphabetical capital characters. When leaving the
factory, the password is AAAA. The user can define his own combination of
characters.
Should the password be lost or forgotten, the modification of the stored parameters
of the relay is prohibited. It is then necessary to contact the manufacturer or his agent
by specifying the serial number of the relay so as to receive a stand-by password
specific to the relay concerned.
3.3.2 Entering the password
The input of the password is requested as soon as a modification of a parameter is
made for any one of the menus or sub-menus. The user enters for each of the 4
characters/letters and validates the entire password with '.
After 5 seconds, the display returns to the point of the preceding menu.
If no action is taken on the keypad for 5 minutes, the password is desactivated. A new
request shall be associated with any subsequent parameter modification.
WARNING : WHILE THE PASSWORD IS ACTIVE, IT IS NOT POSSIBLE TO
DOWNLOAD A SETTING FILE FROM THE PC SETTING SOFTWARE.
Technical Guide P124/EN T41/B44
User Guide CHAPTER 4-1
MiCOM P124 Page 13/68
CB CLOSE FAILURE Circuit breaker closing time longer than the value set
in the AUTOMAT. CTRL/CB Supervision menu.
RECLOSER SUCCESS Successful reclose indication. Indicates that when the
fault has been cleared upon circuit breaker
reclosure, and has not re-appeared before expiry of
the reclaim time.
RECLOSER LOCKED Recloser blocking indication. Generated by:
- auxiliary power supply failure during dead time
(definitive trip).
- external breaker failure indication (ex. SF6 low).
Indication provided via a logic input assigned to the
CB FAILURE function in the AUTOMAT. CTRL/Inputs
menu.
- external blocking indication, external blocking can
be set by the user in the PROTECTION/ [79]
AUTORECLOSE/EXT BLOCK menu. This blocking
information is provided via a logic input assigned to
the Block [79] function in the AUTOMAT.
CTRL/Inputs menu.
- definitive trip.
- remote trip command during the reclaim time.
- pick-up of I2> or thermal trip during dead time.
- breaker failure (circuit breaker failure to trip on
expiry of tBF).
- breaker operating time (or tripping time) longer
than the set time.
CONFLICT RECLOS. Configuration conflict of the recloser function. This
indication is generated by:
- O/O Interlock not assigned to a logic input or
assigned but not wired to the input.
- no output relay assigned to the CB CLOSE function
(AUTOMAT. CTRL/Output Relays menu ).
- trip contact latched.
- no recloser cycle assigned to the protection
functions (PROTECTION/ [79] Autoreclose menu ).
LATCH OUTPUT RELAY Information displayed when at least an output relay
(RL2 to RL6) is latched.
P124/EN T41/B44 Technical Guide
CHAPTER 4-1 User Guide
Page 16/68 MiCOM P124
CONFIGURATION
MEASUREMENTS
COMMUNICATION
PROTECTION G1
PROTECTION G2
AUTOMAT. CTRL
RECORDS
The menu of the MiCOM P124 Dual-powered relays is divided into 8 sections :
⇒ OP PARAMETERS
⇒ CONFIGURATION
⇒ MEASUREMENTS
⇒ COMMUNICATION
⇒ PROTECTION G1
⇒ PROTECTION G2
⇒ AUTOMAT. CTRL
⇒ RECORDS
To access these menus from the default display use $
To return to the default display from these menus or sub-menus press #.
NOTE : a Menu content table is given in the chapter 4-2.
Technical Guide P124/EN T41/B44
User Guide CHAPTER 4-1
MiCOM P124 Page 19/68
TEXT Information
Selection of the I> curve. Select from IEC SI, IEC STI,
Idmt
IEC VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI,
IEC SI
IEEE EI, IEC RC, using # and enable your choice using
the key '.
Selection of the Ie> curve. Select from IEC SI, IEC STI,
Idmt
IEC VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI,
IEC SI
IEEE EI, or IEC RC, using # and enable your choice
using the key '.
Selection of the I2> curve. Select from IEC SI, IEC STI,
Curve
IEC VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI,
IEC SI
IEEE EI using # and validate your choice using the key
'.
4. WIRING
The external connection diagrams of the MiCOM P124 relays are provided in
Appendix 1 of the Technical Guide.
4.1 Current inputs (measurement)
The MiCOM P124 relays have 4 analogue inputs (3 phase current inputs and 1 earth
current input). The rated current value of these measurement inputs is either 1A or 5A
(must be specified on order).
The rated current is indicated on the front panel of the relay, behind the top flap.
WARNING: THE CONNECTION OF THE EARTH CURRENT INPUT MAY DIFFER
DEPENDING ON WHETHER IT IS CONNECTED TO A CORE BALANCED
CT OR TO A SUMMATION OF THE 3 PHASE CTs.
Connection to 3 phase CTs and 1 core balanced CT:
Generally, when the relay is used with three phase CTs and one core balanced CT,
there is not need to power the relay through the earth channel.
In this case, the core balanced CT can be connected to terminals 47 and 48.
For some phase to earth faults, when some specific cores are used, it can be possible
that the fault does not generate a current high enough* to power the relay from only
one phase circuit. It will then be necessary to connect the core TC to terminals 55
and 56 in order to power the relay through the earth circuit as well.
*reminder: the MiCOM P124 relay is self-powered from a 0.2 In current on at least
one phase.
Connection to 3 phase CTs:
In this case the earth current is derived from the summation of the 3 phase currents.
It is not necessary to power the relay via the earth circuit. The summation of the 3 CTs
must be connected to terminals 47 and 48.
Connection to 2 phase CTs and 1 core balanced CT:
In this case it is necessary to power the relay through the earth circuit. The core
balanced CT must be connected to terminals 55 and 56.
4.2 Output relays
7 output relays are available on the DUAL-POWERED model.
6 relays are freely programmable (RL1 à RL6), the first relay RL0 being allocated to
signalling an equipment Fault (WATCH DOG) :
• All the output relays are of change-over relays (1 common, 1 normally open
contact, 1 normaly closed contact).
The protection and control functions to which these relays respond can be selected
by means of the AUTOMAT. CTRL. Menu.
NOTE : RL1 is the default trip contact. This relay can be programmed for
fail-safe operation (Configuration/RL1 output relay menu).
• One watchdog relay with a C/O contact (1 common, 1 normally open, 1
normally closed)
Technical Guide P124/EN T41/B44
User Guide CHAPTER 4-1
MiCOM P124 Page 67/68
In case where the battery box MiCOM E1 is used to power the P124 relay, it is placed
between the PC and the P124 relay.
4.5 Auxiliary supply
The auxiliary supply of the MiCOM P124 dual powered relays can be either :
• Dc (range 24-60 Vdc or 48-150 Vdc or 130-250 Vdc)
• Ac (100-250 Vac/ 50-60 Hz).
The voltage range is indicated on the front panel, under the top flag.
The power supply must be connected to terminals 33-34 only.
P124/EN T41/B44 Technical Guide
CHAPTER 4-1 User Guide
Page 68/68 MiCOM P124
MiCOM P124
CHAPTER 4-2
Menu Content
MiCOM P124 Dual-powered
DEFAULT DISPLAY
IA = 1245 A
OP PARAMETERS CONFIGURATION
Menu content
MiCOM P124
Technical Guide
Password
Display CT RATIO RL1 Output Relay LED 5 / 6 / 7 / 8 Group Select Alarms
****
Description Default Display Line CT primary Fail-safe Relay I> Y/N Change Group Inst. Self-reset ?
P124-D RMS I L1 1000 No tl> Y/N input = EDGE No
I>> Y/N
tI>> Y/N
Reference Phase A Text E/Gnd CT primary I>>> Y/N Setting Group Alarm Battery =
ALST L1 1000 tI>>> Y/N 1 No
Ie> Y/N
tIe> Y/N
Software Version Phase B Text Ie>> Y/N
4.A L2 tIe>> Y/N
Ie>>> Y/N
tIe>>> Y/N
Frequency Phase C Text Led Therm Trip Y/N
50 Hz L3 Led Brkn. Cond Y/N
Led CB Fail Y/N
Led tI2> Y/N
Active Group = E/Gnd Text Led Input 1 Y/N
1 N Led Input 2 Y/N
Led Input 3 Y/N
Led Input 4 Y/N
Input St 54321 Led Input 5 Y/N
01011 Led Recloser
MiCOM P124 D Run Y/N
Led Recloser
Relay St 654321 Blocked Y/N
001011 with autoreclose Led tAux 1 Y/N
Led tAux 2 Y/N
PROTECTION
Page 2/12
Configuration Frequency Max 1L2 Rms Communication ? [50/51] Phase OC [50N/51N] E/Gnd
Date format
P124/EN T42/B44
I L1 = I>? Ie > ?
Max 1L3 Rms
Inputs : 54321 Date format = 257.05 A Baud Rate Yes Yes
0.00 A
10101 PRIVATE 19200 Bd
I L2 = I> Ie >
Average IL1 Rms
258.80 A 0.1 In 0.01 Ien
0.00 A Parity
None
I L3 = Delay Type Delay Type
Average IL2 Rms
257.50 A IDMT IDMT
0.00 A
Data bits
IN= 8 Idmt Idmt
Average IL3 Rms
20.00 A IEC SI IEC SI
0.00 A
t I>>> t Ie >>>
110 ms 300 ms
Menu content
Technical Guide
MiCOM P124
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
AUTOMAT. CTRL
G1/G2
Menu content
MiCOM P124
[37] Under
[46] Neg Seq OC [49] Therm OL [79] Autoreclose Trip Commands Latch Functions Blocking Logic 1/2
Technical Guide
Current
I2 > ? Therm OL ? I<? Autoreclose ? Trip tI > Latch tI > Block1 tI >
Yes Yes Yes Yes Yes Yes Yes
I2 > Iθ> I< [Ext CB Fail ? Trip tI >> Latch tI >> Block1 tI >>
0.1 In 0.3 In 20 % In Yes Yes Yes Yes
Delay Type Te tI < Ext CB Fail Time Trip tI >>> Latch tI >>> Block1 tI >>>
IDMT 1 mn 1 ms 10 ms Yes Yes Yes
Curve K Ext Block ? Trip tIe > Latch tIe > Block1 tIe >
IEC SI 1.05 No Yes Yes Yes
Dead Time
Tms θ Trip Trip tIe >> Latch tIe >> Block1 tIe >>
tD1/tD2/tD3/tD4
0.025 100 % Yes Yes Yes
Reclaim Time
tReset θ Alarm ? Trip tIe >>> Latch tIe >>> Block1 tIe >>>
tR 10 ms
40 ms Yes Yes Yes Yes
Phase Cycles
K 0 Trip tI2 > Latch tI2 > Block1 Thermal θ
0.1 Yes Yes Yes
E/Gnd Cycles
tReset MiCOM P124 D Trip Thermal θ Latch Thermal θ Block1 Brkn. Cond
2
40 ms Yes Yes No
with autoreclose Cycles 4321 Trip Brkn. Cond Latch Brkn. Cond Block1 tAux 1
1110 No Yes No
tI >
tI>>
Menu content tI>>> Trip tAux 1 Latch tAux 1 Block1 tAux 2
tIe > Yes Yes No
tIe >>
From V4.A software tIe >>> Trip tAux 2 Latch tAux 2
t Aux1 Yes Yes
t Aux2
CHAPTER 4-2
Page 3/12
P124/EN T42/B44
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Page 4/12
CHAPTER 4-2
Logic Select. 1/2 Output Relays Latch Output Relays Inputs 1/2/3/4/5 Broken Conductor Cold Load PU CB Fail
P124/EN T42/B44
MiCOM P124
DEFAULT DISPLAY
IA = 1245 A
BLANK PAGE
DEFAULT DISPLAY
IA = 1245 A
OP PARAMETERS CONFIGURATION
Menu content
MiCOM P124
Technical Guide
Password
Display CT RATIO RL1 Output Relay LED 5 / 6 / 7 / 8 Group Select Alarms
****
Description Default Display Line CT primary Fail-safe Relay I> Y/N Change Group Inst. Self-reset ?
P124-D RMS I L1 1000 No tl> Y/N input = EDGE No
I>> Y/N
tI>> Y/N
Reference Phase A Text E/Gnd CT primary I>>> Y/N Setting Group Alarm Battery =
ALST L1 1000 tI>>> Y/N 1 No
Ie> Y/N
tIe> Y/N
Software Version Phase B Text Ie>> Y/N
4.A L2 tIe>> Y/N
Ie>>> Y/N
tIe>>> Y/N
Frequency Phase C Text Led Therm Trip Y/N
50 Hz L3 Led Brkn. Cond Y/N
Led CB Fail Y/N
Led tI2> Y/N
Active Group = E/Gnd Text Led Input 1 Y/N
1 N Led Input 2 Y/N
Led Input 3 Y/N
Led Input 4 Y/N
Input St 54321 Led Input 5 Y/N
01011 Led tAux 1 Y/N
MiCOM P124 D Led tAux 2 Y/N
Relay St 654321
001011 without autoreclose
Date Menu content
06/08/01
PROTECTION
Page 8/12
Configuration Frequency Max 1L2 Rms Communication ? [50/51] Phase OC [50N/51N] E/Gnd
Date format
P124/EN T42/B44
I L1 I>? Ie > ?
Date format = Max 1L3 Rms
Inputs : 54321 257.05 A Baud Rate Yes Yes
PRIVATE 0.00 A
10101 19200 Bd
I L2 I> Ie >
Average IL1 Rms 0.1 In 0.01 Ien
258.80 A 0.00 A Parity
None
I L3 Delay Type Delay Type
Average IL2 Rms
257.50 A IDMT IDMT
0.00 A
Data bits
IN 8 Idmt Idmt
Average IL3 Rms
20.00 A IEC SI IEC SI
0.00 A
IN - fn = I>> Ie >>
Menu content RST = [C] 0.00A 2.0 In 0.1 Ien
t I>>> t Ie >>>
110 ms 300 ms
Menu content
Technical Guide
MiCOM P124
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
AUTOMAT. CTRL
G1/G2
Menu content
MiCOM P124
[37] Under
[46] Neg Seq OC [49] Therm OL Trip Commands Latch Functions Blocking Logic 1/2
Technical Guide
Current
Curve K Trip tIe > Latch tIe > Block1 tIe >
IEC SI 1.05 Yes Yes Yes
Tms θ Trip Trip tIe >> Latch tIe >> Block1 tIe >>
0.025 100 % Yes Yes Yes
tReset θ Alarm ? Trip tIe >>> Latch tIe >>> Block1 tIe >>>
40 ms Yes Yes Yes Yes
Delay Type θ Alarm Trip tI < Latch tI < Block1 tI2 >
RI 100 % Yes Yes Yes
AUTOMAT. CTRL
Page 10/12
CHAPTER 4-2
Logic Select. 1/2 Output Relays Latch Output Relays Inputs 1/2/3/4/5 Broken Conductor Cold Load PU CB Fail
P124/EN T42/B44
MiCOM P124
DEFAULT DISPLAY
IA = 1245 A
BLANK PAGE
Technical Guide P124/EN T05/C44
MiCOM P124
CHAPTER 5
Technical Data & Curves
Characteristics
Technical Guide P124/EN T05/C44
Technical data and CHAPTER 5
curves characteristics
MiCOM P124 Page 1/32
CONTENT
1. PROTECTION FUNCTIONS 3
1.1 Minimum Level of current 3
1.2 Phase overcurrent protection 3
1.3 Neutral/Ground/Earth Overcurrent Protection 4
1.4 Thermal overload protection 6
1.5 Undercurrent protection (P124 dual-powered only) 6
1.6 Negative sequence overcurrent protection (P124 dual-powered only) 6
5. COMMUNICATION 9
5.1 Front communication 9
5.2 Rear communication (dual-powered only) 9
8. CT DATA 11
11. ENVIRONMENT 11
12. CURVES 12
12.1 IDMT Curves 12
12.1.1 Mathematical formula 12
12.1.1.1 IDMT thresholds 12
12.1.1.2 Reset timer 13
12.1.2 IEC CURVES. 16
12.1.3 RI curves. 22
12.1.4 IEEE/ANSI Curves. 23
12.1.5 Rectifier protection curve 29
12.1.6 LABORELEC CURVE 30
12.2 Thermal overload curves 31
12.2.1 Mathematical formula 31
12.2.2 Tripping curve 32
Technical Guide P124/EN T05/C44
Technical data and CHAPTER 5
curves characteristics
MiCOM P124 Page 3/32
1. PROTECTION FUNCTIONS
1.1 Minimum Level of current
Starting current sensitivity to self-power the MiCOM P124 relay on at least one phase:
0.2 In
1.2 Phase overcurrent protection
− Current Fundamental only
− Phase Current Range 0.1 to 40 x rated current, step of 0.01 In
Thresholds 3 independent (I>, I>>, I>>>)
I> 0.1 to 4 In (see note)
I>> 0.5 to 40 In
I>>> 0.5 to 40 In
NOTE : When I> is associated to an IDMT curve the maximum setting
recommanded should be 2 In.
− Hysteresis 95 %
− Instantaneous time
− From zero current < 60 ms
− From a 0.2 In current < 30 ms
− Drop out time 30 ms
− Phase time delays (tI>, tI>>, tI>>>)
DMT 0 ms to 180 s, step of 10 ms
IDMT curves IEC: Short time inverse (Schneider Electric),
Standard Inverse (IEC), Very inverse (IEC),
Extremely inverse (IEC),
Long time inverse (Schneider Electric).
RI : (Electromechanical type).
IEEE/ANSI : Short time inverse (CO2),
Moderately inverse (ANSI),
Inverse (CO8),
Very inverse (ANSI), Extremely inverse (ANSI).
RC : Rectifier curve
Time Multiplier Setting (TMS) 0.025 to 1.5, step of 0.025
P124/EN T05/C44 Technical Guide
CHAPTER 5 Technical data &
curves characteristics
Page 4/32 MiCOM P124
− Reset time
MiCOM P124 self-powered
− For DMT phase time delay: Fixed: 0 ms
− For IDMT Phase time delay : Fixed: 50 ms
MiCOM P124 dual-powered
− For DMT phase time delay : Fixed : 0 ms
− For IEEE/ANSI phase time delay : Short time inverse (CO2),
Moderately Inverse (ANSI),
Inverse (CO8),
Very inverse (ANSI),
Extremely Inverse (ANSI).
Reset Time Multiplier Setting (RTMS) 0.025 to 3.2, step of 0.025
or DMT 0.04 to 100s, step of 0.01 s
For IEC and RI characteristics: 0.04 to 100s, step of 0.01 s
1.3 Neutral/Ground/Earth Overcurrent Protection
− Current Fundamental only
− Earth current Ranges 0.002 to 1 x rated current, step of 0.005 Ien
0.01 to 8 x rated current, step of 0.005 Ien
0.1 to 40 x rated current, step of 0.005 Ien
Thresholds 3 independent (Ie>, Ie>>, Ie>>>)
Range 0.002 to 1 x Ien
Ie> 0.002 to 1 Ien (see note)
Ie>> 0.002 to 1 Ien
Ie>>> 0.002 to 1 Ien
Range 0.01 to 8 x Ien
Ie> 0.01 to 1 Ien (see note)
Ie>> 0.01 to 8 Ien
Ie>>> 0.01 to 8 Ien
Range 0.1 to 40 x Ien
Ie> 0.1 to 25 Ien (see note)
Ie>> 0.5 to 40 Ien
Ie>>> 0.5 to 40 Ien
NOTE : When Ie> is associated to an IDMT curve the maximum setting
recommanded should be :
For the range 0.002 to 1 Ien : 0.05 Ien
For the range 0.01 to 8 Ien : 0.4 Ien
For the range 0.1 to 40 Ien : 2 Ien
− Hysteresis 95 %
Technical Guide P124/EN T05/C44
Technical data and CHAPTER 5
curves characteristics
MiCOM P124 Page 5/32
− Instantaneous time
− From zero current < 60 ms
− From a 0,2 In current < 30 ms
− Drop out time 30 ms
− Earth time delays (tIe>, tIe>>, tIe>>>)
DMT 0 ms to 180 s, step of 10 ms
IDMT Curves IEC : Short time inverse (Schneider Electric),
Standard Inverse (CEI), Very Inverse (CEI),
Extremely Inverse (CEI),
Long time inverse (Schneider Electric).
RI : (Electromechanical type).
IEEE/ANSI : Short time inverse (CO2),
Moderately Inverse (ANSI),
Inverse (CO8),
Very Inverse (ANSI),
Extremely Inverse (ANSI).
RC : Rectifier curve.
Time Multiplier Setting (TMS) 0.025 to 1.5, step of 0.025.
LABORELEC curve 3 types : 1, 2 or 3 used with 0.01 to 8
Ien range only.
− Reset time
MiCOM P124 self-powered
− For DMT phase time delay: Fixed: 0 ms
− For IDMT Phase time delay : Fixed: 50 ms
MiCOM P124 dual-powered
− For DMT phase time delay: Fixed: 0 ms
− For IEEE/ANSI Earth time delay Short time inverse (CO2),
Moderately Inverse (ANSI),
Inverse (CO8),
Very inverse (ANSI),
Extremely Inverse (ANSI).
Reset Time Multiplier Setting (RTMS) 0.025 to 3.2, step of 0.025
or DMT: 0.04 to 100s, step of 0.01s
For IEC and RI characteristics: 0.04 to 100s, step of 0.01 s
P124/EN T05/C44 Technical Guide
CHAPTER 5 Technical data &
curves characteristics
Page 6/32 MiCOM P124
1.4 Thermal overload protection
Current RMS
Current threshold I θ > 0.2 to 3.2 x rated current, step of 0.01
Thermal state (alarm and trip) 50 to 200 % x 2 , step of 1 %
Constant Time Te 1 to 200 min, step of 1 min
k factor 1 to 1.5, step of 0.01
1.5 Undercurrent protection (P124 dual-powered only)
Current Fundamental only
Phase Current Range I< 2 to 100% x rated current, step of 1%
Time delay t<I 0 to 180 s, step of 0.01 s
Hysteresis 105 %
1.6 Negative sequence overcurrent protection (P124 dual-powered only)
− Current Fundamental only
− Phase Current Range I2> 0.1 to 40 x rated current
NOTE : when I2> is associated to an IDMT curve the maximum setting
recommended should be 2 In.
− Hysteresis 95 %
− I2> Time delay
DMT 0 ms to 150 s, step of 10 ms
IDMT curves IEC : Short time inverse (Schneider Electric),
Standard Inverse (CEI), Very Inverse (CEI),
Extremely Inverse (CEI),
Long time inverse (Schneider Electric).
RI : (Electromechanical type).
IEEE/ANSI : Short time inverse (CO2),
Moderately Inverse (ANSI),
Inverse (CO8),
Very Inverse (ANSI),
Extremely Inverse (ANSI).
Time Multiplier Setting (TMS) 0.025 to 1.5, step of 0.025
− Hysteresis 95 %
− Reset time
− For TD phase time delay: Fixed: 0 ms
− For IEEE/ANSI I2> Time delay : Short time inverse (CO2),
Moderately Inverse (ANSI),
Inverse (CO8),
Very Inverse (ANSI),
Extremely Inverse (ANSI).
Reset Time Multiplier Setting (RTMS) 0.025 to 3.2, step of 0.025
or DMT 0.04 to 100s, step of 0.01s
For IEC and RI characteristics: 0.04 to 100s, step of 0.01 s
Technical Guide P124/EN T05/C44
Technical data and CHAPTER 5
curves characteristics
MiCOM P124 Page 7/32
2. AUTOMATION FUNCTIONS (DUAL-POWERED ONLY)
2.1 Cold load pickup
Range 20 to 500 % x nominal settings, step of 1%
Time delay tCL 0,1s to 3600s, step of 100 ms
2.2 Auxiliary timers
2 independent associated to the logic inputs Aux1 and Aux2
tAux1 & tAux2 Range 0 ms to 200 s, step of 10 ms
2.3 Multishot autorecloser
Main shots 4 independent shots phase and/or earth
Dead times Cycles 1 & 2 0.01 to 300s ; step of 10ms
Cycles 3 & 4 0.01 to 600s ; step of 10ms
Reclaim time 20ms to 600s; step of 10ms
Inhibition time 20ms to 600s; step of 10ms
2.4 Broken conductor detection
Principle used I2/I1
Broken conductor threshold 20 to 100 % ; step of 1%
Time delay tBC 1 to 14400s ; step of 1s
2.5 Circuit breaker failure
CB failure time tBF 30ms to 10s ; step of 10ms
Phase current range I< 2 % to 100 % x rated current, step of 1 %
Accuracy from 0.02 In to 0.1 In : 0.006 In
from 0.1 In to 1 In : 2 % x nominal setting
Hysteresis maximum 0.008 In or 0.95 x nominal setting
2.6 Trip circuit supervision
Trip circuit supervision time t SUP 100ms to 10s, step of 50ms
2.7 Circuit breaker control and monitoring
− Circuit breaker opening time (t Open Pulse) 50ms to 1s ; step of 10ms
− Circuit breaker closing time (t Close Pulse) 50ms to 1s ; step of 10ms
− Circuit breaker opening alarm threshold 0 to 50000 operations
− Amps or square amps alarm threshold 0 to 4.10 9 ; step of 10 6
− Circuit breaker tripping time alarm threshold 100ms to 5s ; step of 100ms
− Circuit breaker closing time alarm threshold 100ms to 5s ; step of 100ms
2.8 Logic selectivity
2 Independant timers : tAux 1 & tAux 2
− Range 0ms to 150s ; step of 10ms
P124/EN T05/C44 Technical Guide
CHAPTER 5 Technical data &
curves characteristics
Page 8/32 MiCOM P124
3. RECORDING FUNCTIONS : SELF-POWERED RELAY
Fault recorder
Capacity 5 faults
Triggers Any selected protection alarm and threshold
Data Protection thresholds
AC inputs measurements (RMS)
Fault magnitudes
8. CT DATA
MiCOM P124 relay settings
Phase CT primary 1 to 9999, step of 1
Earth CT primary 1 to 9999, step of 1
Recommendations : 5 VA 5P10 or 5 VA 10P10
Connections: refer to external connection diagrams in Appendix 1
11. ENVIRONMENT
Temperature IEC 60255-6 Storage –25°C to +70°C
Operation –25°C to + 55°C
Humidity IEC 60068-2-3 56 days at 93% RH and 40°C
Protection de l'enveloppe IEC 60529 IP52, IK07
Vibrations IEC 60255-21-1 Response and endurance, class 2
Shocks and bumps IEC 60255-21-11 Response and withstand, class 1
Seismic IEC 60255-21-3 Class 1.
P124/EN T05/C44 Technical Guide
CHAPTER 5 Technical data &
curves characteristics
Page 12/32 MiCOM P124
12. CURVES
12.1 IDMT Curves
12.1.1 Mathematical formula
⎛ K ⎞
t = T×⎜ + L⎟
⎜ (i / Is ) − 1 ⎟
α
⎝ ⎠
Where:
t = Tripping time
K = Coefficient (see table)
I = Value of measured current
IS = Value of the programmed threshold (Pick-up value)
α = Coefficient (see table)
L = ANSI/IEEE coefficient (zero for IEC curves)
T = Time multiplier between 0.025 and 1.5
⎛ 1 ⎞
t = K × ⎜⎜ ⎟⎟
⎝ 0.339 − 0.236 / (I / Is ) ⎠
Although the curves tend towards infinite when the current approaches Is, the
minimum guaranteed value of the operating current for all the curves with the inverse
time characteristic is 1.1Is (with a tolerance of ± 0,05Is), except rectifier Protection
curve for which the minimum value is 1.6 Is ±0.05 Is.
LABORELEC CURVES (P124 Dual-powered only):
The first and second earth threshold can be selected with dedicated Laborelec curves.
There are 3 curves available with the following formula :
t = aI + b
Type of curve a b
LABORELEC 1 – 0.0897 4.0897
LABORELEC 2 – 0.0897 4.5897
LABORELEC 3 – 0.0897 5.0897
In order to be compliant with the Laborelec specifications the relay must be used
with :
− An earth current range 0.01 Ion to 8 Ion
− A rated current wiring 1A
− A core balanced CT with a ratio 20/1.
For a complete operating of the curve, the relay MiCOM P124 must be set to 0.05Ion
(secondary residual current).
DMT 0 ms
LABORELEC *, Rectifier, IDMT IEC or RI Settable from 40 ms to 100s
Settable from 40 ms to 100s
or
IDMT IEEE or CO
Inverse Time
(Choice of 5 IEEE curves)
* earth threshold only
Reset timer settable:
The first phase and earth overcurrent stages in the P124 relays are provided with a
timer hold facility "t Reset", which may be set to a definite time value or to an inverse
time characteristic (IEEE/ANSI curves only). This may be useful in certain applications,
for example when grading with upstream electromechanical overcurrent relays which
have inherent reset time delays.
Another possible situation where the timer hold facility may be used to reduce fault
clearance times is where intermittent faults occur. An example of this may occur in a
plastic insulated cable . In this application it is possible that the fault energy melts and
reseals the cable insulation, thereby extinguishing the fault. This process repeats to
give a succession of fault current pulses, each of increasing duration with reducing
intervals between the pulses, until the fault becomes permanent.
When the reset time of the overcurrent relay is minimum the relay will be repeatedly
reset and not be able to trip until the fault becomes permanent. By using the Timer
Hold facility the relay will integrate the fault current pulses, thereby reducing fault
clearance time.
The reset timer "t Reset" facility for the MiCOM P124 can be found in the following
menu :
− If the first phase (earth) threshold is selected with an IDMT IEC, Rectifier,
Laborelec or RI curve, the reset timer "t Reset" with DMT characteristic is settable
in the menu :
− Protection /[50/51] Phase OC/t Reset for the phase
− Protection /[50N/51N] E/Gnd/t Reset for the earth.
− If the first phase (earth) threshold is selected with an IDMT IEEE or CO curve,
the reset timer "t Reset" with a DMTor IDMT characteristic is settable in the
menu :
− Protection /[50/51] Phase OC/Type Tempo Reset for the phase
− Protection /[50N/51N] E/Gnd/Type Tempo Reset for the earth.
Reset Time "t Reset" with an IDMT characteristic :
The mathematical formula applicable to the five curves is :
⎛ K ⎞
t = T × ⎜⎜ ⎟
⎝ 1 − (I Is ) ⎠
α ⎟
Technical Guide P124/EN T05/C44
Technical data and CHAPTER 5
curves characteristics
MiCOM P124 Page 15/32
Where :
t = Reset time
K = Coefficient (see table)
I = Value of the measured current
IS = Value of the programmed threshold (pick-up value)
α = Coefficient (see table)
T = Reset Time Multiplier (Rtms) between 0.025 and 3.2
1
TIME IN SECONDS
0,1
0,01
0,001
1 10 100
A
B
C
TIME IN SECONDS
0,1
D
0,01 E
0,001
1 10 100
TIME IN SECONDS
TIME IN SECONDS
10000
1000
100
TIME IN SECONDS
A
B
D
1
E
0,1
1 10 100
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
time in seconds
50
1.5
1.0
0.5
40
Primary zero sequence current (A)
30
20
3
10
5
1
5
Time (sec)
Technical Guide P124/EN T05/C44
Technical data and CHAPTER 5
curves characteristics
MiCOM P124 Page 31/32
12.2 Thermal overload curves
12.2.1 Mathematical formula
The thermal time characteristic is given by:
exp(-t/τ) = (I2 - (k.IFLC)2 ) / (I2 - IP2)
Where:
t = Time to trip, following application of the overload current, I;
τ = Heating and cooling time constant of the protected plant;
I = Largest phase current (RMS value);
IFLC = Full load current rating (relay setting 'Thermal Trip');
k = 1.05 constant, allows continuous operation up to < 1.05 IFLC.
IP = Steady state pre-loading before application of the overload.
The time to trip varies depending on the load current carried before application of the
overload, i.e. whether the overload was applied from "hot" or "cold".
⎛ K ² − θ² ⎞
Ttrip = Te In⎜⎜ ⎟
⎟
⎝ K ² − θtrip² ⎠
With :
Ttrip = Time to trip (in seconds)
Te = Thermal time constant of the protected element (in seconds)
K = Thermal overload equal to Ieq/k Iθ>
Ieq = Equivalent current corresponding to the RMS value of the largest phase
current.
Iθ> = Full load current rating given by the national standard or by the
supplier.
k = Factor associated to the thermal state formula.
θ2 = Initial thermal state. If the initial thermal state = 30% then θ2 = 0.3
θtrip2 = Trip thermal state. If the trip thermal state is set at 100%, then θ trip2 = 1
The calculation of the thermal state is given by the following formula :
θι+1 =(Ieq/ k Iθ>)2 [1- exp(-t/Te)] + θι exp(-t/Te)
θ being calculated every 100ms.
Typical alarm setting : 70 % of t he thermal capacity of the protected element.
P124/EN T05/C44 Technical Guide
CHAPTER 5 Technical data &
curves characteristics
Page 32/32 MiCOM P124
12.2.2 Tripping curve
Technical Guide P124/EN T06/B44
MiCOM P124
CHAPTER 6
Applications Guide
Technical Guide P124/EN T06/B44
Applications Guide CHAPTER 6
MiCOM P124 Page 1/22
CONTENT
1. INTRODUCTION 3
1. INTRODUCTION
The P124 Self and Dual-Powered overcurrent relays in the MICOM range have
been designed to test, protect and monitor both industrial installations and public
power distribution networks and substations, without having to resort to an external
auxiliary power supply. They can also be used as backup for HV protections of power
transmission networks.
These two non-directional overcurrent protection models offer functions of protection
and automation that are common with the MiCOM P122 and P123 models. For
instance, for applications of MiCOM relays concerning these functions, the user
should refer to document P124/EN T05/A44.
The protection relays self-powered by the fault current offer the specific feature of
non-conventional current inputs. Accordingly, special attention will be given to the
choice of the current transformers supplying these relays.
The following chapters describe our recommendations for choosing the current
transformers associated to the MiCOM P124 relays.
The MiCOM P124 protection relays combined with the wiring represent a load for the
current transformers. Consequently, the dimensions of the current transformers must
be correctly calculated in order to comply with:
• the electrical installation diagram,
• the electrical data such as the nominal current, short-circuit current, …,
P124/EN T06/B44 Technical Guide
CHAPTER 6 Applications Guide
Page 4/22 MiCOM P124
K * In.
⇒ For a 10PK TC (accuracy class 10P, accuracy limit factor K):
At the saturation voltage Vs2 we will have an accuracy of 10% on the current K*In
Knee point
voltage
2.2.1 How to calculate the rated output burden in VA of a CT from its characteristic
magnitudes (Vk , Rct )
The saturation voltage is derived by the following formula: Vs = (Rct + Rp ) Is
Vs1 = (Rct +Pn1 /In2 )*K1 * In = (Rct + Pn2 /In2 )*K2 *In
60.00
50.00
40.00
Current In (A)
30.00
P124 version In=1A
20.00
10.00
In
0.00
5
0
15
10
60.00
50.00
40.00
Current In (A)
30.00
P124 version In=5A
20.00
10.00
In
0.00
2
The errors calculated reveal a maximum error of 3 % at minimum current, with this
error inversely proportional to the current.
Referring to chapter 2.2.1, we can derive the corresponding rated output burden in
the P class of this transformer expressed in terms of Vk and R ct. as follows:
• The corresponding rated output burden of this CT in class 5 is:
Pn = 3.89 VA 5P10
Pn = 4.71 VA 10P10
Test were conducted on the MiCOM P124 with this CT and confirmed the satisfactory
operation of the combination CT + P124.
NOTE: in this example, the relay was connected along side the CT; in
this way, the influence of the wiring was negligible.
Technical Guide P124/EN T06/B44
Applications Guide CHAPTER 6
MiCOM P124 Page 11/22
The errors calculated reveal a maximum error of 5 % at minimum current, with this
error inversely proportional to the current.
Referring to chapter 2.2.1, we can derive a corresponding rated output burden in
class P of this transformer expressed in terms of Vk and R ct as folles :
• The corresponding rated output burden of this CT in class 5 is:
Pn = 2.87 VA 5P10
Pn = 3.48 VA 10P10
Tests were conducted on the MiCOM P124 with this CT and confirmed the
satisfactory operation of the combination CT + P124.
NOTE: in this example, the relay was connected alongside the CT, so
the influence of the wiring was negligible.
3.3 Recommendations for selecting the CT
Assuming that the CT does not supply any circuits other than the MiCOM P124, in
practice, we can recommend CTs of the following types:
5VA 5P10 or 5VA 10P10
secondary 1A or 5A.
P124/EN T06/B44 Technical Guide
CHAPTER 6 Applications Guide
Page 12/22 MiCOM P124
Example of setting :
CYCLES 4321
tI> 1201
4321 are the cycles 1 to 4 associated to the trip on tI> pick up
1201 are the actions following the tI> time out :
0 = no action on autorecloser : definitive trip
1 = trip on tI> pick up, followed by reclosing cycle
2 = no trip on tI> pick up : and this whatever the setting in AUTOMAT.
CRTL/Trip commands/Trip tI> menu.
In addition to these settings, function links in the PROTECTION G1/Phase OC or
PROTECTION/E/Gnd menus are also required to fully integrate the autoreclose
logic in the MiCOM P124 relay. Refer to the User Guide of the Technical Guide.
5.2.3 Logic Functions
5.2.3.1 Logic Inputs
The autoreclose function has four inputs affecting the logic, which are configured to
any of the opto-isolated inputs on the relay via the AUTOMAT. CTRL/Inputs menu.
External inputs may be used to influence the autorecloser scheme. The function of
these inputs are described below.
5.2.3.2 External CB fail
The majority of circuit breakers are only capable of providing one trip-close-trip cycle.
Following this, it is necessary to establish if there is sufficient energy to reclose the CB.
The input assigned to CB FLT function is used to ensure that there is sufficient energy
available to close and trip the CB before initiating a CB close command. If on
completion of the dead time, sufficient energy is not available by checking the CB FLT
input for a time given by the tCFE, a lockout occur and the CB remains open.
This function is disabled by not allocating the function in the PROTECTION
G1/Autoreclose menu (function Ext CB Fail to NO).
5.2.3.3 External starting orders
Two separate and programmable inputs (AUTOMAT.CTRL/INPUTS/Aux1(2) menu)
may be used to initiate the autorecloser function from an external device (such as an
existing overcurrent relay). These logic inputs may be used independently and also in
parallel with the MiCOM P124 Overcurrent settings.
These external orders can be disabled independently by not allocating the functions
in the PROTECTION G1/Autoreclose/CYCLES tAux1 menu and PROTECTION
G1/Autoreclose/CYCLES tAux2 menu.
5.2.3.4 External blocking order
The input assigned to the Block-79 function (programmable in the
AUTOMAT.CTRL/INPUTS menu) may block the autoreclose function and cause a
lock-out if the autorecloser function is in progress. This input can be used when
protection operation without autorecloser function is required.
A typical example is on a transformer feeder, where autoreclosing may be initiated
from the feeder protection but need to be blocked from the transformer protection
side.
Technical Guide P124/EN T06/B44
Applications Guide CHAPTER 6
MiCOM P124 Page 17/22
These external order can be disabled by not allocating the function in the
PROTECTION/Autoreclose/Ext Block menu.
5.2.3.5 Autoreclose Logic Outputs
The following output signals can be assigned to relay contact or to LEDs to provide
information about the status of the auto Reclose cycle. These are described below,
identified by their namings.
5.2.3.6 Autoreclose in progress
The "Autoreclose in progress" signal is present during the complete reclose cycles
from protection initiation to the end of the reclaim time or lockout.
The "Autoreclose in progress" information is allocated to a LED in the
CONFIGURATION/Led/Recloser Run menu.
The "Autoreclose in progress" information is allocated to the output relays in the
AUTOMAT.CTRL/Output Relays/79 Run menu.
5.2.3.7 Final trip
The "Final trip" signal indicates that an autoreclose cycle has been completed. A
autoreclose signal is given after the CB has tripped from the protection and reclosed
whereupon the fault has not been cleared. The "Final trip" signal is reset at the next
CB manual closing order after the inhibit time (tI).
The inhibit time (tI) is settable in the PROTECTION G1/Autoreclose/Inhib Time
menu.
The "Final trip" signal is allocated to the output relays in the
AUTOMAT.Ctrl/Output Relays/79 Trip menu.
The "Final trip" signal is allocated to a LED in the CONFIGURATION/Led/Recloser
Blocked menu.
5.2.4 Autoreclose logic operating sequence
The autoreclose function provides multi-shot three phase autoreclose control. It can
be adjusted to perform a single shot, two shot, three shot or four shot cycle,
selectable via Phase Cycles numbers and E/Gnd Cycles numbers. Dead times for all
shots (reclose attempts) are independently adjustable.
The number of shots is directly related to the type of faults likely to occur on the
system and the voltage level of the system. Generally, on medium voltage networks
where the percentage of transient and non-permanent faults is likely to be high, a
multi-shot autoreclose device will increase the possibility of the distribution line being
successfully re-energised following reclosure of the circuit breaker.
An autoreclose cycle can be internally initiated by operation of a protection element
(phase or earth), provided the circuit breaker is closed until the instant of protection
operation. The dead time (Dead Time tD1, Dead Time tD2, Dead Time tD3, Dead
Time tD4) starts when the CB has tripped (when the 52a input disappears).
At the end of the relevant dead time, a CB close signal is given, provided system
conditions are suitable. The system conditions to be met for closing are that the circuit
breaker closing spring, or other energy source, is fully charged indicated from the
CB FLT input. The CB close signal is cut-off when the circuit breaker closes.
When the CB has closed the reclaim time (Reclaim Time tR) starts.
If the circuit breaker does not trip again, the autoreclose function resets at the end of
the reclaim time.
P124/EN T06/B44 Technical Guide
CHAPTER 6 Applications Guide
Page 18/22 MiCOM P124
If the protection operates during the reclaim time the relay either advances to the next
shot in the programmed autoreclose cycle, or, if all programmed reclose attempts
have been made, goes to lockout.
The total number of reclosures and for each cycle is shown in the MEASUREMENT
menu. This value can be reset to zero with command "C" (Clear) in the
MEASUREMENTS/Reclose Stats menu.
5.2.5 Autoreclose Inhibit Following Manual Close
The Inhib Time tI setting can be used to prevent autoreclose being initiated when the
CB is manually closed onto a fault. Autoreclose is disabled for the Inhib Time tI
following manual CB Closure.
5.2.6 Recloser lockout
If protection operates during the reclaim time, following the final reclose attempt, the
relay will lockout and the autoreclose function is disabled until the lockout condition
resets.
The lockout condition is reset by a manual closing after the "Inhib Time tI".
Autoreclose lockout can also be caused by a CB FLT input. This CB FLT information
can be issued from the CB springs are not charged/Low gas pressure.
Note, lockout can also be caused by :
• CB no open after tBf delay (CB Fail)
• CB Operating Time over the threshold set.
5.2.7 Setting group change lockout
Change of setting groups is only assumed by the MiCOM P124 relays if no protection
functions (except thermal overload function) or automation functions is running.
During the whole autorecloser cycles, if any setting group change order is received,
this order is stored in memory, and will be executed after the last timer of the
autorecloser cycle.
5.3 Setting Guidelines
5.3.1 Number Of Shots
There are no clear-cut rules for defining the number of shots for a particular
application. Generally medium voltage systems utilise only two or three shot
autoreclose schemes. However, in certain countries, for specific applications, four
shots is not uncommon. Four shots have the advantage that the final dead time can
be set sufficiently long to allow any thunderstorms to pass before reclosing for the
final time, this arrangement will prevent unnecessary lockout for consecutive
transient faults.
Typically, the first trip, and sometimes the second, will result from short time
protection since 80% of faults are transient, the subsequent trips will be time delayed,
all with increasing dead times to clear non-permanent faults.
In order to determine the required number of shots the following factors must be
taken into account.
Technical Guide P124/EN T06/B44
Applications Guide CHAPTER 6
MiCOM P124 Page 19/22
An important consideration is the ability of the circuit breaker to perform several trip-
close operations in quick succession and the effect of these operations on the
maintenance period.
If statistical information on a particular system shows a moderate percentage of non-
permanent faults which could be burned out, two or more shots are justified. In
addition to this, if fused ‘tees’ are used and the fault level is low, the fusing time may
not discriminate with the main IDMT relay and it would then be useful to have several
shots. This would warm up the fuse to such an extent that it would eventually blow
before the main protection operated.
5.3.2 Dead Timer Setting
The factors which influence the choice of dead timer setting are as follows.
5.3.2.1 Load
Due to the great diversity of load which may exist on a system it may prove very
difficult to arrive at an optimum dead time. However, it is possible to address each
type of load individually and thereby arrive at a typical dead time. The most common
types of load are addressed below.
Synchronous motors are only capable of tolerating extremely short interruptions of
supply without loss of synchronism. In practice it is desirable to disconnect the motor
from the supply in the event of a fault; the dead time should be sufficient to allow the
motor no-volt device to operate. Typically, a minimum dead time of 0.2-0.3 seconds
has been suggested to allow this device to operate. Induction motors, on the other
hand, can withstand supply interruptions, up to a maximum of 0.5 seconds and re-
accelerate successfully. In general dead times of 3-10 seconds are normally
satisfactory, but there may be special cases for which additional time is required to
permit the resetting of manual controls and safety devices.
Loss of supply to lighting circuits, such as street lighting may be important for safety
reasons as intervals of 10 seconds or more may be dangerous for traffic. The main
considerations for domestic customers are those of inconvenience.
An important measurement criteria for many power utilities is the number of minutes
lost per year to customers which will be reduced on feeders using autoreclose and will
also be affected by the dead time settings used.
5.3.2.2 Circuit Breaker
For high speed autoreclose the minimum dead time of the power system will depend
on the minimum time delays imposed by the circuit breaker during a tripping and
reclosing operation.
Since a circuit breaker is a mechanical device, it will have an inherent contact
separation time. This operating time for a modern circuit breaker is usually within the
range of 50-100ms, but could be longer with older designs.
After tripping, time must be allowed for the mechanism to reset before applying a
closing pulse. This resetting time will vary depending on the circuit breaker, but is
typically 0.1 seconds.
Once the circuit breaker has reset, the breaker can begin to close. The time interval
between the energisation of the closing mechanism and the making of the contacts is
termed the closing time. Owing to the time constant of a solenoid closing mechanism
and the inertia of the plunger, a solenoid closing mechanism may take 0.3s. A spring
operated breaker, on the other hand, can close in less than 0.2 seconds.
P124/EN T06/B44 Technical Guide
CHAPTER 6 Applications Guide
Page 20/22 MiCOM P124
Where high speed reclosing is required, for the majority of medium voltage
applications, the circuit breaker mechanism itself dictates the minimum dead time.
However, the fault de-ionising time may also have to be considered.
High speed autoreclose may be required to maintain stability on a network with two
or more power sources. For high speed autoreclose the system disturbance time
should be minimised by using fast protection, <50 ms, such as distance or feeder
differential protection and fast circuit breakers < 100 ms. Fast fault clearance can
reduce the required fault arc de-ionising time.
For stability between two sources a dead time of <300 ms may typically be required.
The minimum system dead time only considering the CB is the mechanism reset time
plus the CB closing time. Thus, a solenoid mechanism will not be suitable for high
speed autoreclose as the closing time is generally too long.
5.3.2.3 Fault De-ionising Time
For high speed autoreclose the fault de-ionising time may be the most important
factor when considering the dead time. This is the time required for ionised air to
disperse around the fault position so that the insulation level of the air is restored.
This can be approximated from:
De-ionising time = (10.5 + ((system voltage in kV)/34.5)) / frequency
For 66 kV = 0.25 s (50Hz)
For 132 kV = 0.29 s (50 Hz)
5.3.2.4 Protection Reset
It is essential that the protection fully resets during the dead time, so that correct time
discrimination will be maintained after reclosure on to a fault. For high speed
autoreclose instantaneous reset of protection is required.
Typical 11/33kV dead time settings in the UK are as follows;
1st dead time = 5 - 10 seconds
2nd dead time = 30 seconds
3rd dead time = 60 - 100 seconds
4th dead time (uncommon in the UK, however used in South Africa) = 60 - 100
seconds
5.3.3 Reclaim Timer Setting
A number of factors influence the choice of the reclaim timer, such as;
• Supply continuity - Large reclaim times can result in unnecessary lockout for
transient faults.
• Fault incidence/Past experience - Small reclaim times may be required where
there is a high incidence of lightning strikes to prevent unnecessary lockout for
transient faults.
• Spring charging time - For high speed autoreclose the reclaim time may be set
longer than the spring charging time to ensure there is sufficient energy in the
circuit breaker to perform a trip-close-trip cycle. For delayed autoreclose there is
no need as the dead time can be extended by an extra CB healthy check window
time if there is insufficient energy in the CB. If there is insufficient energy after the
check window time the relay will lockout.
Technical Guide P124/EN T06/B44
Applications Guide CHAPTER 6
MiCOM P124 Page 21/22
BLANK PAGE
Technical guide P124/EN T07/B44
MiCOM P124
CHAPTER 7
Commissioning and
Maintenance Guide
Technical Guide P124/EN T07/B44
Commissioning and Maintenance CHAPTER 7
MiCOM P124 Page 1/22
CONTENT
4. COMMISSIONING 11
4.1 Settings 11
4.2 Measurements 11
4.2.1 MiCOM P124 Self-powered 11
4.2.2 MiCOM P124 Dual-powered 11
4.3 Phase overcurrent (I> and I>>) 12
4.3.1 Test wiring diagram 12
4.3.2 MiCOM settings 13
4.3.3 I> threshold with DMT tI> 13
4.3.4 I> threshold with IDMT tI> 14
4.3.5 I>> threshold 16
4.4 Final checks 17
P124/EN T07/B44 Technical Guide
CHAPTER 7 Commissioning and Maintenance
Page 2/22 MiCOM P124
5. MAINTENANCE 18
5.1 Equipment failure 18
5.1.1 Minor fault (Version Dual-powered only) 18
5.1.2 Major fault 19
5.2 Method of repair 20
5.2.1 Replacing the active part 20
5.2.2 Replacing the complete relay 20
5.2.3 Changing the battery (MiCOM P124 Dual-powered only) 21
5.3 Problem solving 21
5.3.1 Password lost or not accepted 21
5.3.2 Communication (version Dual-powered only) 21
5.3.2.1 Values measured locally and remotely 21
5.3.2.2 MiCOM relay no longer responds 22
5.3.2.3 A remote command is not taken in account 22
Technical Guide P124/EN T07/B44
Commissioning and Maintenance CHAPTER 7
MiCOM P124 Page 3/22
P1 S1
P2 S2
Other ends
of electrical cables
Busbar 1 Busbar 2
Circuit Breaker 1 Electrical line Circuit breaker 2
P124
with CT core
Earthing 1 Earthing 2
P1 S1 _
+ mA
+
_
P2 S2
Opto input 2
00010
13-15 Terminals
Opto input 3
00100
17-19 Terminals
Opto input 4
01000
21-23 Terminals
Opto input 5
10000
25-27 Terminals
4. COMMISSIONING
The various operations for commissioning the MiCOM relays described in this
chapter are not extensive : it is only necessary to verify that the application-specific
software settings applied to the relay are correct.
Using a PC support software MiCOM S1 connected to the RS 485 rear port (dual-
powered model only) or to the RS 232 front port is not compulsory. The various
indications associated to each commissioning module are described for the operator
interface on the P124 front panels.
The commissioning is following the points below :
1. Logging of the settings
2. Validation of the measurements
3. Validation of the thresholds and associated timers.
4.1 Settings
Carry forward the settings on the commissioning test sheets.
4.2 Measurements
The MiCOM P124 relays measure phase and earth currents as a True RMS value up
to the 10th harmonics. The value(s) indicated take account of the phase and/or earth
CT ratio.
WARNING : THE MiCOM P124 RELAYS HAVE 1 OR 5 AMP CURRENT
INPUTS.CHECK THAT THE INJECTED CURRENT IS COMPATIBLE WITH
THE SELECTED RANGE.
To measure the earth channel, the current will be injected via a phase channel in
order to power the relay through that phase channel. This way, by injecting the earth
current through terminals 48 and 47, the earth self-power transformer of the relay is
avoided and the burden on the test equipment lowered.
4.2.1 MiCOM P124 Self-powered
⇒ Note the select phase and earth CTs ratio.
⇒ Inject on each current input (according to the external connection diagram
given in Appendix 1) a current higher than the minimum specified current
level (0,2 In) and check on the LCD display the corresponding current value.
⇒ Carry forward the results to the Commissioning test sheets (Applied values
and relay values displayed).
4.2.2 MiCOM P124 Dual-powered
⇒ Note the select phase and earth CTs ratio.
⇒ Energise the MiCOM P124 relay.
⇒ Inject on each current input (according to the external connection diagram
given in Appendix 1) a current higher than the minimum specified current
level (0,2 In) and check on the LCD display the corresponding current value.
⇒ Carry forward the results to the Commissioning test sheets (Applied values
and relay values displayed).
P124/EN T07/B44 Technical Guide
CHAPTER 7 Commissioning and Maintenance
Page 12/22 MiCOM P124
INJECTION
TEST SET
33 Dual-powered
AUXILIARY +Uaux Model only
-Uaux
SUPPLY 34
* 30
31
+ RS 485 communication port
32
-
MiCOM
P124
49
A 1 ou 5
A 50
51
CURRENT 1 ou 5 A
52
53
1 ou 5 A
N 54
37
35 Watchdog
36 Case earth
29
6 -
TIMER Stop 4
2 RL1 Trip output
+
39
Striker output
_41
Striker
Ie> YES
Ie> 1 In
tIe> DMT or IDMT or RI
tIe> (if DMT) 20 s
Type of curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT) 1
K value (if RI) 1
Ie>> YES
Ie>> 12 In
tIe>> 10 s
Checks :
1. Alarm message on the LCD display.
2. Alarm LED flashes (Dual-powered model only)
3. Trip LED on (Dual-powered model only)
4. The magnetic "Trip" flag's state changes.
5. I> threshold LED on (if programmed and for the version dual-powered only).
6. The state of the magnetic flag assigned to that I> threshold changes (if it has
been set and only for the dual-powered).
7. I> threshold output closes (if programmed and for the version dual-powered
only).
8. The trip contact (RL1) operates on expiry of the time delay.
9. The striker output operates on expiry of the time delay.
tI> time delay check :
1. Apply a current onto one of the phases and measure the time delay tI> by pre-
setting the current above the I> threshold (I injected > 2 x I threshold).
2. Apply a current onto one of the phases and measure the time delay tI> by pre-
setting the current above the I> threshold (I injected > 10 x I threshold).
4.3.4 I> threshold with IDMT tI>
Values to be recorded :
1. I> threshold for each phase
2. I>time delay for each phase.
I> threshold check :
Inject a current equal to 2 x I threshold onto one of the phase current inputs. Repeat
the operation for various current values (n x I threshold with n ranging from 4 to 10,
for example). Check that the values measured correspond to those indicated in the
table below (for TMS = 1).
IEC curves
IEEE/ANSI curves
RI electromechanical curve
Rectifier curve
Laborelec curve
For other injected current values, compare the values found with the theoretical
values calculated according to the formulae of the curves. Equations of IEC,
IEEE/ANSI, RI, RC and Laborelec curves are given in Chapter "Technical data and
curves characteristics" of the present Technical Guide.
P124/EN T07/B44 Technical Guide
CHAPTER 7 Commissioning and Maintenance
Page 16/22 MiCOM P124
Checks :
1. Display of an alarm message on the front panel LCD.
2. Alarm LED flashes (version dual-powered only).
3. Trip LED on (version dual-powered only).
4. The magnetic iaTriplc flag™s state changes.
5. I> threshold LED on (if programmed and for the version dual-powered only).
6. The state of the magnetic flag assigned to that I> threshold changes (if it has
been set and only for the dual-powered).
7. I> threshold output closes (if programmed and for the version dual-powered
only).
8. The trip contact (RL1) operates on expiry of the time delay.
9. The striker output operates on expiry of the time delay.
4.3.5 I>> threshold
Values to be recorded :
1. l>> threshold for each phase
2. tl>> time delay for each phase
I>> threshold check :
1. If tI>> time delay is short, gradually raise the injection current up to the value
of I>> threshold.
2. If tI>> time delay is long, inject 0.95 x I threshold and check there is no trip.
Then inject 1.1 x I threshold and check the trip output is close.
3. Gradually lower the injected current and note the value of the drop out I>>
threshold.
Checks :
1. Display of an alarm message on the front panel LCD.
2. Alarm LED flashes (version dual-powered only).
3. Trip LED on (version dual-powered only).
4. The magnetic "Trip" flag's state changes.
5. I>> threshold LED on (if programmed and for the version dual-powered only).
6. The state of the magnetic flag assigned to that I>> threshold changes (if it has
been set and only for the dual-powered).
7. I>> threshold output closes (if programmed and for the version dual-powered
only).
8. The trip contact (RL1) operates on expiry of the time delay.
9. The striker output operates on expiry of the time delay.
Technical Guide P124/EN T07/B44
Commissioning and Maintenance CHAPTER 7
MiCOM P124 Page 17/22
5. MAINTENANCE
5.1 Equipment failure
MiCOM P124 relays are full digital and permanent self-diagnosing. Any failure of
software or hardware elements is instantly detected. As soon as an internal fault is
detected, depending on its type (minor or major), an alarm message is displayed as
a priority on the front panel LCD before the fault LED is illuminated (fixed or flashing)
and the watchdog relay is closed (if the fault is a major one).
An equipment failure (major or minor) cannot be acknowledged on the front panel
(using the dedicated tactile button keypad). Only the disappearance of the cause will
acknowledge the fault and hence reset the fault LED.
NOTE : any failure detected by the P124 self-powered relay is always a
major failure.
5.1.1 Minor fault (Version Dual-powered only)
In case of minor fault the P124 is fully operational. The RL0 watchdog relay is
energised (35-36 contact open, 36-37 contact closed).
For the MiCOM P124 dual-powered relays a minor fault is :
1. A communication failure. If the communication is in fault, protection and
automation modules are not affected :
Message :
« COMM.ERROR » : Communication fault
Cause :
Hardware or software failure of the communication module
Action :
Withdraw the active part and return it to the factory for repair.
Alternative : If communication is not used, disable communication in the
COMMUNICATION menu (Communication ? = No).
2. Failure of the battery-backed memory or of the battery itself :
Message :
« RAM ERROR » (failure of the battery-backed memory)
Cause :
Hardware or software failure
Action :
Check that the battery is correctly positioned and restart the protection software by
disconnecting the power supply, if the software fault still remain after restart,
withdraw the active part and return the module to the factory for repair.
Message :
« BATTERY FAIL » (battery in fault)
Technical Guide P124/EN T07/B44
Commissioning and Maintenance CHAPTER 7
MiCOM P124 Page 19/22
Cause :
Hardware failure
Action :
Check that the battery is correctly positioned and restart the protection software by
disconnecting the power supply. If the message fault still remains after restart, change
the battery. If the fault still remains after restart, withdraw the active part and return
the module to the factory for repair.
NOTE : it is possible to mask the message "Battery fail" in the
Configuration/Alarms/Alarm Battery menu
3. Clock for event stamping in fault
Message :
« CLOCK ERROR »
Cause :
Hardware or software failure
Action :
Restart the software by disconnecting the power supply, if the fault still remains after
restart, withdraw the active part and return the module to the factory for repair.
5.1.2 Major fault
Major fault for MiCOM P124 relays are dedicated software and hardware failures.
As soon as this type of failure is detected, the watchdog (WD) is de-energised (35-36
contact closed, 36-37 contact open) and all operations are stopped (protection,
automation, communication for Dual-powered model).
1. Hardware and software faults of the memory components
Messages :
« EEPROM ERROR DATA » or « EEPROM ERROR CALIBR. » (Data zone or Calibration
zone in fault)
« CT ERROR » (Analogue channel in fault)
Cause :
Hardware or software failure
Action :
Restart the protection software by disconnecting the power supply, if the software fault
still remains after restart, withdraw the active part and return the module to the
factory for repair.
2. Loss of auxiliary supply (P124 Dual-powered only)
If the trip output relay RL1 is programmed in fail-safe operation and the auxiliary
power supply lost, the MiCOM P124 relay is not able to perform the trip of the CB via
RL1.
In this case only the HMI is operational if the current load is over the minimum
required (0.2 In on at least one phase).
All the protection and automation functions are inhibited.
P124/EN T07/B44 Technical Guide
CHAPTER 7 Commissioning and Maintenance
Page 20/22 MiCOM P124
Messages :
« AUX SUPPLY LOST »
Cause :
RL1 configured with fail-safe operation and the auxiliary power supply is lost.
Action :
Supply the P124 with an auxiliary power supply or configure the trip output relay RL1
in the Configuration/RL1 output relay/Fail-safe relay menu on NO.
5.2 Method of repair
5.2.1 Replacing the active part
The case and the rear terminals blocks have been designed to facilitate removal of
the MiCOM P124 relay should replacement or repair become necessary without
disconnect the scheme wiring.
NOTE : The MiCOM P124 of relays have integral current transformer
shorting switches which will close when the active part is
removed from the case.
Remove the upper and lower flap without exerting excessive force. Remove the
external screws.
Under the upper flap, turn the extractor with a 3 mm screwdriver and extract the
active part of the relay by pulling from the upper and lower notches on the front
panel of the MiCOM relay.
The reinstall the repaired or replacement relay follow the above instruction in reverse,
ensuring that no modification has been done on the scheme wiring.
5.2.2 Replacing the complete relay
Before working at the rear of the relay, isolate all current supplies to the MiCOM
relay and ensure that the relay is no more powered.
To remove the complete relay (active part and case) the entire wiring must be
removed from the rear connector.
NEVER OPEN CIRCUIT THE SECONDARY CIRCUIT OF A CURRENT
Action :
Adjust the frequency for refreshing the measurements of the supervision software or
of the setting software to 1 second.
MiCOM P124
CHAPTER 8
Communication Database
P124 Dual-Powered Relay
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 1/98
CONTENT
1. INTRODUCTION 5
1.1 Purpose of this document 5
1.2 Glossary 5
2. MODBUS PROTOCOL 6
2.1 Technical characteristics of the MODBUS connection 6
2.1.1 Parameters of the MODBUS connection 6
2.1.2 Synchronisation of exchanges messages 7
2.1.3 Message validity check 7
2.1.4 Address of the MiCOM relays 7
2.2 MODBUS functions of the MiCOM relays 7
2.3 Presentation of the MODBUS protocol 8
2.3.1 Format of frames sent by the MiCOM relay 8
2.3.2 Messages validity check 9
2.4 MiCOM P124 Dual-powered relay database organisation 10
2.4.1 Description of the application mapping 10
2.4.2 Page 0h : Product information, remote signalling, measurements 12
2.4.3 Page 1h, MiCOM P124 : general remote parameters 15
2.4.4 Page 2h : setting Group 1 19
2.4.5 Page 3h : setting Group 2 22
2.4.6 Page 4h : remote controls 25
2.4.7 Pages 5h/6h 25
2.4.8 Page 7h 25
2.4.9 Page 8h : time synchronisation 25
2.4.10 Mapping access characteristics 26
2.4.11 Pages 9h to 21h : disturbance record data (25 pages). 27
2.4.12 Page 22h : disturbance record index frame 29
2.4.13 Page 35h (addresses 3500h to 354Ah) : event record data (9 words) 30
2.4.14 Page 36h 32
2.4.15 Page 37h : fault record value data 32
2.4.16 Page 3Eh : most older Fault record value data 34
2.4.17 Pages 38h to 3Ch 35
2.4.18 Pages 3Dh : number of disturbance records available 36
2.4.19 Description of the mapping format, MiCOM P124 Dual-powered 38
2.4.20 Disturbance record additional information 46
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 2/98 MiCOM P124
4. IEC60870-5-103 INTERFACE 83
4.1 Physical connection and link layer 83
4.2 Initialisation 83
4.3 Time synchronisation 84
4.4 Spontaneous events 84
4.5 General interrogation 84
4.6 Cyclic measurements 84
4.7 Commands 84
4.8 Disturbance records 84
4.9 Blocking of monitor direction 85
4.10 List of events produced by the relay 85
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 3/98
BLANK PAGE
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 5/98
1. INTRODUCTION
1.1 Purpose of this document
This document describes the characteristics of the different communication protocol of
MiCOM P124 Dual-powered relay.
The available communication protocols of MiCOM P124 Dual-powered relay are
as follows:
• MODBUS.
• K-BUS/Courier.
• IEC 60870-5-103.
• DNP3
1.2 Glossary
Ir, Is, It : currents measured on the concerned phases (r, s, t)
IE : residual current measured by earth input (= 3.I zero sequence)
pf : soft weight of a word of 16 bits
PF : heavy weight of a word of 16 bits.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 6/98 MiCOM P124
2. MODBUS PROTOCOL
MiCOM P124 Dual-powered relay can communicate by a RS 485 link behind the
unit following the MODBUS RTU protocol.
2.1 Technical characteristics of the MODBUS connection
2.1.1 Parameters of the MODBUS connection
The different parameters of the MODBUS connection are as follows :
• Isolated two-point RS485 connection (2kV 50Hz),
• MODBUS line protocol in RTU mode
• Communication speed can be configured by an operator dialog in the front panel
of the relay :
Baud rate
300
600
1200
2400
4800
9600
19200
38400
− Transmission mode of the configured characters by operator dialog
Mode
1 start / 8 bits / 1 stop : total 10 bits
1 start / 8 bits / even parity / 1 stop : total 11 bits
1 start / 8 bits / odd parity / 1 stop : total 11 bits
1 start / 8 bits / 2 stop : total 11 bits
1 start / 7 bits / 2 stop : total 10 bits
1 start / 7 bits / 1 stop : total 9 bits
1 start / 7 bits / even parity / 1 stop : total 10 bits
1 start / 7 bits / odd parity / 1 stop : total 10 bits
1 start / 7 bits / 2 stop : total 10 bits
1 start / 7 bits / 2 stop : total 10 bits.
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 7/98
2.4.1.1 Settings
MiCOM P123 application mapping has 9 pages of parameters.
Page 0h: Product information, remote signalling, measurements
Page 1h: General remote parameters
Page 2h: Setting group 1 remote parameters
Page 3h: Setting group 2 remote parameters
Page 4h: Remote controls
Pages 5h/6h: Reserved pages
Pages 7h: Quick reading byte
Pages 8h: Time synchronisation
2.4.1.5 Characteristics
Page 0h can only be read through communication.
Pages 1h, 2h, 3h and 4h can be read and write.
Page 7h can be access in quick reading only.
Page 8h can be write.
They are describe more precisely in the following chapters.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 12/98 MiCOM P124
Values Fault
Address Group Description Step Unit Format
range Value
0000 Product Relay description 32-127 1 - F10
Information characters 1 and 2
0001 Relay description 32-127 1 - F10 P1
characters 3 and 4
0002 Relay description 32-127 1 - F10 24
characters 5 and 6
0003 Unit reference characters 32-127 1 - F10 AL
1 and 2
0004 Unit reference characters 32-127 1 - F10 ST
3 and 4
0005 Software version 10-xx 1 - F21
0006 Front communication 0-1 1 - F41
0007 Internal phase ratio - F1
0008 Internal earth ratio - F1
0009 to Reserved
000B
000C Active Group 1-2 1 - F1
n
000D Electromechani- Flag status 0 to FF 2 - F52
cal
000E Password active - F24
000F Relay status - F45
0010 Remote Logical inputs 0 to 31 1 - F12
signalling
0011 Logical data 0 to FFFF 2n - F20
0012 Internal Logic 0 to FFFF 2n - F22
0013 Output contacts 0 to 511 1 - F13
0014 Output information: I> 0 to FFFF 1 - F17
0015 Output information: I>> 0 to FFFF 1 - F17
0016 Output information: 0 to FFFF 1 - F17
I>>>
0017 Output information: IE> 0 to FFFF 1 - F16
0018 Output information: IE>> 0 to FFFF 1 - F16
0019 Output information: 0 to FFFF 1 - F16
IE>>>
001A I> memorisation 0 to FFFF 1 - F17
001B I>> memorisation 0 to FFFF 1 - F17
001C I>>> memorisation 0 to FFFF 1 - F17
001D tI> memorisation 0 to FFFF 1 - F17
001E tI>> memorisation 0 to FFFF 1 - F17
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 13/98
Values Fault
Address Group Description Step Unit Format
range Value
001F tI>>> memorisation 0 to FFFF 1 - F17
0020 Thermal state information 0 to 3 1 - F37
0021 Output information: I< 0 to FFFF 1 - F17
0022 Output information: I2> 0 to FFFF 1 - F16
0023 Output information: 0 to FFFF 1 - F38
broken conductor
/ CB failure
/ CB alarm
0024 tI< memorisation 0 to FFFF 1 - F17
0025 Memorised flag for non - F36
acknowledge alarms
0026 Number of disturbance 0 to 5 1 - F31
records available
0027 Tripping output (RL1) status 0 to 1 1 - F1
0028 CB supervision flag - F43
0029 Non acknowledge alarm - F44
memorised flag 2
002A to Reserved
002F
0030 Remote Phase A current RMS value 0 to 1 A/100 F18
measurements 600 000
0032 Phase B current RMS value 0 to 1 A/100 F18
600 000
0034 Phase C current RMS 0 to 1 A/100 F18
value 600 000
0036 Earth current RMS value 0 to 1 A/100 F18
120 000
0038-0039 Reserved
003A Thermal state % F1
003B Frequency 4500 to 1 1/100 F1
6500 Hz
003C Phase A current peak RMS 0 to 1 A/100 F18
value 600 000
003E Phase B current peak RMS 0 to 1 A/100 F18
value 600 000
0040 Phase C current peak RMS 0 to 1 A/100 F18
value 600 000
0042 Phase A current rolling 0 to 1 A/100 F18
RMS value 600 000
0044 Phase B current rolling 0 to 1 A/100 F18.
RMS value 600 000
0046 Phase C current rolling 0 to 1 A/100 F18
RMS value 600 000
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 14/98 MiCOM P124
Values Fault
Address Group Description Step Unit Format
range Value
0048 Io harmonique 0 to 1 A/100 F18
600 000
004A I2 1 A/100 F18
004C Positive phase sequence 1 A/100 F18
current value
(fundamental)
004E Ratio I2/I1 1 % F1
004F Trip number 0 to 65535 1 - F1
0050 Fourier Module Module IA - F1
0051 Module IB - F1
0052 Module IC - F1
0053 Module IE - F1
0054 Fourier Argument IA - F1
Argument
0055 Argument IB - F1
0056 Argument IC - F1
0057 Argument IE - F1
0058 Module I2 - F1
0059 Module I1 - F1
005A Recloser Cycle total number - F1
statistics
005B Cycle 1 number - F1
005C Cycle 2 number - F1
005D Cycle 3 number - F1
005E Cycle 4 number - F1
005F Definitive tripping - F1
number
0060 Closing order number - F1
0061 to Reserved.
006F
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 15/98
Values Fault
Address Group Description Step Unit Format
range Value
0100 Remote Address 1 to 255 1 - F1 1
parameters
0101 Reserved
0102 Password characters 1 32 -127 1 - F10 AA
and 2
0103 Password characters 3 32 -127 1 - F10 AA
and 4
0104 Frequency 50-60 10 Hz F1 50
0105 Phase A label L1-A-R VTA - F25 A
0106 Phase B label L2-B-S VTA - F25 B
0107 Phase C label L3-C-T VTA - F25 C
0108 Earth label N-G-E VTA - F25 N
0109 Fault display 1-4 1 - F26 1
010A User reference 32-127 1 F10 AL
(characters 1 and 2)
010B User reference 32-127 1 F10 ST
(characters 3 and 4)
010C Fault number to display 1-5 1 F31 5
010D Inputs operation 0-31 1 - F12 0
010E to Reserved
010F
0110 CB monitoring Operation number 1 - F1
measurements
0111 CB Operating time 1/100 s F1
0112 Switched square Amps An F18
phase A sum
0114 Switched square Amps An F18
phase B sum
0116 Switched square Amps An F18
phase C sum
0118 CB Closing time 1/100 s F1
0119 to Reserved
011E
011F Latch relay 0-31 1 - F14 0
0120 Ratio Primary phase CT value 1 to 1 - F1 1000
9999*
0121 Reserved
0122 Primary earth CT value 1 to 1 - F1 1000
9999
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 16/98 MiCOM P124
Values Fault
Address Group Description Step Unit Format
range Value
0123 to Reserved.
012F
Values Fault
Address Group Description Step Unit Format
range Value
0165 Output relay Broken conductor 0-31 1 - F14 0
allocation detection
0166 CB failure 0 - 31 1 - F14 0
0167 I< 0 - 31 1 - F14 0
0168 I2> 0 - 31 1 - F14 0
0169 Thermal overload alarm 0 - 31 1 - F14 0
016A Thermal overload trip 0-31 1 - F14 0
016B CB close 0-31 1 - F14 0
016C tAUX1 0-31 1 - F14 0
016D tAUX2 0-31 1 - F14 0
016E CB alarms 0-31 1 - F14 0
016F Trip circuit 0-31 1 - F14 0
0170 Active group 0-31 1 - F14 0
0171 Trip 0 - 31 1 - F14 1
0172 tI> 0 - 31 1 - F14 0
0173 tI>> 0 - 31 1 - F14 0
0174 tI>>> 0 - 31 1 - F14 0
0175 tIE > 0 - 31 1 - F14 0
0176 tIE >> 0 - 31 1 - F14 0
0177 tIE >>> 0 - 31 1 - F14 0
0178 I> 0 - 31 1 - F14 0
0179 I>> 0 - 31 1 - F14 0
017A I>>> 0 - 31 1 - F14 0
017B IE > 0 - 31 1 - F14 0
017C IE >> 0 - 31 1 - F14 0
017D IE >>> 0 - 31 1 - F14 0
017E Recloser running 0 - 31 1 - F14 0
017F Recloser final trip 0 - 31 1 - F14 0
0180 Automation Trip 0 to 63 1 - F6 1
0181 Relay latching 0 to 63 1 - F8 0
0182 Blocking logic 1 0 to 63 1 - F8' 0
0183 Blocking logic 2 0 to 63 1 - F8' 0
0184 Broken conductor 0-1 1 - F24 0
detection
0185 tBC 0 to 14400 1 - F1 0
0186 Cold load start 0-1 1 - F24 0
0187 Cold load start thresholds 0 to 255 1 - F33 0
0188 Cold load start % 20 to 500 1 % F1 50
0189 Cold load start delay 1 to 36000 1 1/10 s F1 10
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 18/98 MiCOM P124
Values Fault
Address Group Description Step Unit Format
range Value
018A CB failure 0-1 1 F24 0
018B tBF 0 to 1000 1 1/100 s F1 10
018C Selective scheme logic 1 0 to 15 1 F40 0
018D tSEL1 0 to 15000 1 1/100 s F1 0
018E Selective scheme logic 2 0 to 15 1 - F40 0
018F tSEL2 0 to 1 1/100 s F1 0
15000
0190 Disturbance Pre-time 1 to 30 1 - F1 1
0191 Post-time 1 to 30 1 - F1 1
0192 Disturbance starting 0-1 1 - F32 0
condition
0193 CB monitoring Operating time 0-1 1 - F24 0
0194 Operating time 5 to 100 5 1/100 s F1 5
threshold
0195 Operation number 0-1 1 - F24 0
0196 Operation number 0 - 50000 1 - F1 0
threshold
0197 CB switched Amps sum 0-1 1 - F24 0
0198 CB switched Amps sum 0 to 10 E 6 A n F3
threshold 4000
0199 Amps or square Amps 1-2 1 F1' 1
019A Closing time threshold 5 to 100 5 1/100 s F8' 0
019B Auxiliary timer 1 0 to 20000 1 1/100 s F1 0
019C Auxiliary timer 2 0 to 20000 1 1/100 s F1 0
019D Peak value 5 to 60 VTA mn F42 5
019E I2/I1 threshold 20 to 100 1 % F1 20
019F Tripping time 10 to 500 5 1/100 s F1 10
01A0 Closing time 10 to 500 5 1/100 s F1 10
01A1 Closing time threshold 0-1 1 F24 0
validation
01A2 Trip circuit supervision 0-1 1 F24 0
validation
01A3 t SUP* 10 to 5 1/100 s F1 10
1000
01A4 I<thershold for CB fail 2 to 100 1 1/100 F1 2
function
01A5 Instantaneous 0-1 1 - F24 0
I>blocking if CB fail
01A6 Instantaneous 0-1 1 - F24 0
le>blocking if CB fail
01A7 to Reserved.
1AF
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 19/98
Values Fault
Address Group Description Step Unit Format
range Value
0300 Setting group 2 I> 0-1 1 - F24 0
0301 I> threshold 10 to 1 In/100 F1 10
2500
0302 I> time delay type 0 to 2 1 - F27 0
0303 I> IDMT Curve Type 0 to 10 1 - F3 1
0304 I> TMS value 25 to 25 1/1000 F1 25
1500
0305 I> K value (RI curve) 100 to 5 1/1000 F1 100
10000
0306 Ti> value 0 to 1 1/100 s F1 4
15000
0307 I> Reset type 0–1 1 F27 0
0308 I> RTMS value 0 to 25 1/1000 F1 25
15000
0309 I> Treset value 4 to 1 1/1000 F1 4
10000
030A to Reserved 0
030F
0310 I>> 0-1 1 - F24 0
0311 I>> value 50 to 5 In/100 F1 50
4000
0312 Ti>> value 0 to 1 1/100 s F1 1
15000
0313 to Reserved 0
031F
0320 I>>> 0-1 1 - F24 0
0321 I>>> value 50 to 5 In/100 F1 50
4000
0322 Ti>>> value 0 to 1 1/100 s F1 1
15000
0323 to Reserved 0
032F
0330 IE > 0-1 1 - F24 0
0331 IE > value sensitive version 10 to 1000 5 1/1000 I0n F1 10
IE > value normal version 10 to 400 1 1/100 I0n F1 10
IE > value very sensitive 2 to 1000 1 1/1000 I0n F1 2
version
0332 IE > time delay type 0 to 3 1 - F27 0
0333 IE > IDMT curve type 0 to 10 1 - F3 1
0334 IE > TMS value 25 to 25 1/1000 F1 25
1500
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 23/98
Values Fault
Address Group Description Step Unit Format
range Value
0335 IE> K value (RI) 100 to 5 1/1000 F1 100
10000
0336 TiE > value 0 to 1 1/100 s F1 4
18000
0337 IE > reset type 0–1 1 F27 0
0338 IE > RTMS value 25 to 25 1/1000 F1 25 25
3200
0339 IE > Treset value 4 to 1 1/100 s F1 4
10000
033A Laborelec curve 0 to 2 1 F3 0
033B to Reserved 0
033F
0340 IE >> 0-1 1 - F24 0
0341 IE >> value 10 to 5 1/1000 F1 10
8000 I0n
0342 tIE >> value 0 to 1 1/100 s F1 1
18000
0343 to Reserved 0
034F
0350 IE >>> 0-1 1 - F24 0
0351 IE >>> value 10 to 5 1/1000 F1 10
8000 I0n
0352 t E >>>value 0 to 1 1/100 s F1 1
18000
0353 Ith> 0-1 1 F24 0
0354 Ith> value 10 to 320 5 1/100 F1 8
0355 Ith> k value 100 to 1 1/100 F1 105
150
0356 Ith> trip threshold 50 to 200 1 % F1 100
0357 Ith> alarm 0–1 1 F24 0
0358 Ith> alarm threshold 50 to 200 1 % F1 90
0359 Thermal overload time 1 to 200 1 mn F1 1
constant
035A I< 0-1 1 - F24 0
035B I< threshold 0 to 100 1 % In F1 20
035C I2> 0-1 1 - F24 0
035D I2> threshold 10 to 1 In/100 F1 20
4000
035E I2> time delay type 0 to 2 1 - F27 0
035F I2> IDMT type 0 to 9 1 - F3 1
0360 I2> TMS value 25 to 25 1/1000 F1 25
1500
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 24/98 MiCOM P124
Values Fault
Address Group Description Step Unit Format
range Value
0361 I2> K value (RI) 100 to 5 1/1000 F1 100
10000
0362 tI2> value 0 to 1 1/100 s F1 4
15000
0363 I2> Reset type 0–1 1 F27 0
0364 I2> RTMS value 25 to 25 1/1000 F1 25
3200
0365 I2> tRESET value 4 to 1 1/100 s F1 4
10000
0366 to Reserved
036E
036F tI< value 0 to 18000 1 1/100 s F1 0
0370 Recloser valid 0-1 1 F24 0
0371 CB position active 0-1 1 F1 0
0372-0373 Supervision window 1 to 1 1/100 s F18 0
60000
0374 External blocking input 0-1 1 F24 0
0375-0376 Reserved
0377 Dead time 1 0 to 1 1/100 s F1 1
30000
0378 Dead time 2 0 to 1 1/100 s F1 1
3000
0379-037A Dead time 3 0 to 1 1/100 s F18 1
60000
037B- Dead time 4 0 to 1 1/100 s F18 1
037C 60000
037D-037E Reclaim time 2 to 1 1/100 s F18 2
60000
037F-0380 Inhibit time 2 to 1 1/100 s F18 2
60000
0381 Recloser cycles for phase 0 to 4 1 F1 0
faults
0382 Recloser cycles for earth 0 to 4 1 F1 0
faults
0383 t I> cycles configuration 0 to 2222 1 F49 1111
0384 t I>> cycles configuration 0 to 2222 1 F49 1111
0385 t I>>> cycles configuration 0 to 2222 1 F49 1111
0386 t Ie> cycles configuration 0 to 2222 1 F49 1111
0387 t Ie>> cycles configuration 0 to 2222 1 F49 1111
0388 t Ie>>> cycles 0 to 2222 1 F49 1111
configuration
0389 t Aux1 cycles configuration 0 to 2222 1 F49 1111
038A t Aux2 cycles configuration 0 to 2222 1 F49 1111
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 25/98
Address Contents
0900h to 09FAh 250 disturbance data words
0A00h to 0AFAh 250 disturbance data words
0B00h to 0BFAh 250 disturbance data words
0C00h to 0CFAh 250 disturbance data words
0D00h to 0DFAh 250 disturbance data words
0E00h to 0DFAh 250 disturbance data words
0F00h to 0FFAh 250 disturbance data words
1000h to 10FAh 250 disturbance data words
1100h to 11FAh 250 disturbance data words
1200h to 12FAh 250 disturbance data words
1300h to 13FAh 250 disturbance data words
1400h to 14FAh 250 disturbance data words
1500h to 15FAh 250 disturbance data words
1600h to 16FAh 250 disturbance data words
1700h to 17FAh 250 disturbance data words
1800h to 18FAh 250 disturbance data words
1900h to 19FAh 250 disturbance data words
1A00h to 1AFAh 250 disturbance data words
1B00h to 1BFAh 250 disturbance data words
1C00h to 1CFAh 250 disturbance data words
1D00h to 1DFAh 250 disturbance data words
1E00h to 1EFAh 250 disturbance data words
1F00h to 1FFAh 250 disturbance data words
2000h to 20FAh 250 disturbance data words
2100h to 21FAh 250 disturbance data words
NB: The disturbance data pages contain values of one channel from
one given disturbance record.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 28/98 MiCOM P124
Address Contents
2200h Disturbance data index frame
Disturbance record index frame
Word Contents
n° 1 Disturbance record number
n° 2 Disturbance record finish date (second)
n° 3 Disturbance record finish date (second)
n° 4 Disturbance record finish date (millisecond)
n° 5 Disturbance record finish date (millisecond)
n° 6 Disturbance record starting condition :
1 : tripping (RL1)
2 : instantaneous
3 : remote command
4 : logic input
2.4.13 Page 35h (addresses 3500h to 354Ah) : event record data (9 words)
Word n° 1: Event meaning
Word n° 2: MODBUS associated value
Word n° 3: MODBUS address
Word n° 4: Reserved
Words n° 5 & 6: Event date (second) number of seconds since 01/01/94
Words n° 7 & 8: Event date (millisecond)
Word n° 9: Acknowledge
0=event non acknowledged
1= event acknowledged)
Address Contents
3600h Most older event data
2.4.15 Page 37h : fault record value data
Access in word reading (function 03)
Address Contents
3700h Fault value record n°1
3701h Fault value record n°2
3702h Fault value record n°3
3703h Fault value record n°4
3704h Fault value record n°5
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 33/98
Address Contents
3E00h Most older Fault record
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 35/98
Address Contents
3D00h Number of disturbance records available
CODE DESCRIPTION
F1 Unsigned integer – numerical data : 1 - 65535
F2 Signed integer – numerical data : -32768 - 32767
F3 Unsigned integer – curves type
0 : STI (IEC)
1 : SI (IEC)
2 : VI (IEC)
3 : EI (IEC)
4 : LTI (IEC)
5: STI (C02)
6: MI (ANSI)
7 : LTI (CO8)
8 : VI (ANSI)
9 : EI (ANSI)
10 : RC Rectifier curve
F3' Unsigned integer – Laborelec curve type
0 : curve 1
1 : curve 2
2 : curve 3
F4 Unsigned integer : MODBUS speed
0 : 300
1 : 600
2 : 1200
3 : 2400
4 : 4800
5 : 9600
6 : 19200
7 : 38400
F5 Unsigned integer : parity
0 : without
1 : even
2 : odd
F6 Unsigned integer : Tripping configuration
bit 0 : tI>
bit 1 : tI>>
bit 2 : tI>>>
bit 3 : tlE>
bit 4 : tlE >>
bit 5 : tlE >>>
bit 6 : I<
bit 7 : tIth>
bit 8 : Broken conductor detection
bit 9 : t Aux 1
bit 10 : t Aux 2
bit 11 : tI2>
bits 12 to 15 : reserved
F7 Reserved
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 39/98
CODE DESCRIPTION
F8 Unsigned integer : Latching configuration
bit 0 : I> latching
bit 1 : I>>
bit 2 : I>>>
bit 3 : lE>
bit 4 : lE>>
bit 5 : lE>>>
bit 6 : I<
bit 7 : tIth>
bit 8 : Broken conductor detection
bit 9 : t Aux 1
bit 10 : t Aux 2
bit 11 : tI2>
bits 12 to 15 : reserved
F8' Unsigned integer : Blocking logic configuration
bit 0 : I> blocking
bit 1 : I>>
bit 2 : I>>>
bit 3 : lE>
bit 4 : lE>>
bit 5 : lE>>>
bit 6 : reserved
bit 7 : tIth>
bit 8 : Broken conductor detection
bit 9 : t Aux 1
bit 10 : t Aux 2
bit 11 : tI2>
bits 12 to 15 : reserved
F9 Unsigned integer : Remote control 1
bit 0 : Tripping contact delatched
bit 1 : 1st alarm acknowledge
bit 2 : All alarms acknowledge
bit 3 : Remote tripping
bit 4 : Remote closing
bit 5 : Setting group change
bit 6 : Thermal state reset
bit 7 : Peak and rolling value reset
bit 8 : Disturbance record remote start
bit 9 : Maintenance mode
bit 10 : Recloser counter reset
bit 11 : Recloser reset
bit 12 : Local maintenance acknowledge
bit 13 : Oldest event acknowledge
bit 14 : Oldest fault acknowledge
bit 15 : Hardware Sram alarm acknowledge
F10 2 characters ASCII
32 –127 = ASCII character1
32 – 127 = ASCII character 2
F11 Unsigned integer : triggered output type
0 : stricker output
1 : trip output relay, RL1
2 : stricker + trip output relay RL1 outputs
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 40/98 MiCOM P124
CODE DESCRIPTION
F12 Unsigned integer : Logic input status
it 0 : logic input number 1
bit 1 : logic input number 2
bit 2 : logic input number 3
bit 3 : logic input number 4
bit 4 : logic input number 5
bits 5 to 15 : reserved
F13 Unsigned integer : logic outputs status
bit 0 : watchdog RL0
bit 1 : logic output RL1 (tripping)
bit 2 : stricker output
bit 3 : V1 flag command
bit 4 : V1 flag reset
bits 5 to 15 : reserved
F14 Unsigned integer : logic outputs configuration
bit 0 : selection logic output number RL2
bit 1 : selection logic output number RL3
bit 2 : selection logic output number RL4
bit 3 : selection logic output number RL5
bit 4 : selection logic output number RL6
bits 5 to 15 : reserved
F15 Unsigned integer : logical input allocation
bit 0 : delatch allocation
bit 1 : allocation 52 a
bit 2 : allocation 52 b
bit 3 : allocation external CB failure
bit 4 : allocation external input 1
bit 5 : allocation external input 2
bit 6 : allocation logic blocking 1
bit 7 : allocation logic blocking 2
bit 8 : allocation disturbance start
bit 9 : allocation cold load start
bit 10 : allocation selective scheme logic 1
bit 11 allocation selective scheme logic 2
bit 12 : allocation change of setting group
bit 13 : allocation recloser locked
bit 14 : allocation thermal state reset
bit 15 : allocation trip circuit supervision
F15' Unsigned integer : logical input allocation (next)
bit 0 : start CB fail timer
F16 Unsigned integer : threshold earth information status
bit 0 : reserved
bit 1 : reserved
bit 2 : reserved
bit 3 : reserved
bit 4 : reserved
bit 5 : Instantaneous information IE> or IE>> or IE>>>
bit 6 : Tripping information tIE> or tIE>> or tIE>>>
bits 7 to 15 : reserved
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 41/98
CODE DESCRIPTION
F17 Unsigned integer : threshold phase information status
bit 0 : reserved
bit 1 : Instantaneous IA
bit 2 : Instantaneous IB
bit 3 : Instantaneous IC
bit 4 : reserved
bit 5 : Instantaneous information I> or I>> or I>>>
bit 6 : Tripping information tI> or tI>> or tI>>>
bits 7 to 15 : reserved
F18 Long integer
F19 Unsigned integer : LEDs allocation
bit 0 : I>
bit 1 : tI>
bit 2 : I>>
bit 3 : tI>>
bit 4 : I>>>
bit 5 : tI>>>
bit 6 : IE>
bit 7 : tIE>
bit 8 : IE>>
bit 9 : tIE>>
bit 10 : IE>>>
bit 11 : tIE>>>
bit 12 : Thermal overload trip
bit 13 : tI2>
bit 14 : Broken conductor trip
bit 15 : CB failure
bit 16 : Logic input 1
bit 17 : Logic input 2
bit 18 : Logic input 3
bit 19 : Logic input 4
bit 20 : Logic input 5
bit 21 : Recloser running
bit 22 : Recloser locked
bit 23 : t Aux1
bit 24 : t Aux2
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 42/98 MiCOM P124
CODE DESCRIPTION
F20 Unsigned integer : logic input data status
bit 0 : Selective scheme logic 1
bit 1 : Selective scheme logic 2
bit 2 : Relay delatch
bit 3 : CB position (52 a)
bit 4 : CB position (52 b)
bit 5 : External CB failure
bit 6 : External 1
bit 7 : External 2
bit 8 : Blocking logic 1
bit 9 : Blocking logic 2
bit 10 : Disturbance record start
bit 11 : Cold load start
bit 12 : Setting group change
bit 13 : Recloser locked
bit 14 : Thermal state reset
bit 15 : Trip circuit supervision
F21 Unsigned integer : software version
10 : Version 1.A
11 : Version 1.B
20 : Version 2.A
F22 Unsigned integer : internal logic data
bit 0 : Blocking
bit 1 : reserved
F23 Unsigned integer : relay status
bit 0 : Relay status (major alarm)
bit 1 : Minor material alarm
bit 2 : Presence of non-acknowledged event
bit 3 : Synchronisation state
bit 4 : Presence of non-acknowledged disturbance record
bit 5 : Presence of non-acknowledged fault record
bit 6 : reserved
bit 7 : reserved
F24 0 : Out of service
1 : Healthy
F25 2 ASCII characters
F26 1 : IA measurement display (True RMS)
2 : IB measurement display (True RMS)
3 : IC measurement display (True RMS)
4 : IN measurement display (True RMS)
F27 0 : DMT time delay
1 : IDMT time delay
2 : RI time delay
F27' 0 : DMT time delay
1 : IDMT time delay
2 : RI time delay
3 : Laborelec curve
F28 0 : 7 data bits
1 : 8 data bits
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 43/98
CODE DESCRIPTION
F29 0 : 1 stop bit
1 : 2 stop bits.
F30 0 : Communication non-available
1 : Communication available
F31 Unsigned integer : Number of available event records
0 : None
1 : 1 event record available
2 : 2 event records available
3 : 3 event records available
4 : 4 event records available
5 : 5 event records available
F32 Unsigned integer :
0 : Disturbance record start condition on INSTANTANEOUS
1 : Disturbance record start condition on TRIPPING
F33 Cold load start thresholds
bit 0 : tI>
bit 1 : tI>>
bit 2 : tI>>>
bit 3 : tIE>
bit 4 : tIE>>
bit 5 : tIE>>>
bit 6 : Thermal overload trip
bit 7 : tI2>
bit 8 to 15 : reserved
F34 Reserved
F35 0 : No disturbance record uploaded
1 : Disturbance record upload running
F36 Memorised flags of non acknowledged alarms :
bit 0 : IE>
bit 1 : tIE>
bit 2 : IE>>
bit 3 : tIE>>
bit 4 : IE>>>
bit 5 : tIE>>>
bit 6 : Thermal overload alarm
bit 7 : Thermal overload trip
bit 8 : Broken conductor
bit 9 : CB failure
bit 10 : reserved
bit 11 : I2>
bit 12 : tI2>
bit 13 : t Aux 1
bit 14 : t Aux 2
bit 15 : reserved
F37 Unsigned integer : Thermal overload information
bit 0 : Thermal overload alarm
bit 1 : Thermal overload trip
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 44/98 MiCOM P124
CODE DESCRIPTION
F38 Unsigned integer :
bit 0 : reserved
bit 1 : CB failure
bit 2 : Pole A opening
bit 3 : Pole B opening
bit 4 : Pole C opening
bit 5 : Broken conductor
bit 6 : t Aux 1
bit 7 : t Aux 2
bit 8 : Broken conductor time delay
bit 9 : CB failure time delay
bit 10 : Cold load pick up time delay
bit 11 : CB alarms or bits 0,1,2,4 of F43
F39 Unsigned integer : output relay remote word in maintenance mode
bit 0 : RL1 (trip)
bit 1 : RL2
bit 2 : RL3
bit 3 : RL0 (watchdog)
bit 4 : RL4
bit 5 : RL5
bit 6 : RL6
F40 Unsigned integer : selective scheme logic configuration
bit 0 : tI>>
bit 1 : tI>>>
bit 2 : tlE>>
bit 3 : tlE>>
F41 0 : Front and rear MODBUS communication
1 : Front MODBUS and rear Courier communication
F42 5, 10, 15, 30 or 60 minutes
F43 bit 0 : CB operating time overreach
bit 1 : CB operation number overreach
bit 2 : Square Amps sum overreach
bit 3 : Trip circuit self-test
bit 4 : CB closing time overreach
bits 5 to 10 : Reserved
F44 bit 0 : CB, operating time overreach, memorised alarm
bit 1 : CB operation number overreach, memorised alarm
bit 2 : Square Amps sum overreach, memorised alarm
bit 3 : Trip circuit self-test, memorised alarm
bit 4 : CB closing time overreach, memorised alarm
bits 5 to 7 : reserved
F45 Unsigned integer : relay status
bit 0 : Watchdog
bit 1 : Communicatio n failure
bit 2 : EEPROM data failure
bit 3 : Analogue failure
bit 4 : Datation failure
bit 5 : EEPROM calibration failure
bit 6 : SRAM failure
bit 7 : reserved
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 45/98
CODE DESCRIPTION
F46 bit 0 : Io harmonic calculation
bit 1 : trip number reset
F49 bit 0 : cycle 1 configuration (trip followed by reclosing cycle)
bit 1 : cycle 1 configuration (no trip in cycle 1)
bit 2 to bit 3 : reserved
bit 4 : cycle 2 configuration (trip followed by reclosing cycle)
bit 5 : cycle 2 configuration (no trip in cycle 2)
bit 6 to bit 7 : reserved
bit 8 : cycle 3 configuration (trip followed by reclosing cycle)
bit 9 : cycle 3 configuration (no trip in cycle 3)
bit 10 to bit 11 : reserved
bit 12 : cycle 4 configuration (trip followed by reclosing cycle)
bit 13 : cycle 4 configuration (no trip in cycle 4)
F50 Unsigned integer : CTs and model configuration
"A" : model standard, CT 1A
"B" : model standard, CT 5A
"C" : model sensitive, CT 1A
"D" : model sensitive, CT 5A
F51 Unsigned integer : option configuration
0 : 1 electromagnetic flag
1 : 5 electromagnetic flags
2 : 5 flags + autorecloser
F52 Unsigned integer : electromechanical flags status (P124D)
bit 0 : V2 flag
bit 1 : V2 flag reset
bit 2 : V3 flag
bit 3 : V3 flag reset
bit 4 : V4 flag
bit 5 : V4 flag reset
bit 6 : V5 flag
bit 7 : V5 flag reset
F53 Unsigned integer : internal data 2
bit 0 : CB fail by external input
F54 Unsigned integer : datation format
0 : private format
1 : IEC format
F55 0 : setting group change either on edge of digital input, or on
remote command, or of the relay front
1 : setting group change on level of digital input
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 46/98 MiCOM P124
This request may be answered an error message with the error code :
EVT_NOK(OF) : No record available
NOTA : If there is less than 5 records available, the answer will contains
zero in the non-used words.
This request may be answered an error message with two different error codes :
CODE_DEF_RAM(02) : SRAM failure
CODE_EVT_NOK(03) : no disturbance record available in SRAM
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 47/98
This request may be answered an error message with two different error codes :
CODE_DEP_DATA(04) : the required disturbance data number is
greater than the memorised number.
CODE_SERV_NOK(05) : the service request for disturbance record and
channel number has not been send.
This event request may be answered an error message with the error code :
EVT_EN_COURS_ECRIT (5) : An event is being written into the saved RAM.
NOTA : On event retrieval, two possibilities exist regarding the event
record acknowledgement :
a) Automatic event record acknowledgement on event retrieval.
b) Non automatic event record acknowledgement on event
retrieval.
a) Automatic event record acknowledgement on event retrieval :
The bit12 of the remote order frame (format F9 – mapping address 0400h) shall be
set to 0. On event retrieval, this event record is acknowledged.
b) Non automatic event record acknowledgement on event retrieval :
The bit12 of the remote order frame (format F9 – mapping address 0400h) shall be
set to 1. On event retrieval, this event record is not acknowledged.
To acknowledge this event, an other remote order shall be sent to the relay. The bit
13 of this frame (format F9 – mapping address 0400h) shall be set to 1.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 48/98 MiCOM P124
This event request may be answered an error message with the error code :
EVT_EN_COURS_ECRIT (5) : An event is being written into the saved RAM.
NOTA : This event retrieval does not acknowledge this event.
2.4.23 Modbus request definition used to retrieve the fault records
Two ways can be followed to retrieve a fault record :
− Send a request to retrieve the oldest non-acknowledge fault record.
− Send a request to retrieve a dedicated fault record.
NOTA : This fault value retrieval does not acknowledge this fault record.
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 49/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
00 00 SYSTEM DATA
01 Language Ver>: Indexed String 0 Lang1 (French) Setting 0/3/1
1 Lang2 (English) *
2 Lang3 (German)
3 Lang4 (Spanish)
02 Password ASCII Password(4 bytes) AAAA Setting 32/127/1
03 Fnlinks: NON IMPLEMENTE
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
21 Relay Output Status Binary flag (7 bits) 0: relay 1 (trip) Data
1: watchdog relay
2: relay 2
3: relay 3
4: relay 4
5 : relay 5
6 : relay 6
22 Alarm Binary flag (16 bits) 0: reserved Data
1: Comm err
2: Eeprom err data
3: Ct error
4: Eeprom err calib
5: Clock error
6: Bbram error
7 to 15: reserved
23 Pseudo Logic Input Status group 1 Binary flag (16 bits) 0: I> Data
1: I>>
2: I>>>
3: I0>
4: I0>>
5: I0>>>
6: t I>
7: t I>>
8: t I>>>
9: t I0>
10: t I0>>
11: t I0>>>
12: Thermal Alarm
13: Therm. Overload
14: t I<
15: reserved
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 53/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
24 Pseudo Logic Input Status group 2 Binary flag (16 bits) 0: Broken Conductor Data
1: t Aux 1
2: t Aux 2
3: Breaker Fail.
4: Iinv >
5: t Iinv>
6: Open operating time
7: Trip operation Nb
8: SA 2 n
9: SW Trip Circuit
10: Close operating time
11: Successful
autoreclose
12: Locked autorecloser
13: Autorecloser conf. fail
14: reserved
15: reserved
01 00 USER CONTROL
01 Remote control 1 Binary flag (15 bits) 0: Unlock trip cont.* Setting 0/65535/1
1: Ack first alarm
2 : Ack all alarms
3 : TRIP
4 : CLOSE
5 : Setting Change
6 : Th. State Reset
7 : RMS over&max Reset
8 : Dist. Rec. Trig
9 : Maintenance Start
10 : Recloser timer Reset
11 : Recloser Reset
12 : Manual Ack mode
13 : Ack. older event
14 : Ack. older default
15 : SRAM def . ack.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 54/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
02 Remote control 2 Binary flag (10 bits) 0 : Reserved Setting 0/1023/1
1 : Reserved
2 : Reserved
3 : Relay : Special
Tripping
4 : Watchdog Relay
5 : Relay 1
6 : Relay 2
7 : Relay 3
8 : Relay 4
9 : Relay 5
03 Remote control 3 Binary flag (2 bits) 0 : Reset I0 Harmonic Setting 0/3/1
1 : Unlock TRIP Relay
02 00 VIEW RECORDS
01 Record number Unsigned Integer (2 bytes) 5 Setting 1/5/1
02 Occur date Unsigned Integer (2 bytes)
03 Active set group Unsigned Integer (2 bytes)
04 Phase in fault ASCII Text
05 Fault Id ASCII Text
06 Magnitude Courier floating point
number
07 Ia magnitude Courier floating point
number
08 Ib magnitude Courier floating point
number
09 Ic magnitude Courier floating point
number
0A In magnitude Courier floating point
number
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 55/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
03 00 MEASUREMENTS
01 IA RMS Courier floating point Data
number
02 IB RMS Courier floating point Data
number
03 IC RMS Courier floating point Data
number
04 I0 RMS Courier floating point Data
number
05 Idirect Courier floating point Data
number
06 IINV Courier floating point Data
number
07 Ratio Idir / Iinv Courier floating point Data
number
08 THERMAL STATE (Rst) Unsigned Integer (2 bytes) Data
(%)
09 FREQUENCY Courier floating point Data
number
0A Rst MAX & MOY RMS
0B MAX RMS IA Courier floating point Data
number
0C MAX RMS IB Courier floating point Data
number
0D MAX RMS IC Courier floating point Data
number
0E IA RMS AVERAGE Courier floating point Data
number
0F IB RMS AVERAGE Courier floating point Data
number
10 IC RMS AVERAGE Courier floating point Data
number
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 56/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
11 IN – fn (I0 Harmonic) (Rst) Courier floating point Data
number
12 Trip Number (Rst) Courier floating point Data
number
04 00 RECLOSER STATISTICS (Rst)
01 TOTAL CYCLE NUMBER Unsigned Integer (2 bytes) Data
02 CYCLE 1 NUMBER Unsigned Integer (2 bytes) Data
03 CYCLE 2 NUMBER Unsigned Integer (2 bytes) Data
04 CYCLE 3 NUMBER Unsigned Integer (2 bytes) Data
05 CYCLE 4 NUMBER Unsigned Integer (2 bytes) Data
06 DEFINITIVE TRIP NUMBER Unsigned Integer (2 bytes) Data
07 RECLOSE ORDER NUMBER Unsigned Integer (2 bytes) Data
05 00 PROCESS: dans versions >
06 00 SW MONITORING
01 Rst SAn Ix
02 SA2 IA Courier floating point Data
number
03 SA2 IB Courier floating point Data
number
04 SA2 IC Courier floating point Data
number
05 SW operation nb Unsigned Integer (2 bytes) Data
06 SW operation time Courier floating point 0.0 s Data
number
07 SW Closing time Courier floating point Data
number
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 57/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
08 00 TIME:
01 Date/Time IEC870 Time & Date Data
0E 00 CT RATIOS
01 Phase CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/9999/1
03 Neutral CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/9999/1
0F 00 SETTING GROUPS
01 Select setting group Unsigned Integer (2 bytes) 1* Setting 1/2
02 Group 1 visible Indexed String 0 : YES * Setting 0 (YES) / 1 (NO)
1 : NO
03 Group 2 visible Indexed String 0 : YES Setting 0 (YES) / 1 (NO)
1 : NO *
Protection Group n° 1
20 00 PHASE OVERCURRENT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I> Courier floating point 0.1 In * 2002=1 Setting 0.1/4.0/0.1
number
04 Temporisation Type Indexed String 0 0: definite time * 2002=1 Setting 0/2/1
1 1 : inverse time
2 2: RI curve
05 Curve type Indexed String 0 STI (CEI) * 2004=1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
06 TMS Courier floating point 0.025 * 2004=1 Setting 0.025/1.5/0.025
number
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 58/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
07 K Courier floating point 0.1 * 2004=2 Setting 0.1/10.0/0.005
number
08 Tempo I> Courier floating point 0.01 s * 2004=0 Setting 0/180.0/0.01
number
09 Tempo reset type Indexed String 0 : definite time 2004=1 and Setting 0/1
1 : inverse time 2005 >= 5
and 2005
<= 9
0A RTMS Courier floating point 0.025 * 2009 = 1 Setting 0.025/1.5/0.025
number
0B T RESET Courier floating point 0.04 * 2009 = 0 Setting 0.04/100/0.01
number
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I>> Courier floating point 0.50 In * 2011=1 Setting 0.5/40.0/0.05
number
13 Tempo I>> Courier floating point 0.01 s * 2011=1 Setting 0/180.0/0.01
number
14-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I>>> Courier floating point 0.50 In * 2021=1 Setting 0.5/40.0/0.05
number
23 Tempo I>>> Courier floating point 0.01 s * 2021=1 Setting 0/180.0/0.01
number
21 00 EARTH FAULT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I0> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I0> Courier floating point 0.01 I0n* 2102=1 Setting 0.01/1.0/0.005
number
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 59/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
04 Tempo Type Indexed String 0 0: definite time * 2102=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
05 Curve Type Indexed String 0 STI (CEI) * 2104=1 Setting 1/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
06 TMS Courier floating point 0.025 * 2104=1 Setting 0.025/1.5/0.025
number
07 K Courier floating point 0.1 * 2104=2 Setting 0.1/10.0/0.005
number
08 Tempo I0> Courier floating point 0.01 s * 2104=0 Setting 0/180.0/0.01
number
09 Tempo reset Type Indexed String 0 : definite time 2104=1 and Setting 0/1
1 : inverse time 2105 >= 5
and 2105
<= 9
0A RTMS Courier floating point 0.025 * 2109 = 1 Setting 0.025/3.2/0.025
number
0B T RESET Courier floating point 0.04 * 2109 = 0 Setting 0.04/100/0.01
number
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I0>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I0>> Courier floating point 0.01 I0n* 2111=1 Setting 0.01/8.0/0.005
number
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 60/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
13 Tempo I0>> Courier floating point 0.01 s * 2111=1 Setting 0/180.0/0.01
number
14-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I0>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I0>>> Courier floating point 0.01 I0n * 2121=1 Setting 0.01/8.0/0.005
number
23 Tempo I0>>> Courier floating point 0.01 s * 2121=1 Setting 0/180.0/0.01
number
22 00 THERMAL OVERLOAD
01 Ith> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Ith> Courier floating point 0.20 Ith* 2201=1 Setting 0.01/3.2/0.01
number
03 K Ith> Courier floating point 1.05 * 2201=1 Setting 1.0/1.50/0.01 In
number
04 θ TRIP Unsigned Integer (2 bytes) 100 % * 2201=1 Setting 50 / 200/ 1 %
05 θ ALARM ? Binary (1 bit) 0 Disabled * / Enabled 2201=1 Setting 0/1/1
06 θ ALARM Unsigned Integer (2 bytes) 90 % * 2205 =1 Setting 50 / 200/ 1 %
07 Thermal constant Unsigned Integer (2 bytes) 1* 2201=1 Setting 1/ 200 / 1 mn
23 00 MIN I<
01 I< Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold I< Unsigned Integer (2 bytes) 20 %In * 2301=1 Setting 2 / 100 / 1 %In
24 00 NEGATIVE CURRENT
01 Iinv> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Iinv> Courier floating point 0.1 In * 2401 = 1 Setting 0.1/40.0/0.01 In
number
03 Temporisation Type Indexed String 0 0: definite time * 2401 = 1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 61/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
04 Curve type Indexed String 0 STI (CEI) * 2401 = 1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
05 TMS Courier floating point 0.025 * 2403=1 Setting 0.025/1.5/0.025
number
06 K (RI) Courier floating point 0.1 * 2403=2 Setting 0.1/10.0/0.005
number
07 Tempo Iinv> Courier floating point 0.01 s * 2403=0 Setting 0/180.0/0.01
number
08 Reset tempo type Indexed String 0 : definite time 2403=1 and Setting 0/1/1
1 : inverse time 2404 >= 5
and 2404
<= 9
09 RTMS Courier floating point 0.025 * 2408 = 1 Setting 0.025/3.2/0.025
number
0A T RESET Courier floating point 0.04 * 2408 = 0 Setting 0.04/100/0.01
number
25 00 AUTORECLOSER
01 Autorecloser Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 State circuit breaker Binary (1 bit) Disabled * / Enabled 2501 = 1 Setting 0/1/1
03 Control window Courier floating point 0.01 s * 2502 = 1 Setting 0.01 / 600.00 / 0.01 s
number
04 External blocking Binary (1 bit) Disabled * / Enabled 2501 = 1 Setting 0/1/1
07 Temporisation cycle 1 Courier floating point 0.01 s * 2501 = 1 Setting 0.01 / 300.00 / 0.01 s
number
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 62/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
08 Temporisation cycle 2 Courier floating point 0.01 s * 2501 = 1 Setting 0.01 / 300.00 / 0.01 s
number
09 Temporisation cycle 3 Courier floating point 0.01 s * 2501 = 1 Setting 0.01 / 600.00 / 0.01 s
number
0A Temporisation cycle 4 Courier floating point 0.01 s * 2501 = 1 Setting 0.01 / 600.00 / 0.01 s
number
0B Reclaim TIME Courier floating point 0.02 s * 2501 = 1 Setting 0.02 / 600.00 / 0.01 s
number
0C Inhibition time Courier floating point 0.02 s * 2501 = 1 Setting 0.02 / 600.00 / 0.01 s
number
0D Number of short circuit cycle Unsigned Integer (2 bytes) 0* 2501 = 1 Setting 0/4/1
0E Number of earth fault cycle Unsigned Integer (2 bytes) 0* 2501 = 1 Setting 0/4/1
0F Cycles tI> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
10 Cycles tI>> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
11 Cycles tI>>> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
12 Cycles tI0> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
13 Cycles tI0>> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
14 Cycles tI0>>> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
15 Cycles tAux1> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
16 Cycles tAux2> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4 bit
group
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 63/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
Protection Group n° 2
40 00 PHASE OVERCURRENT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I> Courier floating point 0.1 In * 4002=1 Setting 0.1/4.0/0.01
number
04 Tempo Type Indexed String 0 0: definite time * 4002=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
05 Curve Type Indexed String 0 STI (CEI) * 4004=1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
06 TMS Courier floating point 0.025 * 4004=1 Setting 0.025/1.5/0.025
number
07 K Courier floating point 0.1 * 4004=2 Setting 0.1/10.0/0.005
number
08 Tempo I> Courier floating point 0.01 s * 4004=0 Setting 0/180.0/0.01
number
09 Reset tempo type Indexed String 0 : definite time 4004=1 and Setting 0/1
1 : inverse time 4005 >= 5
and 4005
<= 9
0A RTMS Courier floating point 0.025 * 4009 = 1 Setting 0.025/1.5/0.025
number
0B T RESET Courier floating point 0.04 * 4009 = 0 Setting 0.04/100.0/0.01
number
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 64/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I>> Courier floating point 0.50 In * 4011=1 Setting 0.5/40.0/0.05
number
13 Tempo I>> Courier floating point 0.01 s * 4011=1 Setting 0/180.0/0.01
number
14-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I>>> Courier floating point 0.50 In * 4021=1 Setting 0.5/40.0/0.05
number
23 Tempo I>>> Courier floating point 0.01 s * 4021=1 Setting 0/180.0/0.01
number
41 00 EARTH FAULT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I0> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I0> Courier floating point 0.01 I0n* 4102=1 Setting 0.01/1.0/0.005
number
04 Temporisation Type Indexed String 0 0: definite time * 4102=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
05 Curve type Indexed String 0 STI (CEI) * 4104=1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 65/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
06 TMS Courier floating point 0.025 * 4104=1 Setting 0.025/1.5/0.025
number
07 K Courier floating point 0.1 * 4104=2 Setting 0.1/10.0/0.005
number
08 Tempo I0> Courier floating point 0.01 s * 4104=0 Setting 0/180.0/0.01
number
09 Tempo reset Type Indexed String 0 : definite time 4104=1 and Setting 0/1
1 : inverse time 4105 >= 5
and 4105
<= 9
0A RTMS Courier floating point 0.025 * 4109 = 1 Setting 0.025/3.2/0.025
number
0B T RESET Courier floating point 0.04 * 4109 = 0 Setting 0.04/100.0/0.01
number
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I0>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I0>> Courier floating point 0.01 I0n* 4111=1 Setting 0.01/8.0/0.005
number
13 Tempo I0>> Courier floating point 0.01 s * 4111=1 Setting 0/180.0/0.01
number
14-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I0>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I0>>> Courier floating point 0.01 I0n * 4121=1 Setting 0.01/8.0/0.005
number
23 Tempo I0>>> Courier floating point 0.01 s * 4121=1 Setting 0/180.0/0.01
number
42 00 THERMAL OVERLOAD
01 Ith> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 66/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
02 Threshold Ith> Courier floating point 0.20 Ith* 4201=1 Setting 0.01/3.2/0.01
number
03 K Ith> Courier floating point 1.05 * 4201=1 Setting 1.0/1.50/0.01 In
number
04 θ TRIP Unsigned Integer (2 bytes) 100 % * 4201=1 Setting 50 / 200/ 1 %
05 θ ALARM ? Binary (1 bit) 0 Disabled * / Enabled 4201=1 Setting 0/1/1
06 θ ALARM Unsigned Integer (2 bytes) 90 % * 4205 =1 Setting 50 / 200/ 1 %
07 Thermal constant Unsigned Integer (2 bytes) 1* 4201=1 Setting 1/ 200 / 1 mn
43 00 MIN I<
01 I< Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold I< Unsigned Integer (2 bytes) 20 %In * 4301=1 Setting 2 / 100 / 1 %In
44 00 NEGATIVE CURRENT
01 Iinv> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Iinv> Courier floating point 0.1 In * 4401 = 1 Setting 0.1/40.0/0.1 In
number
03 Temporisation type Indexed String 0 0: definite time * 4401 = 1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
04 Curve Type Indexed String 0 STI (CEI) * 4401=1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
05 TMS Courier floating point 0.025 * 4403=1 Setting 0.025/1.5/0.025
number
06 K (RI) Courier floating point 0.1 * 4403=2 Setting 0.1/10.0/0.005
number
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 67/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
07 Tempo Iinv> Courier floating point 0.01 s * 4403=0 Setting 0/180.0/0.01
number
08 Temporisation reset type Courier floating point 0 : definite time 4403=1 and Setting 0/1/1
number 1 : inverse time 4404 >= 5
and 4404
<= 9
09 RTMS Courier floating point 0.025 * 4408=1 Setting 0.025/3.2/0.025
number
0A T RESET Courier floating point 0.04 * 4408=0 Setting 0.04/100.0/0.01
number
45 00 AUTORECLOSER
01 Autorecloser Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 State circuit breaker Binary (1 bit) Disabled * / Enabled 4501 = 1 Setting 0/1/1
03 Control window Courier floating point 0.01 s * 4502 = 1 Setting 0.01 / 600.00 / 0.01 s
number
04 External blocking Binary (1 bit) Disabled * / Enabled 4501 = 1 Setting 0/1/1
07 Temporisation cycle 1 Courier floating point 0.01 s * 4501 = 1 Setting 0.01 / 300.00 / 0.01 s
number
08 Temporisation cycle 2 Courier floating point 0.01 s * 4501 = 1 Setting 0.01 / 300.00 / 0.01 s
number
09 Temporisation cycle 3 Courier floating point 0.01 s * 4501 = 1 Setting 0.01 / 600.00 / 0.01 s
number
0A Temporisation cycle 4 Courier floating point 0.01 s * 4501 = 1 Setting 0.01 / 600.00 / 0.01 s
number
0B Reclaim TIME Courier floating point 0.02 s * 4501 = 1 Setting 0.02 / 600.00 / 0.01 s
number
0C Inhibition time Courier floating point 0.02 s * 4501 = 1 Setting 0.02 / 600.00 / 0.01 s
number
0D Number of short circuit cycle Unsigned Integer (2 bytes) 0* 4501 = 1 Setting 0/4/1
0E Number of earth fault cycle Unsigned Integer (2 bytes) 0* 4501 = 1 Setting 0/4/1
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 68/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
0F Cycles tI> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
10 Cycles tI>> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
11 Cycles tI>>> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
12 Cycles tI0> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
13 Cycles tI0>> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
14 Cycles tI0>>> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
15 Cycles tAux1> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
16 Cycles tAux2> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4 bit
group
60 00 AUTOMATISM
01 Trip Configuration Binary (16 bits) 1* Setting 0/65535/1
02 Latched Configuration Binary (16 bits) 0* Setting 0/65535/1
03 Blocking 1 Configuration Binary (16 bits) 0* Setting 0/65535/1
04 Blocking 2 Configuration Binary (16 bits) 0* Setting 0/65535/1
05 Broken conductor detection Binary (1 bit) Disabled * / Enabled Setting 0/1/1
06 Tempo tBC Unsigned Integer (2 bytes) 0* 6005 = 1 Setting 0/144.0/0.01 s
07 Threshold mod iinv/idirect in % Courier floating point 20 % * 6005 = 1 Setting 20/100/1 %
number
08 Cold load start Binary (1 bit) Disabled * / Enabled Setting 0/1/1
09 Threshold of cold load start Binary (8 bits) 0* 6008 = 1 Setting 0/255/1
0A % of cold load start Unsigned Integer (2 bytes) 50 % * 6008 = 1 Setting 20/500/1
0B Cold load start Tempo Courier floating point 1.0 s * 6008 = 1 Setting 0.1/3600.0/0.1 s
number
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 69/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
0C Breaker failure Binary (1 bit) Disabled * / Enabled Setting 0/1/1
0D I< Threshold for Breaker failure Courier floating point 20 % * 600C = 1 Setting 2/100/1 %
number
0E Tempo tBF Unsigned Integer (2 bytes) 0.1 s * 600C = 1 Setting 0/10.0/0.01 s
0F Phase instant blocking Binary (1 bit) Disabled * / Enabled 600C = 1 Setting 0/1/1
10 Earth instant blocking Binary (1 bit) Disabled * / Enabled 600C = 1 Setting 0/1/1
11 logic selectivity 1 Binary (4 bits) Setting 0/15/1
12 Tempo sélectivity1 Courier floating point 6011 = 1 Setting 0/150.0/0.01 s
number
13 logic selectivity 2 Binary (4 bits) Setting 0/15/1
14 Tempo sélectivity 2 Courier floating point 6013 = 1 Setting 0/150.0/0.01 s
number
61 00 AFFECTATION DES TS
01 Logical input allocation 1 Indexed String 0 0: nothing * Setting 0/16/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: external CB failure
5 5: External input 1
6 6: External input 2
7 7 : Logic blocking 1
8 8 : Logic blocking 2
9 9 : Disturbance start
10 10 : Cold load start
11 11 : Log Selectivity 1
12 12 : Log Selectivity 2
13 13 : Change of group
14 14 : Recloser locked
15 15 : Thermal reset
16 16 : Trip circuit
supervision
02 Logical input allocation 2 Indexed String 0 0: nothing * Setting 0/16/1
1 1: delatch
2 2: 52 a
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 70/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
3 3: 52 b
4 4: external CB failure
5 5: External input 1
6 6: External input 2
7 7 : Logic blocking 1
8 8 : Logic blocking 2
9 9 : Disturbance start
10 10 : Cold load start
11 11 : Log Selectivity 1
12 12 : Log Selectivity 2
13 13 : Change of group
14 14 : Recloser locked
15 15 : Thermal reset
16 16 : Trip circuit
supervision
03 Logical input allocation 3 Indexed String 0 0: nothing * Setting 0/16/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: external CB failure
5 5: External input 1
6 6: External input 2
7 7 : Logic blocking 1
8 8 : Logic blocking 2
9 9 : Disturbance start
10 10 : Cold load start
11 11 : Log Selectivity 1
12 12 : Log Selectivity 2
13 13 : Change of group
14 14 : Recloser locked
15 15 : Thermal reset
16 16 : Trip circuit
supervision
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 71/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
04 Logical input allocation 4 Indexed String 0 0: nothing * Setting 0/16/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: external CB failure
5 5: External input 1
6 6: External input 2
7 7 : Logic blocking 1
8 8 : Logic blocking 2
9 9 : Disturbance start
10 10 : Cold load start
11 11 : Log Selectivity 1
12 12 : Log Selectivity 2
13 13 : Change of group
14 14 : Recloser locked
15 15 : Thermal reset
16 16 : Trip circuit
supervision
05 Logical input allocation 5 Indexed String 0 0: nothing * Setting 0/16/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: external CB failure
5 5: External input 1
6 6: External input 2
7 7 : Logic blocking 1
8 8 : Logic blocking 2
9 9 : Disturbance start
10 10 : Cold load start
11 11 : Log Selectivity 1
12 12 : Log Selectivity 2
13 13 : Change of group
14 14 : Recloser locked
15 15 : Thermal reset
16 16 : Trip circuit
supervision
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 72/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
06 Timer aux 1 Setting 0/200.0/0.01
07 Timer aux 2 Setting 0/200.0/0.01
62 00 CT ALLOCATION
01 GENERAL TRIP Binary (5 bits) 00000 * Setting 0/31/1
02 I> Binary (5 bits) 00000 * Setting 0/31/1
03 tI> Binary (5 bits) 00000 * Setting 0/31/1
04 I>> Binary (5 bits) 00000 * Setting 0/31/1
05 t I>> Binary (5 bits) 00000 * Setting 0/31/1
06 I>>> Binary (5 bits) 00000 * Setting 0/31/1
07 t I>>> Binary (5 bits) 00000 * Setting 0/31/1
08 I0> Binary (5 bits) 00000 * Setting 0/31/1
09 t I0> Binary (5 bits) 00000 * Setting 0/31/1
0A I0>> Binary (5 bits) 00000 * Setting 0/31/1
0B t I0>> Binary (5 bits) 00000 * Setting 0/31/1
0C I0>>> Binary (5 bits) 00000 * Setting 0/31/1
0D t I0>>> Binary (5 bits) 00000 * Setting 0/31/1
0E t I< Binary (5 bits) 00000 * Setting 0/31/1
0F t Iinv> Binary (5 bits) 00000 * Setting 0/31/1
10 Thermal alarm Binary (5 bits) 00000 * Setting 0/31/1
11 Thermal trip Binary (5 bits) 00000 * Setting 0/31/1
12 Breaker alarm Binary (5 bits) 00000 * Setting 0/31/1
13 Trip circuit alarm Binary (5 bits) 00000 * Setting 0/31/1
14 Broken conductor Binary (5 bits) 00000 * Setting 0/31/1
15 Breaker failure Binary (5 bits) 00000 * Setting 0/31/1
16 Reclosing Binary (5 bits) 00000 * Setting 0/31/1
17 TAux 1 Binary (5 bits) 00000 * Setting 0/31/1
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 73/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
18 TAux 2 Binary (5 bits) 00000 * Setting 0/31/1
19 Autoreclose in progress Binary (5 bits) 00000 * Setting 0/31/1
1A Definitive trip Binary (5 bits) 00000 * Setting 0/31/1
63 00 LEDs CONFIGURATION
01 Led 5 Binary (16 bits) 4* Setting 0/65535/1
02 Led 6 Binary (16 bits) 16 * Setting 0/65535/1
03 Led 7 Binary (16 bits) 32 * Setting 0/65535/1
04 Led 8 Binary (16 bits) 64 * Setting 0/65535/1
05 Led PF5 Binary (9 bits) 0* Setting 0/511/1
06 Led PF6 Binary (9 bits) 0* Setting 0/511/1
07 Led PF7 Binary (9 bits) 0* Setting 0/511/1
08 Led PF8 Binary (9 bits) 0* Setting 0/511/1
69 00 SW SUPERVISION
01 Trip circuit supervision ? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Trip circuit time ? Courier floating point 0.1 s * 6901 = 1 Setting 0.1/10.0/0.05 s
number
03 SW Operating time? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
04 SW Operating time Courier floating point 0.05 s* 6903 = 1 Setting 0.05/1.0/0.01 s
number
05 SW Operating number? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
06 SW Closing time ? Courier floating point 0.05 s* 6905 = 1 Setting 0.05/1.0/0.01 s
number
07 SW Closing time Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
08 SW Operating number Unsigned Integer (2 bytes) 0* 6907 = 1 Setting 0/50000/1
09 SA2n? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
0A Sa2n Courier floating point 0 exp+06 A² * 6909 = 1 Setting 0/4000/1 (*exp+06)
number
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 74/98 MiCOM P124
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
0B n Unsigned Integer (2 bytes) 1* Setting 1/2/1
0C TRIP t Courier floating point 0.1 s* Setting 0.1/5.0/0.05 s
number
0D CLOSE t Courier floating point 0.1 s* Setting 0.1/5.0/0.05 s
number
80 00 DISTURBANCE REC
01 Record Number Unsigned integer (1 byte) 0* Setting 0/5/1 (selon contexte)
02 Trigger Time IEC870 Time & Date dd/mm/yy hh:mm Data
03 Available Channel Bit Mask Binary Flag 11111 Data
Indexed String 0 “ Ia ”
1 “ Ib ”
2 “ Ic ”
3 “ I0 ”
4 “ Inputs/Outputs ”
04 Channel Types Binary Flag 0: digital, 1: 01111 Data
analogue
05 Channel Offsets Repeated group of Courier Upload Offsets Data
numbers
06 Scaling Factors Repeated group of Courier Upload Scal. Factors Data
numbers
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 75/98
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
07-0F NON IMPLEMENTE - réservé
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(* : default)
number
0A In Magnitude Courier floating point 12.34 A Data
number
Cell
Code Cell text
reference
00 UNKNOWN EVENT -
01 TC CLOSE 0
02 TC TRIP 0
03 DIST TRIG 0
04 UNLOCK TRIP 0
05 SET. CHANGE 0
06 RESET THERM 0
07 SET MAINT MODE 0
08 SET RELAY MAINT MODE 0021
09 I> 0023
10 I>> 0023
11 I>>> 0023
12 IE> 0023
13 IE>> 0023
14 IE>>> 0023
15 TH. ALARM 0023
16 TH OVERLOAD 0023
17 tI> 0023
18 tI>> 0023
19 tI>>> 0023
20 tlE> 0023
21 tlE>> 0023
22 tlE>>> 0023
23 tI< 0023
24 BROKEN CONDUCTOR 0024
25 t Aux1 0024
26 t Aux2 0024
27 BREAKER FAILURE 0024
28 Logic Sel. 1 0020
29 Logic Sel. 2 0020
30 Blocking Logic 1 0020
31 Blocking Logic 2 0020
32 Setting group change 0020
33 52 a 0020
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 78/98 MiCOM P124
Cell
Code Cell text
reference
34 52 b 0020
35 ACK RELAY LATCHED ( by Input) 0020
36 External failure from the CB 0020
37 COLD LOAD PICKUP 0020
38 TS Change 0020
39 TRIP : TH OVERLOAD 0
40 TRIP : tI> 0
41 TRIP : tI>> 0
42 TRIP : tI>>> 0
43 TRIP : tlE> 0
44 TRIP : tlE>> 0
45 TRIP : tlE>>> 0
46 TRIP : tI< 0
47 TRIP : BROKEN CONDUCTOR 0
48 TRIP : t Aux 1 0
49 TRIP : t Aux 2 0
50 Output relays change 0021
51 ACK 1 ALARM (FRONT) 0
52 ACK ALARMS (FRONT) 0
53 ACK 1 ALARM (COM) 0
54 ACK ALARMS (COM) 0
55 Major material alarm 0022
56 Minor material alarm 0022
57 I2 > 0024
58 t2> 0024
59 OPEN OPERATING TIME 0024
60 TRIP OPERATION Nb 0024
61 SA2N 0024
62 TRIP CIRCUIT SUPERVISION 0024
63 CLOSE OPERATING TIME 0024
64 SUCCESS AUTORECLOSE 0024
65 LOCKED AUTORECLOSER 0024
66 AUTORECLOSER CONF. FAIL 0024
67 TRIP : t I2 > 0
NOTA : When the cell reference is different of zero this means that the
event is generated on event occurrence and another is generated
on event disappearance.
Technical Guide P124/EN T08/B44
Communication Database CHAPTER 8
MiCOM P124 Page 79/98
When the cell reference is equal to zero, only the event on edging edge is generated.
Twelve bits are available in the string of characters to describe the contain of the
Courier cell:
On event occurrence, the corresponding bit of the associated format is set to « 1 ».
On event disappearance, the corresponding bit of the associated format is set to
« 0 ».
3.3 Setting changes
This uses a combination of three commands to perform a settings change:
Enter Setting Mode - checks that the cell is settable and returns the limits
Preload Setting - Places a new value to the cell, this value is echoed to ensure that
setting corruption has not taken place, the validity of the setting is not checked by this
action.
Execute Setting - Confirms the setting change, if the change is valid then a positive
response will be returned, if the setting change fails then an error response will be
returned.
Abort Setting - This command can be used to abandon the setting change.
This is the most secure method and is ideally suited to on-line editors as the setting
limits are taken from the relay before the setting change is made. However this
method can be slow if many settings are being changed as three commands are
required for each change.
3.4 Systems integration data
3.4.1 Address of the relay
The relays can have any address between 1 and 254 included. The address 255
corresponds to the global address to which all relays and all the other slave
peripheries are responding. The Courier protocol specifies that no response can be
resent from a slave periphery to a global message. This permits to avoid that all
peripheries respond at the same time creating by this way user conflict on the Bus.
Each relay possess an address settled on 255 in order to guarantee that in case of his
connection to the operating network, his address cannot create any conflict with the
address of another periphery already in exploitation. In order to permit to a new
periphery to get entirely operational, his address has to be settled. The address can
be modified manually in capturing the password, than in following the method of the
setting change through the user interface on the front plate of the relay.
The same, if the network functioning on a computer takes in charge the auto-
addressing, the relay address can be settled on 0 to active the characteristic of auto-
addressing of the computer software. The relay receives then the next valid address
on the Bus.
If the address is 255 or not known, she can be modified in sending a new address,
with a global message, to a periphery possessing a particular serial number. This
method is used for those peripheries which are not having any user interface for
reading or changing the address in process.
3.4.2 Measured values
Each measured value can be periodically extracted by a selective call of MiCOM
P124 relay.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 80/98 MiCOM P124
4. IEC60870-5-103 INTERFACE
The IEC60870-5-103 interface is a master/slave interface with the relay as the slave
device. This protocol is based on the VDEW communication protocol. The relay
conforms to compatibility level 2, compatibility level 3 is not supported.
The following IEC60870-5-103 facilities are supported by this interface:
• Initialisation (Reset)
• Time Synchronisation
• Event Record Extraction
• General Interrogation
• Cyclic Measurements
• General Commands
4.1 Physical connection and link layer
Connection is available for IEC60870-5-103 through the rear RS485 port. It is
possible to select both the relay address and baud rate using the front panel
interface. Following a change, a reset command is required to re-establish
communications.
The parameters of the communication are the following :
• Even Parity
• 8 Data bits
• 1 stop bit
• Data rate 9600 or 19200 bauds
4.2 Initialisation
Whenever the relay has been powered up, or if the communication parameters have
been changed a reset command is required to initialise the communications. The
relay will respond to either of the two reset commands (Reset CU or Reset FCB), the
difference being that the Reset CU will clear any unsent messages in the relay's
transmit buffer.
The relay will respond to the reset command with an identification message ASDU 5,
the Cause Of Transmission COT of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command. The following information will be
contained in the data section of this ASDU:
Manufacturer Name: Schneider Electric
The Software Identification Section will contain the first four characters of the relay
model number to identify the type of relay, eg P124.
In addition to the above identification message, if the relay has been powered up it
will also produce a power up event.
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 84/98 MiCOM P124
NOTA : The italics events are only valid for the MiCOM P124.
The double arrow ↓↑ means the event is generated on event
occurrence and another is generated on event disappearance.
• List of data contained in General Interrogation
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 86/98 MiCOM P124
• the Point List Tables provided in Section 5.4 (beginning on page 69),
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 0, beginning on page 66.)
Vendor Name: Schneider Electric
Device Name: SERIAL 20 Platform using the Triangle MicroWorks, Inc. DNP 3.0 Slave Source
Code Library, Version 2.18.
Highest DNP Level Supported: Device Function:
For Requests: Level 2 7 Master
For Responses: Level 2
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-stop),
07 and 08 (limited quantity), and 17 and 28 (index) are supported in addition to request
qualifier code 06 (no range – or all points).
Static object requests received with qualifiers 00, 01, 06, 07, or 08, will be responded with
qualifiers 00 or 01. Static object requests received with qualifiers 17 or 28 will be responded
with qualifiers 17 or 28.
For change-event object requests, qualifiers 17 or 28 are always responded.
16-bit and 32-bit Analog Change Events with Time may be requested.
The read function code for Object 50 (Time and Date), variation 1, is supported.
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: 2048
Received 292 Received: 2048
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 88/98 MiCOM P124
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 0, beginning on page 66.)
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 0, beginning on page 66.)
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:
" Never " Never
Configurable When Device Restarts
Only certain objects When Status Flags Change
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED No other options are permitted.
Function codes supported
20 6 16-Bit Binary Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag 7 (freeze) 06 (no range, or all) 17, 28 (index–see
8 (freeze noack) 07, 08 (limited qty) note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
21 1 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
21 2 16-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
21 9 32-Bit Frozen Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag 06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
21 10 16-Bit Frozen Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag 06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – see 06 (no range, or all) 17, 28 (index–see
note 1) 07, 08 (limited qty) note 2)
17, 28 (index)
30 3 32-Bit Analog Input without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag 06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
30 4 16-Bit Analog Input without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Flag 06 (no range, or all) 17, 28 (index–see
07, 08 (limited qty) note 2)
17, 28 (index)
32 1 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty)
32 2 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – see without Time 07, 08 (limited qty)
note 1)
32 3 32-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty)
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 92/98 MiCOM P124
50 0 Time and Date 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index – see
07, 08 (limited qty) note 2)
17, 28 (index)
50 1 Time and Date 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
default – see 2 (write) 06 (no range, or all) 17, 28 (index – see
note 1) 07, 08 (limited qty) note 2)
17, 28 (index)
1 Output r elay 2 0 2
2 Output r elay 3 0 2
3 Output r elay 4 0 2
5 Output r elay 5 0 2
6 Output r elay 6 0 2
9 Opto isolator 1 0 2
10 Opto isolator 2 0 2
11 Opto isolator 3 0 2
12 Opto isolator 4 0 2
13 Opto isolator 5 0 2
26 tI< 0 1
27 thermal start 0 1
28 thermal trip 0 1
29 taux1 0 1
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 94/98 MiCOM P124
31 broken conductor 0 1
32 cb failure 0 1
33 I2> start 0 1
34 tI2> trip 0 1
35 number of cb operation 0 1
37 sa2n 0 1
40 Recloser locked 0 1
41 Recloser success 0 1
42 Recloser running 0 1
43 Logic selectivity 1 0 1
44 Logic selectivity 2 0 1
45 Blocking logic 1 0 1
46 Blocking logic 2 0 1
47 52a 0 1
48 52b 0 1
49 CB external failure 0 1
56 Maintenance mode 0 1
78 Conflict recloser 0 3
P124/EN T08/B44 Technical Guide
CHAPTER 8 Communication Database
Page 96/98 MiCOM P124
5.4.2 Binary Output Status Points and Control Relay Output Blocks
The following table lists both the Binary Output Status Points (Object 10) and the
Control Relay Output Blocks (Object 12).
Binary Output Status points are not included in class 0 polls.
5.4.3 Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters
(Object 21). When a freeze function is performed on a Binary Counter point, the
frozen value is available in the corresponding Frozen Counter point.
Binary Counters and Frozen Counters are not included in class 0 polls.
P120 and P121 do not support binary Counters and Frozen Counters.
Binary Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: not supported
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack)
9 (freeze and clear), 10 (freeze and clear, noack)
Static Variation reported when variation 0 requested: 5 (32-Bit Binary Counter without Flag
Change Event Variation reported when variation 0 requested: none-not supported
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number: not supported
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 9 (32-Bit Frozen Binary without Flag)
Change Event Variation reported when variation 0 requested: none-not supported
Point
Name/Description Data type
Index
0 Max I a R ms D1
1 Max I b R ms D1
2 Max I c R ms D1
3 Average I a R ms D1
4 Average I b R ms D1
5 Average I c R ms D1
6 CB operations D2
7 Σ Amps (n) Ia D3
8 Σ Amps (n) Ib D3
9 Σ Amps (n) Ic D3
11 cycle 1 number D2
12 cycle 2 number D2
13 cycle 3 number D2
14 cycle 4 number D2
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 2 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 2 (Analog Change Event w/o Time)
Change Event Scan Rate: The scan rate for analog input change events is fixed at 1s
Scaling and Units Initial Change Event
Point Initial Change Event
Name/Description (representation of Valid Range Class (1, 2, 3 or
Index Value Dead-band
32767 – see above) none)
1 module IA 0 40 In 0 to 40 In 0.1 In 2
2 module IB 0 40 In 0 to 40 In 0.1 In 2
3 module IC 0 40 In 0 to 40 In 0.1 In 2
11 module I2 0 40 In 0 to 40 In 0.1 In 2
12 module I1 0 40 In 0 to 40 In 0.1 In 2
MiCOM P124
APPENDIX 1
Connection diagrams
A
P2 P1
Alternative : 3 phase CTs + core balanced CT connection A 3 phase CTs connection
B S2 S1
P2 P1 C B
A Phase rotation C
S2 S1
B 49
C 37
S2 S1
49 1 A ou 5A
RL0 35
1 A ou 5A 50 36
Watchdog
MICOM P124
50
44
Technical Guide
42 Trip output
51 51 RL1 for CB coil
1 A ou 5A
40
1 A ou 5A
52
39
52
Connection Diagrams
+ Trip output
53 41 for striker
1 A ou 5A
-
54
53
1 A ou 5A
56 54
1 A ou 5 A
55
- 48
1 A ou 5 A
56
47
-
55
48
1 A ou 5 A
47
-
51 33 34
1 A ou 5A 35 36
39 40
53
41 42
Typical application diagram
1 A ou 5A
54
43 44
Notes :
45 46
MiCOM P124 Self-powered model
56 (1) (a) CT shorting links mode before (b) and (c) disconnect
47 48
1 A ou 5 A
55 49 50 (b) Short terminals break before (c)
- 48
51 52 (c) Long terminals
47
53 54 (d) Pins terminals (p c b type)
55 56
(2) CT connections are typical only
APPENDIX 1
Page 1/6
P124/EN TA1/B44
P124/EN TA1/B44 Technical Guide
APPENDIX 1 Connection Diagrams
Page 2/6 MiCOM P124
NC 29 30 NC
NC 31 32 NC
NC 33 34 NC
P2 P1
A C C
B 49
B S2 S1 Phase rotation
C 37
S2 S1
49
1A or 5A
50 RL0 35 Watchdog
1A or 5A 36
50
MICOM P124
44
51 Trip output
51
42
contact for CB coil
Technical Guide
RL1
1A or 5A 40
1A or 5A 6
52 Programmeble
52 4
RL2 output
2
12
Connection Diagrams
Programmeble
53 53 10
RL3 output
1A or 5A 8
54
1A or 5A 22
Programmeble
54 20
RL4 output
18
56 28
Programmeble
1A or 5A 26 output
56 RL5
55 24
- 48 5
Programmeble
1A or 5A 55 3 output
RL6 1
47 48
1A or 5A
-
47 39 + Trip output
- for striker
9+ P124 41 -
Programmable input L1 11-
13+ Dual-powered
Programmable input L2 15- Case earth
17+
model 29 connection
Programmable input L3 19-
21+ * 30
Alternative : 3 phase CTs + core balanced CT connection. Programmable input L4 +
23- 31 RS 485
25+ - communication port
P2 P1
A Programmable input L5 32
S2 S1
27-
B
C 33 34
S2 S1
49
+ -
1A or 5A Auxiliary (*) terminating resistor for the last
50 Module terminal block supply relay to be connected between
viewed from rear 30-32
51
1 2 29 30
1A or 5A
53
7 8 35 36
9 37 38
Typical application diagram
1A or 5A 10
54 11 39 40
12
13 14 41 42
56
15 16 43 44
MiCOM P124 Dual-powered model
1A or 5A
55 17 18 45 46 Notes :
- 48 19 20 47 48 (1) (a) CTs shorting links mode
1A or 5A before (b) and (c) disconnect
21 22 49 50
47 (b) Short terminals break before (c)
23 24 51 52
(c) Long terminals
25 26 53 54 (d) Pins terminals (p c b type)
27 28 55 56
(2) CT connections are typical only
APPENDIX 1
Page 3/6
P124/EN TA1/B44
P124/EN TA1/B44 Technical Guide
APPENDIX 1 Connection Diagrams
Page 4/6 MiCOM P124
0V (to be linked to the earth case) 29 30 RS485 terminating resistor for the last relay
RS485+ 31 32 RS485 -
NC : no connected
(1) the current inputs are 1 or 5A and defined on ordering code
(2) inputs used when it is necessary to power the MiCOM P124 relay via the earth
current input.
Technical Guide P124/EN TA1/B44
Connection Diagrams APPENDIX 1
MICOM P124 Page 5/6
NC 7 8 Common RL3
BLANK PAGE
Technical Guide P124/EN TA2/B44
MiCOM P124
APPENDIX 2
Commissioning Test and Record
Sheets
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 1/32
CONTENT
BLANK PAGE
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 3/32
1. COMMISSIONING TEST SHEETS
1.1 Relay identification
Commissioning date : ________________________________________________
Engineer : ________________________________________________
Substation : ________________________________________________
Circuit : ________________________________________________
Rated frequency : ________________________________________________
Watchdog contacts
Frequency: ! 50 Hz ! 60 Hz
I> ? ! YES ! NO
I> In
tI> ms
2.1.3.1.A.B [51] I> IDMT
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
2.1.3.1.A.C [51] I> DMT reset time
t Reset ms
2.1.3.1.A.D [51] I> IDMT reset time
Rtms
2.1.3.1.A.E [51] I> RI
K
t Reset ms
I>> ? ! YES ! NO
I>> In
tI>> ms
I>>> ? ! YES ! NO
I>>> In
tI>>> ms
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 9/32
2.1.3.2 Earth Overcurrent [50N/51N]
le> ? ! YES ! NO
le> len
tle> ms
2.1.3.2.A.B [51N] Ie > IDMT
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
2.1.3.2.A.C [51N] Ie> DMT reset time
t Reset ms
2.1.3.2.A.D [51N] Ie> IDMT reset time
Rtms ms
2.1.3.2.A.E [51N] Ie> RI
K
t Reset ms
le>> ? ! YES ! NO
Ie>> Ien
tIe>> ms
Ie>>> ? ! YES ! NO
Ie>>> Ien
tIe>>> ms
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 10/32 MiCOM P124
2.1.3.3 [49] THERMAL OVERLOAD
Therm OL ? ! YES ! NO
Iθ > In
Te ms
k
θ Trip %
θ Alarm ? ! YES ! NO
θ Alarm %
Time Window mn
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 11/32
2.2 MiCOM P124 Dual-powered model
2.2.1 OP PARAMETERS Menu
Password : ________________________________________
Reference : ________________________________________
Software version : ________________________________________
Frequency: ! 50 Hz ! 60 Hz
2.2.2.1 Display
Phase A Text ! A ! L1 ! R
Phase B Text ! B ! L2 ! S
Phase C Text ! C ! L3 ! T
E/Gnd Text ! N ! E ! G
2.2.2.2 CT Ratio
Instantaneous alarm :
self-reset operation ! YES ! NO
Display of alarm battery
message in case of battery
or backed RAM memory ! YES ! NO
failure
2.2.2.7 Configuration of the input mode operation
EL 5 4 3 2 1
Inputs
! ! ! ! !
2.2.2.8 Format of the Modbus date
Communication ? ! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ? ! YES ! NO
Relay Address
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 14/32 MiCOM P124
2.2.3.3 COMMUNICATION Menu (IEC 60870-5-103)
Communication ? ! YES ! NO
Baud Rate
! 1 200 bds ! 2 400 bds
Communication ? ! YES ! NO
Baud Rate
! 1 200 bds ! 2 400 bds
l> ? ! YES ! NO
l> ln
tl> ms
2.2.4.1.A.B [51] I> IDMT
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 15/32
2.2.4.1.A.C [51] I> DMT reset time
t Reset ms
2.2.4.1.A.D [51] I> IDMT reset time
Rtms
2.2.4.1.A.E [51] I> RI
K
t Reset ms
I>> ? ! YES ! NO
I>> In
tI>> ms
I>>> ? ! YES ! NO
I>>> In
tI>>> ms
le> ? ! YES ! NO
le> len
tle> ms
2.2.4.2.A.B [51N] Ie > IDMT
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 16/32 MiCOM P124
2.2.4.2.A.C [51N] Ie> LABOR.
Idmt ! 1 ! 2 ! 3
t Reset ms
2.2.4.2.A.E [51N] Ie> IDMT reset time
Rtms
2.2.4.2.A.F [51N] Ie> RI
K
t Reset ms
Ie>> ? ! YES ! NO
Ie>> Ien
tIe>> ms
Ie>>> ? ! YES ! NO
Ie>>> Ien
tIe>>> ms
I< ? ! YES ! NO
I< %
tI< ms
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 17/32
2.2.4.5 [46] Negative phase sequence overcurrent I2>
I2> ? ! YES ! NO
I2> In
tI2> ms
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 18/32 MiCOM P124
2.2.4.6 [79] AUTORECLOSER (OPTION)
I> ? ! YES ! NO
I> In
tI> ms
2.2.5.1.A.B [51] I> IDMT
Idmt
! IEC SI ! IEC STI ! IEC RC
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
2.2.5.1.A.C [51] I> DMT reset time
t Reset ms
2.2.5.1.A.D [51] I> IDMT reset time
Rtms
2.2.5.1.A.E [51] I> RI
K
t Reset ms
2.2.5.1.B [51] I>>
I>> ? ! YES ! NO
I>> In
tI>> ms
2.2.5.1.C [51] I>>>
I>>> ? ! YES ! NO
I>>> In
tI>>> ms
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 20/32 MiCOM P124
Ie> ? ! YES ! NO
Ie> Ien
tIe> ms
2.2.5.2.A.B [51N] Ie > IDMT
Idmt
! IEC SI ! IEC STI ! IEC RC
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
2.2.5.2.A.C [51N] Ie> LABOR.
Idmt ! 1 ! 2 ! 3
t Reset ms
2.2.5.2.A.E [51N] Ie> IDMT reset time
Rtms
2.2.5.2.A.F [51N] Ie> RI
K
t Reset ms
Ie>> ? ! YES ! NO
Ie>> len
tIe>> ms
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 21/32
2.2.5.2.C [51N] Ie >>>
Ie>>> ? ! YES ! NO
Ie>>> len
tIe>>> ms
2.2.5.3 [49] THERMAL OVERLOAD
I< ? ! YES ! NO
I< %
tI< ms
I2> ? ! YES ! NO
I2> In
tI2> ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 22/32 MiCOM P124
2.2.5.5.C [46] I2> DMT reset time
t Reset ms
Rtms
K
t Reset ms
Functions RL 2 RL 3 RL 4
Trip ! YES ! NO ! YES ! NO ! YES ! NO
I> ! YES ! NO ! YES ! NO ! YES ! NO
tI> ! YES ! NO ! YES ! NO ! YES ! NO
I>> ! YES ! NO ! YES ! NO ! YES ! NO
tI>> ! YES ! NO ! YES ! NO ! YES ! NO
I>>> ! YES ! NO ! YES ! NO ! YES ! NO
tI>>> ! YES ! NO ! YES ! NO ! YES ! NO
Ie> ! YES ! NO ! YES ! NO ! YES ! NO
tIe> ! YES ! NO ! YES ! NO ! YES ! NO
Ie>> ! YES ! NO ! YES ! NO ! YES ! NO
tIe>> ! YES ! NO ! YES ! NO ! YES ! NO
Ie>>> ! YES ! NO ! YES ! NO ! YES ! NO
tIe>>> ! YES ! NO ! YES ! NO ! YES ! NO
tI< ! YES ! NO ! YES ! NO ! YES ! NO
tI2> ! YES ! NO ! YES ! NO ! YES ! NO
Therm Alarm ! YES ! NO ! YES ! NO ! YES ! NO
Therm Trip ! YES ! NO ! YES ! NO ! YES ! NO
CB Alarm ! YES ! NO ! YES ! NO ! YES ! NO
52 Fail ! YES ! NO ! YES ! NO ! YES ! NO
Brkn Cond ! YES ! NO ! YES ! NO ! YES ! NO
CB Fail ! YES ! NO ! YES ! NO ! YES ! NO
CB Close ! YES ! NO ! YES ! NO ! YES ! NO
tAux1 ! YES ! NO ! YES ! NO ! YES ! NO
tAux2 ! YES ! NO ! YES ! NO ! YES ! NO
79 Run ! YES ! NO ! YES ! NO ! YES ! NO
79 Trip ! YES ! NO ! YES ! NO ! YES ! NO
Active Group ! YES ! NO ! YES ! NO ! YES ! NO
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 27/32
2.2.6.7.B OUTPUT RELAYS allocation (RL5 and RL6)
Functions RL 5 RL 6
Trip ! YES ! NO ! YES ! NO
I> ! YES ! NO ! YES ! NO
tI> ! YES ! NO ! YES ! NO
I>> ! YES ! NO ! YES ! NO
tI>> ! YES ! NO ! YES ! NO
I>>> ! YES ! NO ! YES ! NO
tI>>> ! YES ! NO ! YES ! NO
Ie> ! YES ! NO ! YES ! NO
tIe> ! YES ! NO ! YES ! NO
Ie>> ! YES ! NO ! YES ! NO
tIe>> ! YES ! NO ! YES ! NO
Ie>>> ! YES ! NO ! YES ! NO
tIe>>> ! YES ! NO ! YES ! NO
tI< ! YES ! NO ! YES ! NO
tI2> ! YES ! NO ! YES ! NO
Therm Alarm ! YES ! NO ! YES ! NO
Therm Trip ! YES ! NO ! YES ! NO
CB Alarm ! YES ! NO ! YES ! NO
52 Fail ! YES ! NO ! YES ! NO
Brkn Cond ! YES ! NO ! YES ! NO
CB Fail ! YES ! NO ! YES ! NO
CB Close ! YES ! NO ! YES ! NO
tAux1 ! YES ! NO ! YES ! NO
tAux2 ! YES ! NO ! YES ! NO
79 Run ! YES ! NO ! YES ! NO
79 Trip ! YES ! NO ! YES ! NO
Active Group ! YES ! NO ! YES ! NO
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 28/32 MiCOM P124
2.2.6.8 Configuration of the latch of the output relays RL2 to RL6
Output 2 ! YES ! NO
Output 3 ! YES ! NO
Output 4 ! YES ! NO
Output 5 ! YES ! NO
Output 6 ! YES ! NO
Technical Guide P124/EN TA2/B44
Commissioning test and APPENDIX 2
record sheets
MiCOM P124 Page 29/32
2.2.6.9 LOGIC INPUT allocation
2.2.6.9.A Inputs
CB Fail ? ! YES ! NO
I< % In
tBF ms
CT Supervision ! YES ! NO
t SUP s
Σ Amps(n)? ! YES ! NO
n
t Open Pulse ms
t Close Pulse ms
Pre-time ms
Post-time ms
Time Window mn
P124/EN TA2/B44 Technical Guide
APPENDIX 2 Commissioning test and
record sheets
Page 32/32 MiCOM P124
BLANK PAGE
© 2010 Schneider Electric. All rights reserved.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P124/EN T/E44 11/2010