CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In)

100
1.5

10

15

20

30

40

50

60
70
80
90
.5

.6
.7
.8
.9
1

6
7
8
9
10000 10000
9000 9000 MICROLOGIC® 2.0 A TRIP UNIT
8000 8000
7000 7000
CHARACTERISTIC TRIP CURVE NO. 613-9
6000 6000

5000 5000
Long-time Pickup and Delay
4000 4000
Short-time Pickup with No Delay
LONG-TIME PICKUP
3000
x In = Ir 3000
The time-current curve information is to be used
for application and coordination purposes only.
2000 2000 Curves apply from -30°C to +60°C ambient
1500 1500
temperature.
Instantaneous override values are given on
1000
900
1000
900
613-10.
800 800
700 700
Notes:
600 600
24 500
1. There is a thermal-imaging effect that can act
500
16 to shorten the long-time delay. The thermal-
400 400
imaging effect comes into play if a current
300 300 above the long-time delay pickup value exists
for a time and then is cleared by the tripping of
200 200 a downstream device or the circuit breaker
150 150
itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than
100 100
normal. The amount of time delay reduction is
90 90 inverse to the amount of time that has elapsed
80 80
70 20 70 since the previous overload. Approximately 20
60 12 60 minutes is required between overloads to
50 8 50 completely reset thermal-imaging.
40 4 40
2. The end of the curve is determined by the
2
30 30 short-time setting.
1
.5 3. Total clearing times shown include the
20 20
response times of the trip unit, the circuit
24
15 15 breaker opening, and the extinction of the
16 current.
10 10
9
LONG-TIME
9 4. Overload indicator illuminates at 100%.
8 8
7
DELAY BANDS 7
SECONDS AT 6 x Ir
6 6
TIME IN SECONDS

5 5

4 4

3 3

2 2

1.5 1.5

8
1 1
.9 SHORT-TIME 10 .9
.8 PICKUP 6 .8
.7 x Ir 1.5 2 2.5 .7
.6 .6
4
.5 .5

.4 3 5 .4

.3 .3

.2 .2

.15 .15

.1 .1
.09 .09
.08 .08
.07 .07
.06 .06

.05 .05

.04 .04

.03 .03

.02 .02

1 CYCLE
.015 .015

.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006

.005 .005
1

1.5

6
7
8
9
10
.5

.6
.7
.8
.9

15

20

30

40

50

60
70
80
90
100

CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)

Curve No. 0613TC0009


December 2000
Schneider Electric Brands © 2000 Schneider Electric all rights reserved Drawing No. B48095-613-09