SPECIFICATIONS: ( GENERAL NOTES)

1. ALL WORKS SHALL COMPLY WITH THE EXISTING RULES AND REGULATIONS OF LATEST EDITION OF PEC.

2. ALL WORKS SHALL BE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.

3. THERE SHOULD BE ONE SERVICE DROP TO THE BUILDING.

4. ALL MATERIALS SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE.

5. PROVIDE ADEQUATE EQUIPMENT GROUND.

6. THE TYPE OF PANELBOARD SHALL BE AIR CIRCUIT BREAKER.


DESIGN LOAD ANALYSIS
LOAD SCHEDULE

CIRCUI LOAD SWITCHES CB RATING


T DESCRIPTION OF VOLTS CURRENT AT AF P NO. AND SIZES OF CONDUCTORS SIZE OF CONDUIT
NUMBE LOADS IN S S2 S3 S2W AND CONDUIT
R AMPERES
1 11 - LO 230 V 4.78 15 50 2 2 – 2.0 MM2 TW 15 MM PVC

2 11 - CO 230 V 8.61 15 50 2 2 – 2.0 MM2 TW 15 MM PVC

3 8 - CO 230 V 6.26 15 50 2 2 – 2.0 MM2 TW 15 MM PVC

4 7 – C0 230 V 5.48 15 50 2 2 – 2.0 MM2 TW 15 MM PVC

5 E. RANGE , 12 KW 230 V 34.78 50 100 2 2 – 14 MM2 TW 20 MM PVC

6 WP , 2HP, 1 230 V 12 30 50 2 2 – 2.0 MM2 TW 15 MM PVC

7 ACU, WINDOW 230 V 8 20 50 2 2 – 2.0 MM2 TW 15 MM PVC


TYPE, 1 HP, 1
8 ACU, WINDOW 230 V 8 20 50 2 2 – 2.0 MM2 TW 15 MM PVC
TYPE, 1 HP, 1
9 SPARE 10 15 50 2 2 – 2.0 MM2 TW 15 MM PVC

10 SPARE 10 15 50 2 2 – 2.0 MM2 TW 15 MM PVC

TOTAL = 107.91 Amperes

MINIMUM AMPACITY OF FEEDER CIRCUIT CONDUCTOR MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTORS

= 107.91 + 0.25 ( 12 ) = 110.91 amperes USE: 1 – 14 mm2 Copper Wire Conductor

USE: 2 – 50 mm2 TW ( 120 / 110.91 ) in 32 mm PVC

MAXIMUM RATING OF FEEDER CIRCUIT OVERCURRENT PROTECTIVE DEVICE

= 107.91 + 1.5 (12) = 125.91 amperes

USE: 150 AT , 225 AF , 2P , 250V Air Circuit Breaker