Anda di halaman 1dari 4

EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • E

approach
A GREEN

TO AIR CONDITIONING SYSTEMS


Low-flow/low-temperature, high-efficiency systems can deliver greener
HVAC solutions for commercial buildings.
By Eugene “Smitty” L. Smithart, PE, Trane, LaCrosse, Wis.

T
here’s never been a better time reduce the size of the supply fans, duc- temperature will reduce humidity levels,
for HVAC products, systems, and twork, pumps, piping, and other HVAC helping to reduce IAQ by mitigating the
services that are environmen- equipment. This provides an opportunity potential for mold.
tally responsible to businesses to reduce the first-cost investment in the
and their stakeholders. system infrastructure with reduced oper- Chillers
The U.S. Environmental Protection ating costs. When the leaving water temperature
Agency 1 has always encouraged HVAC LLH systems are not optimal for every is reduced, the kW consumption on the
technologies that maximize efficiency building application. It is highly recom- chiller(s) will increase. First, in this example,
with low emissions. Additionally, owners mended that the system designer uses a two 400-ton chillers with screw compressors
are encouraged to sustain and document comprehensive computerized system simu- are used to deliver 800 tons. At ARI Stan-
the performance over the lifetime of the lation program with lifecycle cost analysis to dard 550/590 conditions2, these chillers will
application. In some circumstances, it can evaluate economic and environmental alter- produce 44 F water, and will consume 464
be a challenge to meet the performance natives. The computer model must include kW at full load. When the leaving water
requirements in a cost-effective manner. all aspects of the building design to properly temperature is reduced to 41 F, the energy
The use of low-flow/low-temperature, evaluate the interaction of individual com- consumption increases to 490 kW, a differ-
high-efficiency chilled water systems (LLH) is ponent modifications. ence of 26 kW at full load. This is a single
one way for building owners and engineers Conventional VAV systems are typically component of the system and must be bal-
to deliver cost-effective, environmentally designed for 55 F supply air temperature. In anced against other improvements in the
responsible comfort and added value with- a larger system, this traditionally is accom- performance of other equipment. While the
out excessive added costs. When the systems plished using a water-cooled chiller with chillers consumed 26 more kW at 16 F, the
are integrated with the entire HVAC system, standard design conditions of 44 F leaving increased temperature difference reduces
an added benefit is improved IAQ and air- water temperature and a 10 F temperature the water flow, which results in a smaller
side acoustic characteristics. differential for both chilled water and con- pump and motor.
LLH systems are not a new concept. They denser water. The LLH design leverages components
have been used by innovative system engi- The following discussion will compare that will improve the most in overall system
neers for more than 20 years in new con- a traditional system design to an LLH sys- efficiency over the efficiencies of individual
struction and renovation/retrofit projects. tem. The LLH system will use 41 F leaving components. From a coefficient of perfor-
The fundamentals of an LLH system are chilled water temperature, and 16 F and mance perspective, chiller efficiencies have
similar to traditional systems design, with 15 F, respectively, for the chilled water and improved more than 70% in the past three
several notable differences. LLH systems condenser water temperature difference. decades, which allows unlimited flexibility to
use low supply temperatures and a larger A reduced supply air temperature also will maximize the overall system performance.
temperature differential. This results in be evaluated in conjunction with the lower Traditional building HVAC designs will
lower flow rates, which inherently can chilled water temperatures. The lower air have at least two chillers for redundancy. If

Consulting-Specifying Engineer • DECEMBER 2008 41


EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • E

Parallel chillers Series chillers

44 F 47 F

232 kW 218 kW

44 F 40 F

54 F 232 kW 56 F 246 kW

Figure 1 Series chillers can offset the efficiency impact of producing lower chilled water temperature.
Source: Trane

these chillers are piped in a series configu- ton). Assume a system pressure drop of 110 cooling tower fan for this application would
ration, there is an advantage from cascade ft with pump and motor efficiencies of 80% require about 40 BHP. In comparison, the
cooling (see Figure 1). In this case, the full 26 and 95%, respectively. The energy consump- LLH system design would require only 1,600
kW increase can be recovered using lower tion of the motor would be 52 kW. gpm at 15 F difference or 2 gpm/ton, and
leaving water temperatures. Cascade cool- On this same system, if a variable frequen- use a 30 BHP fan motor. This can result in a
ing simply means the first chiller will have a cy drive is applied to the pump, and the chill- smaller tower with a smaller footprint.
higher leaving water temperature and works ers producing a supply water temperature However, the higher temperature dif-
with a higher suction temperature combined of 41 F, the required gpm would be reduced ference will cause the chiller to work at a
with the downstream machine. This configu- from 1,920 to 1,200 gpm (1.5 gpm/ton). The higher head pressure and consume more
ration will produce the design 41 F leaving total pressure drop is reduced to 49 ft, which energy. System designers need the computer
water temperature; this configuration can can be calculated using the pump affinity model and a lifecycle cost analysis program
deliver first cost savings of 2% to 4% and equation, which states that power varies to establish the optimum balance between
energy savings typically in the range of 1% by the cube of flow reduction. The energy lower tower energy and the increased chiller
to 4%. Series chiller configurations are well requirement would have been reduced by energy consumption with respect to overall
suited for variable primary flow systems. The 36 kW, representing a 70% reduction in system optimization.
extra pressure drop, and thus greater pump- pump energy consumption.
ing energy, of placing the two evaporators In variable flow applications the design- Cooling coils
in series can be offset with variable speed er should use a critical zone reset strat- This example of a traditional system uses
pumps in a variable primary flow pumping egy, which allows the system pressure be a chilled water coil differential temperature
system. This configuration allows for signifi- driven by the most pressure-demanding of 10 F. The entering temperature would be
cant pump energy savings at partial loads. valve. Motor efficiency should be analyzed 44 F, and the leaving temperature at 54 F.
over the range of modulation to optimize These conditions would produce 504 MBH
Pumps efficiency and power factor performance (41 tons) of cooling and require 101 gpm of
Often, the reason for reducing the water throughout the operating curve to meet water. If the system designer selected a 16 F
temperature is not due to coil performance; projected performance. temperature differential, the same coil, now
temperature might be lowered to reduce with 41 F entering water temperature, could
chilled water pumping energy consumption Cooling towers produce the same 504 MBH with 63 gpm or
by reducing the water flow requirements. As a conventional system this 800 ton- 37.5% less water.
In our example, a conventional 800-ton load would require 2,400 gpm at 10 F tem- When the enter water temperature is
design would require 1,920 gpm (2.4 gpm/ perature difference, or 3 gpm/ton. A typical reduced, the leaving water temperature

42 Consulting-Specifying Engineer • DECEMBER 2008


EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • ED

does not go down, it goes up, typically 0.5 to operating costs compared to a traditional 1. Fan pressure optimization, which is a
1 F for every 1 F reduction in entering water HVAC system. This was accomplished by control strategy that will poll the VAV boxes
temperature. Actual performance depends leveraging the combination of reduced to identify the most static-demanding box.
on the type and circuitry of the coil. It is also air-side and low chilled water off-peak Based on the box position, the controls will
important to note that the MBH delivered in utility rates. reset the system static pressure to the lowest
this example remained the same, leaving the possible pressure required to satisfy the air
supply air temperature unchanged. Building automation system flow requirements. This can reduce fan energy
The same MBH can be delivered with sub- An integrated control system is critical consumption by as much as 20% to 40% and
stantially reduced water flows. If the water to the success of LLH systems. It allows the will diminish VAV box noise due to over-pres-
flow was held constant and the entering building owner to sustain maximum build- surization in the duct system. This also can aid
water temperature is reduced, additional ing performance. The control system also the reduction of duct and VAV box leakage.
capacity can be obtained. These alterna- provides critical data necessary to proac- 2. Ventilation reset control strategies,
tives can provide significant opportunities tively respond to performance fluctuations such as demand control ventilation and the
to either reduce pumping BHP or address and report historical data. Five common “Z factor,” will control the correct amount
cooling capacity problems. strategies that enable building owners to of ventilation on a real-time basis. This will
achieve all the benefits associated with minimize or eliminate costs associated with
Low air temperature applications LLH are: excess outside air.
Typically, at least half of the HVAC sys-
tem’s energy consumption is from the air-
side equipment of the system. This is due
in part to the longer run time of fans and
Reducing cold downdrafts and condensation
accessories in many chiller applications. Cold downdrafts and condensation are two critical elements that must be properly
Designers have been hesitant to extend LLH managed in low air temperature applications. The following are suggestions to mitigate
beyond the chilled water side of the system these issues.
due to concerns over condensation. The LLH Cold downdraft recommendations:
principles can be extended to the air side if • The use of parallel, fan-powered VAV boxes at the perimeter is a cost-effective method
the designer uses supply air temperatures in to control drafts efficiently. An energy benefit of these devices is the ability to mix warm
the 45 F to 48 F range for chillers and 50 F plenum/return air with the cold primary air to satisfy the space needs prior to engaging
to 52 F for packaged equipment. This allows reheat. These units should be selected to meet acoustical requirements and properly
designers to optimize the energy consump- controlled to provide required air flows during low loads, which will eliminate on/off sound
tion of both the air and refrigeration side fluctuations due to fan cycling.
of the system. • Cooling-only variable air volume boxes can be used within interior spaces. Using a
Historical data indicate that the combina- supply air reset schedule is recommended to allow for additional hours of economizer
tion of an efficient centrifugal chiller, and usage in addition to minimizing reheat. The interior boxes will need to be designed to
a supply air temperature (SAT) of approxi- meet their loads using this higher reset temperature.
mately 45 F is a good balance point. If some- • To accomplish proper air distribution, use linear slot diffusers with aspirating charac-
what less efficient screw chillers are used, 48 teristics, described as the “Coanda” effect. Properly selected diffusers will induce room
F SAT offers the best balance. If scroll com- air to mix with the supply air at the ceiling before it is dispersed into the room.
pressors are used, especially in air-cooled Condensation recommendations:
applications, like rooftop/VAV, the right SAT • Cold surfaces must be kept inside the humidity controlled envelope.
may be in the range of 52 F. • Insulate supply air ductwork and piping.
For example, a new office-warehouse • Consider the space temperature and humidity level. Compare this to the dew point of
building in Dallas required an efficient any cold service under suspicion. Insulate the surface or change the space parameters
HVAC system for its 60,000-sq-ft two-story to avoid condensation.
space. A 45 F low-temperature air distri- • Night setback and morning pull-down can be controlled by an interior dew point sensor.
bution system, complete with ice storage, In a pull-down mode the process should occur in gradual steps to avoid overcooling.
was installed. The system provided a com- • Positive building pressure is critical to control the interior environment. Ensure the
fortable indoor environment by control- building automation system has the ability, ideally on a floor-by-floor basis, to maintain
ling not only dry bulb temperatures, but a slight positive building pressure.
indoor humidity levels, which were critical, • Design the “P” traps and pitch the condensate drains correctly because LLH systems
based on the outdoor climate conditions. produce a good deal of condensation. Collecting this condensation by piping the con-
The owner saved approximately $17,000 denseate lines and running them to a tank is an excellent way to conserve water for use
per year, i.e., about 18%, of its annual in irrigation or make-up water for cooling towers.

Consulting-Specifying Engineer • DECEMBER 2008 43


EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • EDITORIAL PROOF • E

100 ers to document the building’s predictive to


actual performance and carbon footprint. In
80 today’s challenging energy economy, build-
ing owners need proven systems that will
60 deliver the performance necessary to meet
their increasingly integrated environmental
40 sustainability and business goals.

20 Conclusion
Building owners and designers faced with
0 increased concerns for energy conservation
Conventional system LLH system
and environmental stewardship and are
� Atlanta 100% 83%
searching for cost effective system options
� Minneapolis 100% 93%
� Los Angeles 100% 70% for their projects. LLH systems can deliver
� Denver 100% 83% both low first cost and reduced energy costs
� Philadelphia 100% 89% in new construction and retrofit chilled
� Portland 100% 80% water applications. These systems not only
meet the efficiency and sustainability recom-
Figure 2 By comparison, the right side of the graph shows energy consumption and the mendations of the EPA, but when designed
energy savings achieved by using LLH systems concepts. using advanced selection tools, installed
Source: Trane with an integrated control system, and sup-
ported by trained operators, allow building
3. Chiller/tower optimization is achievable cost and “carbon footprint” perspectives owners to compare predicted energy use to
with BAS control strategies, which can calcu- providing detailed information on levels of actual performance and carbon footprint. In
late on a real-time basis the optimum balance utility-generated CO2, SO2, and NOx. today’s challenging energy economy, build-
point between the chiller, the tower, and the Building models also give owners a base- ing owners need proven systems that will
condenser water pumps. These programs can line for performance comparison, which is deliver the performance necessary to meet
be used on new construction and are a rea- crucial to identifying minor problems before their increasingly integrated environmen-
sonably priced upgrade on retrofitted instal- they become major failures. tal sustainability and business goals. More
lations, with cost-effective results. Figure 2 shows an example of the effec- information on LLH systems is available in
4. Auto-commissioning/auto-calibration tiveness of these tools in determining energy the ASHRAE Green Guide3.
can be done using BAS software to provide savings. Using a lifecycle cost program, the
information from each zone, including the base “conventional VAV” system was mod- Smithart, director of systems and solutions
zone set-point and actual temperature, VAV eled in six different sites with the energy at Trane, has more than 30 years of indus-
box performance, and delivered CFM. Dis- consumption set at 100% for each city. try experience–29 years with Trane and
crepancies can be identified with an alarm. Designers should use lifecycle cost analysis four years with Danfoss Turbocor. He is a
This allows a more proactive response as tools to optimize the right water and air-side recipient of the U.S. EPA Climate Protection
opposed to creating a catastrophic failure. temperatures and flows. It is important they award, one of only five people in the world
5. Virtual graphics help ensure building understand how to design an HVAC system to have received this prestigious award at
systems are easy to understand and operate. that is efficient at both full- and part-load. the time.
Realistic graphics speed problem diagnosis Building owners and designers are increas-
and solutions, by identifying the mechanical ingly concerned with energy conservation References
systems in a “picture-type format.” and environmental stewardship, and are 1. U.S. EPA. Building Owners: Save Money, Save
the Earth, EPA-430-F-02-026, December 2002.
searching for cost-effective system options
Download at no cost at www.epa.gov/Ozone/
System selection tools from the design community. LLH systems title6/608/chiller1_07.pdf.
Lifecycle cost analysis tools help system can deliver both low first cost and energy 2. Air-Conditioning and Refrigeration Institute.
designers and building owners model costs in new construction and retrofit chilled ARI Standard 550/590–2003, Performance Rat-
operating cost savings by calculating the water applications. These systems meet the ing of Water Chilling Packages Using the Vapor
Compression Cycle, 2003. Download at no cost
optimum supply air temperature and the efficiency and sustainability recommen-
at www.ari.org.
right leaving water temperature. When dations of the EPA; when designed using 3. ASHRAE. ASHRAE GreenGuide: The Design,
combined with a program similar to E-Grid, advanced selection tools, installed with an Construction, and Operation of Sustainable
today’s advanced system design tools also integrated control system, and supported by Buildings, 2nd ed., 2006, ISBN/ISSN: 1-933742-
can evaluate a project from both lifecycle trained operators, they allow building own- 07-0. Order at cost from www.ashrae.org.

44 Consulting-Specifying Engineer • DECEMBER 2008

Anda mungkin juga menyukai