DOCUMENT DESCRIPTION:

TDS 2000
HVAC REPORTS
HVAC NOISE REPORT

Status/ No of
Date Written by Checked by Approved By Approved By
Revision Pages

C1 6 Nov 2007 4 P. Gillis D.Wilson J. Fursch N. Beeching

Status:
P - Preliminary for Information A - Approved for Construction or Final Engineering Report
I - Inter Disciplinary Check X - As Built
C - For Comments and/or Approval Z - Changes after delivery of unit to client
V Valid for Construction D - Deleted
© SBM-IMODCO INC. 2007 - Information herein presented is confidential and proprietary information of SBM-IMODCO INC. Any
person accepting this information is required to accept same in confidence; and agrees to make no disclosure, use, reproduction or
copy thereof, except as authorized by SBM-IMODCO INC.; and to return same on request.
OFFICIAL COPY - PDF Generated on 06-Nov-2007 10:22AM

Project Name:

TDS2000PLUS Page 2 of 4
SEMI-SUBMERSIBLE

Client Name: Document Description: Project Number:


TDS 2000
Odebrecht Drilling Services LLC HVAC REPORTS SO17530
HVAC NOISE REPORT
Client Document Number: SBMI Document Number: Revision Number:

DMH08045 C1

DOCUMENT REVISION STATUS

Revision Description of Revision


C1 Preliminary, Issued for Comments and Approval
OFFICIAL COPY - PDF Generated on 06-Nov-2007 10:22AM

TDS 2000
HVAC REPORTS
HVAC NOISE REPORT

SO17530 DMH08045 C1 Page 3 of 4

TABLE OF CONTENTS

1.0 PURPOSE........................................................................................................................................4
2.0 SCOPE.............................................................................................................................................4
3.0 REFERENCE DOCUMENTS ...........................................................................................................4
4.0 NOISE TARGETS ............................................................................................................................4
5.0 HVAC EQUIPMENT NOISE.............................................................................................................4
6.0 HVAC VENTILATION NOISES........................................................................................................4
7.0 ATTACHMENT A.............................................................................................................................4
OFFICIAL COPY - PDF Generated on 06-Nov-2007 10:22AM

TDS 2000
HVAC REPORTS
HVAC NOISE REPORT

SO17530 DMH08045 C1 Page 4 of 4

1.0 PURPOSE

This document will provide a guide to identify noise levels of the HVAC systems being supplied by
Alscott for the TDS 2000 Project.

2.0 SCOPE

The scope of this document is to include the HVAC systems for the Columns and Pontoons, the quarters
and the miscellaneous spaces below and on Main Deck.

3.0 REFERENCE DOCUMENTS

• HVAC Master equipment list


• HVAC P & ID’s
• HVAC Vendor documents

4.0 NOISE TARGETS

Noise targets as indicated in attachment A are not to exceed noise level limits recommended by the
international maritime organization (IMO) resolution 468, code on noise levels on board ships.

5.0 HVAC EQUIPMENT NOISE

HVAC equipment noise is as indicated in attachment A. Unacceptable noise levels and recommended
noise reductions are also indicated (Reservation pending final equipment selection).

6.0 HVAC VENTILATION NOISES

Reservation pending CCTC layout.

7.0 ATTACHMENT A

HVAC Noise Study


ANNEXE - PDF Generated on 06-Nov-2007 10:24AM
SBM Atlantia TDS2000 GustoMSC Inc.

UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
AHU-Q01 FIRST LEVEL QUARTERS AHU DISCHARGE 107 97 98 102 98 94 88 84
INLET 99 90 83 86 84 80 75 68
CASING 98 88 82 86 82 78 63 59

AHU-Q02A SECOND LEVEL QUARTERS AHU DISCHARGE 104 100 103 102 99 95 92 90
INLET 96 93 88 86 85 81 79 74
CASING 95 91 87 86 83 79 67 65

AHU-Q03A THIRD LEVEL QUARTERS AHU DICHARGE 111 102 95 102 95 91 86 81


INLET 103 95 80 86 81 77 73 65
CASING 102 93 79 86 79 75 61 56

AHU-Q04A FOURTH LEVEL QUARTERS AHU DISCHARGE 111 102 94 104 97 92 88 82


INLET 103 95 79 88 83 78 75 66
CASING 102 93 78 88 81 76 63 57

AHU-Q04B FOURTH LEVEL QUARTERS AHU DISCHARGE 111 102 94 104 97 92 88 82


INLET 103 95 79 88 83 78 75 66
CASING 102 93 78 88 81 76 63 57

AHU-Q05 GALLEY AHU DISCHARGE 115 102 95 97 92 89 83 75


INLET 107 95 80 81 78 75 70 59
CASING 106 93 79 81 76 73 58 50

PF-01A ELECTRICAL ROOM PRESSURIZATION FAN Outlet PWL 78 89 88 84 84 77 70 63


Inlet PWL 76 79 86 82 84 76 70 63 90 77

PF-01B ELECTRICAL ROOM PRESSURIZATION FAN Outlet PWL 78 89 88 84 84 77 70 63


Inlet PWL 76 79 86 82 84 76 70 63 90 77

SF-01A ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

SF-01B ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

SF-01C ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

SF-01D ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

SF-01E ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

HVAC NOISE REPORT 3D1D5E1B-F6BD-4475-AE6B-E7A57341C824.XLS


ANNEXE - PDF Generated on 06-Nov-2007 10:24AM
SBM Atlantia TDS2000 GustoMSC Inc.

UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA

SF-01F ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

SF-01G ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

SF-01H ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101

EF-01 A ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 B ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 C ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 D ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 E ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 F ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 G ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

EF-01 H ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98

SF-02A MUD PUMP ROOM SUPPLY Outlet PWL 98 98 95 98 100 99 99 89


Inlet PWL 94 96 94 98 99 98 98 88 106 95

SF-02B MUD PUMP ROOM SUPPLY Outlet PWL 98 98 95 98 100 99 99 89


Inlet PWL 94 96 94 98 99 98 98 88 106 95

EF-03A MUD PUMP ROOM EXTRACTION Outlet PWL 92 93 91 91 92 93 89 81


Inlet PWL 88 90 89 81 80 83 89 80 99 88

EF-03B MUD PUMP ROOM EXTRACTION Outlet PWL 92 93 91 91 92 93 89 81


Inlet PWL 88 90 89 81 80 83 89 80 99 88

HVAC NOISE REPORT 3D1D5E1B-F6BD-4475-AE6B-E7A57341C824.XLS


ANNEXE - PDF Generated on 06-Nov-2007 10:24AM
SBM Atlantia TDS2000 GustoMSC Inc.

UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA

SF-03 SACK STORAGE ROOM SUPPLY Outlet PWL 91 96 90 90 88 87 84 78


Inlet PWL 89 93 89 90 88 85 82 75 98 83

EF-03 SACK STORAGE ROOM EXTRACTION Outlet PWL 91 96 90 90 88 87 84 78


Inlet PWL 89 93 89 90 88 85 82 75 98 83

SF-04 CEMENT ROOM SUPPLY Outlet PWL 98 90 89 90 89 87 86 84


Inlet PWL 96 90 89 89 88 86 84 81 100 82

EF-04 CEMENT ROOM EXTRACTION Outlet PWL 98 90 89 90 89 87 86 84


Inlet PWL 96 90 89 89 88 86 84 81 100 82

EF-05A MUD PIT EXTRACTION Outlet PWL


Inlet PWL 88 91 87 80 78 76 73 69 94 76

EF-05B MUD PIT EXTRACTION Outlet PWL


Inlet PWL 88 91 87 80 78 76 73 69 94 76

EF-06 CO2 ROOM EXTRACTION Outlet PWL


Inlet PWL 75 78 84 81 78 73 67 61 88 74

SF-06 EMERGENCY GENERATOR ROOM SUPPLY Outlet PWL 75 76 87 81 83 76 69 62


Inlet PWL 75 76 87 81 83 76 69 62 88 75

SF-07 AIR COMPRESSOR ROOM SUPPLY Outlet PWL 73 79 75 77 75 71 67 63


Inlet PWL 72 77 75 77 75 70 66 61 83 69

SF-08 HEAVY TOOL STORAGE ROOM SUPPLY Outlet PWL 76 77 85 82 87 81 75 69


Inlet PWL 74 77 82 81 87 81 74 67 90 79

EF-08 WELDING SHOP EXTRACTION Outlet PWL 79 81 89 85 85 77 71 63


Inlet PWL 77 81 87 84 85 77 71 63 91 78

SF-9 APV ROOM SUPPLY Outlet PWL 81 80 89 84 83 82 79 76


Inlet PWL 79 79 86 83 82 81 79 75 91 78

HVAC NOISE REPORT 3D1D5E1B-F6BD-4475-AE6B-E7A57341C824.XLS


ANNEXE - PDF Generated on 06-Nov-2007 10:24AM
SBM Atlantia TDS2000 GustoMSC Inc.

UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA

EF-09 APV ROOM EXTRACTION Outlet PWL 81 80 89 84 83 82 79 76


Inlet PWL 79 79 86 83 82 81 79 75 91 78

SF-10 WAREHOUSE SUPPLY Outlet PWL 83 82 86 83 83 78 75 70


Inlet PWL 82 81 84 82 82 77 74 69 90 76

EF-10 PAINT LOCKER EXTRACTION Outlet PWL 72 76 75 75 69 61 54 47


Inlet PWL 70 74 74 75 68 61 54 47 80 65

EF-11 BATTERY ROOM Outlet PWL 76 77 85 82 87 81 75 69


Inlet PWL 74 77 82 81 87 81 74 67 90 79

SF-11 SUBSEA EQUIPMENT ROOM

SF-P01 PONTOONS AND COLUMNS 76 M. FLAT SUPPLY Outlet PWL 85 81 85 81 76 75 74 67


Inlet PWL 83 81 83 81 76 75 73 65 89 73

AC-P01 76 FT. FLAT A/C COOLING PORT/FWD

SF-P02 A PONTOONS AND COLUMNS SUPPLY/DEHUMIDIFIER Outlet PWL


Inlet PWL 125 119 107 102 95 93 88 89 126 99

SF-P02 B PONTOONS AND COLUMNS SUPPLY/DEHUMIDIFIER Outlet PWL


Inlet PWL 125 119 107 102 95 93 88 89 126 99

SF-P02 C PONTOONS AND COLUMNS SUPPLY/DEHUMIDIFIER Outlet PWL


Inlet PWL 125 119 107 102 95 93 88 89 126 99

SF-P02 D PONTOONS AND COLUMNS SUPPLY/DEHUMIDIFIER Outlet PWL


Inlet PWL 125 119 107 102 95 93 88 89 126 99

SCCU-P01 PONTOONS AND COLUMNS CONDENSER

EF-P01 PONTOONS AND COLUMNS 76 M. FLAT EXHAUST Outlet PWL 85 81 85 81 76 75 74 67


Inlet PWL 83 81 83 81 76 75 73 65 89 73

EF-P02 PONTOONS AND COLUMNS EXHAUST Outlet PWL


Inlet PWL 125 119 107 102 95 93 88 89 126 99

EF-Q01A FIRST LEVEL QUARTERS RETURN/EXHAUST Outlet PWL 93 90 94 90 92 90 86 83


Inlet PWL 91 89 93 89 91 89 85 81 99 86

EF-Q01B FIRST LEVEL QUARTERS RETURN/EXHAUST Outlet PWL 93 90 94 90 92 90 86 83


Inlet PWL 91 89 93 89 91 89 85 81 99 86

EF-Q02A FIRST LEVEL QUARTERS EXHAUST Outlet PWL

HVAC NOISE REPORT 3D1D5E1B-F6BD-4475-AE6B-E7A57341C824.XLS


ANNEXE - PDF Generated on 06-Nov-2007 10:24AM
SBM Atlantia TDS2000 GustoMSC Inc.

UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
Inlet PWL 79 84 86 84 85 82 79 86 92 78

EF-Q02B FIRST LEVEL QUARTERS EXHAUST Outlet PWL


Inlet PWL 79 84 86 84 85 82 79 86 92 78

EF-Q03 A 2ND LEVEL QUARTERS HVAC ROOM Outlet PWL


Inlet PWL 75 78 83 81 79 71 64 60 87 74

EF-Q03 B 2ND LEVEL QUARTERS HVAC ROOM Outlet PWL


Inlet PWL 75 78 83 81 79 71 64 60 87 74

EF-Q04 A 2ND LEVEL QUARTERS (WAREHOUSE) Outlet PWL


Inlet PWL 75 78 83 81 79 71 64 60 87 74

EF-Q04 B 2ND LEVEL QUARTERS (WAREHOUSE) Outlet PWL


Inlet PWL 75 78 83 81 79 71 64 60 87 74

EF-Q05 A 3RD LEVEL QUARTERS Outlet PWL 90 82 93 90 93 91 86 82


Inlet PWL 88 82 91 89 92 90 85 81 98 84

EF-Q05 B 3RD LEVEL QUARTERS Outlet PWL 90 82 93 90 93 91 86 82


Inlet PWL 88 82 91 89 92 90 85 81 98 84

EF-Q06 A 3RD LEVEL QUARTERS Outlet PWL 81 83 90 87 86 78 71 64


Inlet PWL 78 82 87 86 85 77 71 64 92 78

EF-Q06 B 3RD LEVEL QUARTERS Outlet PWL 81 83 90 87 86 78 71 64


Inlet PWL 78 82 87 86 85 77 71 64 92 78

EF-Q07 A 4TH LEVEL QUARTERS Outlet PWL 85 89 83 86 85 83 79 77


Inlet PWL 83 87 83 86 85 83 79 75 93 80

EF-Q07 B 4TH LEVEL QUARTERS Outlet PWL 85 89 83 86 85 83 79 77


Inlet PWL 83 87 83 86 85 83 79 75 93 80

EF-Q08 A GALLEY Outlet PWL


Inlet PWL 95 101 101 108 99 97 91 86 110 96

EF-Q9 A HOSPITAL Outlet PWL 76 78 86 80 82 75 70 63


Inlet PWL 74 78 84 80 81 74 69 62 88 74

EF-Q10 SMOKING ROOM Outlet PWL 76 77 85 82 87 81 75 69


Inlet PWL 74 77 82 81 87 81 74 67 90 79

EF-Q11 LAUNDRY EXHAUST Outlet PWL 75 76 87 81 83 76 69 62


Inlet PWL 73 76 84 80 82 76 69 62 88 75

EF-Q12 DRIER EXHAUST Outlet PWL 75 76 85 82 87 81 75 69


Inlet PWL 73 76 82 81 87 81 74 67 90 79

EF-Q13 WAREHOUSE EXHAUST Outlet PWL 75 76 87 81 83 76 69 62


Inlet PWL 73 76 84 80 82 76 69 62 88 75