PROJECT:
TDS 2000
HVAC REPORTS
HVAC NOISE REPORT
Status/ No of
Date Written by Checked by Approved By Approved By
Revision Pages
Status:
P - Preliminary for Information A - Approved for Construction or Final Engineering Report
I - Inter Disciplinary Check X - As Built
C - For Comments and/or Approval Z - Changes after delivery of unit to client
V Valid for Construction D - Deleted
© SBM-IMODCO INC. 2007 - Information herein presented is confidential and proprietary information of SBM-IMODCO INC. Any
person accepting this information is required to accept same in confidence; and agrees to make no disclosure, use, reproduction or
copy thereof, except as authorized by SBM-IMODCO INC.; and to return same on request.
OFFICIAL COPY - PDF Generated on 06-Nov-2007 10:22AM
Project Name:
TDS2000PLUS Page 2 of 4
SEMI-SUBMERSIBLE
DMH08045 C1
TDS 2000
HVAC REPORTS
HVAC NOISE REPORT
TABLE OF CONTENTS
1.0 PURPOSE........................................................................................................................................4
2.0 SCOPE.............................................................................................................................................4
3.0 REFERENCE DOCUMENTS ...........................................................................................................4
4.0 NOISE TARGETS ............................................................................................................................4
5.0 HVAC EQUIPMENT NOISE.............................................................................................................4
6.0 HVAC VENTILATION NOISES........................................................................................................4
7.0 ATTACHMENT A.............................................................................................................................4
OFFICIAL COPY - PDF Generated on 06-Nov-2007 10:22AM
TDS 2000
HVAC REPORTS
HVAC NOISE REPORT
1.0 PURPOSE
This document will provide a guide to identify noise levels of the HVAC systems being supplied by
Alscott for the TDS 2000 Project.
2.0 SCOPE
The scope of this document is to include the HVAC systems for the Columns and Pontoons, the quarters
and the miscellaneous spaces below and on Main Deck.
Noise targets as indicated in attachment A are not to exceed noise level limits recommended by the
international maritime organization (IMO) resolution 468, code on noise levels on board ships.
HVAC equipment noise is as indicated in attachment A. Unacceptable noise levels and recommended
noise reductions are also indicated (Reservation pending final equipment selection).
7.0 ATTACHMENT A
UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
AHU-Q01 FIRST LEVEL QUARTERS AHU DISCHARGE 107 97 98 102 98 94 88 84
INLET 99 90 83 86 84 80 75 68
CASING 98 88 82 86 82 78 63 59
AHU-Q02A SECOND LEVEL QUARTERS AHU DISCHARGE 104 100 103 102 99 95 92 90
INLET 96 93 88 86 85 81 79 74
CASING 95 91 87 86 83 79 67 65
SF-01A ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
SF-01B ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
SF-01C ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
SF-01D ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
SF-01E ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
SF-01F ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
SF-01G ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
SF-01H ENGINE ROOM SUPPLY Outlet PWL 102 98 104 100 104 105 109 101
Inlet PWL 99 96 102 100 103 104 106 98 111 101
EF-01 A ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 B ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 C ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 D ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 E ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 F ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 G ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
EF-01 H ENGINE ROOM EXHAUST Outlet PWL 107 108 108 107 102 100 98 96
Inlet PWL 104 105 106 106 101 99 97 95 112 98
UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
UNIT No. HVAC SYSTEM THIS NOISE REPORT PROVIDES HVAC MANUFACTURERS NOISE DATA TO SUPPORT AN OVERALL TDS 2000 NOISE STUDY. INFORMATION CONTAINED IN THIS
NOISE REPORT IS PRELIMINARY, PRIOR TO CERTIFIED EQIPMENT DATA BEING AVAILABLE AND HVAC SYSTEM ARRANGEMENTS BEING FINALISED
63 Hz: 125 Hz: 250 Hz: 500 Hz: 1000 Hz: 2000 Hz: 4000 Hz: 8000 Hz: dBW dBA
Inlet PWL 79 84 86 84 85 82 79 86 92 78