37
Smart Series®
NORMAL / IDLE
• Rotary switch (6) provides remote control of DSS-15-02/01, DSS-15-12/11, CSS-15-02/01,
SSM-15-02/01, and SSM-15-12/11
• Control modules can all be commanded to respond from NORMAL to IDLE (Standby Heat)
6
• In IDLE, the modules will adjust to a setting of 93˚C (200°F)
|
Exceptions: SSM-15-02/01 and SSM-15-12/11 adjust to a setting of 100˚C (212°F)
BOOST / OFF
• The SSM-15-02/01 and SSM-15-12/11 can be placed into BOOST and OFF
• BOOST will raise the setpoint of the module by 10, 20, or 30%
• OFF shuts off power to the heater but allows the user to monitor cool down of the
hot runner system
• Each SSM-15-02/01 and SSM-15-12/11 can be individually programmed to respond to OFF,
IDLE and BOOST commands
• The user can quickly drive all nozzle zones into BOOST to open frozen gates
ITEM NOTE: Standard (240 VAC) modules are compatible with mainframes wired for either 240 VAC
VOLTS three-phase (standard) or 240 VAC single-phase. Use TAS-05-11 for 120 VAC operation.
NUMBER
TAS-05-12 240 VAC FUSE REQUIREMENTS: (2) ABC-1 fuses. NOTE: (2) spare fuses included with module.
TAS-05-11 120 VAC WARRANTY: Three years (excluding fuses).
BOOST The “BOOST” setting is the NORMAL setpoint plus 10, 20, or 30%; for example,
BOOST if setpoint = 500˚F and BOOST is 10%, then BOOST temperature = 550˚F.