Anda di halaman 1dari 32

Digital Protective Relays

Larsen & Toubro

Larsen & Toubro infuses engineering with imagination. The Company offers a wide
range of advanced solutions in the field of Engineering, Construction, Electrical &
Automation, Machinery and Information Technology.

L&T Switchgear, a part of the Electrical & Automation business, is India's largest
manufacturer of low voltage switchgear, with the scale, sophistication and range to
meet global benchmarks. With over five decades of experience in this field, the
Company today enjoys a leadership position in the Indian market with a growing
international presence.

It offers a complete range of products including powergear, controlgear, industrial


automation, building electricals & automation, reactive power management, energy
meters, and protective relays. These products conform to Indian and International
Standards.

L&T limited offers a wide range of Microprocessor based State-of-the-art


digital protective relays suitable for LV, MV and HV power distribution systems. These
relays are manufactured at L&T’s Mysore works equipped with modern infrastructure
and employing latest manufacturing and testing equipments. L&T’s range also include
relays for special applications manufactured by Microelettrica Scientifica, Italy. The
applications include Feeder Management, Load Sharing, Load Shedding,
Synchronising, Grid Islanding etc.

L&T also manufactures a range of electronic single phase energy meters, three phase
energy meters and trivector meters at the Mysore works.

Mysore Works
Contents

Pages

ANSI / IEEE Device Function Number Details 1

Time - Current Characteristics 2

Over Current Relays & Earth fault Relays - MC31A, MC61A, MC61C 3

Current Sensing Relays - MC12A, ME12A, SC14S 5


Reverse Power Relay - MRP11
Voltage Relay - MV12 7

Power Factor Control Relays - RPM14, RPM08 9

Motor Protection Relays - MM30, MM30W, N-DIN-MA 11


MCOMP, MPR300 13

Generator Protection Relays - MG30, MG30I, MD32G 15

Transformer Protection Relays - IM30T, MD32T, MD32TM 17

Feeder Protection Relays - MC20, MC30, FMR


19
Vector Surge Protection Relay - UM30A

Control & Supervision Relays - MW33


23
Synchronising Load Sharing Relays - SPM21, RRS

Voltage and Frequency Relays - MC1V, MC3V, UFD34 25


ANSI/IEEE

Correlation between ANSI/IEEE device Function number and Relays

Device Function L&T MS


No. Name Relays Relays

21 Under impedance relay / Distance relay MG30 / MG30-I


25 Auto Synchronising SPM21
Synchro-check relay SCM21
27 AC under voltage relay MV12 UM30-A / MC1V / MC3V
UFD34
32 Power directional relay MRP11 MG30 / MW33 / MG30-I
37 Under current or under power relay MM30
MW33
40 Field control (loss of field) relay MG30 / MG30-I
45 DC over voltage relay UBC / 45
46 Reverse phase or phase balance current relay IM30T
MM30
47 Phase-sequence or single-phasing voltage relay UM30-A, MC3V
49 Machine or transformer thermal relay IM30T
MG30 / MG30-I
MPR300 MM30 / MM30-W
50 Instantaneous over current (or rate-of-rise) relay MC20 / MC30
ME12 IM30-T / IM30-AP
MC12A FMR
MC61A / MC61C MG30 / MG30-I
51V, 50V Voltage restrained over current relay MG30 / MG30-I
50BF Breaker - failure MC20 / MC30 / FMR / IM30T / IM30AP
50N Instanteneous earth fault over current relay MC12A IM30 AP / IM30-T
MC61A MC20 / MC30
MC61C FMR / IM30-T
51 AC time over current relay MC12A IM30-AP / IM30-T
MC61A MC20 / MC30
MC31A FMR / IM30-T
MC61C --
51N-(51G) Ground fault time over current relay MC12A IM30-AP / IM30-T
MC61A MC20 / MC30
MC31A FMR
MC61C --
58 Rectifier failure relay (rotating diodes) – RHS
59 AC over voltage relay MV12 --
-- UFD34, MW33
59/81 Overexcitation relay V/Hz -- UM30-A / MG30 / MG30-I
60 Voltage balance relay UM30-A
64 Ground detector (insulation to ground failure of machine or other apparatus) MG30
64S Machine stator ground fault detector relay -- MG30
64R Machine rotor ground fault detector relay -- UBO / CR
67 AC directional over current relay -- FMR
67N-(67G) Directional ground fault over current relay -- FMR
76 DC over current relay – –
78 Phase angle measuring or out of-step protection relay – IM30-GOS
79 Reclosing relay -- MC20R
80 DC under voltage relay -- UBC / 80
81 Frequency relay – UM30-ASV / MG30
-- UFD34 / MC1V / MC3V / MW33
86 Lock-out relay -- --
87 Differential protective relay SC14S MD32G
-- MD32T / MD32TM
87N-(87G) Ground fault differential protective relay – MD32G, MD32T
90 Regulating device to adjust a quantity – --
95 Automatic active or reactive load sharing relay – RRS
Vector surge protection relay UM30-A
df/dt Rate of change of frequency – UFD34

1
Time - Current Characteristics

Product design standards

Reference standards
IEC 60255, IEC 61000,
IS3231, IS8686

Dielectric test : IS 3231 / IEC 60255-5


Impulse test : IS 8686 / IEC 60255- 5
HF disturbance test : IS 8686 / IEC 60255-22-1
Electrostatic discharge test : IEC 61000-4-2
Electrical fast transient : IEC 61000-4-4
Radiated electro magnetic field test : IEC 61000-4-3
Surge immunity : IEC 61000-4-5
Ring wave test : IEC 61000-4-12
Voltage dips & interruption test : IEC 61000-4-11
Power frequency magnetic test : IEC 61000-4-8

Time - Current Characteristics (At TMS = 1)

1,000

100
Trip Time (Sec.)

10

1 B
C

01
1 10 20

Multiple of set current (Is)

For Trip time at TMS other than 1 A : Normal Inverse 3.0 Sec
Trip time = (Trip time at TMS = 1) x TMS OR B : Normal Inverse 1.3 Sec
50 msec whichever is more C : Very Inverse
D : Extreme Inverse

2
Over Current and Earth Fault Relays
• Three Phase Over Current &
Earth fault Relays

Salient Features

• Display of currents, settings,


Trip data & Trip history for analysis
& trouble shooting

• Built in self supervision & self


testing feature to ensure continuous
reliability

• Separate indication for power ON &


programming mode on relay fault

• Separate fault indication

• In MC61C - Communication with


computer & breaker control through
RS485 Port

• Four user programmable output


relays

Model MC31A MC61A MC61C


Description 3 Phase O/C + E/F 3 Phase O/C + E/F + Highset 3 Phase O/C + E/F + Highset
Communication and breaker control
Device Code 51 RYBN 50/51 RYBN 50/51 RYBN
Design Numerical Relay Numerical Relay Numerical Relay
Functions Available Lowset O/C -Is Lowset O/C -Is Lowset O/C -Is
Lowset E/F -Os Highset O/C -Ihs Highset O/C -Ihs
Lowset E/F -Os Lowset E/F -Os
Highset E/F -Ohs Highset E/F -Ohs
Settings O/C Is = 20-200% Step 5% O/C Is = 20-200% Step 5% O/C Is = 20-200% Step 5%
E/F Os = 5-80% Step 5% E/F Os = 5-80% Step 5% E/F Os = 5-80% Step 5%
Time Characteristics available - HS O/C = (0.2 to 40) x In step of - HS O/C = (0.2 to 40) x In step of -
NI, VI, EI, Definite Time 0.2 In or disable 0.2 In or disable
TMS 0.1 - 1.6 Step 0.05 HS E/F = (0.1 to 20) x On step of - HS E/F = (0.1 to 20) x On step of -
0.1 On or disable 0.1 On or disable
Time Characteristics available - Time Characteristics available -
NI, VI, EI, Definite Time NI, VI, EI, Definite Time
TMS : 0.1 - 1.6 Step 0.05 TMS : 0.1 - 1.6 Step 0.05
Other Features Site selectable Trip time Char. Site selectable Trip time Char. HS delay:0.1-2 Sec step 0.01 -
Sec. or Inst.
Highset can be disabled RS485 Communication
Display of Currents, Trip count Display of Currents, Trip count Breaker control
Self supervision feature Self supervision feature Auto doubling of highset, -
Relay co-ordination - BI & BO
Burden on CT £ 0.25 VA on CT/Phase £ 0.25 VA on CT/Phase £ 0.25 VA on CT/Phase
Burden on PT Not applicable Not applicable Not applicable
Operating temp 0 0C to 600C 00C to 600C 00C to 600C
Weight < 2kg < 2kg < 2kg
Burden on Auxiliary supply £ 10 VA £ 10 VA £ 10 VA
Output Contact 1 N/O Contact for self suprvn 1 N/O Contact for self suprvn 1 N/O Contact for self suprvn, 1N/O for trip
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cut out 113 x 142 113 x 142 113 x 142

Ordering Information
Auxiliary supply Type 1 20-110 V AC / DC or 20-110 V AC / DC or 20-110 V AC / DC or
Type 2 88-264 V AC / DC 88-264 V AC / DC 88-264 V AC / DC
CT Rating 1 A or 5 A 1 A or 5 A 1 A or 5 A
(site selectable) (site selectable) (not site selectable)
Output Contacts 4 NO or 2 NO + 2 NC 4 NO or 2 NO + 2 NC 4 NO
3
Wiring Diagrams

MC31A
R Y B R Y B
1 1

2 2 MICRO
CONTROLLER R1 N0
9
3 3
MC31A 10
4 4
NC
R2
13 13 PROTECTION 11
5 5
F50(Is) 12
6 6 R3
F51(0s) 17
15 15

16 16 18

7 7 R4
27
8 8 R Y B E
28
21
22 R5
PROG. 29
25 ERROR
L/+ 30
In = 1A; 5A ˜
0n = 1A; 5A N/- 26

MC61A

R Y B R Y B
1 1

2 2 MICRO
CONTROLLER R1 N0
9
3 3
MC61A 10
4 4
PROTECTION R2 NC
13 13 11
5 5
F50(Is) 12
6 6 R3
F51(Os)
17
15 15
F50(Ihs)
16 16 18
F51(Ohs)
7 R4
7
27
8 8
R Y B E
28
21
R5
22
PROG 29
25 ERROR
L/+
In = 1A; 5A 30
0n = 1A; 5A 26
N/-

MC61C
R Y B R Y B
1 1 R1
9

2 2 MICRO
CONTROLLER 10 NO
R2
3 3 11

4
MC61C 12
4 NC
PROTECTION R3
13 13 17
BKR
5 5 18 OPEN
F50(Is)
R4
6 6 F51(Os) 27 BKR

15 15 F50(Ihs) 28 CLOSE
F51(Ohs) R5
16 16
29
7 7
30
8 D1
8 19 L/R
R Y B E
D2
20 BI*
21 D3
31
22
C 32
PROG
25 ERROR
In = 1A ; 5A L/+ S-
0n = 1A ; 5A ˜
S+
N/- 26
9 PIN MALE

4
Current Sensing Relays
• Single Phase Over current / Earth fault Relay
• Sensitive E/F Relay / Instantaneous Current Relay

Salient Features

• Easy setting through front panel


DIP switches

• Indication for
Power ON and trip status

• Test feature - helps in better maintenance

• Compact, light weight helps in


reducing panel size & thickness

Model MC12A ME12A SC14S


Description 1 Ph O/C or E/F 1 Ph Sensitive E/F Instantaneous current relay
Device Code 50/51 or 50N/51N 50N/51N 87N/64R
Design Microcontroller Based Microcontroller Based Static
Functions Available Lowset O/C -Is Lowset S E/F -Is
Highset O/C -Ihs Highset S E/F -Ihs.
Lowset E/F -Os
Highset E/F -Is
Settings O/C Is = 50-200% Step 10% OR S E/F = 1-16% step 1% Is = 10-40% step 5%
E/F Is = 10-40% Step 2% OR HS S E/F = (2-16) xls OR 20-80% step 10%
E/F Is = 20-80% Step 4% in steps of 2 ls
HS O/C = (2-16) xls step 2 Is
HS E/F = (2-16) xls step 2 Is
Time Characteristics available- Time Characteristics available- Time Characteristics available-
Nl, VI, EI, Definite Time NI, VI, EI, Definite Time 3 Instantaneous (25ms) OR
3 ranges of def Time (1, 10,100) ranges of def Time (1, 10, 100) time delayed 100ms / 200ms
TMS : 0.1 - 1.6 Step 0.1 TMS : 0.1 - 1.6 Step 0.1 Self Powered
Other Features Site selectable Trip time Char. Site selectable Trip time Char. Relay testing possible by ext. 24 V -
Highset can be disabled Highset can be disabled Supply
Harmonic rejection Flag indication / LED indication
Burden on CT 0.25 VA on CT 0.25 VA on CT 6 VA
Burden on PT Not applicable Not applicable Not Applicable
Operating temp 00C - 600C 00C to 600C 00C to 600C
Weight < 1.5kg < 1.5kg < 1.5kg
Burden on Auxiliary supply 5.5 VA 5.5 VA Not Applicable
Output Contacts 2 C/O Contacts (S/R) 2 C/O Contacts (S/R) 2 C/O Contacts (S/R)
Construction Draw out Draw out Draw out
Dim W x H x D in mm 71 x 158 x 224 71 x 158 x 224 71 x 158 x 224
Panel Cutout 62 x 142 62 x 142 62 x 142

Ordering Information
Auxiliary supply Type 1 20-110 V AC / DC or 20-110 V AC / DC or Not Applicable
Type 2 88-264 V AC / DC 88-264 V AC / DC
CT Rating 1 A or 5 A 1 A or 5 A 1 A or 5 A
Range Setting 10-40% or 20-80% or 50-200% 10-40% or 20-80%
Site Selectable

5
Wiring Diagrams

MC12A / ME12A

1 COM

2 +VE/PH.
Aux. Supply
R1
3 -VE/N
μP. Control
Ckt.
F50/50N COM
10
F51/51N

11

12

MC12A / ME12

SETTING RANGE (Is)


In AUX SUPPLY MC12A ME12
1A 24 - 110V AC/DC (10-40)% In (1-16)% In
5A 95 - 240V AC/DC (20-80)% In
(50-200)% In

SC14S

11
2
10

9 ˜ Control R
1

Ckt. 3

7
+ 5
Test (24V) DC-DC Test
Voltage 6
Convrt.
8
4
12

SC14S

In CT OPERATED RELAY SETTING RANGE (Is)


1A NO AUXILIARY SUPPLY (10-40)% IN
5A REQUIRED (20-80)% IN

6
Reverse Power Relay, Under Voltage or
Over Voltage Relay

Salient Features

• Easy setting through front panel


DIP switches

• LED indication for


Power ON and trip status

• Test feature - helps in better maintenance

• Compact, light weight helps in


reducing panel size & thickness

Model MRP11 MV12


Description Reverse Power 1 Ph U/V OR O/V
Device Code 32 27 OR 59
Design Microcontroller Based Microcontroller Based
Functions Available Reverse Power Level Lowset U/V - Vs
Lowset O/V - Vs

Settings PT input Vn 110 V, 415 V AC U/V Vs = 95-20% step 5%


CT input In 1 A / 5 A O/V Vs = 105-180% step 5%
Pick up level 1% - 15% Time Characteristics available-
Min. setting 0.5% Inverse time, Definite time
TMS 0 to 1.5 step 0.1 TMS : 0.1 - 1.6 Step 0.1
Definite time characteristics

Other Features LED indication Site selectable U/V OR O/V


Test feature Site selectable Trip time Char.

Burden on PT < 0.25 VA < 0.25 VA


Burden on CT < 0.05 VA ?0.075 VA on PT
Operating temp 00C to 600C 00C to 600C
Weight < 1.5 kg < 1.5 kg
Burden on Auxiliary supply < 8 VA ?8 VA
Output Contacts 1 N/O + 1 C/O 2 C/O Contacts (S/R)
Construction Draw out Draw out
Dim W x H x D in mm 71 x 158 x 224 71 x 158 x 224
Panel Cutout 62 x 142 62 x 142

Ordering Information
Auxiliary supply Type 1 20-110 V AC / DC 20-110 V AC / DC
Type 2 88-264 V AC / DC 88-264 V AC / DC
CT Rating 1A or 5 A Not Applicable
PT Rating Upto 380 V AC 110 V / 240 V / 415 V (site selectable)

7
Wiring Diagrams

MRP11

1
4

R Y B 2 + VE / PH. 5
Aux. Supply
3 R1
– VE / N μP.
Control
11
Ckt. 7
F32

8
12

6
9

10 MRP11

Vn In AUX SUPPLY
110 V AC 1A 24–110 V AC/DC
415 V AC 5A 95–240 V AC/DC

MV12

1
5

2 4
R1
3 +VE/PH. μP.Control 6
Aux. Supply Ckt.
4 F27
-VE/N F59 8
11
9
12
7

MV12

8
Power Factor Control Monitoring Relays
• (8 & 14 Stages) Intelligent Power Factor Controller Relay

Salient Features

• On line display of system PF

• Easy setting through - front panel


push button

• Suitable for non-uniform banks

• LED indication for alarm code,


no. of Banks selected, PF status-
lead / lag / unity

• Auto / Manual mode

• Measurement sensitivity of 1%

• Automatic C/K correction

• Display of cuttent, Voltage, kVAr,


& Capacitor values

Model RPM-8 RPM-14


Description Automatic Power Factor Controller Automatic Power Factor Controller
8 stage 14 stage
Device Code
Design Microcontroller Based Microcontroller Based
Functions Available Automatic PF control upto Automatic PF control upto
8 stage 14 stage
Settings Switching time 1-255 Sec. Switching time 1-255 Sec.
in step of 1 sec for same in step of 1 sec for same
Bank switching Bank switching
Auto C/K sellection Auto C/K sellection
PF control range 1% to 120% of PF control range 1% to 120% of
rated current rated current
Other Features Can accept unequal banks Can accept unequal banks
Display of PF, V, l, kVAr Display of PF, V, l, kVAr
LED indications for faults LED indications for faults
Alarm signal for CT reversal, Alarm signal for CT reversal,
under current, Under compensation, under current, Under compensation,
over compensation, over voltage, over compensation, over voltage,
1 A / 5 A field selectable 1 A / 5 A field selectable
Burden on CT 0.3 VA 0.3 VA
Burden on PT 15 VA 15 VA
Operating temp 00C to 600C 00C to 600C
Weight < 2kg < 2kg
Output Contacts 8 N/O 14 N/O
1 N/O contact for alarm 1 N/O contact for alarm
Dim W x H x D in mm 144 x 144 x 100 144 x 144 x 100
Panel Cutout 138 x 138 138 x 138
Ordering Information
Auxiliary supply 240 V AC 240 V AC

9
Wiring Diagrams

RPM-8

Ph
230V AC
1 13 50 Hz
N
2 14

3 15
4 16

ALARM
5 R8 17

6 R7 18
S1(5A)
+ R6 19
BANK #8
7
S1(1A) 8 + R5 20

S2 9
- R4 21

10 R3 22
11 R2 23

12 R1 24

BANK #1

Y TO

B LOAD

RPM-14

Ph
240V AC
R1 1 R13 13 50 Hz
R2 2 R14 14 N
R3 3 15
R4 4 - 16 S2
R5 5 + 17 S1(1A)
R6 6 + 18 S1(5A)
ALARM

R7 7 19 BANK #1
R8 8 20
R9 9 21
R10 10 22
R11 11 23
R12 12 24
BANK #14

R
Y TO
LOAD
B
N

10
Motor Protection Relay
• Motor Protection Relay
• Motor Protection Relay with Voltage input

Salient Features

• Display of various parameters, trip


count and trip data

• LEDs for fault indication

• User programmable output relays

• Built in self supervision & self


testing feature helps maintenance

• RS485 Port for serial communication


with “MSCOM” user friendly software

Model MM30 MM30W N-DIN-MA


Description Motor Protection Motor Protection Motor Protection
Device Code 50/51, 51LR, 64, 68, 50/51, 51LR, 64, 49, 46, 37, St no, 49, 51LR, 46, 37, 50/51, 64, St no, Itr
49, 46, 37, St no, ltr ltr, 55, 68, 81, 47, 12/14, 27/59
Design Numeric Numeric Numeric
Functions Available Trip circuit supervision Trip circuit supervision Thermal O/L and Pre-alarm
Thermal O/L and Pre-alarm Thermal O/L and Pre-alarm Locked Rotor
Locked Rotor Locked Rotor Current unbalance, phase reversal,
Current unbalance, phase reversal, Current unbalance, phase reversal, phase loss
Phase loss phase loss Over Current
Over Current Over Current Earth Fault
Earth Fault Earth Fault Repeat and prolonged starts
Repeat and prolonged starts Repeat and prolonged starts Restart Inhibition
Restart Inhibition Restart Inhibition No load running
No load running No load running Blocking Function
Blocking Function Blocking Function
Under frequency / over frequency
Under voltage / over voltage
Running hours
Low PF
Other Features Auto setting Auto setting 2 Programable digital inputs
1 A or 5 A site selectable 1 A or 5 A site selectable 1 Removable front face panel
(Default 5 AMP) (Default 5 AMP) LCD Display
Selectable motor time constant Selectable motor time constant 1 A or 5 A site selectable (Default 5 AMP)
(1 - 60 min) (1 - 60 min) Selectable motor time constant (1-60 min)
Display of parameters Display of parameters Display of parameters
Built in self supervision Built in self supervision Built in self supervision
RS485 port RS485 port RS485 port, front RS232 port (on FFP)
Burden on CT 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A 0.075 VA for 5 A, 0.01 VA for 1 A
Burden on PT Not Applicable Not Applicable Not Applicable
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg < 1kg
Burden on Auxiliary 8.5 VA 8.5 VA 3 VA
Output Contacts 4 C/O + 1 C/O for self supervision 4 C/O + 1 C/O for self supervision 2 C/O Contacts
Construction Draw out Draw out DIN rail mounting
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 FFP = 106 x 45 x 16
113 x 142 113 x 142 RMB = 106 x 85 x 72
Ordering Information
Auxiliary supply 20-110 V AC / DC or 20-110 V AC / DC or 20-110 V AC / DC or
88-264 V AC / DC 88-264 V AC / DC 88-264 V AC / DC

11
Wiring Diagrams

MM30

A B C A B C R1 21 (10)
(21)
25 25 DISPLAY 10
11 N.O. N.O.
26 26 MICROP. 22
R2 7
27 27 MM30 9 N.C. N.C.

8
28 28 R3 18
FUNCTION 20
39 39
29 29 19
F37 R1 R4 4
41 41 F46 6
30 30 F49
R2 5
32 F51
32
F51R R5 15
43 43
31
In=5A
31 ˜˜˜ F64
St.No.>
AI.0>
R3

R4
17

16
42 42 Itr 14
In=1A
33 33 PROGR. 3
R5
INT. FAULT 2
44
1
C
PRESA/TAP 31:Ion=5A KEYBOARD S- 34/38
S+ 23
PRESA/TAP 33:Ion=1A L/+ 12 24
˜ ˜=
N/- 13
˜ 9 PIN MALE
IEC 255

N-DIN-M
N-DIN-M
A B C A B C A B C
FFP
10 10 10 Display / Keyboard / Signals
A B + 0
RS485
11 11 11

RS485 RMB

8 8 8 A B + 0

N - DIN - M
9 9 9 FUNCTIONS
F26 R1 16

F37
F46 17
12 12 12 F49
F51
13 13 13 BT 2 1
F51LR
R2 15
F64
T 6
St.Ctrl
Digital Input 1 D1 14
T 7
Digital Input 2 D2
0
C 2
PWR / I.R.F B (S-)
THERMISTOR INPUT RTD 4
Trip
1 ON A (S+)
COMMON RS485 5
OFF
21

22

MS - SCE 1752 - R1

12
Motor Protection Relay
• Intelligent Motor Protection & Control Relay - MCOMP
• Economical Motor Protection relay - MPR 300

MCOMP relay MPR 300

Model MCOMP MPR 300


Description Motor Protection Motor Protection
Device Code 49, 14, 46, 50N, 3, 59, 27, 47, 49, 51LR, 64, 46, 37
81H, 81L, 66, 27LV, 47a, 47b
Design Numeric Numeric
Functions Available Thermal Over load Thermal overload
Locked rotor Locked Rotor
Current unbalance Earth fault
Phase loss Single phasing
Under current No load running
Over Voltage
Under Voltage
Over Frequency
Under frequency
Max. no. of starts
Reacceleration
Phase reversal
Other Features Intelligent relay with separate up to 88A
protection, display and CT Trip time characteristics
modules as per
Suitable for 50/ 60 Hz IEC947
Can be used with DOL,
RDOLand Star delta starters
Communication options -
Modbus RTU, Modbus TCP IP
and Profbus
Burden on PT Not Applicable Not Applicable
Burden on CT Not Applicable Not Applicable
c
Operating temp 10 to 60° C 0-60 C
Weight < 2kg < 0.5kg.
Burden on Auxiliary supply < 8VA < 8VA
Output Contacts 4C/O 1NO+1NC
Dim W x H x D in mm Split Protection unit 92 x 123 x 103.95 Not applicable
Panel Cutout Display - 92 x 92 Not applicable
Auxiliary supply 80 - 300 VAC/ 80 - 240 VDC 240V AC

13
Wiring Diagrams

MCOMP Relay

Typical Dol feeder with M COMP

415V, 3PH, 4-WIRE, 50Hz


R 240V AC TEST BUS
Y PH
B N
N
X-25 T X-26 T

Q1
NLK

F11
L11 - 201
111 6A 112
F12
1216A122
F13
1316A132
N11 - 201
2 4 6
K4 DRIVE
AVAILABLE RUN TRIP UNUSED DO

1 3 5
K3 1 2 3 8 81 82 83 84 85 86 87 88 89 90 91 92
D1
XC1-1
P1 S1
T5 N BY R PMR/
T1 XC1-2
XC1-3
C1 REF. VOLTAGE PMR/ LED CO
P2 S2 C8 DIGITAL OUTPUT RELAY COMM
DISPLAY
XC1-4 R Y B C2
MOTOR
P1 S1 L&T MAKE C3 STATUS

T2 XC1-5 MCOMP
ESE

M OOMP P 75
S2 XC1-6 ALARM ESC
P2

CBCT
PICKUP
CT UNIT N 76
XC1-7 C7 AUX. TRIP
ELECT

P1 S1 VOLT C4 E 77
T3 XC1-8 C6 DIGITAL INPUTS N PH RS 485
P2 S2 XC1-9 M COMP
61 62 63 64 65 66 67 71 72
XC1-10

START COMMAND
START COMMAND
STOP COMMAND
R Y B S1 X-42
PH
S
T4

AVAILABLE
X-43 81 84 87

DRIVE
CBCT

TRIP
K3 K3 K3

RUN
S2 S 106 106 106
82 83 85 86 43 88 89
HAND HAND
RST START K4
UNUSED DI P.B. P.B. 44

A1 21 11
M 11

TRIP
RUN
STOP

LED

LED
S1 K4 H2 H1
P.B R G
12 A2 22 12

MPR300 Relay

R Y B N

Start Aux. N/O


N/O

Stop
(N/C)

1 2 3 4 5 6 7 8
NC NO Aux
Supply
MPR300

Typical connection diagram


for ‘Direct Starting’ application
M

14
Generator Protection Relays
• Multifunction Generator Protection Relays
• Percentage Based Generator Differential Relay

Salient Features

• Display of various parameters,


trip count & trip data on 8 digit
alphanumeric display

• Separate LEDs for


various fault indication

• Four user programmable


output relays

• Built in self supervision &


self testing feature help maintenance

• Easy operation by 5 push buttons

• RS485 Port for


serial communication with “MSCOM”
user friendly software

Model MG30 MG30-I MD32-G


Description Generator Protection Generator Protection Generator Differential
Device Code 21, 24, 27/59, 32, 37, 40, 46, 49, 50/27, 21, 24, 27/59, 32, 37, 40, 46, 49, 50/27, 87, 50/51, 64S/87N, 68
50V/51V, 51BF, 60FL, 64S, 68, 81 50V/51V, 51BF, 60FL, 64S, 68, 81
Design Numeric Numeric Numeric
Functions Available Two levels of voltage controlled O/C, Two levels of voltage controlled O/C, Generator Differential
Thermal Image with pre-alarm, Thermal Image with pre-alarm, Bias % with dual adjustable -
Two levels of current unbalance Two levels of current unbalance slope
Two levels of under / over voltage Two levels of under / over voltage Over Current
Two levels of under / over frequency Two levels of under / over frequency Stator E/F
95% + 100% Stator Earth fault, 95% stator Earth fault CB Failure protection
Two levels of Over excitation Two levels of Over excitation
Two levels of Under impedance, Two levels of Under impedance,
Loss of Field, Under Power Loss of Field, Under Power
PT Fuse Failure, Breaker Failure, PT Fuse Failure, Breaker Failure,
Inadvertent C/B Closure etc. Inadvertent C/B Closure etc.
Other Features 1 A or 5 A site selectable 1 A or 5 A site selectable 1 A or 5 A site selectable
Display of Parameters Display of Parameters Display of Parameters
Built in Self supervision Built in Self supervision Wave form capture feature
RS485 Port, MODBUS protocol. RS485 Port, MODBUS protocol. Built in Self supervision, -
Blocking inputs & Blocking outputs Blocking inputs & Blocking outputs RS485 Port
Burden on CT 0.25 VA for 5 Amp CT 0.25 VA for 5 Amp CT 0.2 VA for 5 A, 0.01 VA for 1 A
0.01 VA for 1 Amp CT 0.01 VA for 1 Amp CT Not Applicable
Burden on PT 0.05 VA (MG30) 0.05 VA (MG30)
Burden on Auxiliary supply 8.5 VA 8.5 VA 8.5 VA
Operating temp 100C to 600C 100C to 600C -100C to 600C
Weight < 2kg < 2kg < 2kg
Output Contacts 3 C/O+(1 N/O + N/C)+separate relay 3 C/O+(1 N/O + N/C)+separate relay 4 C/O, S/R or H/R or Time del
1 C/O for self supervision 1 C/O for self supervision 1 C/O for self supervision
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142 113 x 142
Ordering Information
Auxiliary supply Type 1 20-110 V AC / DC or 20-110 V AC / DC or 20-110 V AC / DC or
Type 2 88-264 V AC / DC 88-264 V AC / DC 88-264 V AC / DC

15
Wiring Diagrams

MG30

25 21 (21 – 22)
DISPLAY R1 10
1/5A
N.O. N.C.
26 MICROP. 11
22 (10 – 11)
1/5A MG30 7
R2
27 9 N.O. N.C.
FUNZIONI
1/5A
FUNCTION 8
28 R3 18
20
G 39 1>,Z<,Uo>
29 19
12>,T> R1 R4 4
1/5A 6
Zc<, O> R2 5
30
R5 15
41 U,f 17
1/5A

31 W<, Ir> 16
R3
42
1/5A IC, 60FL 14 14
32 R4
43 B.I./B.F. 3 3
2 2
33 1
MG30 1/5A PROGR. 37(b)
R5
44 INT. FAULT TO REX
C
S–
38(a) RELAY
23 EXPANSION
S+
24
12 KEYB0ARD
TASTIERA 9 PIN MALE
13

CE
MS-SCE 1629-R0 In=1A In=5A Un=100V

MG30-I
25 21 (21 - 22)
DISPLAY R1 10
N.O. N.C.
26 MICROP. 11
22 (10 - 11)
MG30-I R2 7
27 9 N.O. N.C.
FUNZIONI
FUNCTION 8
28 R3 18
20
G 39 I>, Z<, Io> 19
29
I2>, T> R1 R4 4
1/5A 6
30 Zc<, > R2 5
R5 15
41 1/5A
U, 1 17
31 w<+ Ir> 18
R3
42 14
1/5A IC, 60FL 14
32 R4
43 B.I / B.F. 3 3
2 2
1

1/5A
PROGR.
R5 37(b)
33 INT.FAULT TO REX
c
38(0) RELAY
s- EXPANSION
s+ 23
24
12 KEYBOARD RS485
TASTIERA
In = 1A 13
In = 5A MS-SCE1759-R0

MD32-G
A B C
87G + 87N (21)
I1A 25 R1 21
DISPLAY 10
I1B 1/5A N.O.
11
I1C 26 MICROP. 22
1/5A R2 7 N.C.
9
27 MD32-G (10)
8
1/5A
28 R3 18 N.O.
FUNCTION 20
39
G 19 N.C.
F187G R1 R4 4
F287G 6
29 F87N R2
5
1/5A R3 15
I2A R5
30 R4 17
I2B 41 1/5A 16
R = Stabilising resistor
I2C 31 14
Z = Protection surge B3
arrester (if required) 42 PROGR. B2 3
1/5A R5
32 INT. FAULT
B1 2
43
Z 1

˜˜˜
1/5A C 34/38
33 S-
23
R 50-60
KEYBOARD S+
_ 24
L/+ 12
N/- 13 ˜ ˜= 9 PIN MALE
˜
16
Transformer Protection Relay
• Percentage Based Transformer Differential Relay
• 3 Phase Thermal + Over Current + Earth Fault Relay
for transformer protection

Salient Features

• Display of various parameters,


trip count & trip data on 8 digit
alphanumeric display

• Separate LEDs for


individual fault indication

• Four user programmable


output relays

• Built in self supervision &


self testing feature help maintenance

• Easy operation by 5 push buttons

• RS485 Port for


serial communication with “MSCOM”
user friendly software

Model MD32T MD32TM IM30T


Description Transformer Differential + Transformer Differential 3 Ph O/C, E/F + Thermal
Restricted E/F
Device Code 87 RYB, 87N 87 RYB 50/51 RYBN, 49, 46, I2t, 51BF,
50N/51N
Design Numeric Numeric Numeric
Functions Available Lowset Differential Lowset Differential Lowset O/C
Lowset Op time : <=30mS Lowset Op time : <=30mS Highset O/C
Highset Differential Highset Differential Lowset E/F
Highset Op time : 6-20mS Highset Op time : 6-20mS Highset E/F
Restricted Earth Fault Dual slope Bias Thermal Overload
Dual slope Bias Highset can be Biased / Unbiased Lowset current unbalance with
Highset can be Biased / Unbiased 2nd harmonic restraint setting Definite / Inverse time tripping
2nd harmonic restraint setting 5th harmonic restraint setting Highset current unbalance
5th harmonic restraint setting Auto correction of CT Ratio Inrush Energy protection
Auto correction of CT Ratio Zero sequence compensation CB Failure function
Zero sequence compensation Blocking Function Blocking function
Blocking Function
Other Features Display of parameters Display of parameters Display of Parameters
Built in self supervision Built in self supervision Built in self supervision
RS485 Port RS485 Port RS485 Port
1 A OR 5 A site selectable 1 A OR 5 A site selectable 1 A OR 5 A site selectable
Waveform capture feature Waveform capture feature
Burden on CT 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg < 2kg
Burden on Auxiliary supply 8.5 VA 8.5 VA 8.5 VA
Output Contacts 5 C/O, S/R or H/R or Time del 5 C/O, S/R or H/R or Time del 5 C/O, S/R or H/R or Time del
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142 113 x 142
Ordering Information
Auxiliary Supply 20-110 V AC / DC 20-110 V AC / DC 20-110 V AC / DC
88-264 V AC / DC 88-264 V AC / DC 88-264 V AC / DC

17
Wiring Diagrams

MD32T / MD32TM

A B C
(21)
I1A 25 R1 21
87T + 87N 10
DISPLAY
1/5A N.O.
I1B
In1 11
I1C 26 MICROP. 22
R2 7 N.C.
1/5A
MD32T 9 (10)
27
8
1/5A
V1 28 R3 18 N.O.
39 FUNCTION 20
V2 V1
á V1 19 N.C.
Kv =
V2 V2 F187T R1 R4 4
F287T 6
29 F87N R2
5
1/5A R3 15
I2A R5
R4 17
30
R = Stabilising resistor
I2B 41 16
Z = Protection surge 1/5A
arrester (if required) I2C 31 B3 14
42 1/5A
PROGR. R5 B2 3
32 INT. FAULT
43 B1 2
Z 1

R
33
1/5A
˜˜˜
50-60
KEYBOARD
C
S-
S+
34/38
23
24
L/+ 12
IEC 255 ˜ ˜ = 9 PIN MALE
N/- 13
˜

IM30T

A B C A B C A B C
(21)
25 25 25 R1 21
DISPLAY 10
1/5A N.O.
26 26 26 11
MICROP. 22
N.C.
27 27 27 R2 7
9 (10)
1/5A IM30T
28 28 28 8 N.O.
39 39 39 R3 18
FUNCTION 20
29 29 29 N.C.
19
1/5A
41 41 41 R4 4
F46 R1 6
30 30 30 F49
F50 R2
32 32 32 F51 5
43 43 43 15
1/5A
˜
˜
F50N
F51N R3
R5
17
31
42
31
42
31
42
˜
BT 2 50
F51BF
I2t = K R4 16

33 33 33 RT 14

BIO 3
PROGR. R5 2
44 INT.FAULT BIF
1
In = 5A In = 1A
C 34/38
_ S-
L/+ 12 23
N/- 13 ˜ ˜= KEYBOARD S+
24

IEC 255
PRESA/TAP 31 Ion = 5A
PRESA/TAP 33 Ion = 1A ˜ 9 PIN MALE

18
Feeder Protection Relays
• 3 Phase O/C & E/F relay with Highset + Auto Reclosure (Optional)
• 3 Phase Directional O/C & E/F relay with Highset

Salient Features

• Display of various parameters,


trip count & trip data on LCD screen

• Separate LEDs for


various fault indication

• Built in self supervision & self testing


feature

• Wave form capturing

• RS485 Port for


serial communication with “MSCOM”
user friendly software

• Front RS232 Port for


local programming

Model MC20 MC30


Description 3P O/C + E/F + Highset + Autoreclosing (Optional) 3P O/C + E/F + Highset
Device Code 51, 51N, 50, 50N, 51BF, 79 (optional) 51, 51N, 50, 50N, 49, 51BF
Design Numeric Numeric
Functions Available Lowset O/C Lowset O/C
2 Highset O/C Levels 2 Highset O/C Levels
Lowset E/F Lowset E/F
2 Highset E/F Levels 2 Highset E/F Levels
Time current curves selectable according Thermal image
to IEC/IEEE standards Breaker Failure protection
Auto Reclose (In MC20-R) Circuit Breaker control via Serial port
Breaker Failure protection Blocking Output and Blocking Input for pilot
Circuit Breaker control via serial port Wire selectivity coordination
Blocking Output and Blocking Input for pilot Time tagged multiple event recording
wire selectivity coordination Oscillographic wave form capture
Time tagged multiple event recording Accepts 3 Digital inputs
Oscillographic wave form capture Display LCD 16 (2 x 8) characters
Accepts 3 Digital inputs Time current curves selectable according
Display LCD 16 (2 x 8) characters to IEC/IEEE standards
3rd Harmonic Filter on the neutral input current Password protection facility
Password protection facility
Rating 1 A or 5 A site selectable 1 A or 5 A site selectable
Other Features Display of parameters Display of parameters
Built in supervision Built in supervision
Modbus RTU / IEC870-5-103 Modbus RTU / IEC870-5-103
Communication Protocols Communication Protocols
Front RS232 Port for Local Programming Front RS232 Port for Local Programming
Oscillographic recording of input Quantities Oscillographic recording of input Quantities
RS485 serial communication port on Back Panel RS485 serial communication port on Back Panel
Burden on CT 0.1 VA for 1 A, 0.3 VA for 5 A 0.1 VA for 1 A, 0.3 VA for 5 A
Burden on PT NA NA
Burden on Aux. Supply < 7 VA < 7 VA
Operating Temp -100C to 550C -100C to 550C
Weight < 1.5Kg < 1.5Kg
Output Contacts 4 C/O Contacts 4 C/O Contacts
Construction Drawout Drawout
Dim 83 x 164 x 225 83 x 164 x 225
Panel Cutout 64 x 137 64 x 137
Ordering Information
Aux. Supply Type 1 24-110 V AC/DC 24-110 V AC/DC
Type 2 88-264 V AC/DC 88-264 V AC/DC

19
Wiring Diagrams

MC20
A B C A B C

6 6
DISPLAY
R1 R1 16
16
1/5A MICROP.
7 7
R2 R2 OUTPUT
18
MC20 18
OUTPUT
RELAYS

17 17
FUNZIONI RELAYS RELE’
R3 R3
FUNCTIONS 14 14 DI USCITA
4 4 RELE’
15 DI USCITA 15
1/5A
F50
5 5 R1 R4
F51 13

F50N R2 12
8 8 D3 20 DIGITAL
F51N INPUTS
20 D2 21
1/5A D3 DIGITAL
9 9 R3 INGRESSI
BT 2 50 PROGR. 21 INPUTS D1 19
D2 DIGITALI
INT.FAULT 19 INGRESSI 22
R4 D1
DIGITALI
22
H
TO I/0 RELAY
In = □ 1A □ 5A L
13 EXPANSION
12 ALL’ ESPANSIONE
lon = □ 1A □ 5A DI I/0

C COMUNE
C 3
3 COMUNE
10 A (S+)
Auxiliary Supply 2 RS485
RS232 B (S+) A (S+)
Alimentazione Ausiliaria 1 2
11 B (S-) RS485
KEYBOARD 1
TASTIERA
MS - SCE 1828 - R1 BPMC

MS - SCE 1828 - R1 MS - SCE 1839 - R2


Standard Output I/O Output

MC30

4 DISPLAY R1 R1
16 16
1/5A MICROP.
5 OUTPUT
R2 R2 18 RELAYS
6 MC30 18
FUNZION 17 OUTPUT 17 RELE
7
1/5A
FUNCTIONS
R3 14 RELAYS R3 14 DI USCITA
RELE
F50 15 15
8 R1 DI USCITA
R4 13
F51
1/5A
F50N R2 12 D3 20 DIGITAL
9
F51N D2 21 INPUT
D3 20 DIGITAL INGRESS
R3 19
21 INPUTS
D1
1/5A
D2 22 DIGITAL
R4 D1 19 INCRESSI
22 TO I/0 RELAY
PROGR. DIGITAL
L
In= 1A 5A H 13 EXPANSION
INT.FAULT 12 ALL ESPANSIONE
DI I/0
3 COMUNE
C
C
A (S+)
3 COMUNE
AUXILIARY SUPPLY 10 B (S-) 2 RS485
RS232 A (S+)
2 RS485
11 KEYBOARD 1 B (S-) 1
TASTIERA
BPMC

MS-SCE1895-R2 MS -SCE1924-R2
Standard Output I/O Output

20
Feeder Protection Relays / Vector Shift Relay
• 3 Phase Directional O/C & E/F relay with Highset
• 3 Phase voltage and frequency relay with vector shift

FMR - Salient Features :-

• Display of various parameters,


trip count & trip data on LCD screen

• Separate LEDs for


various fault indication

• Built in self supervision & self testing


feature

• Wave form capturing

• RS485 Port for


serial communication with “MSCOM”
user friendly software

• Front RS232 Port for


local programming

Model FMR UM30A


Description Feeder Manager Relay 3 Phase V and F relay with vector shift
Device Code 46, 49, 50/51, 67, 50N/51N, 67N, 27/59, 59UO, 74, 81, 86, 121, I2t 24, 27d/59d, 47, 59, 59Uo, 78, 81
Design Numeric Numeric
Functions Available Three levels for phase over current independently Over Fluxing
programmable as directional or non directional Two Levels of under / over voltage
Three levels for Earth Fault independently programmable Two Levels of under / over frequency
as directional or non directional Zero seq. voltage
Thermal image Voltage unbalance
Selectable Time current curves according to IEC and IEEE standards Vector shift detection
Two over/under voltage levels
Two over/under frequency levels
Zero sequence over voltage level
Two Negative Sequence current levels
One Positive Sequence over voltage level
One Negative Sequence undervoltage level
Trip circuit supervision
Associated Circuit Breaker control
Breaker failure protection
Breaker interruption energy
Rating 1 A or 5 A site selectable / 100-125 V PTI
Other Features Graphical display 128 x 64 dots Display of Parameters
Display of V, I, PF, kW, kVA, kVAr and thermal status Built in Self supervision
Modbus RTU / IEC870-5 Communication Protocols RS485 Port
RS232 serial communication port on front face
MIMIC diagram on LCD
Oscillographic recording of input quantities
RS485 serial communication port on Back Panel
Burden on CT Phase 0.01 VA at In = 1 A; 0.2 VA at In = 5 A Neutral NA
Burden on PT 0.01 VA at In = 1A; 0.2 VA at In = 5 A 0.2 VA / Phase at UN
Burden on Aux. Supply 0.1 VA at UN 8.5 VA
Operating Temp -100C to 550C 100C to 600C
Weight < 2Kg < 2kg
Burden on Aux. < 10 VA 3 C/O+(1 N/O + 1 N/C)+separate relay
Output Contacts 6 C/O Contacts 1 C/O for self supervision
Construction Drawout Draw out
Dim 121 x 164 x 224 121 x 158 x 224
Panel Cutout 113 x 142 113 x 142
Ordering Information
Aux. Supply Type 1 20-110 V AC/DC or 20-110 V AC / DC or
Type 2 88-264 V AC/DC 88-264 V AC / DC

21
Wiring Diagrams

FMR

A B C A B C
2 2 25
R1 28 Trip
3 3 Oxi. sup.
4 4
ULTRA 15
14
5 5 (25)
24
6 6 Feeder R2
35
N.O
7 7 Manager 34
8 8
Relay R3
25
N.C
9 9

R4
41 41 33
42 42 R1
POWER R5
43 43
R2 32
44 44 TRIP 15
R3
45 45 R6 22
R4 31
ON
46 46
12
R5
47 47 OFF D1 25
R6
DIGITAL
D2 15
48 48 INPUTS
D3 25
In = □ 1A □ 5A D4 19 INGRESSI
DIGITALI
38
lon = □ 1A □ 5A +
- 27
17
Un = 230Vac MAX. Auxiliary Supply 11
Alimentazione Ausiliaria 16
21
H
FRONT-RS252 L 34
37
MS - SCE 1844-R3 BPU ON

UM30A

(21)
25 R1 21
A DISPLAY 10
N.O.
26 11
MICROP. 22
27 R2 7 N.C.
B UM30A 9 (10)
28 8
FUNCTION 18 N.O.
39 R3
29 F27 / 59 20
C R1
F27d / 59d 19 N.C.
41 R2 R4 4
30 F59s 6
F59U R3 5
EA F81 R5 15
R4 17
F59 / 81

˜˜
Uo
UC UA ˜
BT 2 50 PROGR.
R5 14
16
14
44 INT. FAULT BI< 3
BI> 2
EC EB 1
UB _ C
34/38
L/+ 12 KEYBOARD S-
N/- 13 ˜ ˜= S+ 23
24
˜ 9 PIN MALE

IEC 255

24(-20%) - 110(+20%)Vac 24(-20%) - 125(+20%)Vdc 80(-20%) - 220(+20%)Vac 90(-20%) - 250(+20%)Vdc

22
Control & Supervision Relays
• Power Management Relay
• Multifunction 3 Phase Measuring Instrument

Salient Features

• Display of various parameters,


event count & event data on 8 digit
alphanumeric display

• Separate LEDs for


various fault indication

• Four user programmable


output relays

• Built in self supervision &


self testing feature help maintenance

• Easy operation by 5 push buttons

• RS485 Port for


serial communication with “MSCOM”
user friendly software

Model MW33 SPM21 RRS


Description Power management Auto Synchronising Relay Generator load sharing
Device Code 81, 27, 59, 32P, 32Q 25, 27 95
Design Numeric Numeric Static
Functions Available Frequence 2 stages, Auto Synchronising with Active / reactive power
Voltage 2 stage, Adjustable Voltage, Over power
Power factor 2 stage, Adjustable Frequency, Load sharing
Active power 2 stage, Adjustable Phase angle Frequency control
Capacitor reactive power 2 stage. Adjustable Reclose time,
Actual measurement of Freq, Bus Live / Dead operation,
V, I, PF, active power, reactive power Speed Regular Control,
Voltage Regulator Control,
Digital inputs to monitor
CB position
Other Features Display of parameters 110V - 125 V PT input 110 V PT input
MD recording & data logging Display of Parameters, 1 A / 5 A CT input
RS485 Port, Event recording Built in self supervision,
RS485 Port
Burden on CT O.2 VA for 5 A, 0.01 VA for 1 A NA NA
Burden on PT 0.04 VA 0.04 VA < 5 VA
Operating temp 100C to 600C 100C to 600C 100C to 600C
Weight < 2kg < 2kg < 1.5kg
Burden on Auxiliary supply 8.5 VA max 8.5 VA 8.5 VA
Output Contacts 5 C/O 5 C/O 3 N/O
Construction Draw out Draw out Draw out
Dim W x H x D in mm 121 x 158 x 224 121 x 158 x 224 71 x 158 x 224
Panel Cutout 113 x 142 113 x 142 62 x 142

Ordering Information
Auxiliary supply Type 1 20-110 V AC / DC 20-110 V AC / DC or 20-110 V AC / DC or
Type 2 88-264 V AC / DC 88-264 V AC / DC 88-264 V AC / DC
Upto 380 V AC
1A /5A

23
Wiring Diagrams

MW33

25 R1 21 (21)
DISPLAY 10
26
1/5A
11 N.O.
MICROP. 22
27 R2 7 N.C.
MW33 9
28
1/5A 8 (10)
FUNZIONI R3 18
39 FINCTION
29 20 N.O.
19
1/5A 4 N.C.
41 F32 W R1 R4
30 R2 6
F32 VAR 5
32 R5 15
43 Wh R3 17
Un VARh R4
31 16
42 14 14
Un 3
33 PROGR. R5 3
INT.FAULT 2 2
44 1
C 34/38
KEYBOARD S-
23
_ S+
L/+12 TASTIERA 24
L/- 13 ˜˜ ˜ = 9 PIN MALE
In = 5A In = 1A Un = 100V

IEC 255

SPM21

21
DISPLAY R1 10 52
C
25 11
MICROP. 22
UG 7
26
SPM21 R2 9 F
8
FUNCTION
29 18
R3 20 F
F25SX
UB 19
30 PROGR. R1
INT. FAULT 4
41 R4 6 U
5
F+ R2 15
G1 R5 17
UG U
F- R3 16
SPM21 44
52 14 B.I.
U+ R4 BX BR
3
BR 52 (N.O.)
UB 2
U- R5 SX 1
C
S-
34/38
S+
23
L/+ 12 24
KEYBORD
N/- 13 9 PIN MALE
IEC 255

RRS

+ -
- 15
G MEDIA
AVERAGE + 14 To other RRS Relays
12
R1
3
INCREASE
4 13
Operation
-
SETTINGS

1 T +
VOIOCOS
R2 1
7

6 2 DECREASE
OPTO OPTO 17
+ R3
8 - OVER POWER
-
+ 18
9
(.) (.)
Lood Shedding Freq. control

22 21 11 10
2 3 Lood 3 Freq. control
1 2
Shedding
Open Open Yes Open Yes
Open Open Yes Close No
Open Open Yes
Open Open Yes

24
Voltage and Frequency Relays
• 3 Phase Voltage and frequency relay with df/dt & dv/dt
• 1 Phase Voltage and frequency relay

Salient Features

• Display of various
parameters, tripcount
& trip data on LCD screen

• Separate LEDs for


individual fault indication

• Built in self supervision


& self testing feature

• RS485 port for serial


communication with
“MSCOM” software

• Easy operation by
push buttons

Model UFD34 MC1V MC3V


Description 3 Ph Voltage and Single phase Voltage and 3 Ph Voltage and
Frequency Relay Frequency Relay Frequency Relay
Device Code 81, 27, 59, df/dt, dv/dt 27, 59, 81 27, 59, 47, 59 V 0, 81
Design Numeric Numeric Numeric
Functions Available Selectable 4 stages Two Under Voltage elements Two Under Voltage elements
of frequency as Under/ Two Over Voltage elements Two Over Voltage elements
Over frequency One UnderFrequency element One Under Frequency element
Selectable 2 stages of One OverFrequency element One Over Frequency element
voltage as Under/Over Blocking Output and Blocking One Zero Sequence Over Voltage Element
voltage Input One Negative Sequence Under Voltage Element
Selectable 2 stages of df/dt Time tagged multiple event One Positive Sequence Over Voltage Element
Selectable 1 stages of de/dt recording Oscillographic wave form capture
Blocking Output and Oscillogarphic wave form capture Modbus RTU / IEC870-5-103
Blocking Input Display LCD 16 (2 x 8) characters Communication Protocols
Time tagged multiple Display LCD 16 (2 x 8) characters
event recording

Rating 100-125 V 100-125 V 100-125 V


Other Features Display of parameters Display of parameters Display of parameters
Built in self supervision Built inSelf supervision Built in self supervision
Oscillogarphic recording of Modbus RTU / IEC870-5-103 Modbus RTU / IEC870-5-103
input quantities Communication Protocols Communication Protocols
RS485 serial communication Front RS232 Port for Local Front RS232 Port for Local
port on Back Panel Programming Programming
Oscillogarphic recording of input Oscillogarphic recording of input
quantities quantities
RS485 serial comunication port on RS485 serial communication port on
Back Panel Back Panel
Burden on CT Not Applicable 0.1 VA for 1 A, 0.3 VA for 5 A 0.1 VA for 1 A, 0.3 VA for 5 A
Burden on PT 0.04 VA NA NA
Operating temp -100C to 600C -100C to 550C -100C to 550C
Weight < 2.5Kg < 1.5Kg < 1.5Kg
BurdenonAuxiliary 8.5 VA < 7 VA < 7 VA
Output Contacts 4 C/O Contacts + 1 C/O for 4 C/O Contacts + 1 C/O for Self 4 C/O Contacts + 1 C/O for Self
Self supervision supervision supervision
Construction Drawout Drawout Drawout
Dim W x H x D in mm 121 x 164 x 224 83 x 164 x 224 83 x 164 x 224
Panel Cutout 113 x 142 64 x 137 64 x 137
Ordering Information
Auxiliary Supply 20-110 V AC/DC or 20-110 V AC/DC or 20-110 V AC/DC or
88-264 V AC/DC 88-264 V AC/DC 88-264 V AC/DC

25
Wiring Diagrams

UFD34

(21)
25 R1 21
A DISPLAY 10
N.O.
26 11
MICROP. 22
R2 7 N.C.
27 9
B UFD34 (10)
28 8
FUNCTION 18 N.O.
39 R3
20
29 F81 - 1 R1
C N.C.
F81 - 2 19
R2 R4 4
41 6
F81 - 3
30
F81 - 4 R3 5
Fdf / dt R5 15
R4 17
F27 / 59
16
PROGR. 14 14
R5
INT. FAULT BI<
3
BI> 2
1
_ C
34/38
L/+ 12 S-
˜ ˜ =
KEYBOARD S+
23
24
N/- 13 ˜
IEC 255 9 PIN MALE

MC1V

DISPLAY R1
R1 16
16
MICROP.
R2 OUTPUT
R2 18 RELAYS
MC1V 18
OUTPUT 17
FUNZIONI 17 RELAYS RELE’
4 R3 R3
14 DI USCITA
FUNCTIONS 14
RELE’
15 DI USCITA 15
5 1F27
R1 R4
13
2F27
1F59 R2 12
D3 20 DIGITAL
2F59 21 INPUTS
D3 20 DIGITAL D2
R3 INGRESSI
PROGR. 21 INPUTS D1 19
D2 DIGITALI
INT.FAULT 22
R4 D1 19 INGRESSI
DIGITALI
22
TO I/0 RELAY
H EXPANSION
13
L ALL ESPANSIONE
12
DI I/0

C COMUNE
C 3
3 COMUNE
10 A (S+) RS485
Auxiliary Supply 2
RS232 B (S-)
1 A (S+)
Alimentazione Ausiliaria 2 RS485
11 KEYBOARD B (S-)
1
TASTIERA
MS - SCE 1836 - R2 BPMC

MS - SCE 1836 - R2 MS - SCE 1837 - R2


Standard Output I/O Output

MC3V

4 DISPLAY R1
16 R1
A 16
MICROP.
5 OUTPUT
R2 R2
6
MC3V 18
OUTPUT
18 RELAYS

B FUNZIONI 17 RELAYS 17 RELE’


R3 R3
FUNCTIONS 14 14 DI USCITA
7 RELE’
15 DI USCITA 15
F24
8 R4
R1 13
C F27
F47 R2 12 D3 20 DIGITAL
9 INPUTS
F59 D2 21
D3 20 DIGITAL
F27d 19 INGRESSI
R3 INPUTS D1
EA D2 21 DIGITALI
F59d 22
R4 D1 19 INGRESSI
22 DIGITALI
UC UA TO I/0 RELAY
PROGR.
L
13 EXPANSION
R5 H
12 ALL ESPANSIONE
INT.FAULT
DI I/0
EC EB
UB C C COMUNE
3 3 COMUNE
10 A (S+)
Auxiliary Supply 2 RS485
RS232 B (S-)
Alimentazione Ausiliaria 1 A (S+)
2
11 KEYBOARD B (S-) RS485
1
TASTIERA
MS - SCE 1834 - R1 BPMC

MS - SCE 1834 - R1 MS - SCE 1835 - R1


Standard Output I/O Output
26
MV12/MC3V

MC61A/
MD32TM MC61C
MC12/ME12

MC31A/MC61A
MC61C/FMR

MV12/MC3V

SCM21

UFD34, UM30
Schematic - Relay Application

SPM21 RPM8/
MG30/
RPM14
MG30I
MV12
MC61A/MC61C
MRP11

SC14S MM30/
MD32G
G1 G2 MPR300 MCOMP

Motor Motor
APFC Panel

scheme - 1 scheme - 2 scheme - 1 scheme - 2

27
Electrical Standard Products (ESP) Branch Offices:

REGISTERED OFFICE AND L&T House, Group MIG-5 No: 73, Karpaga Nagar, 8th Street
HEAD OFFICE Padmanabhpur K. Pudur
L&T House, Ballard Estate Durg 491 001 Madurai 625 007
P. O. Box 278 Tel: 0788-2213833 / 14 / 21 / 29 Tel: 0452-2537404, 2521068
Mumbai 400 001 Fax: 0788-2213820 Fax: 0452-2537552
Tel: 022-67525656 e-mail: esp-durg@LNTEBG.com e-mail: esp-mdu@LNTEBG.com
Fax: 022-67525858
Website: www.Larsentoubro.com Khairasol, Degaul Avenue EBG North Wing Office-Level 2
Durgapur 713 212 Gate 7, Powai Campus
ELECTRICAL STANDARD PRODUCTS (ESP) Tel: 2559848, 2559849, 2559844 Mumbai 400 072
501, Sakar Complex I Fax: 0343-2553614 Tel: 022-67052874 / 2737 / 1156
Opp. Gandhigram Rly. Station e-mail: esp-dgp@LNTEBG.com Fax: 022-67051112
Ashram Road e-mail: esp-bom@LNTEBG.com
Ahmedabad 380 009 Milanpur Road, Bamuni Maidan
Tel: 079-66304006-11 Guwahati 781 021 12, Shivaji Nagar
Fax: 079-66304025 Tel: 0361-2550562 / 65 North Ambazari Road
e-mail: esp-ahm@LNTEBG.com Fax: 0361-2551308 Nagpur 440 010
e-mail: hazrasudipto@LNTEBG.com Tel: 0712-2260012 / 3
38, Cubbon Road, P. O. Box 5098 Fax: 0712-2260020 / 30
Bangalore 560 001 II Floor, Vasantha Chambers e-mail: esp-nag@LNTEBG.com
Tel: 080-25020100 / 25020324 5-10-173, Fateh Maidan Road
Fax: 080-25580525 Hyderabad 500 004 32, Shivaji Marg
e-mail: esp-blr@LNTEBG.com Tel: 040-67015052 P. O. Box 6223
Fax: 040-23296468 New Delhi 110 015
131/1, Zone II e-mail: esp-hyd@LNTEBG.com Tel: 011-41419514 / 5 / 6
Maharana Pratap Nagar Fax: 011-41419600
Bhopal 462 011 Monarch Building, 1st Floor e-mail: esp-del@LNTEBG.com
Tel: 0755-4098721 / 7 / 8 / 9 D-236 & 237, Amrapali Road
Fax: 0755-2769264 Vaishali Nagar L&T House
e-mail: esp-bho@LNTEBG.com Jaipur 302 021 P. O. Box 119
Tel: 0141-4385914 / 18 191/1, Dhole Patil Road
Plot No. 559, Annapurna Complex Fax: 0141-4385925 Pune 411 001
Lewis Road e-mail: esp-jai@LNTEBG.com Tel: 020-26135048 / 26164048
Bhubaneswar 751 014 Fax: 020-26124910, 26135048
Tel: 0674-6451342, 2436696 Akashdeep Plaza, 2nd Floor e-mail: esp-pnq@LNTEBG.com
Fax: 0674-2537309 P. O. Golmuri
e-mail: esp-bbi@LNTEBG.com Jamshedpur 831 003 3rd Floor
Jharkhand Vishwakarma Chambers
SCO 32, Sector 26-D Tel: 0657-2312205 / 38 Majura Gate, Ring Road
Madhya Marg, P. O. Box 14 Fax: 0657-2341250 Surat 395 002
Chandigarh 160 026 e-mail: esp-jam@LNTEBG.com Tel: 0261-2473726
Tel: 0172-4646840, 4646853 Fax: 0261-2477078
Fax: 0172-4646802 Skybright Bldg; M. G. Road e-mail: esp-sur@LNTEBG.com
e-mail: esp-chd@LNTEBG.com Ravipuram Junction, Ernakulam
Kochi 682 016 Radhadaya Complex
10, Club House Road, Tel: 0484-4409420 / 4 / 5 / 7 Old Padra Road
Annasalai Fax: 0484-4409426 Near Charotar Society
Chennai 600 002 e-mail: esp-cok@LNTEBG.com Vadodara 390 007
Tel: 044-28462072 / 4 / 5 / 2109 Tel: 0265-6613610 / 1 / 2
Fax: 044-28462102 / 3 3-B, Shakespeare Sarani Fax: 0265-2336184
e-mail: esp-maa1@LNTEBG.com Kolkata 700 071 e-mail: esp-bar@LNTEBG.com
Tel: 033-44002572 / 3 / 4
67, Appuswamy Road Fax: 033-22821025 / 7587 48-8-16, Dwarakanagar
Post Bag 7156 e-mail: esp-ccu@LNTEBG.com Visakhapatnam 530 016
Opp. Nirmala College Tel: 0891-6620411-2 / 3
Coimbatore 641 045 A28, Indira Nagar, Faizabad Road Fax: 0891-6620416
Tel: 0422-2588120 / 1 / 5 Lucknow 226 016 e-mail: esp-viz@LNTEBG.com
Fax: 0422-2588148 Tel: 0522-2312904 / 5 / 6
e-mail: esp-cbe@LNTEBG.com Fax: 0522-2311671
e-mail: esp-Lko@LNTEBG.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Larsen & Toubro Limited