Anda di halaman 1dari 2

BUILDING REGULATIONS

Extract,wholebuildin
As an electrician I was often involved in the building and its replacement with fresh air from
Don Holmes installation of extractor fans and cooker hoods in outside the building of reasonable quality. Ventilation
runs the rule kitchens to remove steam and cooking smells. This is required for any of the following reasons:
usually involved finding a suitable outside wall or • provision of outside air for breathing
over Approved window to fit a small or large extractor fan and then • dilution and removal of air borne pollutants
Document F1: wiring the circuit.
My memories of this prompted me to move on to
including odours
• control of excess humidity
Means of a new series of articles on ventilation. I will look at • and the provision of air for fuel burning
Approved Document F1: Means of Ventilation, appliances.
Ventilation which covers the requirements of the Building
and how it Regulation 2000 on ventilation in England and
Wales, and the requirements for installation of
Types of ventilation
affects you extractor fans. Three types of ventilation system are covered in
This latter section I will cover in the second part Approved Document F1: extract ventilation, whole
of the series, for there are a lot more factors to building ventilation and purge ventilation.
consider today before installing an extractor fan.
The revised Approved Document F1 Means of Extract ventilation
Ventilation came into force in April 2006 and only
applies to England and Wales. This is from rooms where most water vapour and
pollutants exit which include bathrooms, toilets and
Requirement kitchens. The extract system may be intermittent or
continuous. The purpose is to minimise the spread
The Approved Document F1 states there shall be of vapour and pollutants to other parts of the
adequate means of ventilation provided for people building.
in the building.
The requirement does not apply to a building or Whole building ventilation
space within a building into which people do not
normally go, which is used solely for storage, or This provides fresh air to the building and helps
which is a garage used solely in connection with a dilute and disperse any water vapour and other
single dwelling. pollutants which have been released throughout
the building. Examples include pollutants from
Purpose of ventilation building materials and furnishings, activities such
as photocopying and odours from the occupants of
Ventilation is the removal of stale indoor air from a the room.

Table 1: Extract ventilation rates


Room Minimum intermittent Continuous extract
extract rate Minimum high rate (l/s) Minimum low rate (l/s)
Kitchen 30 adjacent to a hob; 13 Total extract rate must
or 60 elsewhere be at least the whole
Utility room 30 8 building ventilation rate
in Table 2
Bathroom 15 8
Sanitary accommodation 6

Table 2: Whole buildings ventilation rates


Number of bedrooms in dwelling
1 2 3 4 5
Whole buidling ventilation rateab (l/s) 13 17 21 25 29
Notes:
a. In addition, the minimum ventilation rate should not be less than 0.3 l/s per m2 internal floor area (this includes each floor, eg, for a two-
storey building, add the ground and first floor areas). b. This is based on two occupants in the main bedroom and a single occupant in all
other bedrooms. This should be used as the default value. If a greater level of occupancy is expected, then add 4 l/s per occupant.

6 NAPIT 0870 444 1392 www.napit.org.uk


gandpurgeventilation
Fig 1 Trickle Ventilators

Over the window frames In window frames Just above the glass Directly through the wall

Outside Outside Inside

Inside Outside Inside


Inside
Outside

Purge ventilation Ventilation systems for dwellings


This is to remove high concentrations of Approved Document F1 provides guidance on four
Fig 2 Opening
window
pollutants and water vapour released from types of ventilation systems:
occasional activities. This includes decorating • system 1 – background ventilators and intermittent
and any accidental spillage of water or releases extract fans (Fig. 3)
of smoke from cooking food. • system 2 – passive stack ventilation (Fig. 4)
Purge ventilation is only required when the • system 3 – continuous mechanical extract (Fig. 5)
above activities or similar incidents occur. • system 4 – continuous mechanical supply and
extract with heat recovery (Fig. 6).
Ventilation of buildings The Approved Document allows other systems to be
This can be provided by natural or mechanical used, provided that it can be demonstrated to the
ventilation systems – or even a combination of relevant building control authority that the proposed
Vertically pivoted
both. Examples of this type of ventilation ventilation system will not allow air in the dwelling to
provided for a dwelling would be intermittent exceed the set limits.
extractor fans for the extract ventilation For new buildings extract ventilation to the outside
requirements, trickle ventilators in windows for is required in each kitchen, utility room, bathroom and
whole building ventilation (Fig. 1) and opening toilet. The extract may operate intermittently or
windows to meet the purge ventilation continuously. The minimum extract airflow rates at
requirements (Fig. 2). highest and lowest settings should not be less than
When mechanical ventilation or air those given in Table 1.1a Extract Ventilation Rates, and
conditioning is provided in buildings other than 1.1b Whole Building Ventilation Rates, of the
dwellings, the same ventilators provide whole Approved Document. These are illustrated in the
building, extract ventilation and purge ventilation. Tables 1 and 2 opposite. Top hung opening out

Fresh air
Stale air

Bathroom Bedroom Bathroom Bedroom Bathroom Bedroom Bathroom Bedroom

Lounge Kitchen Lounge Kitchen Lounge Kitchen Lounge Kitchen

Fig 3 Background ventilators Fig 4 Passive stack Fig 5 Continuous Fig 6 Continuous
and intermittent extract fans ventilation mechanical extract mechanical supply and
extract with heat recovery

NAPIT 0870 444 1392 www.napit.org.uk 7

Anda mungkin juga menyukai