Series LFN36
Install No. LFN36 in cold water supply line with or above the highest point in the tank.
No. LFN36-M1 must be installed vertically in an upright position as shown. No valve
is to be placed between the relief valve and the tank. Illustrations show typical and
correct positions. Valve opens on vacuum of not over 12" mercury column. Maximum working pressure: 200psi (13.8 bar). (Maximum steam working pressure:
15psi or 103 kPa.) Maximum temperature: 250F (121C).
Watts No. LFN36
Cold
Hot
Hot
Tank
T&P Relief
Valve
Cold
Tank
T&P Relief
Valve
! WARNING
Not Suitable for Crossconnection Control.
Maximum Temperature:
250F (121C).
Watts No.
LFN36
Watts No.
LFN36
Pigtail
Pigtail
Pigtail
Jacketed
Kettles
Zone Control
Valves
Trap
Air Vents
Trap
LFN36-M1
should be
installed on
supply main on
system side of
control zone
valve.
Unit Heaters
Pigtail (Not
needed for
pressure
under 5 psi).
Trap
Temp.
Regulator
Alternate Installation
Watts No.
LFN36
T&P Relief
Valve
Heating Coil
Pigtails
IS-N36-M1 1325
EDP# 1910930
Watts, 2013