The information provided in this document is intended to be general and does not
cover all possible applications. Any specific application not covered should be
referred directly to ABB, or its authorized representative.
This document must not be copied without our written permission, and the contents
thereof must not be imparted to a third party nor be used for any unauthorized
purpose. Contravention will be prosecuted.
Safety information Safety, as defined in this instruction, involves two conditions:
Keep this instruction available to those responsible for the
installation, maintenance, and operation of the bushing. 1. Personal injury or death.
2. Product or property damage (includes damage to the
The installation, operation, and maintenance of a bushing bushing or other property, and reduced bushing life).
present numerous potential unsafe conditions, including, but Safety notations are intended to alert personnel of possible
not limited to, the following: personal injury, death or property damage. They have been
inserted in the instructional text prior to the step in which the
– – High pressures condition is cited.
–– Lethal voltages
–– Moving machinery The safety conditions are headed by one of the three hazard
–– Heavy components intensity levels which are defined as follows:
–– Slip, stumble or fall
Specialized procedures and instructions are required and
must be adhered to when working on such apparatus. Failure WARNING
to follow the instructions could result in severe personal injury,
death, and/or product or property damage. WARNING indicates an imminently hazardous
situation, which if not avoided will result in death or
Additionally, all applicable safety procedures such as regional serious injury. This signal word is to be limited to the
or local safety rules and regulations, safe working practices, most extreme situations.
and good judgement must be used by the personnel when
installing, operating, maintaining and/or disposing such WARNING also indicates a potentially hazardous
equipment. situation, which if not avoided could result in death or
serious injury.
CAUTION
2. Diagnostics............................................................................................................................8
2.1 Capacitance and tan δ measurement..............................................................................8
2.1.1 Test equipment.........................................................................................................8
2.1.2 Measuring procedure................................................................................................8
2.1.2.1 Dissipation factor test......................................................................................9
2.1.2.2 Capacitance test..............................................................................................11
2.1.3 Interpretation of the measurement.............................................................................12
2.2 Partial Discharge measurements.....................................................................................14
2.3 Dissolved Gas Analysis (DGA).........................................................................................14
2.3.1 Oil sampling from bushing.........................................................................................15
2.3.2 Interpretation of the analysis.........................................................................................15
2.4 Moisture analysis.............................................................................................................16
2.4.1 Oil sampling from bushing.........................................................................................16
2.4.2 Interpretation of the analysis......................................................................................16
2.5 Oil leakage inspection.....................................................................................................16
2.6 Insulator inspection.........................................................................................................16
2.6.1 Hydrophobicity classification.....................................................................................16
2.6.1.1 General............................................................................................................16
2.6.1.2 Test equipment................................................................................................17
2.6.1.3 Test procedure.................................................................................................17
2.6.1.4 Classification of the hydrofobicity.....................................................................17
2.6.2 Sample collection and status determination of silicone grease on
porcelain insulators............................................................................................................19
2.6.2.1 Test equipment................................................................................................19
2.6.2.2 Sample collection.............................................................................................19
2.6.3 Instruction for thickness measurement of silicone grease on porcelain insulators.......20
2.6.3.1 Test equipment................................................................................................20
2.6.3.2 Measuring procedure.......................................................................................20
2.7 Thermovision...................................................................................................................21
2.8 De-polymerization analysis..............................................................................................21
3 Conditioning...........................................................................................................................22
3.1 Cleaning of insulators......................................................................................................22
3.1.1 Porcelain insulators...................................................................................................22
3.1.2 Silicone rubber insulators..........................................................................................22
3.2 Silicone grease treatment of wall bushings......................................................................22
3.2.1 Purchase of silicone grease solvent...........................................................................23
3.2.2 Criteria for reapplication............................................................................................23
3.2.3 Precautions at application and reapplication.............................................................24
3.2.4 Application................................................................................................................24
1. General guide to diagnostics and conditioning of bushings
There are several methods for diagnostics of high voltage 2.1.1 Test equipment
bushings available. In general bushings delivered from ABB
shall be considered maintenance free. However inspection Measuring bridge:
and service experience will in some cases lead to diagnostics The measuring bridge shall be of transformer-ratio arm type.
on bushings. Bridges of this type are available in several designs from
various manufacturers. Examples of measuring bridges:
In the following chapters a guide for different test methods
and interpretations are available. Some methods are today Manufacturer Model
not widely commercial available for site diagnostics. In this Doble Engineering M2H
document they are therefore briefly described. Company
Tettex Instruments 2088
2.1 Capacitance and tan δ measurement Tettex Instruments 2805 Can be used at good interference
conditions
CAUTION Multi-Amp Corporation CB-100 For low voltage only (30 V)
Make sure that the transformer is de-energized and Regarding the handling of the bridge, the manufacturer’s
out of service before any work is performed on the manual shall be consulted.For connecting the measuring lead
bushing. to the test tap, a special adapter must be used for certain
bushings. This device is described in the product information
CAUTION for each type of bushing.
The test tap must not be left open during service. Voltage source:
Check that the earthing spring and the protective When measuring the dissipation factor, a voltage source
cap is put in position after test. The test tap design is must be available, either separate or built into the measuring
shown in the installation and maintenance guides. equipment. The voltage should be adjustable up to at least
10 kV, and as far as possible free from harmonics. To avoid
CAUTION problems when adjusting the null indicator, the voltage ought
to be synchronous with the voltage in the plant.
The testing equipment must not be connected to the
test object before the transformer is de-energized Measuring using digital instruments:
and taken out of service. All windings shall be short- If only the main capacitance C1, is to be measured, and an
circuited, and windings not connected to bushings accuracy of ±3 % is accepted, a simpler method can be used.
under test shall be grounded. The method, described later, only requires a voltage source of
400 V/2 A, two digital instruments and a 10 kW/10 W resistor.
Prior to taking a condenser bushing into service, and on a
suspected fault, the capacitance and dissipation factor can be 2.1.2 Measuring procedure
measured and compared with the values given on the rating When testing a bushing having a capacitive test tap, i.e.
plate or in the routine test report. In connection with these practically all our bushings, it is not necessary to disconnect
tests, the electrical connection between transformer tank and the top of the bushing. It is enough to open the disconnecting
bushing flange shall be checked for instance with a buzzer. switch.
In this product information, the terms tangent delta, For the sake of safety and for reduction of the influence from
tan d, power factor and dissipation factor can be used the winding inductance, all transformer windings shall be
interchangeably. short-circuited. Windings not connected to the tested bushing
shall be grounded. See Fig. 1.
At humid conditions drying of the test tap may be required in The measurement procedure shall begin with a low sensitivity
order to get representative readings for tan δ over C2. An air on the bridge. The sensitivity is then increased gradually to
dryer may be used for drying. Cleaning of the air side insulator the highest possible. In rare cases, external interferences can
housing is indispensable for correct measurement of tan δ make it difficult to set the detector to zero. If the interference
over C1. cannot be eliminated, the sensitivity must be lowered. Table 1
shows the connections to be made, when measuring the
dissipation factor of the different insulations. It is to be noted
that most bridges give capacitance and dissipation factor in
the same measuring operation.
Test voltage
HV lead
Test tap
IC1
LV lead
CL
CHL
CH
Fig. 1. Field testing on bushings using the UST method (Ungrounded Specimen Test).
At 50 Hz R2 U2
C1 = U2/U 1 x 318 [pF] U 2 [mV], U1 [V], R2 = 10 [kW] U1
R2 = 10 kΩ, 10 W
At 60 Hz Voltage source
C 1 = U2/U 1 x 265 [pF] U 2 [mV], U1 [V], R2 = 10 [kW] 0-400 V, 50-60 Hz
Please read and follow the suggested measures in the It shall be pin-pointed that during operation condition, the
succeeding section: outer layer is earthed. Consequently, the insulation between
the outer layer and the mounting flange are not subjected to
Measures for different temperature corrected values OIP an electrical field and do thereby not cause any dielectric heat
and RIP bushings losses. It is likely that if the bushing is placed in contaminated
0-25% increase: areas, contaminants on the outside of the test tap affect
The value is taken to the record. No further measures are to the results. Moisture around the test tap do also affect the
be taken. measurement.
25-40% increase: It shall be pointed out that if the test voltage (500 V if the
The measuring circuit is checked regarding leakage and test-tap insulation is delivery tested with 2 kV and 2.5 to 5 kV
external interferences. External interference can for instance if the test tap is delivery tested with 20 kV) is exceeded partial
be influence from nearby current carrying equipment and discharge may occur in the region of the test tap which also
bus bars. If the difference remains, the gaskets of the oil will affect the measurement.
level plugs are replaced (moisture) according to the product
information for the bushing. The measured value is entered in –– Taking all the variations above into account tan delta over
the record, and the bushing can be taken into service. the test tap insulation use to vary between 0.4-3.0 %.
GOB GOE
Fig. 5. Location of sampling plugs for GOA, GOB, GOC, GOE, GOH and GOG.
The internal pressure of the bushing must not be altered Sampling procedure for GOA, GOC and GOG
before and after the sampling as the bushing is supposed to On the GOA, GOC and GOG bushings the oil samples are
work within a specified interval. This is satisfied if the sample taken from the hole for the oil level plug on the top housing
is taken out when the bushing mean temperature is between according to Fig. 5. If the bushing is vertically mounted the oil
0 °C and 30 °C. level is right at the plug level at 20 °C. The sample is sucked
out by a syringe. If the oil temperature is slightly higher than
The time when the bushing is unsealed shall be as short as 20 °C the oil level will be above the plug level. In such a
possible. Flushing with dry air or nitrogen is normally not case the hose on the syringe should be equipped with nipple
necessary. according to Fig. 6. The oil plug is removed and the hose
with the nipple is attached immediately. If the temperature is
The oil removed from the bushing shall always be replaced slightly below 20 °C, the oil level will be below the plug and
by the same volume of new transformer oil. The new oil shall the sample is sucked out according to Fig. 7. The tightening
comply to IEC 60296, class II and shall be clean and dry. torque for the 5/8" sealing plug shall be 50 Nm.
The old gasket shall always be replaced by a new one when 2.3.2 Interpretation of the analysis
the bushing is sealed after sampling. The interpretation of the analysis is done according to
IEC 61464. If questions remains, ABB Components can assist
Sampling procedure for GOB, GOE and GOH with the evaluation.
The sample is taken from a plug in the top of the bushing,
preferably with a syringe with a rubber hose connected to the
top of the syringe.
CAUTION CAUTION
Make sure that the transformer is de-energized and Make sure that the transformer is de-energized and
out of service before any work is performed on the out of service before any work is performed on the
bushing. bushing
This method for diagnostics can only be used on liquid filled A visual inspection for leakage may be performed at normal
bushings e.g. GOx types. Normally we do not recommend station supervision.
our customers to take oil samples from our bushings. The
bushing is sealed and tightness tested at the time for the 2.6 Insulator inspection
manufacturing. An oil sampling means that the bushing has to
be opened. Thus, it is also a risk for improper sealing after the 2.6.1 Hydrophobicity classification
sampling is finished.
CAUTION
However, when a problem is known, for example high power
factor over C1, there might be a need for oil sampling and Make sure that the transformer is de-energized and
moisture analysis. out of service before any work is performed on the
bushing.
To get the proper moisture content in bushing oil is sometimes
difficult. Compared to a transformer, a bushing has a much The following information for hydrophobisity calssification
higher ration of paper to oil. This means that regardless of is with minor changes taken from STRI AB, Guide 1, 92/1
the bushing manufacturing process, there will always be Hydrofobicity Classification Guide. STRI AB is an independent
much more moisture in the paper than in the oil. (In paper company for development and testing in the field of electrical
the moisture is measured in %, whereas in oil the moisture power transmission and distribution. STRI is jointly owned by
content is measured in ppm, "parts per million".) ABB, Svenska Kraftnät (the Swedish National Grid), Vattenfall
AB and Statnett SF (the Norwegian National Grid).
Depending on the temperature of the bushing, the moisture
will move from the paper to the oil or from the oil to the paper, 2.6.1.1 General
all given by the equilibrium curves (piper diagram) on oil-paper The superior electrical performance of composite insulators
moisture. Due to this, a bushing will always show a much and coated insulators stems from the hydrophobicity (water-
higher moisture content in the oil after a certain time in service repellency) of their surfaces. The hydrophobicity will change
a high temperature. Consequently, to get a proper value, the with time due to exposure to the outdoor environment and
oil sample should be taken at least 48 hours after the entire partial discharges (corona).
bushing has reached room temperature.
Seven classes of the hydrophobicity (HC 1-7) have been
2.4.1 Oil sampling from bushing defined. HC 1 corresponds to a completely hydrophobic
The oil sampling is performed similar as for DGA analysis. (water-repellent) surface and HC 7 to a completely hydrophilic
(easily wetted) surface.
2.4.2 Interpretation of the analysis
The bushing is delivered from ABB Components with a These classes provide a coarse value of the wetting status
moisture content in the insulating oil of maximum 3 ppm. If and are particulary suitable for a fast and easy check of
considerably higher concentrations are measured the sealing insulators in the field.
system is damaged on the bushing.
Complementary equipment which could facilitate the The receding angle is the most important when the wetting
judgement are a magnification glass, a lamp, and a properties of an insulator shall be evaluated. The inclination
measuring-tape. angle of the surface affects the θr.
2.6.1.3 Test procedure Table 4. Criteria for the hydrophobicity classification (HC).
The test area should be 50-100 cm2. If this requirement could
not be met it should be noted in the test report. HC Description
1 Only discrete droplets are formed. θr » 80° or larger for the
Squeeze 1-2 times per second from a distance of 25 ±10 cm. majority of droplets.
The spraying shall continue for 20-30 seconds. The 2 Only discrete droplets are formed. 50° < θr < 80° for the
judgement of the hydrophobicity class shall be performed majority of droplets.
within 10 seconds after the spraying has been finished. 3 Only discrete droplets are formed. 20° < θr < 50° for the
majority of droplets. Usually they are no longer circular.
The hydrophobicity classification could be difficult to perform 4 Both discrete droplets and wetted traces from the water runnels
in high winds. If such difficulties, or other, are present this are observed (i.e. θr = 0°). Completely wetted areas < 2 cm2.
should be noted in the test report. Together they cover < 90 % of the tested area.
5 Some completely wetted areas > 2 cm2, which cover < 90 % of
2.6.1.4 Classification of the hydrofobicity the tested area.
The actual wetting appearance on the insulator has to be 6 Wetted areas cover > 90 %, i.e. small unwetted areas (spots/
identified with one of the seven hydrophobicity classes (HC), traces) are still observed.
which is a value between 1 and 7. The criteria for the different 7 Continuous water film over the whole tested area.
classes are given in Table 4. Typical photos of surfaces with
different wetting properties are shown in Fig. 10.
Qa = advancing angle
Qr = receding angle
AIR
LIQUID Qr
LIQUID
Q
Qa
SOLID
SOLID
CAUTION
Detail of shed
This instruction describes the procedure for thickness Table 5. Conversion no. of scrapping to coating thickness.
measurements of silicone grease on insulators.
Number of scrapings Coating thickness (mm)
3 1.1
4 0.85
5 0.68
6 0.57
7 0.49
8 0.42
9 0.38
11 0.31
Fig. 12.
Fig.13. Measurement indicating poor current path between bushing inner and outer terminal.
In general bushings delivered from ABB Components shall 3.2 Silicone grease treatment of wall bushings
be considered maintenance- free. However inspection and The following method is primary developed for grease
service experience will in some cases lead to conditioning of application on wall bushings in DC operation where uneven
bushings. wetting may be problem for bushing operation. However,
the treatment may also be useful at installations close to the
In the following chapters cleaning of insulators and silicone sea where salted winds may cause external corona even if
grease treatment are described. There are several other extreme arcing/creepage distances are specified.
conditioning methods possible for bushings, such as painting,
RTV coating, preparation with shed-extenders (booster
sheds), etc, not covered in this document. For guidance CAUTION
please contact ABB Components.
Make sure that the transformer is de-energized and
3.1 Cleaning of insulators out of service before any work is performed on the
bushing.
CAUTION
CAUTION
Make sure that the transformer is de-energized and
out of service before any work is performed on the Care should be taken to avoid contact with the skin,
bushing. face and eyes.
ABB AB
© Copyright 2013 ABB, All rights reserved. 2750 515-142 en, Rev. 1, 2013-02-15
Components
SE-771 80 Ludvika, Sweden
Phone: +46 240 78 20 00
Fax: +46 240 121 57
E-Mail: sales@se.abb.com
www.abb.com/electricalcomponents