The object, constructed in accordance with the description, drawings and photographs incorporated in
this Certificate, has been subjected to the series of proving tests in accordance with
This Certificate has been issued by DNV GL following exclusively the STL Guides.
The results are shown in the record of proving tests and the oscillograms attached hereto. The values
obtained and the general performance are considered to comply with the above standard and to
justify the ratings assigned by the manufacturer as listed on page 4 and the dynamic ability to
withstand short-circuits.
This Certificate applies only to the object tested. The responsibility for
conformity of any object having the same type references as that tested
rests with the Manufacturer.
*) as declared by the manufacturer
KEMA B.V.
Shankar Subramany
Director, High-Power
Laboratory
Copyright: Only integral reproduction of this Certificate is permitted without written permission from KEMA B.V. Electronic copies as PDF or scan of this
Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
-2- 2054-19
INFORMATION SHEET
1 KEMA Type Test Certificate
A KEMA Type Test Certificate contains a record of a series of (type) tests carried out in accordance
with a recognized standard. The object tested has fulfilled the requirements of this standard and the
relevant ratings assigned by the manufacturer are endorsed by DNV GL. In addition, the object’s
technical drawings have been verified and the condition of the object after the tests is assessed and
recorded. The Certificate contains the essential drawings and a description of the object tested. A
KEMA Type Test Certificate signifies that the object meets all the requirements of the named
subclauses of the standard. It can be identified by gold-embossed lettering on the cover and a gold
seal on its front sheet.
The Certificate is applicable to the object tested only. DNV GL is responsible for the validity and the
contents of the Certificate. The responsibility for conformity of any object having the same type
references as the one tested rests with the manufacturer.
Detailed rules on types of certification are given in DNV GL’s Certification procedure applicable to
KEMA Laboratories.
TABLE OF CONTENTS
3 Legend ...................................................................................................................... 8
6 Summary of tests...................................................................................................... 11
12 Drawings.................................................................................................................. 50
Version: 1
-5- 2054-19
Rated voltage
• HV side 33 kV X
• LV side 415 V X
Tapping range HV ± 3 x 2,5 %
Rated power HV
• ONAN 1,5 MVA X
Rated power LV
• ONAN 1,5 MVA X
Short-circuit impedance at principal tapping
(measured by KEMA Laboratories)
• HV-LV winding 6,27 % X
Short-circuit impedance at principal tapping
(guaranteed value)
• HV-LV winding 6%
Connection and phase displacement symbol Dyn11 X
Rated frequency 50 Hz X
Category I X
Maximum system short-circuit power 500 MVA X
Guaranteed maximum temperature rise
• top liquid 50 K
• HV windings 55 K
• LV windings 55 K
Insulation levels HV
• LI 170 kV
• AC 70 kV
Insulation levels LV
• AC 3 kV
Insulation levels Neutral
• AC 3 kV
Insulation class A
The manufacturer has guaranteed that the object submitted for tests has been manufactured in
accordance with the following drawings and/or documents. KEMA Laboratories has verified that these
drawings and/or documents adequately represent the object tested. The manufacturer is responsible
for the correctness of these drawings and/or documents and the technical data presented.
The following drawings and/or documents have been included in this Certificate:
Drawing no./document no. Revision
4995001 0
PEL S-3214 0
The following drawings and/or documents are only listed for reference and are kept in KEMA
Laboratories' files:
Drawing no./document no. Revision
4995010 0
347.30 0
4995021 0
4995983 0
MNB-00-000 0
3J-36-00Y0101 00
4995984 0
Version: 1
-7- 2054-19
2 GENERAL INFORMATION
Name Company
Shahid, M. A. Pak Elektron Limited (PEL),
Lahore, Pakistan
Salameh, M. SESCO,
Amman, Jordan
Name Company
Rosman, N KEMA B.V.,
Faber. R. Arnhem, the Netherlands
Gesthuizen, S
Chatzis, I.
Name Company
Uçar, A. KEMA B.V.,
Arnhem, the Netherlands
The guaranteed uncertainty for the measured voltages and currents taking into account the total
measuring system, is less than 5%, unless mentioned otherwise.
Version: 1
-8- 2054-19
3 LEGEND
Phase indications
If more than one phase is recorded on oscillogram, the phases are indicated by the digits 1, 2 and 3.
These phases 1, 2 and 3 correspond to the phase values in the columns of the accompanying table,
respectively from left to right.
Tap position 1
Test number Reactance
Measured between the Calculated per leg Change per leg
phases
%
A-B B-C A-C A B C A B C
Before tests 108,99 107,78 108,48 164,36 160,72 162,80 - - -
AT 190221-6012 109,46 108,03 108,67 165,31 161,03 162,93 0,6 0,2 0,1
AT 190221-6014 109,58 108,19 108,78 165,48 161,32 163,07 0,7 0,4 0,2
AT 190221-6017 109,70 108,19 108,86 165,74 161,22 163,20 0,8 0,3 0,2
After tests 109,90 108,71 109,37 165,71 162,14 164,13 0,8 0,9 0,8
Tap position 4
Test number Reactance
Measured between the Calculated per leg Change per leg
phases
%
A-B B-C A-C A B C A B C
Before tests 91,75 90,67 91,33 138,39 135,15 137,11 - - -
AT 190221-6019 92,43 91,30 91,80 139,54 136,15 137,63 0,8 0,7 0,4
AT 190221-6020 92,44 91,37 91,84 139,50 136,31 137,69 0,8 0,9 0,4
AT 190221-6021 92,46 91,42 91,85 139,54 136,39 137,69 0,8 0,9 0,4
After tests 92,54 91,49 92,11 139,56 136,41 138,25 0,8 0,9 0,8
Tap position 7
Test number Reactance
Measured between the Calculated per leg Change per leg
phases
%
A-B B-C A-C A B C A B C
Before tests 76,54 75,64 76,19 115,44 112,76 114,37 - - -
AT 190221-6023 77,19 76,29 76,78 116,45 113,75 115,20 0,9 0,9 0,7
AT 190221-6024 77,19 76,32 76,84 116,41 113,80 115,33 0,8 0,9 0,8
AT 190221-6025 77,22 76,33 76,85 116,48 113,79 115,35 0,9 0,9 0,9
After tests 77,22 76,33 76,85 116,48 113,79 115,35 0,9 0,9 0,9
Maximum deviation
The maximum deviation in reactance per leg was 0,9%.
The maximum deviation allowed in accordance with the IEC 60076-5 is 7,5%.
Version: 1
-10- 2054-19
6 SUMMARY OF TESTS
Short-circuit tests
190221 190221 190221 190221 190221 190221
Test no.
6012 6014 6017 6019 6020 6021
Tap position 1 1 1 4 4 4
Observations
190221-6012 No visible disturbance.
190221-6014 No visible disturbance.
190221-6017 No visible disturbance.
190221-6019 No visible disturbance.
190221-6020 No visible disturbance.
190221-6021 No visible disturbance.
Version: 1
-12- 2054-19
Observations
190221-6023 No visible disturbance.
190221-6024 No visible disturbance.
190221-6025 No visible disturbance.
Version: 1
-13- 2054-19
A kVRMS 18,8
Applied voltage, phase-to-ground, beginning B kVRMS 18,7
C kVRMS 18,7
A kVRMS 18,3
Applied voltage, phase-to-ground, end B kVRMS 18,3
C kVRMS 18,3
A Apeak 717
Current, HV winding B Apeak 701
C Apeak -753
A ARMS 468
Current, a.c. component, HV winding, beginning B ARMS 476
C ARMS 477
A ARMS 464
Current, a.c. component, HV winding, end B ARMS 471
C ARMS 473
A ARMS 465
Current, a.c. component, HV winding, average B ARMS 460
C ARMS 474
A kApeak 49,1
Current, LV winding B kApeak 53,3
C kApeak -54,0
A kARMS 33,9
Current, a.c. component, LV winding, beginning B kARMS 34,6
C kARMS 34,1
A kARMS 33,5
Current, a.c. component, LV winding, end B kARMS 34,3
C kARMS 33,8
A kARMS 33,4
Current, a.c. component, LV winding, average B kARMS 34,4
C kARMS 34,0
A s 5,06
Duration, current B s 5,06
C s 5,06
Observations
190221-6027 No visible disturbance.
Version: 1
-14- 2054-19
Transformer new.
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1025 hPa
Humidity 10 g/m3
Requirement
None.
Result
The results are for information only.
Version: 1
-15- 2054-19
Requirement
IEC 60076-1, table 1: for the principal tapping: ± 0,5% of declared ratio or ± 1/10 of actual
percentage impedance on the principal tapping, whichever is smaller.
Result
The measured average voltage ratio on the principal tapping is within the tolerances.
Vector group has been verified and determined Dyn11.
Version: 1
-16- 2054-19
Requirement
Item Guaranteed Tolerances Minimum Maximum
value 1) (IEC 60076-1, table 1) allowed value allowed value
Load losses 2) kW 10,83 + 15% n.a. -
Impedance voltage 2) % 6 ± 10% - -
1) In accordance with client’s specification.
2) In principal tapping position at reference temperature.
Result
The results are used for further calculations and are for information only.
Version: 1
-17- 2054-19
U '−U RMS
P0 = P 1 +
Note: The no-load losses are calculated with the formula U ' where U' = 1,11 x Umean
Requirement
Item 1) Guaranteed Tolerances Maximum allowed value
value (IEC 60076-1, table 1)
No-load losses W 1540 + 15% -
Total losses 1) kW - + 10% -
No-load current 1) A - + 30% of the design value -
1) In principal tapping position at reference temperature.
2) In accordance with client’s specification.
Result
The results are for information only.
Version: 1
-18- 2054-19
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the test.
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the test.
Version: 1
-19- 2054-19
8 SHORT-CIRCUIT TESTS
TO
G MB MS L PT R1CS
U
U
U
Load
Short-circuit point earthed
Remarks: -
Version: 1
-21- 2054-19
Remarks
-
Version: 1
-23- 2054-19
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
Short-circuit test
TO
G MB MS L PT R1CS
U
U
U
Load
Short-circuit point earthed
Remarks: -
Version: 1
-35- 2054-19
Remarks
-
Version: 1
-36- 2054-19
Environmental conditions
Ambient temperature 20 °C Ambient air pressure 1036 hPa
Temperature of test object Humidity 10 g/m3
Requirement
None.
Result
The results are used for further calculations and are for information only.
Version: 1
-40- 2054-19
Requirement
IEC 60076-1, table 1: for the principal tapping: ± 0,5% of declared ratio or ± 1/10 of actual
percentage impedance on the principal tapping, whichever is smaller.
Result
The measured average voltage ratio on the principal tapping is within the tolerances.
Version: 1
-41- 2054-19
Result
The results are for information only.
Version: 1
-42- 2054-19
U '−U RMS
P0 = P 1 +
Note: The no-load losses are calculated with the formula U ' where U' = 1,11 x Umean
Result
The results are for information only.
Version: 1
-43- 2054-19
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the test.
Requirement
No collapse of the test voltage shall occur.
Result
The object passed the test.
Version: 1
-44- 2054-19
Environmental conditions
Ambient temperature 18 °C Ambient air pressure 1036 hPa
Temperature of test object 16,2 °C Humidity 10 g/m3
Requirement
No breakdown.
Result
The object passed the test.
Version: 1
-45- 2054-19
On 26 February 2019 the transformer was untanked and the active part was inspected.
The out-of-tank inspection with respect to displacements, deformations of core and windings,
connections and supporting structures or traces of discharges did not reveal any apparent defects.
Version: 1
-46- 2054-19
12 DRAWINGS
Version: 1
-51- 2054-19
Version: 1