Anda di halaman 1dari 28

MM-1230D

Installation and
Maintenance Manual

TRAMP METAL
DETECTOR
MODEL 1230

ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506–1440 U.S.A.


WORLD AUTHORITY IN ADVANCED TECHNOLOGY FOR MAGNETIC, VIBRATORY and INSPECTION APPLICATIONS

Tramp Metal Detector : Model 1230

1
Table of Contents
ERIEZ TRAMP METAL DETECTOR MODEL 1230

OPERATION & DESCRIPTION.............................................................................. 3


INSTALLATION...................................................................................................... 8
START-UP & CALIBRATION................................................................................ 13
SYSTEM PROGRAMMING.................................................................................. 16
TROUBLESHOOTING & MAINTENANCE........................................................... 23

2
Operation & The Detector is influenced only by change. Therefore,
stationary structural members, metal belt cores,
Description symmetrical idlers and other objects which do not
represent a moving mass to the field are not detected.
General Metal belt repair clips are passed by the unit with an
The Model 1230 provides protection to downstream optional clip detector sensor and inhibitor circuit which
processing equipment by detecting the presence of is properly adjusted to the clip signal.
potentially damaging metal objects. It is specifically
designed for use on conveyor systems carrying Physical Description
materials which contain consolidated or fractured Main Control Enclosure
magnetic or non-magnetic ore, as well as ores This enclosure houses and protects the Electronic
ranging in electrical conductivity. The Detector and Interface Modules and also serves as a junction
will discriminate between these conveyed materials box for conduit and cables running to and from the
and tramp metal of any type; ferrous, non-ferrous, Detector. As standard, the Detector is housed in a
magnetic or non-magnetic. steel NEMA 12 enclosure. Other enclosures are
available as options.
The Detector makes use of the latest in solid state
technology. The design includes a number of Visible and accessible on the front panel are:
innovative features: self-test circuits that monitor the Power On/Off Switch, Green Power “ON” Indicator
performance of the detection circuitry; light emitting Lamp, Red Trip Indicator Lamp that lights when
diodes (L.E.D.’s) which indicate the status of the the unit has detected metal and a Reset Button.
test circuits wide programming capability to custom See Figure 1.
tailor the Detector to suit specific application Type: JIC NEMA 4
requirements; and solid state relays to provide Size: 16" x 14" x 6" (406 x 356 x 152 mm)
reliable arc-free switching. Weight: 33 Lbs. (15 kg All Electronics)

Method of Operation Electronic/Interface Modules


During normal operation, the transmitter coil is All the electronics and controls for the Detector are
energized to produce a pulsed electromagnetic contained in two modules, the Interface Module
signal. These signals produce a field that locally and the Electronic Module shown in Figure 2. The
permeates the conveyed material. A piece of metal Electronic Module houses the electronic circuitry and
entering this field absorbs energy emitted from the components associated with metal signal processing
transmitter coil. The metal particle then releases the and analysis. Visible on the front panel of the
energy and this change is detected by the receiver Electronic Module are the Metal Sensitivity control
coil. This technique provides optimum discrimination knob, “Clip Override” control knob and L.E.D.
between tramp metal and the conveyed material. status indicators used to monitor the status of the
Product effect is non-existent or minimal. Detector’s self-test circuits. By removing the front
Having detected metal by a waveform change, panel of the module, all of the electronics are exposed
the signal generated is amplified and filtered. The for calibration and troubleshooting. All connections
signal is then compared to a threshold determined for the Electronic Module are made through a 36-pin
by the size of metal that must be detected. When connector located along the bottom edge of the
the signal exceeds this threshold, the Detector, at module. When the modules are in place, this connector
the appropriate time, triggers solid state relays. mates with a connector on the Interface Module.
These solid state relays in turn switch the line
voltage to the Detector’s output alarm terminals.
Various combinations of alarm horns, belt stop
relays, alarm beacons, etc., can then be activated
by the switched alarm outputs.

Tramp Metal Detector : Model 1230

3
Operation & Mounting Frame
The mounting frame supports the antennas on
Description (cont.) troughed and slider bed conveyors. Special designs
are available to accommodate other types of material
The Interface Module interconnects all external signals handling systems. The swing-away assembly, shown
and power to the Electronic Module. This module in Figure 3, protects the transmitter from oversized
houses the power transformer, solid state relays conveyed materials.
and interface circuit board. Visible on the face of the
Interface Module are system fuses and two terminal Interconnecting Cables
blocks for external wiring; all are clearly identified. The Shielded cables connect the receiver and transmitter
right terminal block, a 13-pin, 3/8" center screw type, to the Main Control Enclosure. 25' (7.62 m) of cable
connects the Detector's external transducers and between the frame assembly and control unit is
signals. The left terminal block, a 7-pin, 7/16" center supplied as standard. Optimum performance is
screw type, is used for all connections handling the assured with cable lengths of 25' (7.62 m) or under.
A.C. line voltage. However, lengths of up to 100' (30.5 m) are acceptable
where detector sensitivity requirements are minimal.
ELECTRONIC MODULE INTERFACE MODULE
Size: 10.5" x 8" x 1.5" Size: 11" x 2.5" x 4" Clip Detector (if applicable)
(267 x 203 x 38 ) (279 x 64 x 102 ) The clip detector consists of a compact sensor head
Weight: 2.5 Lbs. (1.13 kg) Weight: 4.75 Lbs. (2 kg) and mounting bracket. The clip detector senses the
proximity of repair clips as they pass over the sensor’s
Search Coil Assembly head. Once the clips are detected, the Metal Detector
The Search Coil Assembly includes receiver and is desensitized, but not disabled. Any large piece of
transmitter antennas, mounting frame and metal riding on the clips will still trigger the Detector.
interconnecting cables. Each assembly is custom Size: 3.5" x 3.5" x 2" (89 x 89 x 51 )
designed to suit its particular application. Please Weight: 1.25 Lbs. (0.6 kg)
refer to the Frame Assembly Design.

Receiver Coil
The receiver coil is typically located under the
conveyed material within 1" (25.4 mm) of the
conveyor belt.

Transmitter Coil
The transmitter coil Is located opposite and parallel to
the receiver coil. The distance between the transmitter
and receiver (aperture) is typically 2" - 4" (51 mm -
102 mm) greater than the maximum burden depth of
the processed material.

4
Figure 1
16"H X 14'W X 6'D
(406 X 356 X 152 MM)
Steel Enclosure

Tramp Metal Detector : Model 1230

5
Figure 2
Programming Controls & Test Point Locations

6
Figure 3
Swing-Away Frame Assembly

Tramp Metal Detector : Model 1230

7
Installation • The magnetic field generated by the transmitter
oil induces eddy currents in nearby metal cross
PLEASE READ THROUGH COMPLETELY bracing, stairways, handrails and pipes. These
BEFORE BEGINNING WORK! eddy currents may cause false tripping if the
current path intermittently makes contact. Eddy
Unpacking current loops can be broken by cutting the
Upon receipt of the crate(s) containing the Metal conductive paths in these structures. Use
Detector System, inspect the contents for physical non-metallic hardware as required to restore
damage and missing parts. If anything is broken or structural support. If conveyor idlers are used in
missing, please contact the carrier and notify your application, the idlers adjacent to the Search
Eriez immediately. Coil Assembly may require modification or
isolation to break eddy current loops. Refer to the
Site Selection & Preparation Conveyor Idler Modification Diagram (if applicable)
While each application is unique, the guidelines listed for details.
below apply to most installations. Specific information • If the Search Coil Assembly is located where a
concerning your installation can be found in the Frame metal skirt passes through the coils, it must be
Assembly and Control Connection Diagrams. Follow replaced with a 5' (1.5 m) section of non-metallic
the steps listed below to choose the best location for material (I.e., wood or plastic).
the detector. • Relocate or tightly secure moving or vibrating
• Choose a location for the detector so the material pieces of metal such as cables, conduit and
handling system has ample time to react to tramp piping within 36" (914 mm) of the Search Coil
metal. Position the detector far enough in advance Assembly. Remove metallic decking, skirt boards,
of the head pulley so the belt can come to a cross bracing and return idlers below and within
stop before the metal falls off the end of the belt. 3' (0.9 m) of the center line of the receiver coil
If a diverter is used, consider the reaction time of (upstream and downstream).
the system and speed of the conveyor belt.
Mounting Search Coil Assembly
• Select a site with minimum vibration. High vibration Note the material flow direction arrows. Match marks
areas may degrade detector sensitivity and and other identification on the Detector components
shorten component life. before beginning work. Please refer to the Frame
• Locate the Search Coil Assembly away from Assembly Diagram for installation.
sources of airborne electrical interference emitted • Assemble the top crossbar to the vertical upright
from variable-speed drives, large motors, ballasts, supports using four 3/8" x 1" bolts with washers
FM radios, induction furnaces and other radio (provided). Be sure the crossbar is located on the
frequency (RF) sources. Because RF energy upstream side of the upright supports and the
travels along a straight line (line-of-sight), position base of the metal mounting feet angles point in
the receiver coil or relocate RF sources so they toward the belt.
are below or out of the direct line-of-sight with the
top and bottom of the receiver coil. Cables carrying • Assemble the top transmitter coil (with swing-
high voltage or varying loads must be enclosed in away brackets attached) to the upright supports.
steel conduit, grounded at both ends and located The height of the transmitter coil should be as low as
at least 4' (102 mm) from the detector antennas. possible without being hit by overburden. Use two
• Position the entire search coil assembly so that 3-1/2" bolts with washers (provided). Each of the two
the bottom coil (usually the receiver) is equally bolts contains four flat washers and two nuts. Make
spaced between the two adjacent idler rollers. sure two washers are located between the swing-
Center the receiver coil. Do not center the 2" x 2" away bracket and upright support to insure proper
(51 mm x 51 mm) uprights. spacing and freedom of movement.

8
The remaining washers are located at the end of each • Familiarize yourself with the type of electrical
bolt. Hand tighten each bolt with a nut until light drag connections required for this installation and any
is exerted on the swing-away bracket. Tighten the safety precautions before proceeding. Please
second nut against the first nut to serve as a jam nut. refer to the Control Connection Diagram for
Verify that the swing-away brackets are free to move. information about connections and color
code hook-up.
CAUTION: If the swing-away assembly is not
free to move, damage to the transmitter coil • Use an electrician’s conduit punch or drill to make
may result in the event of an overburden. conduit entries on the bottom of the Enclosure.
The Control Connection Diagram shows where
• Position the upright assembly onto the conveyor to position each entry. Remember to remove all
frame with the arrow on the transmitter coil metal shavings when you are finished. Use caution
pointing in the direction of belt flow. to not damage the electronics and to ensure that
• Assemble the receiver coil (mounting brackets no metal particles enter the electronics. Do not
attached) to the upright supports using four run metal conduit along the sides or near the
3/8" x 3-1/2" bolts with washers (provided). Position Search Coil Assembly.
the height of the receiver coil as close as possible • Transmitter and receiver cables should be routed
to the belt. Allow for belt sag under load. Bolt the in conduit. Do not run any power wiring in the same
brackets into place with the nuts and washers conduit or near the transmitter and receiver cables.
facing in toward the belt.
• All line voltage connections terminate at TB2.
• Verify that the search coil assembly is square and Install line voltage cables between devices
all bolts installed are properly tightened. controlled by the Detector including diverters,
• Position the entire search coil assembly so the auxiliary relays, marking devices, alarm horns or
bottom receiver coil is equally spaced from the motor control equipment and TB2 in the Main
idler rollers on either side. Control Enclosure. The direct or timed outputs
• Weld or bolt the metal support feet to the conveyor should not be connected to a Programmable
frame. Be sure unwanted twists and torques in the Logic Controller (PLC) or other low voltage
frame assembly are corrected before you weld. A computer interface equipment that may require dry
twist in the frame may cause the swing-away contact closures. The direct and timed output
bracket to pull away from the upright support. This contacts are typically programmed as Normally
may cause the transmitter coil to bounce from “OFF” at the Eriez. They may be set to Normally
vibration while in operation. “ON” if required. Refer to the System Programming
Section for details.
Mounting Main Control Enclosure • If multiple metal detectors are installed either on
After installing the Search Coil Assembly, select a the same conveyor or on different conveyors
place to mount the Main Control enclosure for ease within 100-feet of each other, the detectors may
of operation. Avoid high vibration areas. Note the need to be synchronized. Please see the Control
length of interconnecting cables and the location of Connection Diagram for details.
the connectors on the receiver and transmitter coils. • Connect a 115/220 VAC (50/60Hz), single phase
Locate the Control Enclosure on the same side of the power line with at least 10 amp capacity to TB2.
conveyor frame as the connectors for ease in routing Make sure to connect an electrical ground to
the cables. terminal #3. The power should be the “cleanest”
• The Enclosure should be positioned so the front available and free of significant voltage variations
panel hinge is on the left side and the indicators or spikes.
are on top. Do not connect the Detector to a line that is used
• Fabricate and install a sun/rain shade for added for operation of motors or motor controls. Proceed
protection over the Enclosure if it is mounted with the Start-Up and Calibration Section before
outdoors. Do not obstruct the natural airflow applying power.
around the Enclosure.

Tramp Metal Detector : Model 1230

9
Installation (cont.) • It is recommended that the Clip Detector cable
running to the Main Control Enclosure be installed
CAUTION: The Interface Module is preset at the in conduit. The same conduit that houses the
Factory for 115 or 220 volt (±10%), 50f60Hz, single transmitter coil cable may be used.
phase operation. If the voltage source is different, • Feed the Clip Detector cable into the conduit
contact Eriez for instructions to select the proper from the Clip Detector end to the Main
voltage source. Control Enclosure.
• Cut off excess cable. Connect wires to terminal
Swing-Away Switch (if applicable) block (TB1) using the supplied spade lugs. Refer
The Swing-Away Cutout Switch (Optional) is a to the Control Connection Diagram for color code
prewired switch mounted on the swing-away bracket. hook-up. Be certain all wires are attached securely
Its purpose is to prevent the Metal Detector from and connected to their proper terminals.
tripping when the transmitter coil is hit by an
• When metal repair clips are used, two or more
overburden of material. Route the free end of this
clips close together must pass directly over the
cable in the same conduit as the transmitter cable to
Clip Detector Sensor in order to activate it. If a
the Main Control Enclosure. Refer to the Control
small patch of clips is used on the belt, which
Connection Diagram for hook-up.
would not pass directly over the Clip Detector,
reference clips are required. Reference clips are
Clip Detector (if applicable)
made by installing two or more clips which will pass
• Refer to Control Connection and Frame
directly over the Clip Detector to trip it when a
Assembly Diagrams.
small patch passes by. Numerous repair and
Position the Clip Detector Sensor approximately (but reference clips on the belt will degrade the
no closer than) 2' (0.6m) from the center line of the Detector's performance because it will frequently
receiver call on the upstream side of the Search Coil be in a desensitized mode.
Assembly. If there are idlers adjacent to the search
coils, position the Clip Detector Sensor approximately Marking Device (if applicable)
1" to 3" (25.4 x 76 mm) upstream of the nearest The Marking Device is a pressurized, solenoid
upstream idler before the Search Coil Assembly. The activated liquid spray system that pinpoints the
flat face of the Clip Detector should be facing toward location of metal to eliminate costly search and
the belt with approximately 1/2"-1" (13 - 25 mm) of down time.
clearance. This clearance must be maintained in
order to assure proper operation. The Clip Detector Specifications
should be a few inches from the edge of the belt. Do Tank Pressure Rating
not mount the Sensor too far from the edge, as tramp 150 psig (10.34 bar)(maximum working pressure)
metal lying close to the belt may trigger the sensor Tank Capacity
and pass through the search coils as a repair splice. 3 Gallons (11.36 liters) (liquid)
Operational Voltage
• With the Clip Detector Sensor in the proper
115/220 VAC (50/60 Hz), 15 Watts
position below the belt, weld the 3/4" support
Air
pipe (provided) to the conveyor frame.
Plant air or any source of 100 to 200 psig
These pipes may be cut to the proper size for an (6.9 = 13.8 bars) inert gas
easier fit. The multi-axis swivel joint will provide
adequate movement for proper adjustment.

10
Ink Marking System

15°F

Tramp Metal Detector : Model 1230

11
12
Installation (cont.) Start-up &
Installation Instructions
• Refer to the Sensing Coil and Frame Assembly
Calibration
Drawing for layout of the Marking Device on the belt. Startup
Before turning on the system, locate the switches
• Position the solenoid support upright and cross
and lights on the door panel and the controls inside
arm as shown. Distance from the coils should be
the cabinet.
3' to 6' (0.9 to 1.8 m). Clamp in place temporarily.
• Position the support bracket of the solenoid spray • The power switch is located on the lower left-hand
valve so that the nozzle is pointed directly on the corner of the door panel, place it in the “ON”
center of the conveyor belt. The nozzle may be position. The green “ON” indicator should light
positioned as shown or on the opposite side of the at this time.
arm. Bolt the bottom of the support frame to the • If the green “ON” indicator does not come on,
conveyor frame. return the power switch to the “OFF” position and
• The solenoid control cable is connected to the inspect the light bulb and fuses. Also check the
Interface Module Timed Output (Terminal TB2, power and wiring for proper connections.
Pins 4 and 5). Route the cable accordingly. • Approximately 5 seconds later, power “ON” the
• Connect the hose between the tank outlet and the No. 1 status indicator (power supply) located on
solenoid valve. the front panel of the Electronic Module will light
(reference Figure 2). This indicates that the power
• Connect the facility air source to the tank’s
supply is fully operational and all the electronics
regulator inlet. Be sure the facility air source is
are enabled.
shut off and no pressure is in the tank.
• If the power supply L.E.D. status indicator or the
• Remove the top of the spray tank.
“ON” indicator does not light, refer to Trouble-
• The spray solution is supplied by the user. The shooting Flow Diagram #1 for instructions. Until
recommended mixture is five (5) fluid ounces the power supply L.E.D. is lit, calibration of the
(0.148l) of colorant, Chrome Yellow (or other unit cannot begin.
contrasting color) manufactured by Tenneco
Chemical (or equivalent) mixed with a two (2) Main Detector Unit – Metal
gallon (7.61) solution of water and antifreeze Sensitivity Calibration
appropriate for local climate conditions (minimum Before proceeding with the calibration procedure,
of 25 % antifreeze). obtain two samples of tramp metal. One piece should
• Mix the solution and pour it into the holding tank. be larger than the minimum size to be detected and
Replace the cap. the other smaller. These samples will be used to
• Verify that the pressure regulator valve is closed calibrate the Detector and should represent the type
prior to turning on the facility air. of metal most likely found in the conveyed material.
The clip timer, L.E.D. No.7, cannot be lit during
• Apply the facility air and adjust the pressure
calibration. This results in erroneous data Calibration
regulator between 60 and 100 psig (4.13 and
adjustments to be performed using controls on the
6.7 bars), as noted on the pressure gauge on top
Electronic Module in the following manner:
of the holding tank.
1. Set the “Metal Sensitivity” control knob, located on
Calibration of Marking Device the front panel of the Electronic Module, to the
• Refer to System Programming - Delay Before middle of the dial (reading of 5).
Alarm and Time Alarm On to set the desired 2. The Detector discriminates between interference
timing for marking a predetermined location. and a signal given off by tramp metal. The tramp
• Using a sample piece of tramp metal, with the metal must enter the sensing coil at the direction
belt operating at normal load, adjust the Marking and speed of normal belt flow before the Detector
Device timing by trial and error. will alarm.

Tramp Metal Detector : Model 1230

13
Start-up & Main Detector Unit – Clip Detector
Calibration (if applicable)
Calibration (cont.) • Turn the “Clip Override” control knob fully
clockwise to position 10 on the dial. This knob
However, the “Metal Signal” L.E.D. No. 2 will light is located on the front panel of the Electronic
anytime moving metal is in the sensing field. Module as shown in Figure 2.
When calibrating the system, be careful not to • Observe the reference clips to see if they are
introduce extraneous metal into the field in the passing within 1" (25.4 mm) of the Clip Sensor
form of rings, belt buckles, keys, steel-toed shoes, Head when the belt is empty. Adjust the Clip
etc. When calibrating the system, it is best to set Detector if it is not within this distance, making
the metal to be detected on a cardboard box (with sure that the clips or the belt do not hit the Clip
no staples) at the appropriate height and pass at Detector Sensor Head when the belt is fully
the speed and direction of belt flow. loaded. If the clip is located properly, the clip timer,
3. Pass the larger sample piece of metal between status indicator No. 7, located on the Electronic
the coils at the height of the average burden and Module will light for approximately 1 second each
at a speed comparable to belt travel. If the time the clips pass over the Clip Detector Head.
Detector does not trip on the test sample, turn the
“Metal Sensitivity” control knob to a higher NOTE: If the Clip Detector is spaced more than
sensitivity (in the direction of ascending numbers) 1" (25.4 mm) from the passing clips, erratic
so the Detector will trip just as the metal is passed performance may occur.
between the coils. In the event that the unit • If the Detector is tripping on the clips with a “Clip
doesn’t trip with the “Metal Sensitivity” control Override” setting of 10, refer to System
knob on 10, check to see if the metal signal L.E.D. Programming - Clip Gain.
No. 2 lights as the metal is passed through the
• Gradually turn the clip control knob counter-
field. If the L.E.D. does not light as the metal is
clockwise to a lower setting until the unit trips on
passed through the field, additional sensitivity may
the largest set of repair clips on the belt.
be required. In this case, please refer to System
Programming - Metal Gain. If the L.E.D. does light • Turn the clip control knob clockwise one number
and the unit won’t trip. Refer to Troubleshooting higher as a safety factor.
Flow Diagram #1. NOTE: This setting should be periodically checked
4. Pass the smaller sample piece of metal between to compensate for shifting of the conveyor belt.
the coils in the same manner as the larger piece. Turn the control knob to a “0” setting if the Clip
The unit should not trip when the small piece of Detector is not used.
metal passes between the coils. If the unit does
trip, adjust the “Metal Sensitivity” control knob Operation
until it does not trip on the metal. The Detector may be programmed to operate in a
5. Repeat Steps (3) and (4) until the system accepts manual or an automatic reset mode. The standard
the larger piece of metal and rejects the smaller. mode of operation is manual reset.
When the final setting is made, note the number
on the control knob for future reference. If this Manual Reset
number is greater than 8, increase the gain of the In the manual reset mode, once the unit has tripped,
Detector as described in System Programming - the Detector’s Direct Output provides a continuous
Metal Gain. alarm indication to alert the operator of detected
metal and/or to stop the belt. To reset the unit, the
reset button located on the front panel must be
manually depressed.

14
Figure 4
Programming Controls & Test Point Locations

Tramp Metal Detector : Model 1230

15
Start-up & System
Calibration (cont.) Programming
Automatic Reset General
The Detector may be converted to an “Automatic The Detector provides a wide range of programming
Reset Mode”. In this mode, the Detector will capability. The Detector can be individually tailored
momentarily signal when tripped then self-reset to the customer’s specific requirements; taking into
according to the placement of the programming account the type and size of metal to be detected,
switches. For complete programming instructions, the type of material being conveyed and the mode
refer to System Programming - Manual/Auto Reset and combination of alarm signals required.
Manual Reset.
Removing/Replacing Cover
Remote Reset To program the Electronic Module, the cover must be
Provisions have been made to externally reset the removed. Remove the control knobs with the 1/16"
Detector from a remote location. Wire a normally Allen wrench (provided). Unscrew the six screws
open set of contacts across the remote reset securing the cover with the 5/64" Allen
terminals TB1 pins 1 and 2 located on the Interface wrench (provided).
Module. Upon closure of the contacts, the unit
will reset. When replacing the cover, it is essential to re-index
the control knobs. Before tightening the set screw,
Excessive Electrical Interference line it up with the flat of the shaft. The knob, when
The Metal Detector has a unique circuit that properly indexed, will indicate 10 in a full clockwise
distinguishes electrical noise from a legitimate metal position and 0 in a full counterclockwise position.
signal. When this circuitry “sees” interference that
lasts longer than .1 second, or that interferes more Metal Gain
than 25% of the time, the Detector will turn off L.E.D. When a piece of tramp metal passes through the
status indicator No. 4 each time the interference search coils, a change in the received signal occurs.
occurs. In addition, the incoming “noisy” signals are This change is extremely small and must be amplified
blocked from downstream circuitry to reduce the to produce a suitable signal to trigger the relay
chance of any false tripping. driver circuitry.
If an excessive amount of electrical interference The amount of gain required in the receiver circuitry
occurs, the source of the interference must be found depends on the following factors:
and corrected. Excessive interference will reduce the
• Coil Length
Detector’s sensitivity and may false trigger the system.
Such interference problems are usually associated • Coil Aperture
with motor phase to ground shorts, severely arcing • Belt Speed
brushes on motors, poor ground conditions, etc. • Type of Metal to be Detected
• Size, Shape and Orientation of the Metal to the
Search Coils
The internal gain of the Detector is adjusted by a
rotary switch, S4, located inside the Electronic
Module (refer to Figure 4). Each step in gain
represents an increase over the last step. Ideally, the
gain is adjusted to pick up the desired piece of tramp
metal with the “Metal Sensitivity” control knob located
on the outside of the Electronic Module set to 5.

16
If the gain must be changed, use a sample of tramp For calibration of the clip gain, follow the steps below:
metal the same size as the piece to be detected and
• Run the belt at normal running speed and
follow the procedures listed below:
maximum belt load.
• Remove the control knobs and cover of the • Verify that the clip timer, status indicator No. 7,
Electronic Module as indicated in Section IV. A. lights each time a clip passes the sensor head.
• Set the “Metal Sensitivity” control knob (R70) to its If it does not, adjust the clip sensor head as
rotational midpoint. (If the cover was not removed, described in Installation - Clip Detector.
the “Metal Sensitivity” setting would be 5). • Adjust the “Clip Override” control knob, shown in
• Check that the clip timer, status indicator No. 7, is Figure 2, to a setting of 5.
not lit during any portion of this test. If the clip • Remove the cover as described in System
timer is lit, the data will be incorrect. Programming - General without changing the
• Pass the sample piece of tramp metal completely setting on the “Clip Override” control.
through the coils at a height midway between the • Adjust the Clip Gain, Switch S5 shown in Figure 4,
transmitter and receiver coils, and at a speed to the highest gain that does not trip the Detector
near that of the conveyed material under normal when the clips pass. If the unit continues tripping
operating conditions. even at the minimum clip gain of 1, the
Increase or decrease the gain of the system with the desensitized length of the belt may be too short.
rotary switch as needed until the Detector will trip just In other words, the system is switched back to full
as the sample metal is passed between the coils. The sensitivity before the clips are completely out of
larger numbers on the gain setting switch correlate to the Detector's field. To correct, increase the clip
a higher gain. The lowest gain being 1 and the highest detector time delay as described in System
0 (representing 10). If the unit never trips, refer to Programming - Clip Detector Time Delay.
Troubleshooting Flow Diagram #1. • If all other functions are properly programmed,
replace the cover as described in System
• If all other functions are properly programmed,
Programming - General. Return the controls
replace the cover and knobs. Re-index the
to recorded settings.
control knobs as indicated In System
Programming - General. • Calibrate the “Clip Override” as described in
Start-up and Calibration - Main Detector Unit -
• Recalibrate the “Metal Sensitivity” control knob
Clip Detector Calibration.
as instructed in Start-up and Calibration - Main
Detector Unit - Metal Sensitivity Calibration.
Clip Detector Time Delay
Clip Gain If the clip detector is used, the length of belt
When belt repair clips are used on a conveyor belt, desensitized to permit the clips to pass can be
the repair clips represent a stronger metal signal adjusted by properly programming the clip detector
than the tramp metal. In this situation, it is necessary time delay switches S1-5, 6 & 7. The locations of
to reduce the gain of the system to allow the clips to these switches are shown in Figure 4. The range
pass. Rotary Switch S5, shown in Figure 4, of delay times is from .10 seconds to 2.93 seconds
establishes the gain whenever the clip detector circuit as tabulated in Table 1. These switches are set at
is energized. In the event that Switch S5 is set higher the factory according to customer requirements and
than S4, the system will choose the smaller gain should not be adjusted unless absolutely necessary.
setting of the two. As long as the Detector is desensitized, the clip timer,
status indicator No. 7, will remain lit.

Tramp Metal Detector : Model 1230

17
System TABLE 2
S2 – Delay Before Alarm
Programming (cont.) S3 – Time Alarm On

TABLE 1
Clip Time Delay
(Switch S6)

Delay Before Alarm


The timed output alarm can be accurately
programmed with a time delay before turn on. This
allows the conveyed material to travel for a programmed
period before the timed output alarm signal is energized.
Typically, this feature is used in conjunction with a
marking device or diverter gate to delay the system
until the detected tramp metal has reached the
auxiliary equipment. Switches S2-1 through S2-5
control this time delay from .01 to 22.0 seconds. Refer
Time Alarm On
to Table 2 for tabulation of the delay time versus switch
The timed output can be accurately programmed to
settings and Figure 4 for the switch locations.
remain energized for a timed period once it is switched
on. This feature can activate a diverter gate,sound an
alarm for a given period, command a marking device
to spray a given length of the belt, etc. Switches S3-1
through S3-5 control this time delay from .01 to 22.0
seconds. Refer to Table 2 for a tabulation of the delay
time versus switch settings and Figure 4 for the
switch locations.

18
Standard or Fail-Safe Automatic Reset
Output Operation The Detector may be converted to an “Automatic
As standard, the alarm outputs of the Detector will Reset Mode.” In this mode, the Detector will
energize when tramp metal is detected. In this mode, momentarily signal when tripped then self-reset.
the solid state relay is programmed to operate in a
The direct output can be programmed to automatically
normally “OFF” condition. The outputs will not energize
reset by shorting the remote reset terminals TB1 pins
until metal is detected.
1 and 2, located on the front of the Interface Module.
TABLE 3 To “short”, install a jumper from pin 1 to pin 2. Open
S2 – Direct Output Normally On/Off Select Switch S2-7.
S3 – Timed Output Normally On/Off Select
The operating mode of the timed output is governed
by the position of Switch S3-7 as shown in Table 4.
With the switch in the open position, the timed output
operates In the Automatic Reset Mode. When the
switch is closed, the timed output will follow the mode
programmed on the direct output.

TABLE 4
Timed Output Reset Mode (S3)

Provisions have been made to program the Detector


to operate in a fail-safe mode. In this mode, the
outputs of the Detector are always energized and
de-energize when tramp metal is detected or when
power to the Detector is turned off. In the fail-safe
mode, the solid state relay is programmed to operate
in a normally “ON” condition. TABLE 5
Bell Reset Override (S2 )
Both outputs can be independently programmed. The
direct output (status indicator No. 9) and timed output
(status indicator No. 8) will monitor the alarm's output
condition. If the status indicator is lit, its associated
output is energized. Switch S2·6 controls the direct
output and S3·6, the timed output as shown in Table
3. To operate the solid state relay in a normally “OFF”
condition, open the appropriate switch. Conversely, to
operate the relay in a normally “ON” condition, close
the switch.

Manual/Auto Reset Reset Override


Manual Reset If required, the Detector can be programmed so the
In the manual reset mode, once the unit has tripped, system is disabled during the reset period. This means
the Detector’s Direct Output provides a continuous the Detector is prevented from tripping as long as a
alarm indication to alert the operator of detected reset signal is provided, either manually on the front
metal and/or to stop the belt. To reset the unit, the panel or remotely through a set of external contacts.
reset button located on the front panel must be
manually depressed.

Tramp Metal Detector : Model 1230

19
System
Programming (cont.)
With S2-7 in the open position, the reset signal does
not disable the Detector. Closing S2-7 will program
the Detector so it is disabled while a reset signal is
applied. Refer to Table 5.

Sampling
The Detector Sampling Mode is set at the factory
to make the Detector sensitivity selective between
various materials as required for each particular
application. Switches S1-1 through S1-4 inclusive
are preset and are not to be adjusted by the user.

Fine Frequency Select


The Detector is calibrated to operate at a transmitting
frequency of 1380 Hz when using a 60 Hz line
frequency, and 1350 Hz when using a 50 Hz line
frequency. This frequency can be fine-tuned over a 5%
range by adjusting potentiometer R96, shown in Figure
4. However, this is not usually necessary as all units
are calibrated at the factory prior to shipment
The operating frequency of the Detector can be
measured at the zero gate test point “Z” shown in
Figure 4. The signal switches between 0V and +15V
as referenced to 0V of the system (Test Point 0V). If
viewed on an oscilloscope, this signal would be low
for seven counts and high for one.

20
TABLE 6
Programming Controls Summary

Tramp Metal Detector : Model 1230

21
22
Troubleshooting Electronic Module Troubleshooting
In the event that the unit does not operate and the
& Maintenance trouble has been traced to the Electronic Module,
consult Eriez or its representative.
Status Indicators
In order to facilitate troubleshooting of the Detector, Maintenance Kit
a number of self-test circuits have been designed to Prior to shipment, a maintenance kit is packed in the
monitor the condition of the detection circuitry. The Main Control Enclosure. This kit contains all parts
results of these test circuits are visible to the operator necessary for basic maintenance. The items included
through L.E.D.’s on the front panel of the Electronic are as follows:
Module (refer to Figure 2). These L.E.D.’s are referred (1) 1 Amp Fuse
to as Status Indicators. For a description of what each (1) 10 Amp Fuse
L.E.D. monitors and their normal operating condition, (2) Spare Bulbs
refer to the Status Indicator Summary (Table 7)on the (1) 1/16" Allen Key Wrench
next page. (1) 5/64" Allen Key Wrench
Troubleshooting Flow Diagrams NOTE:
Before working with Troubleshooting Diagrams,
check all terminals, connectors and cables for
open circuits and correct as required.
To aid in troubleshooting the Detector, three easy-to-
follow, step-by-step, flow diagrams were designed.
Troubleshooting Flow Diagram #1 deals with insufficient
metal sensitivity. This diagram is used if the unit detects
metal, but is not sensitive enough for the required
application or if the Detector does not respond to
metal at all.
Refer to Troubleshooting Flow Diagram #2 if the unit
continually false trips (triggers with no metal in
the field).

Tramp Metal Detector : Model 1230

23
Troubleshooting &
Maintenance (cont.)

TABLE 7
Electronics Module Status Indicator Summary

24
MODEL 1230
Troubleshooting
Flow Diagram #1
***
Insufficient
Metal Sensitivity

25
Tramp Metal Detector : Model 1230
Maintenance (cont.)
Troubleshooting &

26
MODEL 1230
Troubleshooting
Flow Diagram #2
***
False Tripping
Tramp Metal Detector : Model 1230

27
EM 80E6
IM8015
Note: Some safety warning labels or guarding may have been removed before photographing this equipment.
Eriez and Eriez Magnetics are registered trademarks of Eriez Manufacturing Co, Erie, PA ©2011 Eriez Magnetics All Rights Reserved

World Authority in Advanced Technology for Magnetic, Vibratory and Inspection Applications
Headquarters: 2200 Asbury Road, Erie, PA 16506-1440 U.S.A.
Telephone: 814/835-6000 • 800/345-4946 • Fax: 814/838-4960 • International Fax: 814/833-3348
Web Site: http://www.eriez.com e-mail: eriez@eriez.com
Manufacturing Facilities: AUSTRALIA • BRAZIL • CANADA • CHINA • INDIA • JAPAN • MEXICO • SOUTH AFRICA • UNITED KINGDOM • UNITED STATES

811-3M-AHA-SHAM ERIEZ MANUFACTURING CO ©2011 PRINTED IN USA

28

Anda mungkin juga menyukai