Anda di halaman 1dari 24

n° 168

lightning and
HV electrical
installations

Benoît de Metz-Noblat

Following graduation from the ESE


engineering school, worked for
Saint-Gobain first as a research
engineer, then in maintenance and
new projects on a production site.
Joined Merlin Gerin in 1986 and is
currently in the Network Research
Section where he directs a group
investigating overvoltages,
harmonics and the dynamic stability
of networks.

E/CT 168 first issued june 1994


glossary

BIL: (Basic Impulse Level): the impulse Note


voltage that the insulation of a device is Voltage levels have been classed in various manners, defined by national and
designed to withstand. international standards as well as by specifications issued by certain electricity
Gas-insulated metal-enclosed distribution utilities. The following are definitions for alternating voltages greater than
substation: a substation which is made 1,000 V:
up of only gas-insulated (generally ■the French regulation dated 14 november 1988 defines two voltage levels:
SF6) metal-enclosed switchgear, often
HTA (High Voltage A) = 1 kV < U ≤ 50 kV,
referred to in as GIS (Gas-Insulated
Switchgear) in EHV applications. HTB (High Voltage B) = U > 50 kV.
Must not be confused with metal-clad ■ CENELEC (European Electrotechnical Standardisation Committee) defined two
switchgear which is placed in separate levels in a document issued on 27 july 1992:
compartments with metal partitions MV = 1 kV < U ≤ 35 kV,
(see IEC 298). HV = U > 35 kV.
MCOV: (Maximum Continuous ■ IEC 71 defines a range of maximum voltages for equipment:
Operating Voltage): the maximum range A = 1 kV < U < 52 kV,
continuous voltage that a lightning range B = 52 kV ≤ U < 300 kV,
arrester is designed to withstand. range C = U ≥ 300 kV.
pace voltage: voltage that may appear A revision is planned and will result in only two ranges:
between the feet of someone walking. range I = 1 kV < U ≤ 245 kV,
range II = U > 245 kV.
■ the French electrical authority (EDF) presently uses the definition laid out in the
French regulation mentioned above.

Note: The acronyms EHV and UHV, though occasionally used, have never been
officially defined by a standard. In this document, EHV is used for voltages greater
than 300 kV.

Cahier Technique Merlin Gerin n° 168 / p.2


lightning and HV electrical installations The goal of this «Cahier Technique»
publication is to:
■ present an overview of lightning
phenomena and their effects on
electrical installations,
■ present currently available means to
protect installations and limit
detrimental effects,
■ discuss problems concerning
continuity of service,
summary ■ indicate the main steps in lightning
studies on the basis of an example
involving an EHV installation developed
1. Introduction p. 4 by the Network Research Department
2. Lightning General p. 5 at Merlin Gerin.
Main characteristics p. 5 This document deals in particular with
Lightning forecasting p. 6 the transmission and distribution of
electricity over medium and high-
Impact mechanism and
voltage networks. When designing
electro-geometrical model p. 7
these networks, the effects of lightning
3. Lightning and electrical Lightning strikes on a line p. 8 must be taken into account for
installations Wave propagation p. 9 insulation coordination. Low-voltage
Effects of lightning p. 10 aspects are also mentioned, but in no
4. Protection General p. 10 great detail.
Protection level 1 p. 11 A short bibliography is included in the
Protection level 2 p. 12 appendix.
Protection level 3 p. 12
Protection distance p. 13
Network operation and
non-availability p. 16
Standards p. 17
5. Example of a lightning study General p. 19
Calculation methods p. 19
Substation modelling p. 19
Deterministic simulations p. 20
Statistical calculation of lightning
frequencies and the associated
risks p. 20
Interpretation of calculations p. 22
6. Conclusion p. 23
Appendix: bibliography p. 24

Cahier Technique Merlin Gerin n° 168 / p.3


1. introduction

Lightning is a major source of distur- availability, continuity of service, etc.) knowledge on lightning mechanisms is
bances for all electrical installations and must be taken into account, as well as available.
can affect them in several manners: the permanent necessity to minimise The two steps are:
■ all power and voltage levels are the costs of the production and the use ■ anticipate what can happen in a given
concerned, ranging from EHV of electrical power. It may be said that installation and recommend
transmission systems to integrated in the efforts to improve the above improvements. This is possible using
circuits and including LV power factors, lightning has come to dedicated software, validated by
supplies and data transmission circuits, constitute an obstacle. That explains experience, that simulates installation
■ it can cause transient disturbances to why it is now one of the major behaviour.
■ carry out an engineering and cost
the continuity of service, thereby preoccupations of everyone in the
study on insulation coordination, taking
reducing the quality of the power supply sector, whether they are distributors
into account the cost of installations,
system, (EDF, private companies),
maintenance and disruptions in
■ it can damage equipment and result manufacturers (Merlin Gerin, etc.), operation.
in long interruptions in installation designers (design offices, engineering
firms) or installers. Note: insulation coordination consists in
operation,
defining, on the basis of the voltage
■ it can be dangerous for life (pace A study on the effects of lightning and overvoltage levels likely to occur in
voltage, increased potential of exposed comprises two steps, but first requires an installation, one or several levels of
conductive parts and earthing circuits). in-depth knowledge of the protection against overvoltages, then in
Lightning has always been a source of phenomenon. Starting in the 1970's, selecting installation equipment and
disturbances for users of electricity, yet major international research programs protection devices. This subject is
the fairly recent and growing demand were initiated, notably by EDF in covered in the «Cahier Technique»
for quality electrical systems (reliability, France, and today, sufficient n° 151.

Cahier Technique Merlin Gerin n° 168 / p.4


2. lightning

Following a few general indications on The cloud-to-earth electrical field may ■ ascending lightning strikes, in which
atmospheric electrical phenomena, this reach up to -15 to -20 kV/meter on flat the leader runs from the earth to the
section presents: terrain. However, the presence of cloud (mountainous terrain),
■ the main characteristics of lightning, obstacles locally increases and ■ negative lightning strikes when the
considered from an engineering point of deforms the electrical field by a factor negatively charged part of the cloud
view, of 10 to 100, or even 1,000, depending discharges (80 % of lightning strikes
■ information on forecasting, on the form of the irregularities under temperate climates),
■ the impact mechanism using the (sometimes referred to as the point ■ positive lightning strikes when the
electro-geometrical model. effect). The air ionisation threshold positively charged part of the cloud
(approximately 30 kV/cm) is then discharges.
reached and discharges due to the
general corona effect take place. For relatively
The earth and the electrosphere large objects (skyscrapers, main characteristics
(conductive zone of the atmosphere, smokestacks, towers), these Wave form
ranging in thickness from roughly 50 discharges may result in lightning Lightning, as a physical phenomenon,
to 100 km) constitute a natural, strikes or orient them. corresponds to an impulse current
spherical capacitor which charges by Classification of lightning strikes source, that is a series of discharges of
ionisation, producing an electrical field, A lightning strike between a cloud and a quantity of electricity over a short
some several hundred V/m (Volt/ the earth comprises two phases, first period of time.
meter) in strength, directed toward the the development of a predischarge or The actual wave form is quite variable
earth. leader (an ionised channel), which and comprises a steep front to the
In that air being a poor conductor, provokes the lightning strike itself, a maximum amplitude (ranging from a
there is a permanent conduction discharge of a visible, high-current arc. few to 20 microseconds), followed by a
current associated with the electrical Two main criteria distinguish lightning long decreasing tail of several tens of
field, of approximately 1,500 A for the strikes, their direction and their polarity: microseconds (see fig. 1).
entire earth. Electrical equilibrium is ■ descending lightning strikes, in which The associated spectral field covers a
maintained by discharges via points, the leader runs from the cloud to the band ranging from 10 kHz to several
rain and lightning strikes. earth (relatively flat terrain), MHz.
The formation of storm clouds, in effect
masses of water in the form of
aerosols, is accompanied by
electrostatic phenomena in which
differently charged particles separate. 0 25 50 75 100 125 150
The light, positively charged particles 0
are drawn upward by ascending air time
currents and the heavy, negatively - 20 in µs
charged particles fall under their own
weight. There may also be clusters of
positive charges at the bottom of
- 45
clouds where there is intense rainfall.
On the overall macroscopic scale, a
dipole exists.
When the limiting gradient of the
breakdown voltage is reached, a I in kA
discharge takes place in the cloud,
between clouds or between the cloud
and the earth. The latter case is called fig. 1: oscillogram of a lightning impulse current.
lightning.

Cahier Technique Merlin Gerin n° 168 / p.5


Amplitude of lightning strikes
The experimental statistical distribution
of lightning strikes as a function of their probability
amplitude follows a normal distribution 99.9 %
as illustrated in figure 2.
Wave front
99
The distribution of lightning strikes as a
function of front steepness is illustrated IEEE
in figure 3. average
90
For lightning studies, the following
values are generally used: 80
■ amplitudes of 100 kA or 200 kA, with 70
respective probabilities of 5 % and 1 % 60
50
that the level will be exceeded, 40
positive
■ triangular wave form with a 2 µs front lightning
30
duration and a 50 µs time to half value, strikes
20
i.e. a 50 or 100 kA / µs front.
10
Note: this front duration is not that of negative
the standardised wave (1.2 µs) defined 5 lightning
for laboratory testing (see IEC 60). strikes
Charge of lightning strikes 1
On average, the charge is a few tens of 0.5
coulombs, but may exceed 300 C. 0.1
1 2 5 10 20 50 100 200 1,000 amplitude (kA)
lightning forecasting
In France, the Météorage lightning
observation network was set up fig. 2: experimental statistical distribution of positive and negative lightning strikes as a function
in 1986. of their amplitude (IEEE).

This network comprises detection


stations spread over the entire country
and linked to the operational computing probability
centre in Paris.
The stations, positioned 200 to 300 km 99.9 %
from one another, measure the
99.5
electromagnetic waves created by 99
storm discharges up to 800 km away. 98
Storms can be characterised on the 97
96
basis of the following measured data: negative
■ location, 90 lightning
■ date and time (to the millisecond), 80 strikes
■ wave polarity (> 0, < 0), 70
■ wave amplitude (0 to several 60
hundred kA), 50
40
■ number of arcs. positive
30
Météorage offers a number of useful lightning
20
services for a wide range of strikes
10
applications, in particular the
transmission and distribution of 5
3
electrical power. Among the services
offered are warnings, indications, 1
observations, monitoring, assessments, 0.9
di
qualification, consulting and statistics. (kA / µs)
0.1 dt
The following two forecasting elements 0.1 0.5 1 2 5 10 20 50 100
are used in lightning studies.
Keraunic level Nk fig. 3: experimental statistical distribution of positive and negative lightning currents as a
This corresponds to the number of days function of front steepness (IEEE).
per year when thunder is heard at a

Cahier Technique Merlin Gerin n° 168 / p.6


given location. Though at first glance, ■ an electro-geometrical model can H if the distance to H is less than the
this may seem a highly approximate then be established, similar to the one striking distance d.
notion, it is nonetheless a useful value. for a vertical rod in the example below It follows that for a given current I, i.e.
In France, the average Nk level is 20, (see fig. 4). for the resultant striking distance d, the
with extremes ranging from 10 in the Consider a vertical rod with a height h distance x to the rod, called the capture
Channel coast regions to over 30 in and its summit at H. The zones defined range, is:
mountainous regions. in the surrounding space are the
In other parts of the world, Nk levels if d > h x = 2 d h − h2
following:
may be much higher, for example over ■ zone I, situated between the ground if d < h x = d
180 in tropical Africa and Indonesia, for and parabola p. The latter defines the The capture range of the rod
example. points equidistant from H and the increases with the amplitude of the
Lightning density N ground. At the moment of the strike, a lightning strike. For very low
This is defined as the number of leader located in this zone will hit the amplitudes, the capture range drops to
lightning strikes hitting the earth per ground because it is closer than H. less than the height of the rod which
square kilometer and per year, ■ zone II, situated above the parabola. can then capture strikes along its
whatever the amplitude. At the moment of the strike, a leader length. This has been verified
In France, density N ranges, depending located in this zone will be captured by experimentally.
on the region, from 2 to 6 strikes
per km2 and per year.
The general ratio between the two
above values may be defined, on the y parabola p
basis of average values, as N = Nk / 7.

impact mechanism and


electro-geometrical model zone II
The lightning impact mechanism may rod capture zone
be broken down as follows: d
■ a leader originating in a cloud
approaches the ground at low speed.
As soon as the electrical field is strong
enough, conduction takes place h
H
suddenly, producing the discharge of
lightning. d
■ experimental data has been used to
derive the relationship between the
distance separating the beginning (arc) h/2 h

,,,,,,,,
and the end (discharge) of a lightning

,,,,,,,,
channel (i.e. the striking distance), on
the one hand, and the amplitude of the zone I
lightning strike, on the other: ground strikes

d = 9. 4 I 2/3 or d = 6.7 I 0.8 x

depending on the authors, where:


d is the striking distance in meters, fig. 4 : protection zones surrounding a vertical rod.
I is the lightning current in kA.

Cahier Technique Merlin Gerin n° 168 / p.7


3. lightning and electrical installations

This section deals with lightning strikes Direct lightning strikes At the towers, the voltage increases
on a line, wave propagation and the (on phase conductors) and propagates:
effects of lightning. When lightning hits a phase conductor ■ as a full impulse, reaching its
of a line, the total current i(t) at the maximum value
point of impact is split in two and the I max
lightning strikes on a line U max = Z
two halves are propagated along the 2
On the basis of the electro-geometrical conductor in opposite directions. when
model, the frequency of lightning strikes The wave impedance Z of the
can be calculated using the capture I max
conductor is 300 to 500 Ω (see fig. 7). Z < Ua
range of the considered object. 2
The result is an associated voltage
Figure 5 indicates, for a density N = 4 wave: where Ua = impulse flashover voltage
(4 lightning strikes per km2 and per of the insulators string or of any
year and a corresponding keraunic i(t)
u(t) = Z protective spark-gap devices that may
level of approximately 30), the 2 be present. This voltage is roughly
frequency of lightning strikes (number
of strikes per year) for a vertical rod
with a height h and for a horizontal
conductor with a length of 100 km and strikes/year
a height h. N1
The general empirical formula for
calculating lightning strikes (total
number per year) on a line (towers,
30
phase and earth wires) is the following:
 N1 l  L (2)
NL = Nk  + α
 30 70  100 20
where:
Nk = keraunic level,
NL = strikes on a line, (1)
10
N1 = strikes on the highest horizontal
conductor (see fig. 5),
L = lenght of the line in kilometers,
l = width of the line in meters (distance 0
2 3 4 5 6 8 10 20 30 40 50 70 100 200 500 1,000 h in
between outside conductors),
meters
α = influence coefficient taking into
account the influence of towers and
earth wires (see fig. 6). fig. 5: lightning frequency for a density N = 4 lightning strikes per km2 and per year:
This formula takes into account: ■ curve 1: vertical rod with a height h (with N1 x 10-3),
■ lightning trikes on a conductor (N1), ■ curve 2: horizontal conductor, 100 km long, at height h (with N1).
■ presence of outside conductors (l),
■ distribution between the tower and
the line depending on the structure of number of earth
the line (α), wires 0 1 2 3
■ length of the line (L) :
■ for insulation coordination lightning strike on tower (%) 55 35 20 10
calculations, L ≈ 1.5 km is generally on wires 45 65 80 90
selected because over greater (earth or
distances, the effect of the lightning phase)
strike becomes negligible, influence coefficient α 1.65 1.40 1.20 1.05
■ for continuity of service calculations,
the important factor is the total length of
the line exposed to strikes, therefore to fig. 6: distribution of strikes between towers and wires.
interruptions in service.

Cahier Technique Merlin Gerin n° 168 / p.8


proportional to the distance through air What actually takes place ? greater than the «low» 50 Hz or 60 Hz
(≈ 550 kV / m) and must take into Any modification in the electrical state power frequencies.
account a delay in flashover for very of a conductor at a given point travels Characteristics of «high-frequency»
steep fronts at high speed, ranging from 150,000 to phenomena
■ as a chopped impulse, with a voltage 300,000 km/s depending on the In this range of frequencies, the
limited by flashover, when insulator surrounding the conductor. At electrical laws commonly used are no
a power frequency of 50 Hz, the longer sufficient for our purposes:
I max
Z ≥ Ua distance covered in one period is 3,000 ■ first, the system cannot be
2 to 6,000 km. considered to be under standing (state)
The lightning current above which In the industrial sector, this distance is conditions, with instantaneous
flashover, i.e. interruption in service, far greater than the length of the transmission of the wave throughout
occurs is called the critical current Ic: concerned conductors, except in very the installation. The transmission time
Ic = 2 Ua / Z. particular situations. It is therefore is no longer negligible with respect to
possible to simplify by considering that the period of the considered
The magnitude of Ic is in the region of
the transmission of the wave is phenomena (at 1 MHz, the period is
5.5 kA for 225 kV lines, 8.5 kA for
400 kV lines and 19 kA for 750 kV
instantaneous throughout the 1 µs which corresponds to 300 m).
installation. ■ secondly, stray capacitance from the
lines. The corresponding frequencies of
Lightning produces «high-frequency» various elements, skin effect,
occurrence are respectively 95 %, 90 %
phenomena ranging from several tens electromagnetic coupling, etc. become
and 60 % (see fig. 2). Note that for
of kHz to several MHz, levels far important, even dominant, factors.
20 kV lines, the Ic value is practically 0
and flashover always occurs.
Indirect lightning strikes (on earth
wires or towers)
(see fig. 8)
The flow of the lightning current to earth U i
causes an increase in the potential of i/2
i
the metal structures. U = Z
i/2 2
The top of the tower reaches a potential
that depends on its inductance L and
the resistance of the earth R to the
impulse. i
di(t)
u(t) = R i(t) + L
dt
This voltage may reach the impulse t
flashover voltage of the insulators, in
which case «back-flashover» occurs. A fig. 7: lightning strike on a phase conductor.
part of the current is propagated along
the affected phase conductor(s) toward
users. This current is in general greater
(1/2 - k) i i
than that of a direct lightning strike.
ki
On extra high-voltage transmission U i/2
systems, «back-flashover» is unlikely i/2
due to the insulation level of the
insulators. Earth wires are therefore a
solution in that they limit the number of
interruptions in service. However, L
below 90 kV, «back-flashover» and the
resulting interruption in service occur
even when earth resistance values are

,,
ÀÀ
€€
@@
low (< 15 Ω), thus reducing the
usefulness of earth wires.

,@€À
wave propagation R
R i + L di 
U = k
Propagation of lightning impulse waves  dt 
is a concept with which electro-
technicians are rarely confronted in day fig. 8: lightning strike on an earth wire.
to day work.

Cahier Technique Merlin Gerin n° 168 / p.9


…and the practical consequences effect (losses due to ionisation of the the earthing electrodes of the
for lightning studies air surrounding the conductor, which concerned HV equipment. The
It follows that to quantitatively determine can be sizeable when U > 1 MV). The relationship describing the potential as
the effects of lightning (see the example result is an attenuation in amplitude a function of the distance to the
in section five), it is necessary to: and in front steepness. It is generally earthing connector is approximately
■ first, take into account the laws considered that over distances greater hyperbolic, resulting in very high
governing wave propagation. Given the than 1.5 km, lightning surges no potentials and associated gradients
distances involved, ranging from a few longer represent a danger for near the earthing electrode and even
meters to several kilometers, propa- substations. at distances of several tens of meters.
gation does not stabilise instanta- ■ high-frequency electromagnetic
neously, either in space or in time. interference (very wide spectrum),
■ then, take into account the laws effects of lightning including radiated interference,
governing reflection, refraction at points This section discusses the main effects, induction and circuit coupling.
of discontinuity and superposition of both direct and indirect, of the ■ electrochemical, acoustic and
waves at each point in time and at each propagation of lightning currents. Note
point along the line. physiological.
that even if the current is transmitted by
■ finally, adapt the model describing the the high-voltage lines, it can affect all All the above phenomena can cause:
physical operation of the various electrical circuits (conducted and ■ damage to equipment, either violent,
elements to take into account the radiated disturbances) at all voltage for example dielectric breakdowns due
dominant «high-frequency» levels. The effects can be: to overvoltages, or in the form of
phenomena. ■ thermal (welding of parts, fire, premature ageing due to non-
Example: under «high-frequency» explosions). destructive, but repeated stresses,
conditions, a transformer subjected to a ■ mechanical, due to the ■ malfunctions in installations due in
transient no longer behaves like a electrodynamic forces exerted on particular to interference in control/
series-connected inductance with a nearby parallel conductors. monitoring and communication
transformation ratio, but as a capacitive ■ dielectric shock, following increases equipment connected to low-current
divider (HV/earth, LV/earth, in potential during wave propagation circuits,
HV/LV capacitances), in which case the through the impedance of the ■ reduced continuity of service due to
HV/LV transformation ratio may be quite conductors. interruptions that may be long (damage
different from its value at power ■ insulation breakdown following to equipment) or short (malfunctions in
frequencies. flashover of a phase insulator, network automatic control systems),
Propagation attenuation due to the resulting in a follow-on current flowing ■ dangerous situations for people or
corona effect to earth at power frequency. animals, in particular due to pace
Lightning surges travelling along ■ increase in earth potential. Potentials voltages which may result in electrical
conductors are distorted by the corona commonly reach several hundred kV at shock or even electrocution.

4. protection

Following a few general remarks on Effective protection therefore requires These are based on energy levels:
protection, this section discusses in the lowest possible earth impedances. ■ level 1, consisting of diversion of the
greater detail the means to ensure This can be ensured by creating major part of the impact to earth and
protection, both primary (direct earthing networks and interconnections initial clipping. This level applies
discharge) and secondary (limitation of between earthing electrodes wherever primarily to objects likely to be struck by
the transmitted disturbances). possible. On high voltage B systems, lightning (lines and substations).
an earth impedance of less than 1 Ω at ■ level 2, consisting of limitation of the
power frequency is commonly residual voltage by further clipping. This
general specified for substations, whereas for level is intended to protect substation
The best protection, in particular of towers, an impedance of 10 to 15 Ω is equipment and/or installations against
human life, is provided by directing a strived for. conducted overvoltages. Several pro-
maximum of the disturbance to earth at There are several levels of protection tection devices distributed throughout
the closest possible point to the source against lightning currents and the the installation may be required to
of the disturbance. resulting increases in potential. dissipate the clipped energy.

Cahier Technique Merlin Gerin n° 168 / p.10


■ level 3, consisting of additional It is as if the leader were at the centre ■ screens
devices such as series-connected of a fictive sphere with a radius d. To This category comprises earth wires
filters and/or overvoltage limiters, which ensure proper protection, the fictive which are conductors running parallel
may be required in LV systems for sphere, as it moves along the ground to and above the phase conductors.
sensitive equipment (computer with the leader, must encounter a Earth wires are connected to the earth
systems, automatic control systems, protection device without touching the via the towers and constitute effective
telecommunications, LV networks, objects requiring protection (see fig. 9). protection against lightning strikes on
etc.). For protection against a very low overhead lines in that they capture
Note: All the above protection systems lightning current, approximately 2 kA strikes with amplitudes greater than the
should be considered right from the (cumulative probability ≈ 100 %), the critical current Ic.
design phase of installations and critical striking distance is 15 m. If a The concepts discussed in the
systems because subsequent 97 % probability is acceptable, the preceding section can be used to
modifications are difficult to implement corresponding lightning current is 5 kA determine the optimum position of earth
and costly. and the critical distance is 27 m. wires.

protection level 1
The purpose of level 1 protection is to
limit the effects of direct impacts on
electrical installations by diverting the
lightning current to the desired
locations.
Controlled diversion of lightning
current to precise points is possible
using:
■ lightning rods implementing the
striking distance principle. These thin
rods are placed at the top of the leader
structure requiring protection and
connected to earth by the most direct
path (via conductors descending d = critical
around the protected structure and striking distance
connected to the earthing network).
Observations have shown that a good
protection against direct lightning
strikes is provided in a cone with its
summit at the top of the lightning rod
and extending downward at 45° angles
with respect to the vertical.
■ Faraday cages or shields which
consist of closed grids of horizontal protected fictive
zone sphere
and vertical conductors connected to
an earthing network. The mesh size (cone)
must be less than 15 m and vertical
rods are placed at the nodes on the lightning rod
top part. Coverage of the zone
requiring protection is equivalent to
that provided by a multitude of 45°
lightning rods.

,,,,,,,,,,,
In either case, lightning rods or cages,

,,,,,,,,,,,
the electro-geometrical model
determines the protected zone using
the fictive sphere method.
The point of impact of the lightning
strike is determined by the first object
on the ground falling within the striking fig. 9: determining the protected zone using the «fictive sphere» method.
distance d of the leader.

Cahier Technique Merlin Gerin n° 168 / p.11


The different striking zones for an It is connected between the phases ■ lightning arresters or spark gaps
overhead line are shown in figure 10: and the earth. provide effective protection only when
■ zone I: earth strikes, ■ operation is similar to that of the certain installation conditions are
■ zone II: strike on a phase conductor spark gap, but it offers better control of respected, in particular the distances
without insulator flashover (I < Ic), the voltage:
separating them from the equipment
■ zone III: strike on the earth wire. - low dispersion of its residual voltage
U = f(I), to be protected and from the earth.
Protection of the phase conductors by That explains the importance of the
- virtually no delay in conduction,
the earth wire is determined by the protection distance of the lightning
- natural return to its initial state
optimum protection angle θopt. arrester, which will be discussed
(insulator), thus avoiding follow current.
When θ ≠ θopt, screen faults may ■ the main sizing criteria for a lightning below.
occur, i.e. lightning strikes with currents arrester are:
exceeding the critical current may - maximum continuous operating
reach the phase conductors and
provoke faults. The number of screen
voltage (MCOV), which must be greater protection level 3
than the maximum network operating
faults depends on θ. voltage with a safety margin of 5 %;
Applied in LV systems and for sensitive
- rated voltage, which must be equipment, this level of protection
1.25 x MCOV; against lightning and its effects is not
protection level 2 - protection level; discussed in length in this
This type of protection applies to HV - capacity to withstand the energy of «Cahier Technique» publication. For
systems. transient overvoltages, determined by further information, consult the
It must ensure that the BIL (Basic an amplitude vs. duration curve. documents listed in the bibliography.
Impulse Level) of the various substation
elements is not exceeded (coordination
of insulation). line determining the position of the
It creates an earthing circuit enabling earth wire for θ = θopt
diversion of the lightning current by
sparkover or conduction. Two types of
devices are used to limit lightning
limiting striking distance on phase
surges, spark gaps, based on a
wires when I = Ic
relatively old technique, and lightning
arresters, which today are used to zone III
replace the former in a wide range of
applications. θ
■ spark gaps, which implement
sparkover, have a number of major zone II
handicaps:
■ fairly high dispersion of the sparkover
voltage (up to 40 %),
■ a sparkover delay that is a function of
d
the overvoltage,
■ the sparkover phenomenon is
sensitive to external influences, for
example atmospheric conditions, earth cable d
■ the spark gap creates a very steep phase 1
chopped wave front that can destroy the phase 2
windings of nearby machines, phase 3
■ it also creates a 50 Hz follow current.
The diverted current is detected by the p
earth-fault protection device which

,,,,,,,,
h
actuates upstream breaking of the

,,,,,,,,
concerned line.
■ a lightning arrester (or more generally
zone I
a surge arrester) is a semi-conductor
with non-linear resistance ranging from
a few Ω to several MΩ. It is generally
made of zinc oxide (ZnO), a material fig.10: different cases for lightning strikes on an overhead line. Note that protection
whose characteristics are well angle θ = θopt.
understood.

Cahier Technique Merlin Gerin n° 168 / p.12


Note that this type of protection is There are three possible cases which
based on the following: are summarised in figure 13.
■ electromagnetic-compatibility (EMC) The diagrams in figures 14, 15 and 16
studies, line
illustrate the phenomena for cases 1

€@,ÀÀ€@,
■ earthing-network design and 2 (see pages 14, 15 and 16).
(interconnections, sizing, etc.), Example Zc
■ coordination of overvoltage limiters If the maximum permissible impulse
with overload, short-circuit and voltage for the transformer is set at
differential protection devices, A
1.3 x Vp, then
■ parallel-connected protection to limit lightning arrester
r D
impulse voltage using surge arresters: 1. 3 x Vp ≥ Vp + 2 Zc D, v, τ
gas spark gaps, varistors (SiC, ZnO), v
avalanche diodes, RC filters,
It follows that the arrester/transformer B
■ series-connected protection to limit
distance must not exceed:
the power transmitted using wave
absorbers (or HF filters), shielded Vp v
D ≤ 0.15 = 0.15 T v transformer
isolating transformers, network r
conditioners or UPS systems. Using the applicable figures: A and B: measurement points
Vp = 1,200 kV,
v = 300 m / µs, fig. 11: circuit diagram (line and transformer
protection distance r = 2,000 kV / µs, substation) for study of lightning overvoltage
The concept of protection distance is ⇒ D ≤ 27 m. wave propagation.
illustrated in the example below, which
Note:
has been voluntarily simplified. V
In reality, the following elements must be
Example taken into account:
Consider an overvoltage impulse wave ■ lightning arrester connections to
travelling down a line and arriving at a equipment and to the earth, Vp
substation comprising a transformer ■ actual lightning arrester
protected by a lightning arrester (see characteristics,
fig. 11). ■ network configuration with impedance
The various elements are defined as breaks and the different propagation
velocities, T t
follows:
■ capacitive elements, including the fig. 12: overvoltage wave diagram.
■ line:
■ surge impedance: Zc,
transformers.
■ wave propagation velocity: v,
■ distance between arrester and case criteria maximum overvoltage comments
transformer: D, on transformer
■ propagation time between A and B: 1 v Vp 2 Vp steep front slope r, long distance D.
D >
τ = D / v, 2 r Arrester distance has no effect on the
maximum voltage on transformer, the
■ lightning arrester with perfect i.e.: T < 2 τ
characteristics, i.e. for all voltages arrester limits the voltage to 2 Vp.
greater than Vp, conduction is 2 v Vp r D steep front slope r, long distance D.
instantaneous and the voltage is limited D < Vp + 2 Arrester presence limits, by the distance
2 r v
to precisely Vp, r D effect, the maximum voltage on the
■ earthing electrode with an impedance i.e.: T > 2 τ overrun = 2 transformer. Overrun of threshold
v
equal to zero, Vp is proportional to D and to r, hence
■ arrester/equipment and arrester/earth 2τ the «protection distance» concept.
= Vp
connections zero in length, T
■ transformer with an input impedance, r D 2 τ
⇒ Vp + 2 = Vp (1 + )
at the considered frequencies, much v T
higher than Zc. An arriving voltage
3 v Vp r D limit case between 1 and 2.
wave is almost totally reflected (voltage D = Vp + 2
doubles at point of reflection), 2 r v
■ incident overvoltage wave with a
i.e.: T = 2 τ = Vp + Vp = 2Vp
constant-slope (r = dV / dt) front and a
constant tail voltage where T = Vp / r is fig. 13: maximum overvoltages on the transformer, a practical example.
the front duration up to Vp (see fig. 12).

Cahier Technique Merlin Gerin n° 168 / p.13


case n° 1 A B case n° 2 A B

Vp wave arrives at A Vp wave arrives at A

t=0 t=0
Vp wave arrives at B Vp wave arrives at B

t=τ t=τ
Vp wave reflection at B Vp wave reflection at B,
reflection reaches A
t=T
t=2τ
reflection reaches A
Vp Vp

t=2τ t = T/2 + τ
2 Vp arrester produces a arrester produces a
wave to maintain at Vp
wave to maintain at
Vp A a constant voltage A a constant voltage
equal to Vp equal to Vp

t=T+τ t=3τ
2 Vp wave from the
2 Vp wave from the
arrester arrives at B Vmaxi arrester arrives
Vp at B
Vp

t=3τ t = T/2 + 2 τ
wave from the wave from the
Vp arrester reflected at B Vp
arrester reflected
at B

t=T+2τ -Vp
t=4τ
Vp wave from the Vp wave from the
arrester reflected at B arrester reflected at
reaches A B reaches A

-Vp t = T/2 + 3 τ
t=4τ
Vp arrester produces a
Vp arrester produces a
second wave to
second wave to
maintain at A a
maintain at A a
constant voltage constant voltage
equal to Vp -Vp equal to Vp
t=T+3τ -Vp t=5τ
Vp second wave from the Vp second wave from
arrester arrives at B the arrester arrives
at B

t=5τ -Vp
t = T/2 + 4 τ
-Vp

Vp second wave from the Vp second wave from


arrester reflected at B the arrester reflected
at B

t=T+4τ -Vp t=6τ -Vp

Cahier Technique Merlin Gerin n° 168 / p.14


fig. 14 (opposite page): diagrams illustrating lightning wave propagation for cases 1 (steep front slope) and 2 (low front slope) described in
figure 13. Positions A and B are shown in figure 11.
incident wave (T) reflected incident wave (T)
first wave produced by the arrester first wave produced by the arrester (reflected)
second wave produced by the arrester second wave produced by the arrester (reflected)
voltage profile

D, v, τ

A B

line
transformer

lightning arrester

case 1

2 Vp ÀÀ
€€
@@
,,6
5
4
1 2 3 45 6

2
Vp
1

0
0 τ 2τ 3τ 4τ 5τ 6τ
T T+τ T+2τ T+3τ T+4τ T+5τ
case 2

2 Vp

5
4
3
2
Vp
1

0
0 τ 2τ 3τ T 4τ 5τ 6τ 2T
T/2 + τ T/2 + 2 τ T/2 + 3 τ T/2 + 4 τ T/2 + 5 τ

fig. 15: voltages on the line protected by the lightning arrester as a function of time, for cases 1 (steep front slope) and 2 (low front slope)
described in figure 13.

Cahier Technique Merlin Gerin n° 168 / p.15


D, v, τ

A B
line line

transformer
lightning arrester

,@€À
T=2τ
2 Vp
T=3τ
T=4τ
T=5τ
T=6τ
T=7τ T = 10 τ T = 12 τ T = 14 τ T = 16 τ
T=8τ

Vp

0 τ 2τ 3τ 4τ 5τ 6τ 7τ 8τ 9τ

fig. 16: maximum overvoltage at transformer input (point B) as a function of T for a given τ (case 2 in figure 13).

network operation and non- Automatic reclosing cycles differ, ■ implementing auxiliary sources such
depending on the voltage level: as UPS systems for control/
availability monitoring applications, computer
■ > 300 kV: high-speed reclosing on
In public distribution networks, lightning single-phase systems (< 0.5 s) or slow systems, etc.,
is one of the causes (50 %) of voltage ■ designing and implementing correct
on 3 phase systems (1.5 to 5 s),
dips and brief interruptions. discrimination between the protection
■ 50 kV < U < 300 kV: 3 phase
These interruptions in the supply of reclosing and the use of shunt circuit devices on the user’s network, to
power, provoked by the protection ensure rapid clearing of faults caused
breakers on single-phase systems
devices, are required to clear the fault by lightning,
(end of spark gap discharge or stop of (0.15 s),
■ preventing isolating of priority
insulator flashover). ■ 1 kV < U 50 kV: high-speed and
consumers during storms. Sensitive
slow 3 phase reclosing (0.35 s, 15 s). loads can then be supplied by an
To improve continuity of service,
interruptions are shortened by automatic Interruptions are troublesome for internal power supply, while other
reclosing of the protection devices users and may be alleviated or loads continue to be supplied by the
(circuit breakers). eliminated by: public distribution network.

Cahier Technique Merlin Gerin n° 168 / p.16


standards IEC 71-1: insulation coordination - margin determines a safety coefficient
parts 1 and 2 that should not be less than the value
Installation designers can use
The capacity of insulation to withstand derived from practical experience which
standards to assist in determining:
■ the overvoltage situations that must
lightning impulses must be determined is approximately 1.25.
be taken into account when calculating taking into account foreseeable over- ■ using the statistical method, which
representative electrical stresses, voltages such that insulation accepts that insulation faults may
■ the basic impulse levels (BIL) of coordination requirements are satisfied occur, the goal is to quantify the risk of
equipment, for lightning overvoltages. Coordination a fault.
■ protection device characteristics. may be based on conventional or The coordination criterion to be
The main applicable standards are statistical methods. determined is the margin characterised
listed in the appendix. A few particular ■ using the conventional method, the by a statistical safety coefficient relating
points are listed below. coordination criterion is the margin the statistical impulse withstand voltage
IEC 60-1: high-voltage test between the maximum foreseeable (withstand probability of 90 %) to the
techniques - part 1 value and the withstand voltage statistical overvoltage (2 % probability
■ section 6: lightning impulse tests. indicated by an impulse test. This of being exceeded).
Different wave forms are defined (full
lightning impulse, impulse chopped on
the front or impulse chopped on the tail) U
with characteristic durations.
Figure 17 shows a standardised
lightning strike.
■ section 8: current impulse tests. For
1.0
the tests, four standardised current B
impulses of the bi-exponential type, 0.9
defined by their front duration and the
time to half value, may be used:
■ 1 µs / 20 µs impulse,
■ 4 µs / 10 µs impulse,
■ 8 µs / 20 µs impulse,
0.5
■ 30 µs / 80 µs impulse. A
0.3
IEC 694: common clauses for high-
voltage switchgear and controlgear
standards
(French standard: NF C 64-010) 0
01 t
This standard stipulates that the rated T'
insulation levels must be selected from
the values contained in a series of T
tables (see fig. 18 for an example).
It also stipulates that lightning impulse T1
voltage tests must use the standardised T2
1.2 / 50 µs wave.
IEC 99-1: surge arresters - part 1
T1 = 1.67 T
(French standard: NF C 65-100) T' = 0.3 T1 = 0.5 T
Section 6: type tests.
This section presents the type tests fig. 17: example of a standardised lightning strike defined by IEC 60. HereT1 = 1.2 µs,
defined by the standard: T2 = 50 µs.
■ external insulation withstand
capacity;
■ verfication of the residual voltage for rated voltage (kV rms) 7.2 24 72.5 245 420 525
8 / 20 µs lightning impulses; rated insulation levels for 40 95 325 850 1,300 1,425
■ withstand capacity for long impulse lightning impulses (kV) 60 125 950 1,425 1,550
currents; 145 1,050
■ tests on operation, accelerated
ageing, heat dissipation capacities, fig. 18: examples of voltage levels (defined by IEC 694) from which the rated insulation levels
thermal stability, lightning and operating for lightning impulses must be selected.
overvoltages, etc.

Cahier Technique Merlin Gerin n° 168 / p.17


Figure 19 is an example showing the
correlation between the risk of a fault
R
and the statistical safety coefficient.
1
Note that currently, the statistical
method is almost exclusively limited to 5
self-regenerating insulation applications
where faults do not result in damage to 10-1
equipment.
5
σg = 60 %
10-2
5

10-3
σg = 40 %
5

10-4
5

10-5 γ
0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3

fig. 19 : correlation between the risk of a fault (R) and the statistical safety coefficient (γ) for
various distributions of lightning overvoltages (σg = standard deviation), as defined by IEC 71.

Cahier Technique Merlin Gerin n° 168 / p.18


5. example of a lightning study

This section outlines the procedure for lightning strike, the intensity and point second line tower (most unfavourable
a lightning study, the methods used of impact, the existence and location of case).
and the practical conclusions. It deals lightning arresters, earth impedance, ■ lightning impulse on the earth wire:
in particular with calculation methods, etc. ■ peak value: 200 kA,
substation modelling using the ■ secondly, calculations on lightning ■ triangular shape: 2 / 50 µs.
calculation assumptions, deterministic frequencies and the corresponding
■ length of the struck line taken into
simulations, statistical aspects and the risks, on the basis of lightning statistics,
conclusions. ■ finally, calculations on substation
account is limited to 1.5 km from the
withstand capacities expressed in substation (see section 2).
probabilistic terms. ■ phase subject to flashing:
general ■ farthest from the struck earth wire,
Deterministic calculations
This study deals with insulation ■ with a negligible power voltage.
■ substation modelling
coordination for an extra high voltage ■ substation configuration: GIS
The operation of each network element
GIS (gas-insulated switchgear) configuration with the maximum length
and its configuration (physical
substation. Adequate dielectric of in-service busbars (most
interconnections) in the network
behaviour must be ensured for the unfavourable case).
topology are described by equations
various elements in the chain
comprising the electrical system. The based on the applicable electrical laws. ■ modelling frequency: 1 MHz.

elements have different BILs and Modelling requires prior analysis of the Main technical data
practically speaking, the question is network to limit the description to
■ 500 kV line:
whether lightning arresters are required pertinent aspects.
■ 4 wires per phase, 2 earth wires,
and if so, how to define their The equations are solved by computers
■ impedance data:
characteristics (location, ratings). using dedicated software, for example
EMTP (Electromagnetic Transient  Zdirect ≈ 300 Ω 
This type of study is becoming Program).  
increasingly common for large  Zzero − sequence ≈ 500 Ω
substations. Customers require that ■ simulation of lightning current waves
and the associated voltages for each ■ towers:
installers and suppliers of turn-key
proposed solution. Stepwise equation ■ surge impedance: 120 Ω,
installations provide numerical data
solving makes it possible to express ■ height: 43 m,
justifying sizing decisions.
virtually continuously the evolution of ■ earth resistance 25 Ω.
This type of study must be carried out
by teams of specialised engineers with current/voltage variables at each point ■ insulators:
sufficient experience and know-how in the network as a function of time. ■ chain of 29 elements (cap and pin
and using specific computer software. The simulation reproduces actual type),
operation analogically. Lightning is ■ flashover voltage: 2,600 kV,
Note: The example presented here was
represented by a supply of current ■ discharge delay depends on the
drawn from a true study concerning the
supply of a 500 kV substation, carried comprising a triangular or bi- shape and the level of the overvoltage
out by the Network Research Section exponential wave with adjustable front/ defined by a typical voltage-time curve.
(a part of the R&D Department), on tail durations and peak values. ■ GIS:
request from the Contracting ■ surge impedance: 70 Ω,
Department of Merlin Gerin in charge of substation modelling ■ substation earthing electrode
the project. impedance: < 1 Ω.
Modelling in this example is limited to a
general description that should suffice ■ capacity:
calculation methods for a basic understanding of the ■ power transformer: 7 nF,
procedure and does not include a ■ instrument transformer: 4 nF.
A number of successive and
complementary calculations are made: number of details required only by ■ lightning arresters: the U = f(I)

■ first, deterministic calculations


specialists. characteristic expresses their
evaluate voltages present in the General assumptions non-linearity.
installation depending on a number of ■ lightning strike on an earth wire, with ■ all connections (lines excepted):
different parameters such as the type of «back-flashover» of an insulator on the 1 µH/m linear.

Cahier Technique Merlin Gerin n° 168 / p.19


Studied installation The table in figure 21 and the main strikes, as calculated using the electro-
(see fig. 20) curves in figure 22 correspond to the geometrical model, to approximately
safest case in which three identical 12 kA.
lightning arresters (n° 1, 2 and 3) are That is less than the critical current and
deterministic simulations used. the insulators are not subject to
The simulations are carried out for a Note the distribution of the 200 kA flashover. Under these conditions, the
number of cases, e.g. with or without lightning strike: the lines and towers calculated currents in the substation
lightning arresters downstream of the absorb the major part of the current resulting from a direct impact are less
substation and at the transformer and less than 14 % arrives at the than those resulting from back flashover.
terminals, and for various arrester substation, where approximately half
characteristics. is absorbed by the lightning arresters.
It is a small fraction of the lightning
statistical calculation of
For each case, the maximum
overvoltages occurring at the current (< 5 %) that provokes voltage lightning frequencies and
instrument transformers, the rises approaching the maximum the associated risks
substation and the power transformer dielectric withstand capacities of the The average frequency of lightning
are closely observed and compared equipment. strikes on a line is calculated using the
to the possible BILs. The results (see Note: it has been demonstrated that formula presented in section 3:
fig. 21) show that for a BIL of direct hits on phase conductors are less
 N1 l  L
1,550 kV, at least two lightning of a problem than back flashover. The NL = Nk + α
 30 70  100
arresters are required (for the schielding effect of the earth wires
instrument and power transformers). limits the currents resulting from direct hence NL = 1.03 strikes / year.

a) network transformer substation

1 sub- 2 3 transfor-
station mer
b)

2 2

point of earth wire


maximum
voltage in phase conductor
the substation
flashover

instrument
transformer

lightning arresters:
n° 1 = incoming line,
circuits: n° 2 = for substation,
energised 1 1 n° 3 = for transformer
de-energised source n° 1 source n° 2

fig. 20: general substation layout and configuration.

Cahier Technique Merlin Gerin n° 168 / p.20


location of lightning arresters
overvoltages (kV) and safety coefficients (%) = BIL − U max
near the downstream upstream from U max
instrument from the the power for each element
transformer substation transformer instrument transformer substation power transformer
BIL 1,550 kV BIL 1,800 kV BIL 1,550 kV BIL 1,550 kV BIL 1,800 kV
yes yes yes 1,096 kV 1,103 kV 1,004 kV

41.4 % 64.2 % 40.5 % 54.2 % 79.3 %


yes no yes 1,263 kV 1,235 kV 1,044 kV

22.7 % 42.5 % 25.5 % 48.5 % 72.4 %

yes yes no 1,096 kV 1,103 kV 1,560 kV

41.4 % 64.2 % 40.5 % - 0.6 % 15.4 %

fig. 21: safety coefficients for each element of the studied equipment. The valid figure for the overall installation is 40.5 %.

kA kA
200
a d
12

150 10

8
100 a
6 c

b 4
50 b
c 2
d 0
0
0 2 4 6 8 10 12 14 0 2 4 6 8 10 12 14
µs µs
a = lightning current portion of lightning current flowing:
portion of lightning current flowing: a = to earth via the lightning arrester at the head of the line (1),
b = to earth via the struck tower, b = to earth via the lightning arrester for the substation (2),
c = to earth via the last tower before the substation, c = to earth via the lightning arrester for the transformer (3),
d = to the substation via the phase subject to flashover. d = to the substation via the phase subject to flashover.

MV MV
0 0

-0.2 a b c -0.2 a b c

-0.4 -0.4

-0.6 -0.6

-0.8 -0.8

-1.0 -1.0
-1.2 -1.2
0 2 4 6 8 10 12 14 0 2 4 6 8 10 12 14
µs µs
a = voltage at the lightning arrester at the head of the line (1), a = voltage affecting the instrument transformer,
b = voltage at the lightning arrester for the substation (2), b = maximum voltage affecting the substation (see fig. 20),
c = voltage at the lightning arrester for the transformer (3). c = voltage affecting the power transformer.

fig. 22: curves plotted on the basis of lightning overvoltage simulations.

Cahier Technique Merlin Gerin n° 168 / p.21


The probability of surges caused by This result is of use in defining
lightning strikes ≥ 200 kA is indicated by protection levels for equipment,
the curve in figure 2: depending on standards, technical
Probability (P) = 1 %. possibilities and cost factors, etc.
The frequency of occurrences is Note that all the above calculations are
therefore: based on selected values for important
Fd = NL x P ≈ 0,01 surges / year. parameters, including a number which
The statistical return period Tr between are:
two occurrences is ■ decisive, for example, tower and
Tr = 1 / Fd ≈ 100 years. substation earth impedances, lightning
A practical means to express these strike amplitudes,
figures is to determine the correspon- ■ and/or characterised by very wide
ding risk R of such a surge occurring dispersion ranges, for example,
during the service life t of the substation. breakdown voltages and flashover

t delays of insulators,
R = 1 − e Tr . ■ and/or poorly understood, for
For a 30-year service lise: R ≈ 26 %. example, network configuration
statistics or the correlation between
lightning impulse amplitudes and
fronts,
interpretation of ■ and/or neglected, for example,
calculations ageing processes and corona effect.
The conclusion of this study may be The values used for these parameters
summed up in a single phrase. There is may lead the reader to suspect
one chance in four (26 %) that, during inaccurate results. However, practical
the service life of the substation experience, accumulated and analysed
(30 years), an overvoltage caused by primarily by electrical distribution
lightning will reach or exceed 1,103 kV, utilities, confirms their suitability. The
corresponding to 71 % of the defined methods outlined in the example
BIL (1,550 kV), i.e. a calculated safety presented in this section are similar to
coefficient of 40 %. those implemented by EDF, the French
electrical authority.

Cahier Technique Merlin Gerin n° 168 / p.22


6. conclusion

This document sums up the main discussed in an effort to provide a The lightning study, broken down into
aspects concerning lightning in maximum of information, both its component parts, shows how the
electrical installations, thus constituting quantitative and qualitative, including risk of damage to equipment by
a basic introduction to this often the physical aspects of lightning itself, lightning can be calculated.
obscure, but nonetheless increasingly its effects on electrical installations,
important subject. The electrotechnical community is
currently available means of protection
today increasingly aware of the
It deals primarily with medium and high and standards. However, from all the
information contained in this document, problems caused by lightning and such
voltage installations. Lightning is a
two main points should be remembered: studies are increasingly carried out for
major constraint on equipment and is a
decisive factor in ensuring insulation ■ the concept of the lightning-arrester major international projects.
coordination. protection distance, corresponding to The current trend to take lightning
In the low-voltage field, lightning is but wave propagation phenomena at very phenomena into account starting from
one of many possible electrical high frequencies (MHz); the initial installation design phase will
disturbances (see the bibliography). ■ the example of a lightning study, continue to grow in coming years, thus
In this «Cahier Technique» publication, based on an actual study carried out by contributing to further improve the
the main practical aspects are Merlin Gerin for a 500 kV installation. quality of electrical power.

Cahier Technique Merlin Gerin n° 168 / p.23


appendix: bibliography

Standards Other publications


■ IEC 56: HV AC circuit breakers. ■ Dielectric properties of air and extra
■ IEC 60-1: HV test techniques, part 1 high voltages.
(French standard: NF C 41-101 EDF collection.
and 102). ■ «Lightning: understanding the pheno-
■ IEC 71: Insulation coordination menon in order to protect against it.»
(French standard: NF C 10-100). Nathan publishing.
■ IEC 76-1: Power transformers, part 1, ■ Electricity.
insulation levels and dielectric tests Volume 22: high voltage.
(French standard: NF C 52-100, part 3). Ecole polytechnique de Lausanne - EPL
■ IEC 99-1: Surge arresters, part 1 ■ Electrical and electromagnetic
(French standard: NF C 65-100). disturbances.
CIGRE, Electra Magazine.
■ IEC 289: Reactors (French standard:
NF C 52-300). ■ Editions des techniques de
l’ingénieur.
■ IEC 298: AC metal-enclosed
■ Overvoltage and Insulation
switchgear for rated voltages above
1 kV and up to and including 52 kV Coordination
(French standard: NF C 64-400). CIGRE, Committee 33.

■ IEC 694: Common clauses for hifh- Merlin Gerin «Cahier Technique»
publications
voltage switchgear and controlgear
■ Protection of LV wiring against
standards (French standard:
NF C 64-010). electromagnetic interference in the HV/
EHV electric substations.
■ NF C 17-100: Protection against Cahier Technique n° 137
lightning - Rules governing installation B. CAVALADE.
of lightning arresters.
■ Les perturbations électriques en BT.
EDF (French electrical authority Cahier Technique n° 141
specifications) R. CALVAS.
Series HN 65 : ■ EMC : Electromagnetic compatibility.
■ protection against overvoltages in HV Cahier Technique n° 149
applications, F. VAILLANT.
■ spark gaps in HV installations,
■ Surtensions et coordination de
■ lightning arresters in HV applications.
l'isolement.
HN 112: Insulation coordination on Cahier Technique n° 151
400 kV networks. D. FULCHIRON.
HN 115: Design and execution ■ Calcul des courants de court-circuit.
guidelines for earthing systems. Cahier Technique n° 158
HN 119: Insulation coordination on B. DE METZ NOBLAT
225 kV networks. G. THOMASSET.

Real. : Illustration Technique Lyon -


Edition: DTE - Grenoble
06/94 - 2500 - Printing: Léostic
Cahier Technique Merlin Gerin n° 168 / p.24 Printed in France

Anda mungkin juga menyukai