Anda di halaman 1dari 10

FOR APPROVAL

B 02.07.2019 P.N.ANH N.V.DAT D.T.LIEM FOR APPROVAL


A 01.06.2018 P.N.ANH N.V.DAT D.T.LIEM FOR APPROVAL
Rev Date Prepared Checked Approved Details of Revision
Owner
VIETNAM ELECTRICITY

Owner’s Engineer

Contractor

Sub-Contractor

BCA – THANG LONG CO., LTD.

Project Project Code


VINH TAN 4 EXTENSION VT4E
THERMAL POWER PLANT PROJECT UAS Code
YT10
(600MW x 1 UNIT)
Date Unit Code
Name Title P3
(DD.MM.YYYY)
KKS Code
Prepared 02.07.2019 P.N.ANH SGA
Reg. No.
Checked 02.07.2019 N.V.DAT HYDRAULIC CALCULATION
540001
OF INDOOR HYDRANT SYSTEM
Approved 02.07.2019 D.T.LIEM FOR AMMONIA STORAGE SHELTER Rev.
Dept. Fire Fighting Eng. B
Document No. Page-No.
VT4E-YT10-P3SGA-540001 10 Pages
EVN Vinh Tan 4 Thermal Power Project
DMPP Consortium

CONTENTS

1. INTRODUCTION ....................................................................................................................... 3

2. CODES AND STANDARDS....................................................................................................... 3

3. BASIC DATA AND ASSUMPTIONS ....................................................................................... 3

4. FIRE WATER DEMAND ........................................................................................................... 4

5. CALCULATION METHOD ...................................................................................................... 4

6. RESULTS OF HYDRAULIC CALCULATION SUMMARY ................................................ 5

7. EQUIVALENT TABLE .............................................................................................................. 6

8. APPENDIX

A. HYDRAULIC CALCULATION......................................................................................... 7

B. ISOMETRIC DRAWING .................................................................................................... 9

DOC.NO. VT4E-YT10-P3SGA-540001 Rev. B 2 of 10


EVN Vinh Tan 4 Thermal Power Project
DMPP Consortium

1. INTRODUCTION

1.1 Purpose
The purpose of this hydraulic calculation “AMMONIA STORAGE SHELTER” is to check that
the adequate flow and pressure are available to meet the required flow demand and
pressure demand at each indoor hydrant.

2. CODES AND STANDARDS

The following codes and standards will be employed;

 TVCN 4513-1998 Vietnamese standard – Inside water supply – Design standard

3. BASIC DATA AND ASSUMPTIONS

The following data and assumptions were used in the Hydraulic Calculations.

3.1 Software
Spray / Sprinkler Program “WinSprink” Ver. 2.21

3.2 Pipe Data


- Hazen and William’s 'C' Value
150 for HDPE Fire Main pipe
120 for Aboveground Galvanized Carbon Steel Pipe

3.3 Design Criteria


1) The minimum discharge pressure of discharge devices
2.4 barg

3.4 Reference Drawings


1) P&ID drawing (VT4E-XG02-P3SGA-540001)
2) Fire Fighting Drawing (VT4E-XH01-P3SGA-540001).
3) Schematic Hydraulic Diagrams : Fire Fighting Layout Drawing attached at the end
of calculation sheet (VT4-YT10-P3SGA-540001).

DOC.NO. VT4E-YT10-P3SGA-540001 Rev. B 3 of 10


EVN Vinh Tan 4 Thermal Power Project
DMPP Consortium

4. FIRE WATER DEMAND

4.1 Estimated Flow Demand for “AMMONIA SHELTER HOUSE”.

Building / Fire
Water demand Discharge Water
NO. Fighting Equipment Remarks
(Lpm) pressure (barg)

Ammonia Shelter House


1
Indoor Hydrant 936 2.4

5. CALCULATION METHOD

5.1 Friction Losses


Hazen and William's formula has been used to calculate the friction losses.

Qm1.85
pm = 6.05 x 105
1.85
C dm4.87

Where, pm : Frictional resistance (bar per m of pipe)


Qm : Water flow rate (Lpm)
C : Friction loss coefficient
dm : Actual internal diameter of pipe (mm)

DOC.NO. VT4E-YT10-P3SGA-540001 Rev. B 4 of 10


EVN Vinh Tan 4 Thermal Power Project
DMPP Consortium

6. RESULTS OF HYDRAULIC CALCULATION SUMMARY

Flow / Pressure Demand


at Ring Main Tie-in Point
Protected Fire Protection
Remarks
Hazard System Applied
Result Result
Flow rate (Lpm) Pressure (bar)

Water Treatment Hose Pressure Drop =


Plant Indoor Hydrant 1,971.59 12.056 2.8 Bars

*According to TCVN 4513_1988 item 6.19

q = 651.9 L/min

= 10.87 l/sec

Kp = 0.012 (50mm Hose)

l = 20m

Hose Pressure Drop, H = Kp x q² x l

= 0.012 x 10.87² x 20

= 28.36m
= 2.8 Bars Approx

DOC.NO. VT4E-YT10-P3SGA-540001 Rev. B 5 of 10


EVN Vinh Tan 4 Thermal Power Project
DMPP Consortium

7. EQUIVALENT TABLE

EQUIVALENT LENGTH TABLE

TYPE OF
DN INSIDE T B W S K V V V
PIPE
TEE GATE WET DRY
VALUE DIAMETER 45DEG. 90DEG. CHECK VALVE/ SPRAY VALVE
PIECE VALVE VALVE VALVE
ELBOW ELBOW STRAINER
20 20.96 1.2 0.3 0.6 0 0 0 0 0 ASTM
25 26.64 1.5 0.3 0.6 0 0 0 0 0 ASTM
32 35.08 1.8 0.3 0.9 0 0 0 0 0 ASTM
40 40.94 2.4 0.6 1.2 0 0 0 0 0 ASTM
50 52.48 3.1 0.6 1.5 0.3 3.4 0 0 3.1 ASTM
65 62.68 3.7 0.9 1.8 0.3 4.3 0 0 0 ASTM
80 77.92 4.6 0.9 2.1 0.3 4.9 4.6 5 7.1 ASTM
100 102.26 6.1 1.2 3.1 0.6 6.7 5.4 7.4 21.4 ASTM
125 128.2 7.6 1.5 3.7 0.6 8.2 0 0 0 ASTM
150 154.08 9.2 2.1 4.3 0.9 9.8 9.6 9.9 26.9 ASTM
200 202.74 10.7 2.7 5.5 1.2 13.7 11.2 0 24.4 ASTM
250 254.56 15.3 3.4 6.7 1.5 16.8 0 0 0 ASTM
300 303.28 18.3 4 8.2 1.8 19.8 0 0 0 ASTM
350 339.76 21.7 5 10 2.1 22.8 0 0 0 ASTM
151 130.80 13.89 3.17 6.49 1.36 14.8 0 0 0 HDPE
201 163.60 16.16 4.08 8.31 1.81 20.69 0 0 0 HDPE
251 204.60 23.1 5.13 10.12 2.27 25.37 0 0 0 HDPE
301 257.80 27.63 6.04 12.38 2.72 29.9 0 0 0 HDPE

C - VALUE = 150 FOR HDPE PIPE


C- VALUE = 120 FOR ASTM PIPE

DOC.NO. VT4E-YT10-P3SGA-540001 Rev. B 6 of 10


Appendix - A : Hydraulic Calculations

Builder : Mode of operation : BG :


Minimax GmbH Singapore Branch Kind of system : wet system Effective area: favourable
25, International Business Park, #03-15/19, dry system least favourable
German Centre, Singapore 609916 fast dry system
Operator : prior driven dry system Demand : pressure at sprinkler
Vinh Than 4 Thermal Power Plant tandem system pump pressure
Vietnam
Roughness of pipe (C-value) 150 and 120 Use of pipes according to DIN A53.Gr.B + HDPE
Supply of hydrants with water : l/min at node No. Strangrohr-No. : 0 ; Sprinkler-No. : 0
Project-No.: Operating company :
Ceiling protec. Rack protec.
VT4 Extension Ammonia Shelter House
Height of storage (m)
min. water admission (mm/min)
Person in charge : real effective area (ea) (m²)
Glen Golle max. protection area/sprinkler in ea (m²)
No. of sprinklers / effection area
No. of additional sprinkler / effection area
Date : Object :
hydraulic considered no.of sprinkler
01 June 2018 Indoor Hydrant System
no. of protected decks
biggest distance of sprinkler (m)

Demand press required / Supply press available / cushion in bar 12.000 according Hazen-Williams

Water rate at point to feed in / Pump in l/min 1971.59


© By IDAT-GmbH 2000 - 2012 V 2.21 1226

hydraulic unfavourabelst sprinkler in the effective area


No. of pipe / Sprinkler-No.
minimum pressure / Required density in bar
geodetic difference in height sprinkler - point to feed in m
geodetic difference in height lowest sprinkler - point to feed in m 0.62
max. pressure of sprinkler in the effective area in bar 10.758
min. pressure of sprinkler in the effective area in bar 10.476
max. water speed in the effective area in m/s 5.09
No. of sprinkler in the effective area 0
7 of 10
Calculation of pressure loss : Name of project : VT4 Extension No. of protection area : 1 Date : 31 May 2018 Appendix - A : Hydraulic Calculations
Page : 1

Name Beg.- End.- pbeg K Qsprinkler Qstrang dia- C-Value length Fittings hydraulic p difference p pend v remarks
node node meter of pipe B/W/T/TAV/NAV/S/V/R/D total length friction in height total
[bar] [l/min] [l/min] DN [m] kind and no [m] [bar/m] [m] [bar] [bar] [m/s]
Z 2- 1 28 29 11.823 1971.6 300 120 4.47 2W+ 1S+ 1K 42.47 0.0001 1.77 0.1774 12.000 0.45 Pump = 9464 l/min
Z 1- 1 28 27 11.823 -1971.6 300 120 6.17 1W 14.37 -0.0001 2.65 0.2587 12.081 0.45
H 3- 1 27 26 12.081 -1971.6 301 150 441.03 9W+ 5S 629.94 -0.0001 1.70 0.0859 12.167 0.63
H 2- 1 26 25 12.167 -1971.6 201 150 82.48 1W 95.04 -0.0012 -0.1117 12.056 1.56
H 1- 1 25 24 12.056 -1971.6 151 150 1.90 1W 11.71 -0.0035 -1.90 -0.2273 11.828 2.45
V 18- 1 24 23 11.828 -1971.6 150 120 0.35 0.35 -0.0024 -0.35 -0.0352 11.793 1.76
V 17- 1 23 22 11.793 -1971.6 100 120 1.67 1W+ 1S+ 1K 12.07 -0.0175 -0.2114 11.582 4.00
V 16- 1 22 21 11.582 -1971.6 100 120 3.10 1W 4.87 -0.0175 -1.77 -0.2589 11.323 4.00
V 15- 1 21 20 11.323 -1971.6 100 120 5.00 1W 5.40 -0.0175 -0.0946 11.228 4.00
V 14- 1 20 19 11.228 -1971.6 100 120 3.00 1W 7.00 -0.0175 -3.90 -0.5052 10.723 4.00
V 13- 1 19 18 10.723 -1971.6 100 120 3.82 1W 4.00 -0.0175 -0.0701 10.653 4.00
V 12- 2 17 18 10.624 660.6 100 120 9.17 1W 12.27 0.0023 0.0284 10.653 1.34
V 12- 1 18 8 10.653 -1311.0 100 120 1.03 1T 7.13 -0.0082 -0.0587 10.594 2.66
V 11- 1 17 16 10.624 -660.6 100 120 20.41 1W 23.51 -0.0023 -0.0545 10.570 1.34
V 10- 1 16 15 10.570 -660.6 100 120 6.73 3W 16.03 -0.0023 5.00 0.4534 11.023 1.34
V 9- 1 15 14 11.023 -660.6 100 120 0.50 1W 3.60 -0.0023 -0.50 -0.0574 10.966 1.34
V 8- 1 14 12 10.966 -660.6 50 120 0.35 1T 3.45 -0.0597 -0.2059 10.760 5.09
V 8- X2 13 12 10.758 201.40 660.6 660.6 50 120 10.760 IH = 312 l/min
V 7- 1 6 11 10.225 -659.2 100 120 7.25 7.25 -0.0023 7.25 0.6945 10.920 1.34
V 6- 1 11 9 10.920 -659.2 50 120 0.35 1T 3.45 -0.0594 -0.2051 10.715 5.08
© By IDAT-GmbH 2000 - 2012 V 2.21 1226

V 6- X3 10 9 10.712 201.40 659.2 659.2 50 120 10.715 IH = 312 l/min


V 5- 1 8 7 10.594 -1311.0 100 120 2.53 1W 5.63 -0.0082 -2.53 -0.2945 10.300 2.66
V 4- 2 7 6 10.300 -1311.0 100 120 5.95 1W 9.05 -0.0082 -0.0745 10.225 2.66
V 4- 1 6 5 10.225 -651.9 100 120 7.86 1T 13.96 -0.0023 -0.0316 10.194 1.32
V 3- 1 5 4 10.194 -651.9 100 120 20.41 1W 23.51 -0.0023 -0.0531 10.140 1.32
V 2- 1 4 3 10.140 -651.9 100 120 8.50 1T+ 1W 17.70 -0.0023 7.25 0.6712 10.812 1.32
V 1- 1 3 1 10.812 -651.9 50 120 0.83 1T+ 1W+ 1S 5.73 -0.0582 -0.3336 10.478 5.02
V 1- X1 2 1 10.476 201.40 651.9 651.9 50 120 10.478 IH = 312 l/min

8 of 10
Appendix - B : Isometric Drawing

RING MAIN - AMMONIA SHELTER HOUSE

540001

9 of 10
Appendix - B : Isometric Drawing

5000 14
3000

3821
3098

AMMONIA SHELTER HOUSE

540001

10 of 10