ELECTRÓNICA
MEMORIA EXPLICATIVA
Planta Procesadora de maderas
OTOÑO 2018
INDICE
MEMORIA EXPLICATIVA ..................................................................................................................................................... 1
1 INTRODUCCIÓN.......................................................................................................................................................... 3
2 DESCRIPCIÓN DE LA OBRA ...................................................................................................................................... 4
3 CÁLCULOS JUSTIFICATIVOS .................................................................................................................................... 8
3.1 Potencia total instalada........................................................................................................................................ 8
3.2 Potencia total demanda. .................................................................................................................................... 12
3.3 Empalme............................................................................................................................................................ 22
3.4 Protección general. ............................................................................................................................................ 24
3.5 Alimentador general........................................................................................................................................... 24
3.6 Caída de tensión................................................................................................................................................ 25
3.7 Dimensionamiento y selección de Conductores. ............................................................................................... 26
3.8 Descripción técnica de los alimentadores, sub-alimentadores, conductores a instalar. .................................... 33
4 Calculo de Corto Circuito............................................................................................................................................ 34
4.1 Calculo de impedancias reales. ......................................................................................................................... 34
4.2 Calculo de Impedancias en pu. ......................................................................................................................... 35
4.3 Calculo de niveles de cortocircuito trifásicos. .................................................................................................... 36
4.4 Calculo de niveles de cortocircuito instantáneo simétrico ................................................................................. 37
2
1 INTRODUCCIÓN
La presente memoria de cálculo contiene el dimensionamiento de conductores eléctricos, diseño de diagrama de
impedancias, cálculo de corto circuito trifásico y regulación de tensión, más el dimensionamiento de transformador de poder
(entre otros), a instalarse en proceso industrial “Aserradero Arauco” ubicado en la localidad de Arauco km 3, ruta P-20 s/n,
VIII región, Chile.
El objetivo basal es establecer los parámetros y análisis respectivos que se llevaran a cabo en el dicho proyecto, modelando
un soporte técnico a fin de crear un sistema eléctrico lo suficientemente seguro, tanto en el aspecto del resguardo humano,
como también el de las máquinas y equipos que la empresa contemple a utilizar.
Los equipos y materiales eléctricos a utilizar deben cumplir estas especificaciones y las normas y códigos vigentes. Cabe
señalar que en aquellas materias en que las especificaciones no realicen exigencias explícitas, se aplicarán las
prescripciones de las normas y códigos.
La instalación eléctrica con sus detalles de montaje se muestra en los planos respectivos adjuntos al proyecto y en esta
especificación.
3
2 DESCRIPCIÓN DE LA OBRA
DESCRIPCION DEL PROYECTO.
A continuación, se dan a conocer los aspectos más relevantes que constituyen este proyecto tanto en su
característica constructiva como también eléctrica. Entre ellos se encuentran:
Incluye:
- Tanto la acometida a la celda como la celda al transformador, se efectuará en canaleta (al piso) de
características y dimensiones por definir.
ALIMENTADOR L1
- Celda de Baja Tensión como Centro de Distribución de cargas. Esta celda actuará como “TGF-A y Cal.”
- Con el propósito de compensar el Factor de Potencia de la Planta, este tablero debe incluir un Banco de
Condensadores Estáticos el cual debe considerar protecciones, elementos de maniobra y un relé automático
de conexión de pasos.
- Desde este tablero, se derivarán los ALIMENTADORES que se detallan y que convergen a los siguientes
tableros:
- También desde este tablero, se derivarán los SUB-ALIMENTADORES que se detallan y que convergen a los
siguientes tableros:
ARCHIVO, ETC.
4
ETAPAS:
- AREA DE ASERREADO
- AREA DE MOLDURAS
ESTRELLA
M6 MI/JA TRIF.380V 100KW 0,89 87 %
TRIANGULO
ESTRELLA
M7 MI/JA TRIF.380V 100 HP 0,87 90 %
TRIANGULO
100 HP
84 %
MULTIMAQUI
M10 MI/JA TRIF.380V PARTIDA DIRECTA 0,84
NA
CINCO
MOTORES
“TDFyA-G1-1” - SUB-ALIMENTADOR LC
“TDFyA-G1-2” - SUB-ALIMENTADOR LD
5
Información adicional galpón G1:
SUB-ALIMENTADOR: LC
M1 1,0
M2 1,0 O,88
1.15
M3 0,9
M4 1,0 0,83
M5 0,9
SUB-ALIMENTADOR: LD
FACTOR DE FACTOR DE
MOTOR
CARGA DEMANDA
M6 1,0
M7 0.8
M8 0,9 0,93
M9 1,0
SUB-ALIMENTADOR: LE
FACTOR DE FACTOR DE
Circuitos
CARGA DEMANDA
F-G-3-1 1
F-G1-3-2 1
F-G1-3-3 1 0,7
F-G1-3-4 1
disponible
6
FACTOR DE DIVERSIDAD ENTRE
FACTOR DE
SUB- ALIMENTADOR
DIVERSIDAD
SUB – ALIMENT. LC
SUB – ALIMENT. LE
ALIMENTADORES L2, LA y LB
FACTOR DE
ALIMENTADOR
DIVERSIDAD
ALIMENTADOR LA
ALIMENTADOR LB 1.12
ALIMENTADOR L2
REGLAMENTOS Y NORMAS.
Las obras se ejecutarán de acuerdo con las exigencias habituales de la buena práctica de la ingeniería eléctrica, de montaje y selección
de materiales a realizar por el contratista y se deberá dar cumplimiento a lo dispuesto en la última edición y/o modificaciones de los
siguientes reglamentos y normas eléctricas chilenas oficiales.
N. CH. ELEC. 10/84: Tramite para la puesta en servicio de una instalación interior.
7
3 CÁLCULOS JUSTIFICATIVOS
CARGAS FUERZA
TABLERO POTENCIA(KW)
TDF-G1-1 433.34
TDF-G1-2 445
TDF-G1-3 32
CARGAS ALUMBRADO
TABLERO POTENCIA(KW)
TDA-ADM. 8.126
TDA-G1-3 18.031
CARGAS CALEFACCION
TABLERO POTENCIA(KW)
TD CAL-ADM. 24
RESUMEN POTENCIA: 24
8
TABLA B-4: CARGAS CONTROL
CARGAS CONTROL
TABLERO POTENCIA(KW)
TD CONT-G1-2 4.14(KW)
NOTA: LA POT. INST. DE CONTROL SE ESTIMA EN APP. 1 % DE DEM. MAX. POT. DE FUERZA
EJ.: POT. CONT. “TD CONT-G1-1”, SERIA 1 % DE DEM. MAX. POT. “TDF-G1-1”
RESUMEN DE CIRCUITOS
CARGAS: FUERZA
(AREA DE ASERREADO)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
FUERZA 6 433.34
(AREA DE MOLDURAS)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
FUERZA 6 445
(Maestranza)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
FUERZA 4 32
9
POTENCIA TOTAL: 32 (KW)
CARGAS: ALUMBRADO
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
ILUMINACION 4 6.109
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
ILUMINACION 8 2.3
ENCHUFES 3 4.5
(AREA DE MOLDURAS)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
ILUMINACION 10 14.908
ENCHUFES 3 3.15
CARGAS: CALEFACCION
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
ENCHUFES 6 24
10
CARGAS: CONTROL
(AREA DE ASERREADO)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
CONTROL 1 3.24
(AREA DE ASERREADO)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
CONTROL 1 3.24
(AREA DE MOLDURAS)
CANT. POTENCIA
TIPO CARGA
CIRCUITOS (KW)
CONTROL 1 4.14(KW)
PROYECTO
(REF.: ESTA ES LA POTENCIA QUE SE INDICA EN CUADRO DE CARGAS DE PLANOS Y QUE SE DOCUMENTA EN EL
FORMULARIO SEC TE1)
ALUMBRADO 32,023
CALEFACCION 24
FUERZA 910,34
CONTROL 10,62
11
3.2 Potencia total demanda.
TRANSFORMADOR SUBESTACION
FUERZA
PN (KW)
MOT / PTO. PN (KW)
CIRC. PN (HP) SALIDA REND. F. POT. ANG. X SN /x (KVA)
ENCH. IND. ENTR.
PTO. ENCH.
ENCH-
8 (KW) 0.83 33.9 9.64/33.90
G1-1
G1-1
12
TABLA B-2: TDF-G1-2
PN (KW)
MOT / PTO. PN (KW)
ANG.
CIRC. PN (HP) SALIDA REND. F. POT. SN /x (KVA)
ENCH. IND. ENTR. X
EJE MOT.
PN (KW)
ANG.
Circuito. CIRC. xxxxxx xxxxxx Xxxxx F. POT. SN /x (KVA)
ENTR. X
13
ALUMBRADO
CIRC. PN (KW)
F. DE POT. 0.5
ANG. X 60
14
TABLA B-6: TDA-ADM
CIRC. PN (KW)
A-ADM-5 0.456
A-ADM-6 0.38
A-ADM-7 0.228
A-ADM-8 0.608
A-ADM-9 0.228
A-ADM-10 0.132
A-ADM-11 0.114
A-ADM-12 0.132
A-ADM-13 1.5
A-ADM-14 1.5
A-ADM-15 1.5
A-ADM-16 1.5
F. DE POT. 0,9
ANG. X 25.84
15
TABLA B-7: TDA-G1-3
CIRC. PN (KW)
A-G1-3-23 0.187
A-G1-3-24 0.228
A-G1-3-25 0.304
A-G1-3-26 0.456
A-G1-3-27 0.304
A-G1-3-28 0.304
A-G1-3-29 4.29
A-G1-3-30 4.29
A-G1-3-31 4.29
A-G1-3-32 1.05
A-G1-3-33 1.05
A-G1-3-34 1.05
A-23(OF.SUPERV.) 0.228
F. DE POT. 0,8
ANG. X 36.86
16
CALEFACCION
CIRC. PN (KW)
CAL-ADM-17 4
CAL-ADM-18 4
CAL-ADM-19 4
CAL-ADM-20 4
CAL-ADM-21 4
CAL-ADM-22 4
F. DE POT. 0,95
ANG. X 18.19
CONTROL
CIRC. PN (KW)
CONT-G1-1 3.24
F. DE POT. 0,85
ANG. X 31,8º
17
TD CONT-G1-1-2
CIRC. PN (KW)
CONT-G1-1-2 3.24
F. DE POT. 0,85
ANG. X 31,8º
CIRC. PN (KW)
CONT-G1-2 4.143
F. DE POT. 0,85
ANG. X 31,8º
18
TABLA B-18: SUB ALIMENTADOR LC
TDF-G1-1 380.15/31.30
TD CONT-G1-1 3.81/31.8
TD CONT-G1-1-2 3.81/31.8
TDF-G1-2 475.62/29.4
TD CONT-G1-2 4.87/31.8
TDF-G1-3 25.27/27.65
TDA-G1-3 20.27/36.86
Sub-ALIMENTADOR LC 387.76/31.3
Sub-ALIMENTADOR LD 480.49/29.42
Sub-ALIMENTADOR LE 45.39/31.74
19
ESPECIFICACION DE POTENCIA
PARA EL TRANSFORMADOR
20
Selección del transformador
Fases 3
Primario
Conexión Delta
Fusible Bayoneta 40 A
Secundario
Conexión Estrella
Frecuencia 50 Hz
Impedancia 5%
21
3.3 Empalme.
Se conectará a un empalme de M.T. 23 KV, de propiedad de FRONTEL S.A. Para ello se realizará a través de un Seccionador tipo cuchillo
o bien un DBC, un Reconectador Automático en forma aérea, en el punto de arranque de la red de M.T.
También en forma aérea se instalará un Equipo Compacto de Medida (E.C.M.); al pie de la estructura en que se monta E.C.M., se instalará
el Medidor el que se definirá adecuadamente para cumplir los propósitos del proyecto.
P.Activa*(Tan(actual°)-Tan(ideal°))
P(KW):781,04
Utilizaremos una botella capacitiva de 21 KVAR por ende usaremos 11 botellas capacitivas cada una con la siguiente descripción
FRECUENCIA 50HZ
DIELECTRICO POLIPROPILENO
FIJACION M12
22
50 HZ 400 VOLTS
Qn(KVAR) 21
In(A) 29,8
Capacitancia µF 3x137,0
23
3.4 Protección general.
Fusible Bayoneta 40 A
24
3.6 Caída de tensión.
FORMULAS EMPLEADAS: Caída de tensión: √3 ∗ ZL1 ∗ In
TABLA C-15: PRESENTACION DE VOLTAJES EN PUNTOS CRITICOS Y REGULACION DE TENSION (RESPECTO A V N = 380 V) -
VB0=400 V
PERDIDA DE
PERDIDA DE
VOLTAJE (REF.: VN=
PUNTO CRITICO UBICACION VOLTAJE (V) VOLTAJE (V)
380 V)
(REF.: VN= 380 V)
(%)
25
3.7 Dimensionamiento y selección de Conductores.
Y CIRCUITOS DERIVADOS
C.1- ALIMENTADORES
FORMULA EMPLEADAS:
𝑫𝒎𝒂𝒙 𝑲𝑽𝑨
In Al:
√𝟑∗𝑽𝒏
1186,6
L1 781.04/30.33 1519,34 520
/-30,33
DEMANDA CORRIENTE
MAXIMA (KVA) MAXIMA Corriente Soportada por
(MODULO Y ALIMENTADOR el Alimentador (A)
ALIMENT.
ANGULO) (A)
LA 12.21/60 18.55/-60 40
26
TABLA C-5: ALIMENTADOR LB
DEMANDA
MAXIMA CORRIENTE
(KVA) CORRIENTE
MAXIMA
ALIMENT. ALIMENTADOR
(MODULO ALIMENTADOR
(A)
Y (A)
ANGULO)
LB 34,23/20.2 52,00/-20,2 75
C.2- SUB-ALIMENTADORES
DEMANDA
MAXIMA CORRIENTE
SUB CORRIENTE
(KVA) MAXIMA
ALIMENTADOR
ALIMENTADOR
ALIMENT. (A)
(MODULO Y (A)
ANGULO)
LE 45.39/31.74 68.96/-31.74 95
27
C.3- CIRCUITOS DERIVADOS
CORRIENTE
PN (KW)
CARGA F. POT. IN (A) CIRCUITO
POT. ENTRADA
DERIVADO (A)
PTO. ENCH.
8 0.83 14.64 30
G1-1
CORRIENTE
PN (KW)
CARGA F. POT. IN (A) CIRCUITO
POT. ENTRADA
DERIVADO (A)
PTO. ENCH.
8 0.83 14.64 30
G1-2
28
TABLA C-11: “TDF-G1-3”
CORRIENTE
PN (KW)
CIRCUITO F. POT. IN (A) CIRCUITO
POT. ENTRADA
DERIVADO (A)
29
DIMENSIONAMIENTO DE CONDUCTORES.
Trabajaremos con la norma eléctrica chilena NCH Elec. 4/2003. “Instalaciones de consumo en baja tensión”, Realizaremos las siguientes consideraciones para
nuestro cálculo de conductores: para la sección de los conductores lo haremos con un 125% de la corriente nominal del circuito tomando en consideración lo
establecido en Norma Nch Elec. 4/2003. El dimensionamiento de la sección del neutro se consideró del mismo diámetro del conductor de fase. La sección
del conductor de tierra de protección se dimensiono según la tabla 10.23 Norma Nch Elec. 4/2003. Para el diámetro de las canalizaciones los encontramos de
la tabla 8.17, 8.17a, 8.18a y 8.19 Norma Nch Elec. 4/2003. El procedimiento para llevar a cabo el cálculo de los alimentadores de los motores: Para determinar
la sección del conductor tenemos que seguir el siguiente procedimiento:
De la tabla N° 8.8 y N° 8.9a determinamos los factores fn y ft que se aplicaran directamente a la corriente de cada motor antes determinada.
Nota: a) El factor de corrección fn para conductores al aire libre es 1. b) Los conductores empleados para energizar los motores son del tipo TTMU, temperatura
de servicio 75°C. c) Debido a que nuestros conductores son transportados en escalerillas, el factor de corrección fn para todos los motores es igual a 1. d) Si
se analiza la tabla N° 8.9a determinamos que el factor ft para todos los motores es 1.05 correspondiente a temperatura ambiente 25°C. D” de cada motor. Por
lo tanto, la corriente de ICOND se define por:
Según la tabla N° 8.7a, podemos determinar la sección necesaria según el tipo de conductor y la capacidad de corriente (ICOND
𝑲∗𝑰𝒏
FORMULA EMPLEADA: Cond It:
𝒏∗𝑭𝒏∗𝑭𝒕
Buscar tabla 8. 7a
30
TABLA C-14-A: DESCRIPCION DE ALIMENTADORES - SUB ALIMENTADORES
SECCION DEL
AISLACION TEMP. DE CONDUCTOR NUMERO CANTIDAD DE CAPACIDAD DE
TIPO LONGITUD TEMP. TIPO
DEL SERVICIO CONDUCTORES “DUCTOS” POR CORRIENTE POR
ACOMET (M) AMB.(ºC) “CANALIZACION”
CONDUCTOR (ºC) (MM2) - (AWG POR FASE ACOMETIDA CONDUCTOR (A)
O MCM)
SUB 25
10 XTU 90 5,26 MM2 1 TRINCHERA 1 40
ALIM LA
SUB 25
65 XTU 90 13,3 MM2 3 PVC 1 75
ALIM LB
SUB 25
30 XTU 90 202,7MM2 3 E.P.C 1 380
ALIM LC
25 3
SUB
75 XTU 90 303,6MM2 E.P.C 1 475
ALIM LD
SUB 25
75 XTU 90 21,2MM2 3 E.P.C 1 95
ALIM LE
CIRC. 75 25 1 225
DERIV 20 TTMU 85 MM2 1 E.P.C
M1
CIRC. TTMU 75 25 1 1
DERIV 20 33,6 MM2 E.P.C 130
M2
31
CIRC. TTMU 75 25 1 1
DERIV 40 33,6 MM2 E.P.C 130
M3
CIRC. TTMU 75 25 1 1
DERIV 10 53,5 MM2 E.P.C 170
M4
CIRC. TTMU 75 25 1 1
DERIV 36 126,7 MM2 E.P.C 290
M5
CIRC. TTMU 75 25 1 1
DERIV 20 107,2 MM2 E.P.C 260
M6
CIRC. TTMU 75 25 1 1
DERIV 20 67,4 MM2 E.P.C 195
M7
CIRC. TTMU 75 25 1 1
DERIV 38 13,3MM2 E.P.C 75
M8
CIRC. TTMU 75 25 1 1
DERIV 60 107,2 MM2 E.P.C 260
M9
CIRC. TTMU 75 25 1 1
DERIV 35 67,4 MM2 E.P.C 195
M10 (*)
32
𝟏
FORMULAS EMPLEADAS: ZL: ∗ (𝒓Ω ∗ 𝑭𝒓 + 𝑱𝒙Ω ∗ 𝑭𝒙) ∗ 𝑳
𝒏
𝒛𝒓𝒆𝒂𝒍
Z(PU):
𝒛𝒃𝒂𝒔𝒆
𝑽𝑩𝟐
ZB:
𝑺𝑩
3.8 Descripción técnica de los alimentadores, sub-alimentadores, conductores a
instalar.
TABLA C-14-B: DESCRIPCION DE ALIMENTADORES - SUB ALIMENTADORES
34
4.2 Calculo de Impedancias en pu.
IMPEDANCIA
TIPO ACOMET
(0/1)
ALIM L1 0,0019868/53,7
ALIM L2 0,01941437/51,5
TAB1 0,820683/1,3
TAB2 0,854878/1,3
TAB3 0,854878/1,3
TAB4 1,367805/1,3
35
4.3 Calculo de niveles de cortocircuito trifásicos.
VTHN
FORMULAS EMPLEADAS: ICC TRIFASICO =
ZTHN
1
ICC TRIFASICO (PU)=
ZTHN
1
ICC TRIFASICO (PU) =
∑REACTANCIAS
𝑆𝑛
ICC TRIFASICO real = ICC TRIFASICO (PU) ∗
√3 ∗ Vn
𝑺𝑩
IB:
√𝟑∗𝑽𝑵
ICO CI TRFAS.
PUNTO CRITICO UBICACION
(AMP)
36
FORMULAS:
(ICC)INSTANTANEA: k*ICC TRIFASICO real
4.4 Calculo de niveles de cortocircuito instantáneo simétrico
ICO CI TRFAS.
PUNTO CRITICO UBICACION
(AMP)
37
38