VT Sizing Calculation for

132 kV Cable Feeder

Page 1 of 8
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 132kV Cable Feeder - BC-2 S/S (Adopted Parameters)

Project : GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
(VA)
IEC 60044-1

A 132kV Cable Feeder VT

Core-1 Protection & Metering CL 1.0 / 3P 100


132 KV/√3 / 110 V/√3 /
1 Cable Feeder VT
110 V/√3
Core-2 Protection & Metering CL 1.0 / 3P 100

Page 2 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 132kV Cable Feeder VT MM SMS AKS 10/11/2011

A. VT Sizing Calculation for 132kV Cable Feeder VT (Typical) : C106 TO C406

Core Details Device Connected & Purpose


Core-1 & 2 : C106 & C406 Main I, II Protection and Metering
1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 132kV bus)

1.2 VT Details

a. VT : C106 & C606

b. Voltage Rating : 132 KV/3 / 110 V/3 / 110 V/Ö3

c. VA Rating : 100 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the cable : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 100/63.51

: 1.6 A

g. Two way lead burden : 1.6*1.6*1.104

: 2.83 VA

1.4 Connected Burden Particulars - Core 1

P545 (87C) - Main I Protection : 0.02 VA (Refer ANNEXURE - R1 )

Synchro check relay (P143) : 0.02 VA (Refer ANNEXURE - R5)

BCU (C264) : 0.10 VA (Refer ANNEXURE - R4)

Voltmeter @ LCC : 0.50 VA (Refer ANNEXURE - V2)

Lead Burden : 2.83 VA

Total Burden : 3.47 VA

With 20% Design margin : 4.2 VA

Rated VA Burden of the VT : 100 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is adequate.

Page 3 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 132kV Cable Feeder VT MM SMS AKS 10/11/2011

1.5 Connected Burden Particulars - Core 2

7SD532 - Main II protection : 0.1 VA (Refer ANNEXURE - R2)

Lead Burden : 2.83 VA

Total Burden : 2.93 VA

With 20% Design margin : 3.5 VA


Rated VA Burden of the VT : 100 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is adequate.

We have provided VT with 100 VA Burden.

1.9 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 100 VA CL.1.0 / 3P


132 KV/√3 / 110 V/√3 /
110 V/√3
2 Core-2 100 VA CL.1.0 / 3P

Page 4 of 8
VT Sizing Calculation for
132kV Bus VT

Page 5 of 8
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 132kV Bus VT - BC-1 S/S (Adopted Parameters)

Project : GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
((VA))
60044 1
IEC 60044-1

C 132kV Bus VT

1 Bus VT Core-1 132 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 200

Page 6 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION Doc No.: PH10-XX-XX-XX-XXXX Rev. 0
PROJECT
- PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 132kV Bus VT MM SMS SMS 10/11/2011

A. VT Sizing Calculation for 132kV Bus VT (Typical) : C166 & C266

Core Details Device Connected & Purpose


Core-1 : C166 & C266 Metering (BCU)
1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 132kV bus)

1.2 VT Details

a. VT : C166 & C266

b. Voltage Rating : 132 KV/3 / 110 V/3

c. VA Rating : 200 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the calble : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/"1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 200/63.51

: 3.1 A

g. Two way lead burden : 3.1*3.1*1.104

: 10.61 VA

1.4 Connected Burden Particulars - Core 1

Synchro check relay (P143) - Feeder C12 : 0.02 VA (Refer ANNEXURE - R5)

BCU (C264) - Feeder C10 : 0.10 VA (Refer ANNEXURE - R4)

BCU (C264) - Feeder C12 : 0.10 VA (Refer ANNEXURE - R4)

Lead Burden : 10.61 VA

Total Burden : 10.83 VA

With 20% Design margin : 13.0 VA

Rated VA Burden of the VT : 200 VA

Page 7 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION Doc No.: PH10-XX-XX-XX-XXXX Rev. 0
PROJECT
- PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 132kV Bus VT MM SMS SMS 10/11/2011
p q
adequate.

1.5 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 132 KV/√3 / 110 V/√3 200 VA CL.1.0 / 3P

Page 8 of 8