Page 1 of 8
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of Voltage Transformer Parameter for 132kV Cable Feeder - BC-2 S/S (Adopted Parameters)
Project : GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
(VA)
IEC 60044-1
Page 2 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE
TITLE VT Sizing calculation for BC-2 S/S - 132kV Cable Feeder VT MM SMS AKS 10/11/2011
b. System frequency fn : 50 Hz
1.2 VT Details
c. VA Rating : 100 VA
d. Class : CL.1.0 / 3P
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
: 2*100*5.52/1000
: 1.1040 Ohm/km
: 1.6 A
: 2.83 VA
The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is adequate.
Page 3 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE
TITLE VT Sizing calculation for BC-2 S/S - 132kV Cable Feeder VT MM SMS AKS 10/11/2011
The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is adequate.
1.9 Summary
Page 4 of 8
VT Sizing Calculation for
132kV Bus VT
Page 5 of 8
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of Voltage Transformer Parameter for 132kV Bus VT - BC-1 S/S (Adopted Parameters)
Project : GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
((VA))
60044 1
IEC 60044-1
C 132kV Bus VT
1 Bus VT Core-1 132 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 200
Page 6 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION Doc No.: PH10-XX-XX-XX-XXXX Rev. 0
PROJECT
- PHASE X - SUBSTATIONS PRPD CHKD APPD DATE
TITLE VT Sizing calculation for BC-2 S/S - 132kV Bus VT MM SMS SMS 10/11/2011
b. System frequency fn : 50 Hz
1.2 VT Details
c. VA Rating : 200 VA
d. Class : CL.1.0 / 3P
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
: 2*100*5.52/"1000
: 1.1040 Ohm/km
: 3.1 A
: 10.61 VA
Synchro check relay (P143) - Feeder C12 : 0.02 VA (Refer ANNEXURE - R5)
Page 7 of 8
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION Doc No.: PH10-XX-XX-XX-XXXX Rev. 0
PROJECT
- PHASE X - SUBSTATIONS PRPD CHKD APPD DATE
TITLE VT Sizing calculation for BC-2 S/S - 132kV Bus VT MM SMS SMS 10/11/2011
p q
adequate.
1.5 Summary
Page 8 of 8