Table of Contents
1 PURPOSE 2
2 MAIN FEATURES 2
2.1 Main Features 2
3 CHANGES 3
3.1 Release 8.2.0.2 3
3.1.1 New Feature in REB500 8.2.0.2 3
3.1.2 Fixed Product Feedbacks in REB500 8.2.0.2 3
3.1.3 Fixed Product Feedbacks in HMI500 8.2.0.2 4
3.2 Release 8.2.0.1 4
3.2.1 Fixed Product Feedbacks in HMI500 8.2.0.1 4
3.2.2 Fixed Product Feedbacks in REB500 8.2.0.1 5
3.3 Release 8.2 5
3.3.1 Fixed Issues in REB500 8.2 5
3.4 Known Issues 6
4 REFERENCES 7
4.1 Firmware 8.2.0.2 7
4.2 Tool 8.2.0.2 7
4.3 IED 8.2 7
5 RELEASE HISTORY 7
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without
express authority is strictly forbidden. © Copyright 2013 ABB
(2013-05-31) Form: 1KHL000228-0101 / E
Version: page:
REB500 V8.2.0.2 Release Notes 4 2/7 1KHL501779
1 Purpose
This release note is for internal use only, e.g. test field, sales, commissioning, training, etc. of SA-Products
and for REB500 certified LEC’s.
2 Main Features
2.1 Main Features
Included functionalities (● standard, ○ optional)
Feature 8.00 8.10 8.2 8.2.0.2
Busbar protection ● ● ● ●
Busbar protection with subcycle tripping time ● ● ●
Busbar protection with neutral current ○ ○ ○ ○
Breaker failure protection including neutral current detection ○ ○ ○ ○
End-fault protection ○ ○ ○ ○
Breaker pole discrepancy ○ ○ ○ ○
Overcurrent release feature ○ ○ ○ ○
Voltage release feature ○ ○ ○ ○
Check zone ● ● ● ●
Current plausibility check ● ● ● ●
Overcurrent protection (definite time) ○ ○ ○ ○
Trip command redirection ● ● ● ●
Software matrix for inputs / outputs / trip matrix ● ● ● ●
Event recording up to 1000 events ● ● ● ●
Disturbance recorder (4 x I, 5 x U) up to 20 s at 2400 Hz ○ ○ ○ ○
Disturbance recorder for busbar differential currents ● ●
Communication interface IEC 61850-8-1 Edition 1 ○ ○ ○ ○
Communication interface IEC 61850-8-1 Edition 1 and Edition 2 ○ ○ ○
Communication interface IEC 62439-3 Parallel Redundancy Protocol PRP/PRP0 ○ ○ ○
for IEC 61850-8-1
Communication interface IEC 61850-8-1 GOOSE Receive for BFP Start ○ ○
Communication interface IEC 60870-5-103 ○ ○ ○ ○
Communication interface IEC 60870-5- 103 with individual link layer addresses for ○ ○ ○
each bay unit and central unit.
Time synchronization (SNTP V4, IRIG-B, Sec-Pulse, IEC60870-5-103) ● ● ● ●
Redundant power supply for central unit ○ ○ ○ ○
Isolator supervision ● ● ● ●
Differential current supervision ● ● ● ●
Comprehensive self-supervision ● ● ● ●
Dynamic busbar replica with display of currents ● ● ● ●
Test generator for commissioning and maintenance ● ● ● ●
Remote HMI ● ● ● ●
Web HMI ● ●
Hotpluggable Local HMI ● ●
Delay / Integrator function ● ● ● ●
Binary logic and flip-flop functions ● ● ● ●
Bay Protection: Line Variant 2 ○ ○
Directional earth fault for grounded system in Line Variant 2 ○
Cyber Security: User Account Management ● ● ● ●
Cyber Security: User Activity logging ● ● ● ●
Cyber Security: Secure Communication with HMI500 ● ● ●
Cyber Security: Centralised User Account Management ● ● ●
Cyber Security: Use of IEC 62351 standard roles ● ● ●
Support for fast switching isolators ● ● ●
High speed binary output module ○ ○ ○
Version: page:
REB500 V8.2.0.2 Release Notes 4 3/7 1KHL501779
3 Changes
HMI500 TFS 32394 It is now possible to select more than 7 Bay Units to upload disturbance recorders.
HMI500 TFS 32442 Allow the HMI500 Configurator to enable/disable the “Analogue Channel Supervision” in
the System parameters menu.
HMI500 TFS 32455 Corrected evaluation of signals which are mapped to IEC 61850. In som e Settings, signals
were mapped to 61850 but they shouldn't. i.e BP Logic Output.
HMI500 TFS 32585 Correct event and object address configuration for Faultlocator Output-Signals in case of
no DIST function is used
HMI500 TFS 33319 Allow the HMI500 Configurator to enable/disable the “Enabled for Checkzone” in the
Current transform ers menu.
HMI500 TFS 33318 Allow the HMI500 Configurator to enable/disable the “U0 calculated internally” in the
Voltage release menu.
HMI500 TFS 33320 File BayModel_base.sdb corrected, i.e. in some bay models “Enabled for Checkzone”
activated.
HMI500 TFS 33485 Corrected some french signal text
HMI500 TFS 33502 Preview Report/Plant Data does not generate "internal program error:" any more
HMI500 TFS 33839 Correctd objectAddres handling for Projects with more than 30 BU's (Object Addrss >
32000)
HMI500 TFS 33841 Correction for IEC61850 LDevice.LNInstance.DOInstance.DAInstance column in SCS
Export date report where the logical device name was wrong in some cases
HMI500 TFS 34439 In previous versions the SCS export Data report did not contain IEC 103 signals from the
CU. This has been corrected.
Due to the fact that the changes in the HMI500 were mainly for minor conformance purposes, they were
integrated into a hotfix which was not distributed with an official CD image.
Version: page:
REB500 V8.2.0.2 Release Notes 4 5/7 1KHL501779
4 References
4.1 Firmware 8.2.0.2
Firmware Type Version
Operating System VxWorks 6.8.3 PID 3.8
IEC61850 ABB 61850 Stack and Services (ISS) 5.30.00.02
Security ABB Central Account Management (CAM) 2.17.5536.3
Security ABB User Activity Logging Component (UAL) 2.6.1.0
Security ABB Secure Configuration Access (SCA) 2.9.0.2
Security OpenSSL (including Eric Young Cryptographic Software) 0.9.8za
AFS677 AFS677 8.0.05
Update tool REB500fwu_8.2.0.2.378
REB500fwu_8.2.0.1.346
REB500fwu_8.2.0.0.308
ConnPack REB500 8.2.0.2 ConnPack is compatible with PCM600 2.7(32-bit and 8.2.0.2
64-bit versions) as well as PCM600 2.8 (32-bit and 64-bit versions
PCM600 2.7 (32-bit / 64-bit)
2.8 (32-bit / 64-bit)
5 Release History