Anda di halaman 1dari 7

ABB Switzerland Ltd 1KHL501779

Version: -Date:
REB500 V8.2.0.2 Release Notes 4 2017-10-09
Department resp.: Created: Approved: Distribution: Language: Page:
PGGA-PT 2017-10-09 H.Brodbeck 2017-09-27 Lars Frisk project library EN 1/7
Effective for: Derived from: Replaces: Classification: File:
1KHL501779 REB500 V8.2.0.2 Release
PGGA-PT - - draft Notes.docx

Table of Contents
1 PURPOSE 2
2 MAIN FEATURES 2
2.1 Main Features 2
3 CHANGES 3
3.1 Release 8.2.0.2 3
3.1.1 New Feature in REB500 8.2.0.2 3
3.1.2 Fixed Product Feedbacks in REB500 8.2.0.2 3
3.1.3 Fixed Product Feedbacks in HMI500 8.2.0.2 4
3.2 Release 8.2.0.1 4
3.2.1 Fixed Product Feedbacks in HMI500 8.2.0.1 4
3.2.2 Fixed Product Feedbacks in REB500 8.2.0.1 5
3.3 Release 8.2 5
3.3.1 Fixed Issues in REB500 8.2 5
3.4 Known Issues 6
4 REFERENCES 7
4.1 Firmware 8.2.0.2 7
4.2 Tool 8.2.0.2 7
4.3 IED 8.2 7
5 RELEASE HISTORY 7

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without
express authority is strictly forbidden. © Copyright 2013 ABB
(2013-05-31) Form: 1KHL000228-0101 / E
Version: page:
REB500 V8.2.0.2 Release Notes 4 2/7 1KHL501779

1 Purpose
This release note is for internal use only, e.g. test field, sales, commissioning, training, etc. of SA-Products
and for REB500 certified LEC’s.

2 Main Features
2.1 Main Features
Included functionalities (● standard, ○ optional)
Feature 8.00 8.10 8.2 8.2.0.2
Busbar protection ● ● ● ●
Busbar protection with subcycle tripping time ● ● ●
Busbar protection with neutral current ○ ○ ○ ○
Breaker failure protection including neutral current detection ○ ○ ○ ○
End-fault protection ○ ○ ○ ○
Breaker pole discrepancy ○ ○ ○ ○
Overcurrent release feature ○ ○ ○ ○
Voltage release feature ○ ○ ○ ○
Check zone ● ● ● ●
Current plausibility check ● ● ● ●
Overcurrent protection (definite time) ○ ○ ○ ○
Trip command redirection ● ● ● ●
Software matrix for inputs / outputs / trip matrix ● ● ● ●
Event recording up to 1000 events ● ● ● ●
Disturbance recorder (4 x I, 5 x U) up to 20 s at 2400 Hz ○ ○ ○ ○
Disturbance recorder for busbar differential currents ● ●
Communication interface IEC 61850-8-1 Edition 1 ○ ○ ○ ○
Communication interface IEC 61850-8-1 Edition 1 and Edition 2 ○ ○ ○
Communication interface IEC 62439-3 Parallel Redundancy Protocol PRP/PRP0 ○ ○ ○
for IEC 61850-8-1
Communication interface IEC 61850-8-1 GOOSE Receive for BFP Start ○ ○
Communication interface IEC 60870-5-103 ○ ○ ○ ○
Communication interface IEC 60870-5- 103 with individual link layer addresses for ○ ○ ○
each bay unit and central unit.
Time synchronization (SNTP V4, IRIG-B, Sec-Pulse, IEC60870-5-103) ● ● ● ●
Redundant power supply for central unit ○ ○ ○ ○
Isolator supervision ● ● ● ●
Differential current supervision ● ● ● ●
Comprehensive self-supervision ● ● ● ●
Dynamic busbar replica with display of currents ● ● ● ●
Test generator for commissioning and maintenance ● ● ● ●
Remote HMI ● ● ● ●
Web HMI ● ●
Hotpluggable Local HMI ● ●
Delay / Integrator function ● ● ● ●
Binary logic and flip-flop functions ● ● ● ●
Bay Protection: Line Variant 2 ○ ○
Directional earth fault for grounded system in Line Variant 2 ○
Cyber Security: User Account Management ● ● ● ●
Cyber Security: User Activity logging ● ● ● ●
Cyber Security: Secure Communication with HMI500 ● ● ●
Cyber Security: Centralised User Account Management ● ● ●
Cyber Security: Use of IEC 62351 standard roles ● ● ●
Support for fast switching isolators ● ● ●
High speed binary output module ○ ○ ○
Version: page:
REB500 V8.2.0.2 Release Notes 4 3/7 1KHL501779

Bay unit variant with 4 current inputs. ○ ○ ○

3 Changes

3.1 Release 8.2.0.2


3.1.1 New Feature in REB500 8.2.0.2

Module Identification Explanation


HMI500 TFS 32291 Enabled Bay Protection: directional Earth Fault for grounded systems DIREFGND 67N

3.1.2 Fixed Product Feedbacks in REB500 8.2.0.2

Module Identification Explanation


In some cases the events were deleted from the queue after restart of the central unit. This
System TFS 29556 has been corrected.
The session timeout handling is also active in case of inactive external time
Security TFS 31044 synchronization.
IEC103 TFS 31097 In case of active maintenance mode raising and also falling IEC 103 events are generated.
Correction of incorrect event generation in FCT/SCT/SPR timing supervision by the
Diagnostic TFS 31103 diagnosis software (Minor_Error;188, 189 and 190).
TFS 31208
System TFS 31172 REB500 now also support a single bus bar in case IEC 61850 is configured.
Robustnes TFS 31249 No reboot of CU when connecting to Web server via intercepting Proxy Burp.
Recommendation to use rate limiter on the switch which connected to the X1001, X1002 in
“Security Deployment Guideline”. Because BBP blocks if Package rate on station bus
Documentation TFS 31252 interface exceed more than 2100 packages per second.
Documentation TFS 31277 Improved description of firmware update in 1KHL501616
Malfunction
In case of a PCP-Error condition an additional extended BU event (BBP Minor_Error 040)
TFS 31389 indicates which bay unit had a current change and in addition a General Start DR is
System TFS 31215 activated.
Central unit output signal '41835_Test generator active' will be set in case of activation of
test generator functionality, even there are other signals configured to the same output
System TFS 31560 channel.
System TFS 31990 Improved analogue sample timeout supervision (DIA Minor_Error 190).
LHMI TFS 31989 Ä, Ö, Ü, ä, ö and ü are now shown on the LHMI500 display of the Feeder names.
The indication of missing SNTP time synchronization was improved. (Same behaviour as
System TFS 32494 other Relion IED’s)
New document for AFS677 Configuration and setup is available 1KHL020793-
Documentation TFS 32817 Aen_B_en_APN_Switch configuration guideline.docx
Disabled week WebServer SSL/TLS security protocol and encryption algorithms (SSLv2,
Robustnes TFS 32822 SSLv3, TLSv1.0 RC4-SHA, TLSv1.0 RC4-MD5 and TLSv1.0 DES-CBC-SHA)
If a modified Boot line is detected during start up, then is corrected so that next boot will not
block. This corrects an error where the IED ended up in a reboot loop because the start up
System TFS 33095 path to the OS was wrong.
TFS 33615 After start-up, a pre-engineered BU does not perform continuous restarts but remains in a
System not active, stable state.
IEC 61850 TFS 34403 Str.dirGeneral was not mapped correct. This has been corrected.
Version: page:
REB500 V8.2.0.2 Release Notes 4 4/7 1KHL501779

3.1.3 Fixed Product Feedbacks in HMI500 8.2.0.2

Module Identification Explanation


Screen position of dialogs will be set to default if save position is outside the current
HMI500 TFS 28251 connected monitor
HMI500 TFS 30824 Also default Signals are listed in HMI Report -> SCS 61850 report
HMI500 TFS 31037 HMI500 binary output signal delay time configuration corrected.
HMI500 TFS 31050 The menu "Close All Session" is always active in operator mode.
HMI500 TFS 31068 Remote Trip does now work at all feeder configurations.
HMI500 TFS 31095 Fixed blocking of HMI500 when printing of LMI LED labels has been selected
HMI500 TFS 31242 Export of Security events
HMI500 TFS 31310 Improvement of file verrification
HMI500 TFS 31338 Some menu items in German version has been translated.
HMI500 TFS 31440 No false trip generation in case of not configured binary input signals of breaker or isolator.
HMI500 TFS 31486 Wrong position indication of breaker and isolators in case of not configured binary input
signals was corrected.
HMI500 TFS 31907 Correction for IEC61850 logical device text in 61850 SCS Data Export.

HMI500 TFS 32394 It is now possible to select more than 7 Bay Units to upload disturbance recorders.
HMI500 TFS 32442 Allow the HMI500 Configurator to enable/disable the “Analogue Channel Supervision” in
the System parameters menu.
HMI500 TFS 32455 Corrected evaluation of signals which are mapped to IEC 61850. In som e Settings, signals
were mapped to 61850 but they shouldn't. i.e BP Logic Output.
HMI500 TFS 32585 Correct event and object address configuration for Faultlocator Output-Signals in case of
no DIST function is used
HMI500 TFS 33319 Allow the HMI500 Configurator to enable/disable the “Enabled for Checkzone” in the
Current transform ers menu.
HMI500 TFS 33318 Allow the HMI500 Configurator to enable/disable the “U0 calculated internally” in the
Voltage release menu.
HMI500 TFS 33320 File BayModel_base.sdb corrected, i.e. in some bay models “Enabled for Checkzone”
activated.
HMI500 TFS 33485 Corrected some french signal text
HMI500 TFS 33502 Preview Report/Plant Data does not generate "internal program error:" any more
HMI500 TFS 33839 Correctd objectAddres handling for Projects with more than 30 BU's (Object Addrss >
32000)
HMI500 TFS 33841 Correction for IEC61850 LDevice.LNInstance.DOInstance.DAInstance column in SCS
Export date report where the logical device name was wrong in some cases
HMI500 TFS 34439 In previous versions the SCS export Data report did not contain IEC 103 signals from the
CU. This has been corrected.

3.2 Release 8.2.0.1


3.2.1 Fixed Product Feedbacks in HMI500 8.2.0.1

Module Identification Explanation


HMI500 TFS 29378 Attributes original SclVersion and originalSclRevision are missing

Due to the fact that the changes in the HMI500 were mainly for minor conformance purposes, they were
integrated into a hotfix which was not distributed with an official CD image.
Version: page:
REB500 V8.2.0.2 Release Notes 4 5/7 1KHL501779

3.2.2 Fixed Product Feedbacks in REB500 8.2.0.1

Module Identification Explanation


System TFS 21507 Different behavior of protection zone measurement depending on startup.
System TFS 21512 Problem with verification of breaker reclaim time
System TFS 22434 LHMI-CU: Bus zone names in the Alarm list differ from the names configured in HMI500
System TFS 22503 Depending on configuration of 11610_External_reset signal, no system-wide reset possible
System TFS 26372 Device restart in case of major error even if device is permanently blocked
System TFS 28040 Time_sync via IEC103 does not work
System TFS 29364 LeapSecondsKnown is not set to ISS Stack on IAL interface
System TFS 29365 Delete unknown file returns wrong error code, shall be file non existent
System TFS 29366 GetFileAttribute on unknown file return wrong error code, if file does not exist
System TFS 29367 ActiveSettinggroup is not stored in non-volatile memory. After reboot the
ActiveSettinggroup shall remain as before reboot.
System TFS 29384 Corrections in Conformance Documentations (PIXIT, PICS and MICS)
System TFS 30142 SDL removal of debug Symbols from VxWorks Kernel

3.3 Release 8.2


The following change notes are based on changes between Version 8.10 and Version 8.2.0.0. For changes
to other versions refer to the respective earlier release notes. The issues listed here are partly reflected in
the above list of product feedbacks.
3.3.1 Fixed Issues in REB500 8.2

Module Identification Explanation


HMI500 TFS 18458 HMI500 Color Scheme Symbols Single Line "Close Command " should have the same
color as "Breaker Closed"
Documentation TFS 22402 Application Note for Switch setup should cover "generic" AFS677 switches
System TFS 22331 Reduced the long delay in case of configuration download on large systems.
HMI500 TFS 22405 A new user created in SDM600 using CAM can change his password
Documentation TFS 24376 The usage of supervision signals has been clarified
HMI500 TFS 24628 The dialog to change the password has been improved
HMI500 TFS 24707 The security options menu has been improved
System TFS 24779 A mismatch between QR code and order code at display has been corrected
HMI500 TFS 26736 Ethernet configuration for interface LAN0 will be reflected in the database
HMI500 TFS 26434 BU in service functionality can now be monitored in extended event list via DIA events with
error numbers numbers 100 to 171
HMI500 TFS 27066 Corrected a behavior that prevented assignment of sectionalizer inputs
System TFS 19556 The reporting of login and logout in the security events has been improved.
System TFS 21705 Reporting of isolator alarm during startup of the entire REB500 system has been improved
Version: page:
REB500 V8.2.0.2 Release Notes 4 6/7 1KHL501779

3.4 Known Issues


Module Identification Explanation
Monitoring TFS 7527 The disturbance recorder has reduced accuracy at low frequency (<10Hz). Signals with DC
offset may have distortion.
Communication TFS 7982 Disturbance record may not exceed 1 second (per one disturbance record) if uploaded over
IEC103.
Communication TFS 8179 There is no default configuration for the In Service output CR01. The Signal
21805_In_Service or 41810_In_Service must be configured if In_Service CR01 is needed.
System TFS 8613 Trip coil supervision function is not supported.
System TFS 8779 In cases where a configuration is not covered by the license of the device. The central unit
has to be rebooted and the set file must be deleted manually using the maintenance menu
of the LHMI.
Communication TFS 8928 Port 8401/tcp on the X1000 interface can handle only 9 simultaneous TCP connections at a
time.
Communication TFS 8929 Telnet session to SFTP server port on the Lan X1000 interface leaks SSH protocol version
in its greeting banner (“SSH-2.0-IPSSH-6.8.0”).
System TFS 9802 Standalone mode of a bay unit is always accompanied by warning message "RPB
Interruption" on LHMI.
System TFS 14718 Simultaneous use of CPU Load indication on several bay units slows down communication
with HMI500.
System TFS 17994 Changing of system frequency (50Hz/60Hz) or changing of bus cycle time (4,6,8,10ms)
requires a manual reboot of all bay units.
System TFS 18524 The system may be blocked by differential current alarm in case where the external switch
is rebooted and at the time window a bus bar fault appears.
Communication TFS 18575 The maximum interruption time in the auxiliary DC voltage without resetting the IED refers
to Bay Unit and Central unit IED only. The interruption time of the external switch may
differ.
System TFS 24311 If a BU reconnects to the CU (after a restart or a communication interruption) the BU state
becomes valid -> invalid -> valid sometimes.
System TFS 25231 For bus cycle 6.67ms and 8.33 ms the BPP “Isolator Operating Time“ is not correct if the
system frequency is set to 60Hz. For all system 50Hz and bus cycle 10ms at 60Hz it is
correct.
HMI500 TFS 20618 It is not possible to change BU device type using HMI500
Communication TFS 26088 When using PRP, the substation automation system (SAS) has to run in PRP mode
"duplicate discard".
System TFS 27978 There is a Security event "Log-in failed - unknown user" when the HMI connects to the
REB500 before the User enters his credentials. This is due to the fact that the HMI500
issues a "get device ID" call.
System TFS 34301 DE170705-24482 REB500 unexpected minor error 177 during short supply interuption <
50ms
Version: page:
REB500 V8.2.0.2 Release Notes 4 7/7 1KHL501779

4 References
4.1 Firmware 8.2.0.2
Firmware Type Version
Operating System VxWorks 6.8.3 PID 3.8
IEC61850 ABB 61850 Stack and Services (ISS) 5.30.00.02
Security ABB Central Account Management (CAM) 2.17.5536.3
Security ABB User Activity Logging Component (UAL) 2.6.1.0
Security ABB Secure Configuration Access (SCA) 2.9.0.2
Security OpenSSL (including Eric Young Cryptographic Software) 0.9.8za
AFS677 AFS677 8.0.05
Update tool REB500fwu_8.2.0.2.378
REB500fwu_8.2.0.1.346
REB500fwu_8.2.0.0.308

4.2 Tool 8.2.0.2


Tool Type Version
Setting and Operating HMI500 Operator V8.2.0.2
Tool
Configuration Tool HMI500 Configurator V8.2.0.2
IEC61850 ABB 61850 SCL Component 2.9.0.80
IEC61850 ABB 61850 Libraries 5.5.0.8
Security ABB Secure Configuration Access (SCA) 2.9.0.2
Security OpenSSL (including Eric Young Cryptographic Software) 1.0.1p
Setfile Migration REB500 Setfile Migrator 3.1.5
Standalone DR Upload Not Available -
Embedded Web Server WebUI 1.0
commit hash:
b7c6c8faeb9021d3ca82b8450e26e5f5aed9f503

Security ABB Central Account Management (CAM) 2.17.3

ConnPack REB500 8.2.0.2 ConnPack is compatible with PCM600 2.7(32-bit and 8.2.0.2
64-bit versions) as well as PCM600 2.8 (32-bit and 64-bit versions
PCM600 2.7 (32-bit / 64-bit)
2.8 (32-bit / 64-bit)

4.3 IED 8.2


Hardware Identification Revision
Central Unit 1MRK010003 AB
Bay Unit 1MRK010004 AB
Switch Switch AFS677 R 08.0.5 or higher

5 Release History

Revision Target Date Changes


V8.00 REB500 2013-12-09 Limited Release
V8.10 REB500 2015-05-06 Market Release
V8.10.01 REB500 2015-10-16 Bugfix Release
V8.10.01 HMI500 2015-11-10 Bugfix Release
V8.2.0.0 REB500 2016-03-23 Market Release
V8.2.0.1 REB500 2016-09-08 Bugfix Release
V8.2.0.2 REB500 2017-09-22 Bugfix Release