VARIABLE FREQUENCY
DRIVE
Limitation or Liability
The remedies of the Purchaser set forth herein are exclusive, and the total liability of the Company with respect to this
contract or the Equipment and services furnished hereunder, in connection with the performance or breach thereof, or
from the manufacture, sale, delivery, installation, repair or technical direction covered by or furnished under this
contract, whether passed on contract, warranty negligence, indemnity, strict liability or otherwise, shall not exceed the
purchase price of the unit of Equipment upon which such liability is based.
The Company and its suppliers shall in no event be liable to the Purchaser, any successors in interest or any
beneficiary or assignee of this contract for any consequential, incidental, indirect, special or punitive damages arising out
of this contract or any breach thereof, or any defect in, or failure of, or malfunction of the Equipment hereunder, whether
based upon loss of use, lost profits or revenue, interest, lost goodwill, work stoppage, impairment of other goods, loss
by reason of shutdown or non-operation, increased expenses of operation, cost of purchase of replacement power or
claims of Purchaser or customers of Purchaser for service interruption whether or not such loss or damage is based on
©INGERSOLL-RAND COMPANY
TABLE OF CONTENTS
2.0 INTRODUCTION
2.1 purpose
2.2 general operation
2.3 service contacts
3.0 INSTALLATION
3.1 VFD mechanical installation
3.2 VFD electrical installation
3.3 control signal warning
3.4 conversion
3.5 VFD start-up proceedure
5.0 OPERATION
5.1 compressor operation control
5.2 parameter description and adjustment
5.3 VFD operation control
5.4 start-up check list
1
0.0 SAFETY SAFETY PRECAUTIONS
Safety instructions in the this manual are bold-faced for BEFORE PROCEEDING, READ THE
emphasis. The signal words DANGER, WARNING and FOLLOWING CAREFULLY BEFORE
CAUTION are used to indicate the level of hazard INSTALLING THE COMPRESSOR OR
seriousness as follows: PERFORMING ANY MAINTENANCE.
! DANGER
WARNING
Danger is used to indicate the presence of a
hazard which will cause severe personal injury,
death, or substantial property damage if Compressed air and electricity are dangerous.
ignored. Before doing any work on this unit, be sure
the electrical supply has been cut off, locked
! WARNING and tagged. Ensure the entire compressor
system has been vented of all pressure.
Warning is used to indicate the presence of a
hazard which can cause personal injury or
substantial property damage if ignored. 1. Do not remove the covers, loosen or remove any
fittings, connections or devices when this unit is in
! CAUTION operation. Hot liquid and air that are contained
within this unit can cause severe injury or death.
Caution is used to indicate the presence of a
hazard which will or can cause minor personal
injury or property damage if ignored. 2. The compressor has high and dangerous voltage in
the motor starter and control box. All installations
NOTICE must be in accordance with recognized electrical
A notice is used to emphasize important codes. Before working on the electrical system, be
installation, operation, or maintenance sure to remove voltage from the system by use of a
information which is not hazard related. manual disconnect switch. A circuit breaker or fuse
safety switch must be provided in the electrical
0.1 Compressor Warnings and Precautions supply line leading to the compressor.
Before installing this air compressor, carefully read all 3. Those responsible for installation of this equipment
the instructions contained in this manual. must provide suitable grounding, maintenance
clearance and lighting arrestors for all electrical
Electricity and compressed air have the potential to components as stipulated in O.S.H.A.1910.308
cause death, severe personal injury or property damage. through 1910.309.
Before installing, wiring, starting, operating or making 4. Do not operate the compressor at higher discharge
any adjustments, identify the components of the air pressure than those specified on the compressor
compressor using this manual as a guide. namplate or motor overload will occur. This
condition will result in compressor motor shutdown.
The operator should use common sense and good
working practices while operating and maintaining this 5. Install a manual shut off valve (isolation type) in the
unit. Follow all codes, understand the starting and discharge line. When a saftey valve is installed
stopping sequence, and pipe adequately. Check the between the isolation valve and the compressor it
safety devices by following the procedures contained in must have sufficient capacity to relieve the full
this manual. capacity of the compressor(s).
Maintenance should be done by qualified personnel 6. Whenever pressure is released through the
adequately equipped with proper tools. Follow the pressure relief valve it is due to excessive pressure
maintenance schedules as outlined in the operator's in the system. The cause for the excessive
manual to ensure problem free operation after start up. pressure should be investigated immediately.
2
7. Before doing any mechanical work on the
compressor: 2. The Stop/Reset key on the local control panel of
the VFD DOES NOT disconnect the equipment
a) Shut the unit down. from the AC line. DO NOT use the Stop/Reset key
as a safety switch.
b) Electrically isolate the compressor by use of
the manual disconnect switch in the power 3. The installer must supply correct protective
line to the unit. Lock and tag the switch so grounding of the equipment. The user must be
that it cannot be operated. protected against supply voltage, and the motor
must be protected against overload in accordance
c) Vent pressure from the compressor and with National Electric Code and local codes.
isolate the unit from any other source of air.
4. To avoid potential shock hazard when servicing a
8. There can be adverse effects if compressor motor or VFD, remove all power to all drives with
lubricants are allowed to enter plant air systems. Air wiring that shares any conduit to be worked on. If
line separators, properly selected and installed, will that is not possible, remove power to the drive and
minimize any liquid carryover. ground the motor wires at the drive. When the
The use of plastic bowls on line filters without metal work has been completed, remove the grounds
guards can be hazardous. From a safety before reapplying power to the drive. In general, a
standpoint, metal bowls should be used on any conduit should not contain unshielded power
pressurized system. Review of your plant air lines conductors for more than three PWM operated
system is recommended. motors.
9. When a receiver is installed, it is recommended that 5. The ground leakage currents are higher at 3.5 mA.
occupational safety and health standards; as
covered in the Federal Register, volume 36, number 6. The Electronic Thermal Relay (ETR) in UL/cUL listed
105, part 11, paragraph1910.159; be adhered to in VFDs provides class 20 motor overload protection in
the maintenance of this receiver. accordance with the NEC in a single motor
applications when parameter 128 is set for "TRIP"
10. Before starting the compressor, its maintenance and parameter 105 is set for the nominal motor
instructions should be read thoroughly and rated (nameplate) current. Protection against motor
understood. overload is NOT included in the factory setting. If
this function is desired, set parameter to 128 to
11. After maintenance functions are completed, covers data value ETR trip or data value ETR warning.
and guards must be replaced.
12. Use only safety solvent for cleaning the compressor Note
and auxiliary equipment. ETR function is initialized at 1.16 x rated
motor current.
Safety Precautions
3
0.3 Warning Against Unintended Start 2. While parameters are being changed, the motor
may start. Consequently, the Stop/Reset button must be
1. The motor can be brought to a stop by means of enabled (Parameter 014) after which data can be modified.
digital commands, bus commands, references or a When the drive is in local stop the LCP will be flashing.
local stop, while the VFD is connected to the AC Parameter 014 will be changed later during the startup
line. procedure.
These stop functions are NOT sufficient to ensure 3. A motor that has been stopped may start if faults
that no unintended start occurs and should NOT be occur in the electronics of the VFD or if a temporary
used for personal safety considerations. overload or a fault in the AC line supply or the motor
connection clears.
The Variable Frequency Drive contains dangerous voltages when connected to line voltage. After
disconnecting from the line wait at least 15 minutes before touching any electrical components. Also
make sure that other voltage inputs have been disconnected, such as external 24 VDC, load-shar-
ing
(linkage of DC intermediate circuit), as well as the motor connection for kinetic back-up. Only a
competent electrician should carry out the electrical installation. Improper installation of the motor or
the VFD may cause equipment failure, serious injury or death. Follow this manual and National
Electrostatic Discharge (ESD) Precaution. Many electronic components are sensitive to static
electricity. Voltages so low that they cannot be felt, seen or heard, can reduce the life, affect
performance, or completely destroy sensitive electronic components.
When performing service, proper ESD equipment should be used to prevent possible damage from
occurring.
It is the responsibility of the user or the person installing the VFD to provide proper grounding, as
! well as motor overload and branch circuit protection according to the National Electrical Code and
local codes.
4
1.0 RECEIPT OF EQUIPMENT 1.2 Uncrating and Handling (5350-5500 Series)
Dimensions H W D
NEMA 1 91.5 (2324) 53.0 (1346) 30.0 (762)
NEMA 12 91.5 (2324) 53.0 (1346) 30.0 (762)
THOROUGHLY INSPECT THIS SHIPMENT A qualified person with a forklift or other similar lifting
IMMEDIATELY UPON ARRIVAL device will be needed to remove the drive from the crate.
To open the crate:
OUR RESPONSIBILITY FOR THIS SHIPMENT
CEASED WHEN THE CARRIER SIGNED Pry up the metal locking tabs that secure the top panel
of the crate, this will allow access to the lifting rings on
If goods are received short or in damaged condition, it is impor- the top of the drive.
tant that you notify the carrier and insist on a notation of the loss
or damage across the face of the freight bill. Otherwise no claim
can be enforced against the transportation company.
Ingersoll-Rand Company
Davidson, North Carolina
APDDG-99-79
5
A forklift or similar lifting device should be used at this At this point refer to Section 3.0.
time to ensure the stability of the VFD while the rest of
the crating is removed. Position the lifting device to the NOTE
front side of the crate. Observe all warnings and safety precautions as well
as all National Electrical Codes (NEC) and local
The VFD should be lifted using a spreader bar or other codes.
similar lifting device. Lift the VFD slightly, using all four
lifting rings, distributing the weight as evenly as possible.
NEMA 1 and NEMA 12
DO NOT lift in this manner.
NEMA 1 and NEMA 12 units are secured to the floor
using the four mounting holes in the bottom panel.
6
2.0 INTRODUCTION The compressor with the VFD will only load and unload
2.1 Purpose at minimum speed, unless the system pressure swings
outside the Intellisys pressure band faster than the drive
The purpose of this manual is to provide instructions can react (See Section 5.2 and Section 8.0 to avoid this
needed to install, operate, and maintain the Ingersoll- occurrence). When the system pressure rises above the
Rand rotary screw air compressor with the I-R 5000 Off Line pressure setpoint, the blowdown valve opens
Variable Frequency Drive (VFD) control. The and the inlet valve closes to unload the compressor. The
Operators/Instruction Manual supplied with the compres- load relay, 2CR, simultaneously opens to switch the
sor and this Instruction Manual supplied with the drive to Setup 1 (constant, minimum speed).
Variable Frequency Drive should be referenced for more
detailed instructions regarding each of these compo- Conversely, when the system pressure falls below the
nents. On Line pressure setpoint, the blowdown valve closes
and the inlet valve opens to load the compressor. The
The VFD will maintain a constant pressure in com- load relay, 2CR, simultaneously closes to switch the
pressed air systems by adjusting the compressor drive to Setup 2 (pressure regulation).
motor’s speed to match the compressed air usage.
Depending on the application and air demand profile, the Even with the VFD wired to the compressor, the Start
VFD system can achieve 25-35% energy savings. button on the Intellisys controller initiates the full-voltage
Smooth start-up, reduced machine cycling, lower noise, or star-delta starters. When the 1M contactor closes, the
and monitoring energy parameters are other benefits start relay, 1CR, closes to start the VFD. On air-cooled,
from an Ingersoll-Rand compressor equipped with VFD. SSR units, the contactors have no power flowing through
them. However, the 1M contactor does provide power to
2.2 General Operation the constant-speed fan (for a water-cooled unit) and the
oil pump (on Sierra units only). After the Start process is
The I-R 5000 drive is an external device that is wired to completed, the compressor will automatically load and
the compressor’s motors through the starter panel. The the VFD will try to regulate the pressure.
Intellisys controller on the compressor still starts and
stops the compressor, while the VFD’s controller varies On SSR air cooled units, the VFD controls the main
the compressor’s motor speed to regulate constant sys- drive motor and the cooling fan motor.
tem pressure. The VFD operates in two different setups:
On SSR water cooled units, the VFD controls the main
1) In Setup 1, the VFD runs at constant minimum drive motor. The small enclosure fan motor gets its
speed and the compressor is unloaded. power from the compressor starter.
2) In Setup 2, the VFD regulates a constant pressure On Sierra units, the air cooled and water cooled units
and the compressor is loaded. are configured the same as the SSR units, except the
externally driven oil pump gets its power from the com-
The Intellisys controller logic determines which setup the pressor starter.
VFD operates. See Intellisys and VFD Controllers
Interface Logic Diagram Figure 2.2-1. As always, the 2.3 Service Contacts
Intellisys controller, set to On / Off Line mode, will load
and unload the compressor, depending on the system Contact your local Ingersoll-Rand distributor or air center
pressure relative to the pressure band limits. The VFD, for any service inquiries, maintenance, or any other
however, tries to keep the system pressure within the additional technical support.
pressure band as long as possible.
7
Figure 2.2-1 INTELLISYS AND VFD CONTROLLERS INTERFACE LOGIC DIAGRAM
8
3.0 INSTALLATION I-R 5052, 200-240V, NEMA 1, NEMA 12
A = 10 inches (250mm)
3.1 VFD Mechanical Installation
I-R 5062-5102, 380-500V, NEMA 1, NEMA 12
3.1.1 Environment A = 8 inches (200mm)
The area selected for the location of the VFD should be I-R 5075-5125, 550-600V, NEMA 1, NEMA 12
free of dust, chemicals, metal filings, paint fumes and A = 10 inches (250mm)
overspray.
I-R 5122-5302, 380-500V, NEMA 1, NEMA 12
A = 8.9 inches (225mm)
OVERSPRAY
3.1.3 Cooling
NOTE
For proper cooling, mount the VFD against a
flat surface, such as a wall or a piece of sheet
metal.
9
3.1.3.b Cooling (I-R 5350-5500 Series)
The I-R 5300-5500 Series VFD drive does not require
The I-R 5000 VFD is cooled by means of air circulation. free air space between the drives.
For the cooling air to escape from the unit a minimum
clearance of 15.7 inches (400mm) must be left above
the units.
NOTE
For proper cooling, mount VFD against a flat surface
such as a wall or sheet metal.
Mounting
10
3.1.4 Terminal and Switch Locations In general, a conduit should not contain unshielded
power conductors for more than three PWM operated
For VFD terminal and switch locations, please refer to motors.
the Terminal and Switch Locations drawings in Section
10.0. NOTE
It is the responsibility of the user or installer to
3.2 VFD Electrical Installation ensure correct grounding, branch circuit and motor
protection in accordance with the NEC and local
The voltage of the VFD is dangerous when the unit is codes.
connected to the AC line. Incorrect installation of the
motor or I-R 5000 VFD may lead to material damage or
serious injury or death. Follow the instructions in this
manual and comply to National Electrical Codes (NEC)
and local codes and safety guidelines.
11
3.2.1 Connection of AC Line 3.2.2 Schematics
Connect the three AC line phases to L1 (91), L2 (92), Table 3-1 lists the electrical schematics that illustrate the
and L3 (93) of the terminal block labeled Mains. Refer to proper way to wire the VFD to the compressor. Locate
the Terminal and Switch Location Drawings in Section the correct schematic for the corresponding compressor
10.0. as shown in Table 3.1 and Section 10.0. The three con-
trol relays, pressure transducer, and contactor (Sierra
NOTE only) should be wired per the proper schematic. Also
To minimize electrical noise, install the drive within refer to Figure 10.2, Control Relay Wiring.
100 feet (30 meters) of compressor.
NOTE
NOTE For proper safety, wire compressor and drive to a
To avoid electrical noise, do not route high-voltage common ground.
motor wires and low-voltage control wires through
the same conduit.
12
FIGURE 3.2-1 RECOMMENDED VFD AND COMPRESSOR SYSTEM DESIGN DATA
13
3.2.3 Pre-fuses 3.2.5 Switches 1-4
External pre-fuses must be installed in the AC line sup- The switch located on the control card is used for serial
ply to the I-R 5000 VFD. communication, terminals 68 and 69 and the 24V supply.
Switch 1 has no function. Switch 2 and 3 are used for
TABLE 3.2 FUSING terminating an RS 485 interface, serial communication.
Switch 4 is used for separating the common potential for
Drive Voltage Fuse Type Max. Amps.
the internal 24 VDC supply from the common potential of
5016 80 an external 24 VDC supply, if used.
5022 KTN-R or JJN 125 3.2.6 RFI Switch (optional)
5027 200-240 125
5032 150 Refer to the Terminal and Switch Location drawings in
5042 FWX Semi-Conductor 200 Section 10.0. In special situations, it may be desirable to
5052 250 cut off the internal RFI filter capacitors between the
5016 63 chassis and the intermediate circuit. Units are shipped
5022 63
from the factory with the switch in the ON position.
5027 63
5032 KTS-R or JJS 80 Disconnect by moving the RFI switch to the OFF posi-
5042 100 tion.
5052 125
5062 150 NOTE:
5072 200 The RFI switch is NOT to be operated with the
5102 380-500 250 AC line connected to the unit. Check that the AC line
5122 300 has been disconnected before removing the motor and
5152 350 line terminal plugs.
5202 FWH Semi-Conductor 400
5252 500
5302 600 The RFI switch disconnects the capacitors galvanically;
5350 700 however, transients higher than approx. 1,000 V will be
5450 800 bypassed by a spark gap. It is necessary that the RFI
5500 800 Switch is opened when installing on Delta configuration
5052 KTS-R 90 AC power systems. Failure to open this switch may
5062 KTS-R 100 result in occasional tripping or possible unit damage.
5075 FWP 125
5100 550-600 FWP 175 For units with RFI Option only;
5125 FWP 200
It is necessary that the two (2) RFI Jumpers are
5150 FWP 250
5200 FWP 350 removed when installing on Delta configured AC power
5250 FWP 400 systems. Failure to open these RFI Jumpers may result
in occasional tripping or possible unit damage. Both RFI
Jumper assemblies are "plug-in" type that do not require
Suitable for use on a circuit capable of delivering not tools to be removed or re-installed.
more than 100 kA rms symmetrical amperes, 500 Volts
maximum when protected by the above fuses. One jumper is located on the RFI Filter itself on the far
left side, midway between the top and bottom of the unit.
On NEMA 1 drives, it is necessary to remove the wiring
NOTE channel for the routing of the logic wiring to the control
Fuse Type: Bussmann FWH Semi-conductor. Use card, (do not remove the control card) to gain access to
proper pre-fuse for corresponding VFD. the jumper. The jumper is a small black plastic tab with
two wire prongs (approx. 0.25 x 0.5 inch). It is inserted
3.2.4 Safety Grounding on the circuit board of the RFI Filter assembly. The
jumper may be removed or re-inserted by hand.
Please note that the I-R 5000 variable frequency drive
has a high leakage current and must be grounded The other jumper is on a circuit board located in the
appropriately for safety reasons. Use the ground termi- lower portion of the unit on the bottom of the capacitor
nals (refer to the terminal drawings) which enable rein- bank assembly. The jumper assembly is a black wire
forced grounding. All national and local safety codes approximately 1.5 inches long with a right-angle fast-on
must be observed. connector on each end.
14
3.2.7 Motor Connection
3.3.2 Transducer Installation
The power cables from the VFD connect to the motor
terminal block located at the bottom of the compressor’s A pressure transducer (4-20 mA; 0-200 psig / 0-13.8
starter box. The compressor and fan motors’ leads are barg) has been provided as a feedback sensor for the
connected to the other side of this block. I-R 5000 variable frequency drive. In order to maximize
stability, it is recommended that the transducer receives
The power cables from the compressor/VFD system’s its pressure signal from the system tank.
main disconnect (DIS1) to the top of the compressor’s
starter contactors should be sized for the full amp rating The transducer has a 0.125-in NPT threaded connec-
of the machine. This setup allows for the compressor to tion. A 6-ft long cable has also been provided to wire the
be quickly converted from variable speed to constant transducer into the drive (see proper wiring schematic).
speed control should the VFD need servicing. The transducer is to be mounted somewhere on the
drive. This will provide a cleaner installation and mini-
3.3 Control Signal Wiring mize electrical noise interfering with the transducer’s sig-
nal. With the transducer on the drive, a plastic tube can
3.3.1 Cable and Control Terminal Connection be plumbed into the system’s receiver tank.
For models up to I-R 5302, all terminals for the control Connect the transducer to the VFD per the proper wiring
cables are located under the protective cover of the I-R schematic.
5000 variable frequency drive. The protective cover can
be removed as pictured, using care. 3.4 Conversion
Max. 16 AWG (4.0mm2) wire for all I-R 5000 models. 3.4.1 Field Conversion
Screw size M3. Torque to 5 in-lbs (0.6 Nm).
For field conversions contact your local I-R distribu-
tor or air center to ensure that the motor and con-
trols are appropriate and to determine the proper
speed range of your compressor. Conversion to an
SG Controller may be required in some applications
to avoid operation problems. Check with your I-R
representative.
15
! CAUTION 3) Move the motor leads from the starter contactor termi-
nal lugs to the tie-off block mounted in the bottom of the
Prime Sierra oil pump by filling suction hose with oil starter box (where the VFD leads come into the com-
BEFORE applying power to compressor. Once filled pressor starter box). For air cooled units, the fan motor
with oil, quickly start and stop compressor until leads must also be moved. The lugs on the bottom of
pump and associated hose are free of vibrations. the 1M, 2M, and 1S contactors may have to be removed
Note: compressor should not be started and to meet the terminal clearance requirements of some
stopped in this manner more than 3 times. Pump local
seals may fail if pump runs dry. Once primed, there electrical codes.
should be no need to prime pump again unless com-
pressor has sat idle for extended time. 4) Wire the normally-open contact of the VFD alarm
relay (3CR) into the control power wiring as shown in the
NOTE wiring schematics. Make sure relays (1CR and 2CR) are
If Sierra oil pump was not installed at factory, check properly wired as shown on the appropriate wiring
for proper pump rotation. Ensure pump rotates schematic (see Section 10.0).
counter-clockwise while viewing pump from behind
motor. 5) Restore power to the machine and VFD.
If the VFD is wired as shown in the schematics in For conversion back to the starter from the VFD, recon-
Section 10.0, a simple procedure is followed to convert nect the motor leads to the motor contactors and remove
the compressor from operation with the compressor’s the VFD alarm relay (3CR).
conventional starter to operation with the VFD and vice
versa.
16
3.5 VFD STARTUP PROCEDURE 16) Check or complete wiring from VFD ouput to motor
terminal block MTB.
1) Locate customer’s compressor power supply discon-
nect box. Lock and Tag-out this power source. Note: Remember to attach fan motor wiring as
shown on the proper wiring schematic for aircooled
2) Determine which Semi-conductor quick blow fuses units.
are necessary. Ensure the fusible disconnect is appropri-
ately sized for the necessary fuses. 17) Remove lock and tag from disconnect.
8) Locate control relays 1CR, 2CR and 3CR on the Note: Main Motor Power KW is determined by taking
wiring schematic. Main motor nameplate horsepower and multiplying it
by .75 to get your kW. (HP X .75 = kW).
9) Check installation of the 1CR, 2CR and 3CR relays in
the compressor starter cabinet. 22) Parameter 103 – Motor Voltage (Motor
Nameplate Voltage)
10) Wire 1CR, 2CR and 3CR relays according to the
proper wiring schematic. 23) Parameter 104 – Motor Frequency (Motor
Nameplate Frequency (Hz).
11) Verify a normally closed alarm contact internal to the
drive, located on terminals 01 and 03, using a continuity 24) Parameter 105 – Motor Current (Motor
meter. Nameplate Amps)
12) Complete interface wiring for all 3 relays from termi- Note: Some units may give you a Alarm during AMA
nal strip 3TB to the VFD terminal strip shown on the If a motor does not match message you may need to
wiring schematic. change Parameter 105 to motor nameplate amps
plus service factor.
13) Add jumper wires as shown on the VFD control wire
terminal strip. (39 to 55) and (12 to 18). 25) Parameter 106 – Motor Nominal Speed (Motor
Nameplate RPM)
14) Complete wiring for pressure transducer on VFD;
refer to the proper electrical schematic. 26) Parameter 107 – AMA (Automatic Motor Adaptation)
Skip at this time.
15) Check and confirm proper wiring of the oil stop valve
starting from wiring location 3CR N.O. contact (contact 27) Parameter 204 – Minimum Reference (Parameter
cooled compressor only). setpoint on Table 5.2 use the setup 1 setpoints)
17
28) Parameter 205 – Maximum Reference (Parameter Note: After disconnecting the AC power, the DC bus
setpoint on Table 5.2 use the setup 1 setpoints) in the drive can stay live for 15 minutes so NO
WORK SHOULD BE DONE IN THE STARTER PANEL
29) Parameter 207 – Ramp Up Time (Parameter setpoint UNTIL 15 MINUTES HAS PASSED AFTER DISCON-
on Table 5.3) NECTING INCOMING POWER.
Note: If Ramp Up Time (Par 207) is set too short, you 41) Depress the Menu button.
may get a overcurrent alarm at startup.
42) Select the “0” menu, depress the “+” button until
30) Parameter 208 – Ramp Down Time (Parameter set- Parameter 002 is displayed.
point on Table 5.3)
43) Parameter 002 – Local / Remote Control (Parameter
31) Parameter 002 – Local / Remote Control (Parameter should be set for REMOTE at this time)
should be set for Local at this time) (The LCP display
should start flashing). 44) Parameter 004 – Active Setup (Parameter should be
set for MULTI SETUP)
32) Parameter 003 – Local Reference (Should be set at
the factory default of 30Hz) This is the last step on the 45) Parameter 005 – Edit Setup (Parameter should be
Quick Menu. set for SETUP 1)
33) Depress the Menu button on the LCP (Use the left 46) Parameter 008 – Display Scaling of Motor
and right arrows on the LCP to get to the “0” menu. Frequency ( Parameter should be set for 0.01)
Then depress the “+” until Parameter 013 is displayed.
47) Parameter 009 – Display Line 2 (Parameter should
34) Parameter 013 – Local Control / Configuration as be set for FREQUENCY [Hz])
Parameter 100 (Set Parameter to LCP CTRL / AS P100
48) Parameter 010 – Display Line 1.1 (Parameter should
35) Parameter 014 – Local Stop (Set Parameter to be set for REFERENCE [unit])
ENABLE)
49) Parameter 011 – Display Line 1.2 (Parameter should
36) Check your motor rotation (Start and Stop the com- be set for FREQUENCY X SCALE)
pressor with the Start and Stop buttons on the LCP).
50) Parameter 012 – Display Line 1.3 (Parameter should
Note: After disconnecting the AC power, the DC bus be set for POWER [kW])
in the drive can stay live for 15 minutes so NO
WORK SHOULD BE DONE IN THE STARTER PANEL 51) Parameter 013 – Local Control / Config. ( Parameter
UNTIL 15 MINUTES HAS PASSED AFTER DISCON- should be set for “LCP+DIG CTRL / AS P100)
NECTING INCOMING POWER.
52) Parameter 014 – Local Stop ( Parameter should be
37) Shut off incoming power, disconnect fan motor set for “DISABLED”)
(record your fan motor lead connections to ensure prop-
er rotation when reinstalled) Turn power back on after 53) Depress Right Arrow Button until the “1” menu is dis-
disconnecting fan motor. played, Depress the “+” button until Parameter 100 is
displayed.
38) Depress the menu button.
54) Parameter 100 – Configuration ( Parameter should
39) Use the right arrow on the LCP to get to the 100 be set for SPEED OPEN LOOP)
menu. Depress the “+” key until you get to Parameter
107 – AMA (Set Parameter to ENABLE Rs + Xs) 55) Parameter 101 – Torque Characteristics ( Parameter
depress the Start button on the LCP. The LCP display should be set for N-CONSTANT TORQUE)
will stop flashing and display “WORKING” (AMA could
take up to 10 minutes to complete) When the AMA has 56) Review Parameters 102 through 109. Write these
completed, the LCP will display “ALARM 21 AUTO parameters down to ensure they are properly copied to
MOTOR ADAPT OK”. Depress the Reset / Stop button. setup 2.
40) Shut off incoming power. Reconnect fan motor. Turn 57) Parameter 120 – Start Delay ( Parameter should be
power back on after reconnecting the fan motor. set for 0.1 sec)
18
58) Parameter 128 – Motor Thermal Protection played. Depress the “+” key until Parameter 400 is dis-
(Parameter should be set for ETR TRIP 1) played.
59) Depress the right arrow button until the “2” menu is 77) Parameter 400 – Brake Function (Parameter should
displayed. Depress the “+” key until Parameter 201 is be set per Table 5.1)
displayed. Parameters 201 – 205 need to be set per
Table 5.2. 78) Parameter 409 - Trip Delay Torque (Parameter
should be set for 10 sec.)
60) Parameters 207 and 208 need to be set per Table
5.3. Note: Parameter 414 through 416 should be pro-
grammed in reverse order for proper setup.
61) Parameter 215 – Preset Reference 1 ( Parameter
should be set for 0.00) 79) Parameter 416 – Process Unit ( Parameter should
be set for NO UNIT)
62) Depress the right arrow button until the “3” menu is
displayed. Depress the “+” key until parameter 300 is 80) Parameter 415 – Maximum Feed Back (Parameter
displayed. should be set for 200)
63) Parameter 300 – Terminal 16, Input (Parameter 81) Parameter 414 – Minimum Feed Back (Parameter
should be set for NO OPERATION) should be set for 0)
64) Parameter 301 – Terminal 17, Input (Parameter 82) Setup 1 is complete, depress the right arrow button
should be set for NO OPERATION) until menu “0” is displayed, depress the “+” key until
Parameter 006 is displayed.
65) Parameter 302 – Terminal 18 Start, Input (Parameter
should be set for START) 83) Parameter 006 – Copying of Setups (Parameter
should be set for COPY TO SETUP 2) After the “OK”
66) Parameter 303 – Terminal 19, Input (Parameter button is pushed the LCP will display “COPYING”
should be set for NO OPERATION)
84) Parameter 005 – Programming Setup (Parameter
67) Parameter 304 – Terminal 27, Input (Parameter should be set for SETUP 2) The small 2 should be flash-
should be set for COAST INVERSE) ing on the right hand side of the LCP screen.
68) Parameter 305 – Terminal 29, Input (Parameter 85) All the Parameters on Tables 5.1, 5.2 and 5.3 for
should be set for NO OPERATION) setup 2 should be verified. A large portion of these
Parameters are the same as setup 1, the following are
69) Parameter 306 – Terminal 32, Input (Parameter the ones that are different.
should be set for NO OPERATION)
86) Parameter 008 – Display Scaling of Motor
70) Parameter 307 – Terminal 33, Input (Parameter Frequency (Parameter should be set for the solution of
should be set for SETUP, lsb/SPEED DOWN) the equation in section 5.3.2 “setting VFD display”.
71) Parameter 308 – Terminal 53, Analog Input Voltage 87) Depress the right arrow until “1” menu is displayed.
(Parameter should be set for NO OPERATION) Depress the “+” key until Parameter 100 is displayed.
72) Parameter 314 – Terminal 60, Analog Input Current 88) Parameter 100 – Configuration (Parameter should
(Parameter should be set for NO OPERATION) be set for Process Closed Loop)
73) Parameter 315 – Terminal 60, Min. Scaling 89) Depress the right arrow until “2” menu is displayed.
(Parameter should be set for 4.0mA)
Note: Parameter 205 should be set before parameter
74) Parameter 316 – Terminal 60, Max Scaling 204.
(Parameter should be set for 20.0mA)
90) Parameter 205 – Maximum Reference ( Parameter
75) Parameter 323 – Relay 01, Output (Parameter should be set for max rated pressure of the compressor)
should be set for ALARM)
Note: Hundreds must be set before tens in most
76) Depress the right arrow key until menu “4” is dis- cases with parameter 205.
19
91) Parameter 204 – Minimum Reference (Parameter 101) Setup 2 is now completed.
should be set to Table 5.2 for the correct compressor). 102) Depress the left arrow button until “0” menu is dis-
played. Depress the “+” button until Parameter 005 is
92) Parameter 215 – Preset Reference 1 (Parameter displayed.
should be set for the solution of the equation in section
5.3.8 “preset reference data”). 103) Parameter 005 – Programming setup (Parameter
should be set for ACTIVE DISPLAY).
93) Depress the right arrow until “3” menu is displayed.
104) Set SG Controller customer setpoints. Set on-line
94) Parameter 314 – Terminal 60, Analog Input Current and off-line pressures on each side of the target pres-
(Parameter should be set to FEEDBACK). sure (Parameter 215) selected for the VFD transducer.
95) Depress the right arrow until “4” menu is displayed. Note: Be aware of any pressure drop that may exist
between the drive pressure transducer pick-up loca-
96) Parameter 409 - Trip Delay Torque (Parameter tion and the SG controller pressure transducer pick-
should be set to OFF). up location.
97) Parameter 440 – Process PID Proportional Gain 105) Start the compressor from the Compressor control
(Parameter should be set to 3). panel. Adjust Parameter 215 as required to meet the
customer’s requirements.
98) Parameter 441 – Process PID Integral Time
(Parameter should be set for 1 sec). Note: The fine-tuning of Parameter 215 should be
done with the customer’s air load at a normal steady
99) Parameter 442 – Process PID Differentiation Time condition.
(Parameter should be set for .01 sec).
20
4.0 USER INTERFACE locked out via parameter 018.
2nd line
The control panel is detachable (except NEMA 12 units) 12345678 SETUP
1
and can, as an alternative, be installed up to 10 feet (3
meters) away from the VFD, e.g., on a control panel
3rd line 12345678901234567890
• display
• keys for changing program parameters
• keys for local operation
21
4.4 Control Keys 4.5 Display Modes
The control keys on the LCP are divided into functions. In normal operation, up to 4 different operating variables
The keys between the LCD display and the LEDs are can be indicated continuously, 3 on line one (1.1, 1.2 and
used for parameter setup, including choice of display 1.3) and another on the large display (line 2). Line four
indication during normal operation. displays the present operating status or any alarms or
warnings that have occurred.
+
STATUS
–
+ [+] and [–], [<] and [>] provide the user the
– ability to move the cursor around the LCD
display, or sequence through display
values. These keys are active during
operation as well as programming modes.
22
4.5.1 Display Mode Selection
Mode: I II III
REF% TORQ% CUR A
Line 1 display: Description 3 operational Description
for operating data values of the 3
value in line 2. in line 1. values in 60.0 HZ SETUP
1 In
line 1.
RUNNING
Mode I
This display type shown is the default after start up or
re-initialization. Line 1 describes the value in line 2 (large
dis- mode II, data for four operating values are shown at
the same time, in the selected unit. In the example
shown, Reference, Torque, Current and Frequency are
FREQUENCY selected as variables in the first and second lines.
60.0 HZ SETUP
1
RUNNING
Mode III
play). FREQUENCY
60.0 HZ SETUP
1
In
60.0 HZ SETUP
1
the
RUNNING
23
When the desired parameter group has been selected, a 4.5.3.2 Changing a Number Value
parameter within that group can be chosen with the [+]
and [–] keys: The numerical value of some parameters are selected
from a fixed list of values, such as 0.37 kW, 0.55 kW or
1.00 kW. These cannot be individually modified, as they
are part of the software data base. Other parameters
FREQUENCY provide data values that can be set within a range (i.e.,
0-130 Hz) and fine-tuned by the user.
60.0 HZ SETUP
1
4.5.3.2.1 Selection from a List
001 LANGUAGE
Pressing the [CHANGE DATA] key gives access to the 60.0 HZ SETUP
1
selected parameter value shown on the 4th line of the 102 MOTOR POWER
display. 0.37 KW
0.55 KW
FREQUENCY
60.0 HZ SETUP
1
The chosen data value is indicated by the digit flashing.
001 LANGUAGE The bottom display line shows the data value that will be
ENGLISH entered (saved) by pressing the [OK] key.
The bottom display line shows the text value that will be
entered (stored) when acknowledgment is given by
pressing the [OK] key. The [CANCEL] key abandons the
selection.
24
4.5.3.2.2 Changing in a Value Range
10. 0 Hz
FREQUENCY
60.0 HZ SETUP
1
Selecting a digit to the left allows for faster programming
130 START FREQUENCY when a larger change is desired. Fine-tuning is easier
09 . Hz using digits farther to the left on the data value. The
bottom display line shows the data value that will be
entered (saved) when pressing the [OK] key.
25
5.0 OPERATION I-R 5000 Series LCD display:
5.1 Compressor Operation Control
have enough range to allow the VFD as much as 3 to 5 4th line 12345678901234567890
psi of overshoot of the target pressure. In addition to the
overshoot range, the off line setpoint must be set high
enough to allow for the pressure drop between the com-
pressor’s pressure transducer and the VFD’s transducer.
On the right hand side of the display the active setup is
The unloaded inlet vacuum may be lower than expected shown, as well as the setup in which programming is
when the VFD controls the compressor to minimum taking place. A flashing setup number indicates that pro-
speed. Therefore, the stepper motor inlet valve control gramming is taking place.
system on some compressors may create nuisance
alarms or warnings at startup. This is most likely to hap- SETUP
pen if the Intellisys controller is programmed to remain 1
12
unloaded after start-up. To prevent these problems, pro-
gram the controller in accordance with the following: Active Flashing
Operation Programming
1) Perform the Inlet Valve Getting Smart Procedure at Setup Setup
minimum speed. (Contact your service representative To change the programming setup, select the corre-
for details.) sponding setup in parameter 005.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
26
5.3 VFD Operation Control
NOTE
Table 5-1 lists all of the important VFD parameters that Both Setup 1 and Setup 2 must be programmed
must be programmed for proper compressor operation. for proper compressor operation. Parameters
(See Chapter 4, VFD User Interface, for instructions on may not have been programmed completely at
programming parameters.) Section 5.1 contains detailed the factory. Before startup, ensure that all
descriptions and instructions for programming the VFD parameters are programmed in accordance with
parameter. values in Table 5.1.
27
5.3.1 Language and Setup
Description
This parameter selects the setup number to control the
functions of the I-R 5000.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
28
007 LCP Copy 5.3.2 Setting VFD Display
(LCP COPY)
Value In normal operation, up to four different operating
★No copying (NO COPY) [0] variables can be viewed continuously. The last line of
Upload all parameters (UPLOAD ALL PARAM) [1] the
Download all parameters (DOWNLOAD ALL) [2] display indicates status. Please refer to Chapter 4, User
Download power-independent parameters Interface, for details on display settings.
(DOWNLOAD SIZE INDEP.) [3]
For a compressor application some of the most impor-
tant operating variables to view are Frequency (Hz),
Description Input Reference indicating target pressure, Capacity,
and
Parameter 007 is used for the integrated copying Motor Power.
function of the control panel. This function is used if a
given parameter setup is to be copied from one variable In order to show the correct value for capacity the dis-
frequency drive to another by the removable control play scaling of the motor frequency must be set properly
panel.
008 Display scaling of motor frequency
Select Upload all parameters [1] if all parameter values (FREQUENCY SCALE)
are to be transmitted from the VFD to the control panel. Value
Select Download all parameters [2] if all transmitted 0.01 - 100.00 ★Depends on
parameter values are to be copied to the VFD from the capacity unit of
control panel. measure
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
29
009 Display line 2 011 Display line 1.2
(DISPLAY LINE2) (DISPLAY LINE 1.2)
Value Value
[0] See parameter 009. ★ Frequency Scale
Reference [%] (REFERENCE [%]) [1]
Reference [unit] (REFERENCE [UNIT]) [2] Description
Feedback [unit] (FEEDBACK [UNIT]) [3] Display line 1.2 indicates the second of three data val-
★Frequency [Hz] (FREQUENCY [HZ]) [4] ues to be displayed in line 1, position 2.
Frequency x Scaling [–] (FREQUENCY x SCALE) [5] Setting this parameter to FREQUENCY SCALE will
Motor current [A] (MOTOR CURRENT [A]) [6] display the approximate capacity that the compressor is
Torque [%] (TORQUE [%]) [7] delivering. The scale is set by parameter 008.
Power [kW] (POWER [KW]) [8]
Power [HP] (POWER [HP] [US]) [9]
Output energy [kWh] (OUTPUT ENERGY [KWH]) [10]
Motor voltage [V] (MOTOR VOLTAGE [V]) [11] 012 Display line 1.3
DC link voltage [V] (DC LINK VOLTAGE [V]) [12] (DISPLAY LINE 1.3)
Thermal load, motor [%] (MOTOR THERMAL [%]) [13] Value
Thermal load, VLT [%] (VLT THERMAL [%]) [14] See parameter 009. ★ Power [kW]
Hours run [Hours] (RUNNING HOURS) [15]
Digital input [Binary code] (DIGITAL INPUT [BIN]) [16] Description
Analog input 53 [V] (ANALOG INPUT 53 [V]) [17] Display line 1.3 indicates the third of three data values
Analog input 54 [V] (ANALOG INPUT 54 [V]) [18] to be displayed in line 1, position 3.
Analog input 60 [mA] (ANALOG INPUT 60 [MA]) [19] Setting this parameter to POWER [kW] will display the
Pulse reference [Hz] (PULSE REF. [HZ]) [20] power the compressor is consuming in kilowatts.
External reference [%] (EXTERNAL REF [%]) [21]
Status word [Hex] (STATUS WORD [HEX]) [22]
Brake effect/2 min. [kW] (AVERAGE BRAKE ENERGY) [23]
Brake effect/sec. [kW] (ACTUAL BRAKE ENERGY) [24]
014 Local Stop
Heatsink temp. [°C] (HEATSINK TEMP [°C]) [25]
Alarm word [Hex] (ALARM WORD [HEX]) [26] (LOCAL STOP)
Control word [Hex] (CONTROL WORD [HEX]) [27] Value
Warning word 1 [Hex] (WARNING WORD 1 [HEX]) [28] Not possible (DISABLE) ★ [0]
Warning word 2 [Hex] (WARNING WORD 2 [HEX]) [29] Possible (ENABLE [1]
Description
Description
Display line 2 is the main line of the display. For Set this parameter to DISABLE so that the drive can
compressor operation this parameter should be set to only be stopped from the Intellisys controller.
FREQUENCY [Hz].
Description
Display line 1.1 indicates the first of three data values to
be displayed in line 1, position 1.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
30
5.3.3 Operation and Load Data
Setup 1 (Unloaded Mode) = Speed Open Loop Normal overload torque (110%)
Setup 2 (Loaded PID) = Process Closed Loop
★ Norm-constant torque
SPEED REGULATION OPEN LOOP allows for normal (N-CONSTANT TORQUE) [11]
speed control, without process feedback from the Norm-variable torque low
pressure transducer. In this setup, the compressor is (N-VAR. TORQ. : LOW) [12]
unloaded and will run at a constant minimum speed. N-variable torque medium
(N-VAR. TORQ.: MED) [13]
PROCESS REGULATION CLOSED LOOP activates the Norm-variable torque high
internal process regulator. This allows for accurate (N-VAR. TRQ.: HIGH) [14]
regulation of the compressor with respect to the Norm-special motor characteristics
pressure setpoint. The output from the pressure (N-SPEC.MOTOR. CHARACT) [15]
transducer is the feedback signal to the VFD. Normal-variable torque with low constant
starting torque (N-VT LOW W. CT-START) [16]
Normal-variable torque with medium constant
starting torque (N-VT MED W. CT-START) [17]
Normal-variable torque with high constant
starting torque (N-VT HIGH W. CT-START) [18]
Description
Set this parameter to N-CONSTANT TORQUE. The
compressor application is optimized when using the
NORMAL constant torque overload mode. This mode
will provide 100% of rated drive torque on a continuous
basis and 110% of torque intermittently.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
31
5.3.4 Motor Tuning Procedures 5.3.5 Motor Data
Description
This parameter sets the kW value that corresponds to
the compressor. If the compressor’s motor is
horsepower-rated, multiply the horsepower by 0.75 to
convert to kilowatts.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
32
103 Motor Voltage 106 Rated Motor Speed
(MOTOR VOLTAGE) (MOTOR NOM. SPEED)
Value Value
200 V [200] 100 - 60000 RPM [100 - 60000]
208 V [208] ★ Depends on the unit
220 V [220]
230 V [230] Description
240 V [240] This parameter sets the rated motor speed (rpm) value
380 V [380] that corresponds to the compressor.
400 V [400]
415 V [415] NOTE
440 V [440] Parameters 108 and 109 normally are not set if
460 V [460] nameplate data has been entered.
480 V [480]
500 V [500]
550 V [550]
575 V [575] 108 Stator Resistor
★ Depends on the unit
(STATOR RESIST)
Description Value
This parameter sets the voltage (Volt) value that x ohm - y ohm
corresponds to the compressor. ★ Depends on the choice of motor
Description
104 Motor Frequency
This parameter corresponds to the value of stator
(MOTOR FREQUENCY) resistance of the main motor.
Value
50 Hz (50 HZ) [50]
60 Hz (60 HZ) [60]
Max. motor frequency 1000 Hz 109 Stator Resistance
★ Depends on the unit (STATOR REACT.)
Value
Description x ohm - y ohm
This parameter sets the frequency (Hz) value that ★ Depends on the choice of motor
corresponds to the compressor.
Description
This parameter corresponds to the value of stator
105 Motor Current resistance of the main motor.
(MOTOR CURRENT)
Value
0.01 to drive rating Set nameplate data 119 High Starting Torque
★ Depends on the unit (HIGH START TORQU.)
Value
Description 0.0 - 0.5 sec. ★ 0.0 sec
This parameter sets the current (A) value that
corresponds to the compressor. Description
For compressors with normally open inlet valves
(e.g. 50 SE Full Voltage), the drive may need to supply
higher startup torque. In order to secure a high starting
torque, approx. 2 times the maximum normal output cur-
rent for max. 0.5 sec. is allowed. However, the current is
limited by the protection limit of VFD. This should only
be adjusted in Setup 1 if needed.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
33
120 Start Delay 5.3.6 Setting Motor Operation Range
(START DELAY)
Value Parameters 201 and 202 set the minimum and
0.0 - 10.0 sec. ★ 0.1 sec. maximum frequency of operation. This range is based on
Depends on the choice of motor the type of compressor.
Description CAUTION
For compressor operation this value should be set to Severe damage to compressor or motor can
0.1 result if minimum or maximum frequencies
sec. This enables a delay of the start time. (parameters 201 and 202) are set outside
recommended speed range. Warranty will be
voided if recommended settings are not
128 Motor Thermal Protection followed.
(MOT. THERM PROTEC)
Value Parameters 204 and 205 set the operation range for both
No protection (NO PROTECTION) [0] the Unloaded and Loaded PID modes. For the Unloaded
Thermistor warning (THERMISTOR WARN) [1] mode (Setup 1) and the Loaded PID mode (Setup 2), the
Thermistor trip (THERMISTOR FAULT) [2] values of Parameters 204 and 205 should correspond to
ETR Warning 1 (ETR WARNING 1) [3] Tables 5.2A and 5.2B.
★ETR Trip 1 (ETR TRIP 1) [4]
ETR Warning 1 (ETR WARNING 2) [5] Pressure units selected in setting parameters 204 and
ETR Trip 2 (ETR TRIP 2) [6] 205 in Setup 2 must be consistent with those used in
ETR Warning 1 (ETR WARNING 3) [7] parameters 414, 415, and 416.
ETR Trip 3 (ETR TRIP 3) [8]
ETR Warning 1 (ETR WARNING 4) [9] NOTE
ETR Trip 4 (ETR TRIP 4) [10] Compressor will not operate properly if parameters
204 and 205 are not set properly for Setup 2. For SSR
Description compressors, a minimum of 65 psig (4.5 barg) is
For compressor operation set this parameter to ETR required for proper coolant flow through the com-
TRIP 1. This parameter provides motor thermal pressor. For Sierra compressors, 65 psig (4.5 barg) is
protection based on calculation of thermal load. required for proper oil pressure to operate inlet
valve. Maximum pressure must be rated pressure of
machine, or less.
Description
In this parameter, the minimum motor frequency limit
can be set. For parameter value, see Tables 5.2A and
5.2B.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
34
202 Maximum Frequency 205 Maximum Reference
(MAX OUTPUT FREQ.) (MAX REFERENCE)
Value Value
Parameter 201 to parameter 200 ★ See Tables 5.2A Min reference to 100,000.000 ★ See Tables 5.2A
and 5.2B and 5.2B
Description Description
In this parameter, the maximum motor frequency limit This parameter sets the value of the maximum refer-
can be set. For parameter value, see Tables 5.2A and ence.
5.2B. For compressor operation the maximum reference
corresponds to different values depending on which
setup parameter is active.
In Setup 1 (Open-loop mode), this parameter controls
204 Minimum Reference the maximum speed that the compressor is allowed to
(MIN. REFERENCE) operate. In Setup 2 (Closed-loop mode), this parameter
Value controls the maximum discharge pressure that the
-100,000.000 to max reference ★ See Tables compressor is allowed.
5.2A and For proper compressor operation, set the value of the
5.2B parameter according to Tables 5.2A and 5.2B.
Depends on parameter 100.
Description
This parameter sets the value of the minimum refer-
ence.
For compressor operation the minimum reference
corresponds to different values depending on which
setup parameter is active.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
35
UNLOADED (Setup 1) LOADED (Setup 2)
Parameter 201 202 204 205 201 202 204 205
Description Min. Speed Max. Speed Min. Speed Max. Speed Min. Speed Max. Speed Min. Speed Max. Speed
Compressor Motor (Hz) (Hz) (Hz) (Hz) (Hz) (Hz) [psig] (barg) [psig] (barg)
SSR (Oil-Flooded)
37-75 kw -50 Hz, 1 Stage All 0 50 25 25 25 50 65 (4.5) rated
50-100 hp - 60 Hz, 1 Stage All 0 60 30 30 30 60 65 (4.5) rated
XFE & EPE 100 -60 Hz, 2 Stage All 0 60 40 40 40 60 65 (4.5) rated
HPE 100 hp - 60 Hz, 2 Stage All 0 60 42 42 42 60 65 (4.5) rated
ML/MM/MH 75-50 Hz, 2 Stage All 0 50 33 33 33 50 65 (4.5) rated
125-150 hp, 60 Hz, 1 & 2 Stage All 0 60 30 30 30 60 65 (4.5) rated
MM 90 -50 Hz, 1 Stage All 0 50 27 27 27 50 65 (4.5) rated
MH 90 -50 Hz, 1 Stage All 0 50 30 30 30 50 65 (4.5) rated
90-160 kw -50 Hz, 1 Stage (except
All 0 50 25 25 25 50 65 (4.5) rated
MM & MH 90)
110-160 kw, -50 Hz, 2 Stage All 0 50 25 25 25 50 65 (4.5) rated
Stnd. ODP 0 28 28 28
200 hp - 50 Hz, 1 & 2 Stage 50 50 65 (4.5) rated
All Others 0 25 25 25
Stnd. ODP 0 34 34 34
200 hp - 60 Hz, 1 & 2 Stage 60 60 65 (4.5) rated
All Others 0 30 30 30
Stnd. Eff. 0 32 32 32
250 hp - 50 Hz, 1 Stage 50 50 65 (4.5) rated
Prem. Eff. 0 25 25 25
Stnd. Eff. 0 38 38 38
250 hp - 60 Hz, 1 Stage 60 60 65 (4.5) rated
Prem. Eff. 0 30 30 30
250 hp - 50 Hz, 2 Stage All 0 50 32 32 32 50 65 (4.5) rated
250 hp - 60 Hz, 2 Stage Stnd. Eff. 0 38 38 38
60 60 65 (4.5) rated
Prem. Eff. 0 34 34 34
Stnd. Eff. 0 32 32 32
300 hp - 50 Hz, 1 & 2 Stage 50 50 65 (4.5) rated
Prem. Eff. 0 25 25 25
Stnd. Eff. 0 38 38 38
300 hp - 60 Hz, 1 & 2 Stage 60 60 65 (4.5) rated
Prem. Eff. 0 30 30 30
Stnd. Eff. 0 35 35 35
350 hp - 50 Hz, 1 & 2 Stage 50 50 65 (4.5) rated
Prem. Eff. 0 25 25 25
Stnd. Eff. 0 42 42 42
350 hp - 60 Hz, 1 & 2 Stage 60 60 65 (4.5) rated
Prem. Eff. 0 30 30 30
Stnd. Eff. 0 38 38 38
400 hp - 50 Hz, 1 & 2 Stage 50 50 65 (4.5) rated
Prem. Eff. 0 25 25 25
Stnd. Eff. 0 45 45 45
400 hp - 60 Hz, 1 & 2 Stage 60 60 65 (4.5) rated
Prem. Eff. 0 30 30 30
Stnd. Eff. 0 38 38 38
450 hp - 50 Hz, 1 & 2 Stage 50 50 65 (4.5) rated
Prem. Eff. 0 25 25 25
Stnd. Eff. 0 45 45 45
450 hp - 60 Hz, 1 & 2 Stage 60 60 65 (4.5) rated
Prem. Eff. 0 30 30 30
EP & HP 30-40 SE 60 Hz All 0 60 30 30 30 60 65 (4.5) rated
XF & EP & HP 50 SE 60 Hz All 0 60 30 30 30 60 65 (4.5) rated
UP6- 15-125 All 0 60 43 43 43 60 65 (4.5) rated
UP6- 20-125 All 0 60 33 33 33 60 65 (4.5) rated
UP6- 20-150 All 0 60 38 38 38 60 65 (4.5) rated
UP6- 25-125 & 150 All 0 60 30 30 30 60 65 (4.5) rated
UP6- 30-125 & 150 All 0 60 30 30 30 60 65 (4.5) rated
UP6- 40-115 & 125 & 150 All 0 60 30 30 30 60 65 (4.5) rated
HF & EP & HHP 50-PE 60 Hz All 0 60 30 30 30 60 65 (4.5) rated
NOTES:
1. Parameters apply only to machines that are pressure related up to 140 psig or 10 barg unless otherwise noted (upg 20-50 is 150 psig.
2. Non-IR supplied motors, and motors manufactured prior to 1996 may not be suitable for VFD use. Contact IR before applying VFD to motors of this type.
36
UNLOADED (Setup 1) LOADED (Setup 2)
Parameter 201 202 204 205 201 202 204 205
Description Min. Speed Max. Speed Min. Speed Max. Speed Min. Speed Max. Speed Min. Speed Max. Speed
Compressor Motor (Hz) (Hz) (Hz) (Hz) (Hz) (Hz) [psig] (barg) [psig] (barg)
Sierra (Oil-Free)
H150 (125 psig) All 0 60 40 40 40 60 65 (4.5) rated
H200 (125 psig) All 0 60 32 32 32 60 65 (4.5) rated
H250 (125 psig) All 0 60 48 48 48 60 65 (4.5) rated
H300 (125 psig) All 0 60 33 33 33 60 65 (4.5) rated
H350 (125 psig) All 0 60 35 35 35 60 65 (4.5) rated
H75 (125 psig) All 0 60 41 41 41 60 65 (4.5) rated
HH150 (150 psig) All 0 60 50 50 50 60 65 (4.5) rated
HH350 (150 psig) All 0 60 38 38 38 60 65 (4.5) rated
HH400 (150 psig) All 0 60 44 44 44 60 65 (4.5) rated
L100 (100 psig) All 0 60 30 30 30 60 65 (4.5) rated
L100 (125 psig) All 0 58 30 30 30 58 65 (4.5) 125 (8.6)
L125 (100 psig) All 0 60 50 50 50 60 65 (4.5) rated
L150 (100 psig) All 0 60 40 40 40 60 65 (4.5) rated
L200 (100 psig) All 0 60 30 30 30 60 65 (4.5) rated
L200 (125 psig) All 0 57 30 30 30 57 65 (4.5) 125 (8.6)
L250 (100 psig) All 0 60 35 35 35 60 65 (4.5) rated
L350 (100 psig) All 0 60 30 30 30 60 65 (4.5) rated
L350 (125 psig) All 0 54 30 30 30 54 65 (4.5) 125 (8.6)
L75 (100 psig) All 0 60 30 30 30 60 65 (4.5) rated
SH110 (10 barg) All 0 50 40 40 40 50 65 (4.5) rated
SH150 (10 barg) All 0 50 36 36 36 50 65 (4.5) rated
SH250 (10 barg) All 0 50 36 36 36 50 65 (4.5) rated
SH300 (10.0 barg) All 0 50 28 28 28 50 65 (4.5) rated
SL110 (7.0 barg) All 0 50 35 35 35 50 65 (4.5) rated
SL132 (7.0 barg) All 0 50 31 31 31 50 65 (4.5) rated
SL150 (7.0 barg) All 0 50 25 25 25 50 65 (4.5) rated
SL150 (8.5 barg) All 0 48 25 25 25 48 65 (4.5) 123 (8.5)
SL200 (7.0 barg) All 0 50 35 35 35 50 65 (4.5) rated
SL250 (7.0 barg) All 0 50 25 25 25 50 65 (4.5) rated
SL45 (7.0 barg) All 0 50 38 38 38 50 65 (4.5) rated
SL55 (7.0 barg) All 0 50 30 30 30 50 65 (4.5) rated
SL75 (7.0 barg) All 0 50 25 25 25 50 65 (4.5) rated
SL75 (8.5 barg) All 0 47 25 25 25 47 65 (4.5) 123 (8.5)
SL90 (7.0 barg) All 0 50 42 42 42 50 65 (4.5) rated
SM110 (8.5 barg) All 0 50 36 36 36 50 65 (4.5) rated
SM132 (8.5 barg) All 0 50 31 31 31 50 65 (4.5) rated
SM150 (8.5 barg) All 0 50 25 25 25 50 65 (4.5) rated
SM200 (8.5 barg) All 0 50 37 37 37 50 65 (4.5) rated
SM250 (8.5 barg) All 0 50 30 30 30 50 65 (4.5) rated
SM55 (8.5 barg) All 0 50 36 36 36 50 65 (4.5) rated
SM75 (8.5 barg) All 0 50 27 27 27 50 65 (4.5) rated
NOTES:
1. Parameters apply only to machines that are pressure rated up to 150 psig or 10 barg.
2. Non-IR supplied motors, and motors manufactured prior to 1996 may not be suitable for VFD use. Contact IR before applying VFD to motors of this type.
3. Some factory configured VFD compressors that are nameplated as “H” or “SM” have “L” or “SL” gear sets. These machines may be operated at 125 psig or 8.5
barg using the “L” or “SL” values listed above.
4. 200HP TEFC motors must be premium efficiency.
37
5.3.7 Setting Ramp Up and Down Times 5.3.8 Preset Reference Data
Table 5-3 describes the values for parameters 207 and 215 Preset Reference 1
208. If values below these recommended settings are (PRESET REF.1)
used, the drive may trip on high DC-bus voltage or over- Value
current. If values above these recommended settings are –100.00% TO + 100.00% ★ See Formula below
used, the motor may take a longer time than necessary to of maximum frequency external reference
ramp up or down to the correct speed.
208 Ramp-down Time The value of this parameter is the target pressure set
(RAMP DOWM TIME 1) point in Loaded PID mode (Setup 2). (See Figure 5.3-1)
Value
For more detail on how to set compressor output
0.05 - 3600 sec. ★ See Table 5.3
pressure, please refer to Section 7.0.
Description
The ramp-down time is the acceleration time from the
rated motor frequency to 0 Hz. To ensure proper
compressor operation set the parameter value to
correspond with Table 5.3.
Transmitter
4 - 20 mA
0 - 200 psi
Parameters
314 Term 60 = Feedback
315 low mA = 4.0 mA
316 high mA = 20 mA
0% - Reference 100 %
38
TABLE 5.3 MINIMUM RAMP TIMES
39
5.3.9 Setting Control Inputs and Outputs 300 Terminal 16, Input
(Digital Input 16)
Parameters in the 300 group refer to inputs and out- Value
puts. Parameters 300 – 307 program digital input func- [0] to [13] ★ No Operation [0]
tions. Parameters 308 and 314 correspond to analog
inputs. Parameter 323 programs a Form C relay func-
tion. Description
This parameter sets the operation of terminal 16. For
Digital Inputs compressor application, set this parameter at NO
For the compressor application, three digital inputs are OPERATION.
used:
Relay Outputs
Set Parameter 323 for ALARM. This will warn the
Intellisys controller of a drive fault and shut down the 302 Terminal 18, Start Input
compressor. (Digital Input 18)
Value
[0] to [3] ★ Start [1]
Description
This parameter sets the operation of terminal 18. For
compressor application, set this parameter at START.
Description
This parameter sets the operation of terminal 19. For
compressor application, set this parameter at NO
OPERATION.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
40
304 Terminal 27, Input 308 Terminal 53, Analog input voltage
(Digital Input 27) (AI [V] 53 FUNCT.)
Value Value
[0] to [4] ★ Coast Inverse [0] ★No operation (NO OPERATION)
Reference (REFERENCE)
Feedback signal (FEEDBACK)
Description Torque limit (TORQUE LIMIT CTRL)
This parameter sets the operation of terminal 27. For Thermistor (THERMISTOR INPUT)
compressor application, set this parameter at COAST Relative reference (RELATIVE REFERENCE)
INVERSE to allow the compressor to send a start signal Max. torque frequency (MAX. TORQUE FREQ.)
to the VFD.
Description
This terminal activates the analog voltage input, terminal
53. For compressor application, this parameter should
305 Terminal 29, Input be set to NO OPERATION.
(Digital Input 29)
Value
[0] to [28] ★ No Operation [0]
Description
This terminal activates the analog current input, terminal
60.
306 Terminal 32, Input
(Digital Input 32) For Setup 1, this parameter needs to be set to NO
Value OPERATION.
[0] to [24] ★ No Operation [0]
For setup 2, this parameter needs to be set to
FEEDBACK to enable the 4-20 mA transducer to
Description provide a signal to the VFD.
This parameter sets the operation of terminal 32. For
compressor application, set this parameter at NO
OPERATION.
315 Terminal 60, Min. Scaling
(AI 60 LOW)
Value
307 Terminal 33, Input 4.0 - 20.mA ★ 4.0 mA
(Digital Input 33)
Value
[0] to [25] ★ Setup LSB/Speed Down [11] Description
This parameter sets the value of the reference signal
that is to correspond to the minimum reference value
Description set in parameter 204. The pressure transducer used
This parameter sets the operation of terminal 33. For with the compressor ranges from 4 to 20 mA. This para-
compressor application, set this parameter at SETUP meter
LSB/SPEED DOWN to allow the compressor to switch needs to be set to 4 mA.
the VFD between the unloaded constant speed mode
and the loaded PID constant pressure mode.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
41
316 Terminal 60, Max. Scaling 5.3.10 Setting Feedback
(AI 60 HIGH)
Value 414 Minimum Feedback
4.0 - 20.0 mA ★ 20.0 mA (MIN. FEEDBACK)
Value
-100,000.000 to Feedback High ★ Min. feedback
Description
This parameter sets the value of the reference signal
that is to correspond to the maximum reference value Description
set in parameter 205. This parameter needs to be set to This parameter determines the minimum feedback of
20 mA. the VFD’s pressure transducer. For the pressure trans-
ducer supplied, set this parameter value to 0.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
42
416 Process Unit 440 Process PID Proportional Gain
(PROCESS UNIT) (PROC. PROP. GAIN)
Value Value
★NO UNIT [0] t/min [21] 0.00 - 10.00 ★ 3.00 sec.
% [1] t/h [22]
PPM [2] m [23]
RPM [3] Nm [24] Description
bar [4] m/s [25] For compressor operation, set this parameter value at
CYCLE/min [5] m/min [26] 3.00.
PULSE/s [6] °F [27]
UNITS/s [7] in wg [28]
UNITS/min [8] gal/s [29]
UNITS/h [9] ft 3 /s [30]
°C [10] gal/min [31]
Pa [11] ft 3 /min [32] 441 Process PID Integral Time
l/s [12] gal/h [33] (PROC. INTEGR.T.)
m3/s [13] ft 3 /h [34] Value
l/min [14] lb/s [35] 0.01 - 9999.99 sec. (OFF) ★ 1.0 sec.
m3/min [15] lb/min [36]
l/h [16] lb/h [37]
m3/h [17] lb ft [38] Description
kg/s [18] ft/s [39] For compressor operation, the starting value of this
kg/min [19] ft/min [40] parameter should be set at 1.00 sec. If instability
kg/h [20] occurs, this value may be lowered by decrements of 0.1
sec. or less until system stability is achieved.
Description
This parameter sets the units of measure for the
feedback pressure display. Pressure units selected in 442 Process PID Differentiation Time
setting parameter 416 must be consistent with those
(PROC. DIFF.TIME)
used in parameters 204, 205, 414 and 415. The units of
“psi” may not be available, so parameter 416 should be Value
set to NO UNIT. 0.00 (OFF) - 10.00 sec. ★ 0.01 sec.
★= proper parameter value, ( ) = display text, [ ] = data value for use in communication via serial communication port
43
5.4 Startup Checklist
Drive and Compressor Operation:
The following is a list of questions that should be Are all the correct parameters loaded into the
answered before starting the compressor for the first drive?
time. The section of this manual that gives instructions (Section 5.3)
for the appropriate procedure is also listed. Table 9.2 in
Section 9, Troubleshooting, lists some faults and Were the motor and package amp parameters
remedies. loaded in the correct sequence?
(Section 5.3.5; Parameters 102-109)
Environment:
Are clearances allowed for and installation Is the compressor Intellisys in on/off line control?
suitable for proper ventilation? (Section 5.1)
(Section 3.1.2)
Have proper minimum and maximum speed
Has the drive been installed with the back points been set?
covered for proper cooling? (Section 5.3.6; Parameters 201, 202)
(Section 3.1.3)
Have proper minimum and maximum pressure
Drive Connections: set points been set?
Are fast blow semiconductor fuses installed? (Section 5.3.6; Parameters 204, 205)
(Section 3.2.4)
Have proper ramp up and ramp down times
Inspect and tighten drive input, output, and been set?
control connections? (Section 5.3.7; Parameters 207, 208)
(Terminal and Switch Location Drawings in
Section 10.0)
Running Conditions:
Ensure proper earth ground? Is the nominal voltage within the range of the
specific drive ±10%? (Section 5.3.5)
Are the relays wired properly?
(Section 3.2.3) Are all equipment, personnel, and/or
obstructions clear from the equipment?
Are the motor leads connected properly? (Sections 0.1, 0.2, and 0.3)
(Section 3.2.8)
Is the rotation of the main motor correct?
If fused disconnect option is used, have all (Installation Section of Compressor Operation
connections been tightened and inspected? Manual)
(Section 3.2.3)
For Sierra units, is the rotation of the oil pump
motor correct?
(Section 3.4.1)
44
6.0 AUTOMATIC MOTOR 3) Alarms will be shown on the display if a problem is
spotted during auto-tuning.
ADAPTATION (AMA)
4) If automatic motor adaptation is to be discontinued,
In some cases, the efficiency of the motor may be slight- push the [STOP/RESET] key.
ly increased by allowing the VFD to tune itself to the
motor’s characteristics. The fan motor leads on an air-
cooled compressor must be removed from the VFD For Automatic Motor Adaption Procedure refer to Section
power block before this procedure can be performed to 3.5.
ensure that only the main motor’s characteristics are
considered.
1) Stator resistance, Rs
2) Reactance at normal magnetizing level, Xs
45
7.0 MODIFYING COMPRESSOR Any unit of measure for pressure is possible, provided
that all relevant parameters are consistent. Parameters
OUTPUT PRESSURE 315, 316, 414 and 415 determine the scale of the trans-
ducer. For example, a 4-20 mA transducer can have a
The VFD allows a compressor to provide a constant range of 0-200 psig or 0-13.8 barg. If parameters 414
pressure by varying airend speed. This desired pressure and 415 are set up for metric units, parameters 204 and
can be set at any time by following the method below. 205 must also reflect those units.
46
TABLE 9.1 WARNINGS AND ALARMS
47
TABLE 9.1 WARNINGS AND ALARMS
47
WARNING/ALARM 11 There is no serial communication with the VFD.
Motor Thermistor (MOTOR THERMISTOR) The warning will only be enabled if parameter 804, Bus
The thermistor or the thermistor connection has been Time Interval Function, has been set to a value other
disconnected. Parameter 128, Motor Thermal Protection, than OFF. If parameter 804 has been set to Stop and
allows a choice of whether the VFD is to give a warning Trip [5], the drive will first give a warning, ramp down,
or an alarm. Check that the thermistor has been correct- and finally trip while giving an alarm. The interval is set
ly connected between terminal 53 or 54 (analog voltage in parameter 803, Bus Time Interval. Parameter 803 is
input) and terminal 50 (+10 V supply). only available when a communication option card is
installed in the drive.
WARNING/ALARM 12
Torque Limit (TORQUE LIMIT WARNING 19
The torque is higher than the value in parameter 221, Fault on the Power Card (EE ERROR POWER)
Torque Limit for Motor Mode, in motor operation, or the There is a fault on the power card EEPROM. The VFD
torque is higher than the value in parameter 222, Torque will continue to function, but is likely to fail at the next
Limit for Generating Operation, in regenerative mode. power up. Contact your local I-R distributor or air center.
WARNING/ALARM 13 WARNING 20
Overcurrent (OVER CURRENT) Fault on the Control Card (EE ERROR CONTROL)
The inverter peak current limit, approximately 200% of There is a fault in the control card EEPROM. The VFD
the rated current, has been exceeded. The warning will will continue to function, but is likely to fail at the next
last approximately 1 or 2 seconds, and then the VFD will power up. Contact your local I-R distributor or air center.
trip and signal an alarm. This can be caused if parame-
ter 201 in setup 1 is not set for 0. ALARM: 21
AMA OK (AUTO MOTOR ADAPT OK)
Remove power to the VFD and check for free rotation of
Automatic Motor Adaptation (AMA) has completed suc-
the motor shaft and other causes of the overload.
cessfully and the VFD is ready for operation.
Ensure
that VFD and motor sizes match.
ALARM 22
ALARM 14 Automatic Motor Adaptation Failed (AMA FAULT)
Ground Fault (EARTH FAULT) A fault has been found during Automatic Motor
There is current leakage from the output phases to Adaptation (AMA). The text shown in the display indi-
ground, either in the leads between the VFD and the cates a fault message. AMA will only function with no
motor or in the motor itself. alarms active.
Remove power to the VFD and correct the ground fault.
CHECK 103,105
ALARM 15 Parameter 103 or 105 has a wrong setting. Correct the
Switch Mode Fault (SWITCH MODE FAULT) setting and repeat AMA.
Fault in the switch mode power supply (internal ±15 V
supply). Contact your local I-R distributor or air center. LOW P 105
The motor is too small for AMA to be carried out. If AMA
ALARM 16 is to be enabled, the rated motor current, parameter 105,
Short Circuit (CURR. SHORT CIRCUIT) must be higher than 35% of the rated output current of
There is a short circuit in the output from the VFD or in the VFD.
the motor.
Remove power to the VFD and correct the short circuit. ASYMMETRICAL IMPEDANCE
AMA has detected an asymmetrical impedance in the
WARNING/ALARM 17 motor connected to the system. The motor could be
Serial Communication Timeout (STD BUS TIMEOUT) defective.
There is no serial communication with the VFD.
This warning will only be enabled if parameter 514, Bus MOTOR TOO BIG
Time Interval Function, has been set to a value other The motor connected to the system is too big for AMA to
than OFF. be carried out. The setting in parameter 102 does not
If parameter 514 has been set to Stop and Trip [5], the match the motor used.
VFID will first give a warning, ramp down, and finally trip
while giving an alarm. The interval is set in parameter MOTOR TOO SMALL
513, Bus Time Interval. The motor connected to the system is too small for AMA
to be carried out. The setting in parameter 102 does not
WARNING/ALARM 18 match the motor used.
Serial Bus Timeout (HPFB BUS TIMEOUT)
49
TIME OUT WARNING:35
AMA failed because of noisy measuring signals. Retry Out of Frequency Range (OUT OF FREQ. RANGE):
until AMA is successfully completed. Please note that This warning is active if the output frequency has
repeated AMA runs may heat the motor to a level where reached its low limit (parameter 201) or high limit (para-
the stator resistance is increased. meter 202). If the VFD is in closed loop process regula-
tion, the warning will be active in the display. If the VFD
INTERRUPTED BY USER is in a mode other than closed loop process regulation, a
AMA has been interrupted by the user. serial bus output (warning word 2) will be active, with no
INTERNAL FAULT warning in the display.
An internal fault has occurred in the VFD. Contact your
local I-R distributor or air center. WARNINGIALARM: 36
AC Power Failure (MAINS FAILURE):
LIMIT VALUE FAULT The supply voltage to the VFD has been lost and
The parameter values found for the motor are outside parameter 407, Mains fault, has been set to a value
the acceptable range within which the VFD is able to other than OFF.
work.
If parameter 407 has been set to Contr. ramp-down trip
MOTOR ROTATES [2], the VFD will first give a warning and then ramp down
The motor shaft is rotating. Make sure that the load is and trip, while giving an alarm. Check the fuses to the
not able to make the motor shaft rotate while the AMA is VFD.
being performed. Then start AMA over again.
ALARM 37
ALARM 29 Inverter Fault (GATE DRIVE FAULT):
Heat Sink Temperature Too High (HEAT SINK OVER A VFD output IGBT or the power card is defective.
TEMP.): Contact your local I-R distributor or air center.
The heat sink temperature is too high. For NEMA 1
VFDs, the limit is 194°F (90°C). For NEMA 12 VFDs, the WARNING 39
limit is 176°F (80°C). The tolerance is ±9°F (±5°C). The Check Parameters 104 and 106
fault cannot be reset until the temperature of the heat (CHECK PAR. 104,106)
sink has fallen below 140°F (60°C). AMA has stopped. Parameter 104, Motor Frequency, or
The fault could be due to the following: 106, Rated Motor Speed, has probably been set wrong.
- Ambient temperature too high Correct the setting and run AMA again.
- Air obstructed
- Cooling fan(s) not operating WARNING 40
- Motor leads too long Check Parameters 103 and 105
- Switching frequency too high (CHECK PAR. 103,105)
ALARM 30 Parameter 103, Motor Voltage, or 105, Motor Current,
Motor Phase U Missing (MISSING MOT.PHASE U): has probably been set wrong. Correct the setting and
Motor phase U, as indicated by the letters on the output run AMA again.
terminal block, is missing or has a high impedance.
Remove power to the VFD and check motor phase U. WARNING 41
Motor Too Large (MOTOR TOO BIG)
ALARM 31 Motor Phase V Missing (MISSING The motor is probably too large for AMA. The setting in
MOT.PHASE V): parameter 102 Motor Power, may not match the motor.
Motor phase V, as indicated by the letters on the output Check the motor size and select ‘Continue’ or press the
terminal block, is missing or has a high impedance. STOP key to exit.
Remove power to the VFD and check motor phase V.
WARNING 42
ALARM 32 Motor Phase W Missing (MISSING Motor Too Small (MOTOR TOO SMALL)
MOT.PHASE W): The motor is probably too small for AMA. The setting in
Motor phase W, as indicated by the letters on the output parameter 102 Motor Power, may not match the motor.
terminal block, is missing or has a high impedance. Check the motor and select ‘Continue’ or press the
Remove power to the VFD and check motor phase W. STOP key to exit.
ALARM: 33 Quick Discharge Error (QUICK DIS-
CHARGE NOT OK): WARNING/ALARM: 44
Check whether 24 Volts external DC supply has been Encoder loss (ENCODER FAULT)
connected. The encoder signal is interrupted from terminal 32 or 33.
Check the connections or health of encoder device.
50
9.2 Compressor Warnings and Alarms 9.3 Troubleshooting Faults and Remedies
If the VFD shuts down on an alarm condition, the com- Table 9.2 lists some faults and remedies.
pressor will shutdown on a “Control Power Loss” alarm
or a “No Control Power” alarm. Please refer to the com-
pressor’s Operation Manual for other warnings and
alarms that the compressor may develop.
VFD trips on Alarm 13 (Overcurrent) Confirm all motor parameters in Section 5.3.5 and
on Start Group 1 are set correctly. If problem Section 5.3.7
persists, increase ramp up time,
parameter 207, in Setup 1
Compressor oscillates above and Increase PID low-pass filter time, Appendix C
below target pressure due to parameter 444
transducer noise
SSR: Compressor fails on Check Inlet Change Intellisys controller settings Section 5.1
Control Alarm on start with SG
Intellisys controller
51
10.0 REFERENCE DRAWINGS
WIRING SCHEMATIC FOR SIERRA 200 HP (150KW) & 350 HP (300 KW)
STAR DELTA,AIRCOOLED (1 OF 2)
54629894
REV D
WIRING SCHEMATIC FOR SIERRA 200 HP (150KW) & 350 HP (300 KW)
STAR DELTA,AIRCOOLED (2 OF 2)
75
76
54630686
REV C
WIRING SCHEMATIC FOR SIERRA 200 HP (150KW) & 350 HP (300 KW)
STAR DELTA, WATERCOOLED (1 OF 2)
54630686
REV C
WIRING SCHEMATIC FOR SIERRA 200 HP (150KW) & 350 HP (300 KW)
STAR DELTA, WATERCOOLED (2 OF 2)
77
78
54576137
REV B
REF PART
NO NO. QTY. DESCRIPTION
REF PART
NO NO. QTY. DESCRIPTION
REF
NO PART NO. QTY. DESCRIPTION
FIGURE 10.21 OIL PUMP ASSEMBLY FOR SIERRA 250-400 HP (150-300 KW)
DRIVE ENCLOSURE
DISCONNECT ENCLOSURE
Exterior
DISCONNECT
L1, L2, L3
LINE INPUT
Fuse Disconnect
FIGURE 10.22
FIGURE 10.22 I-R 5016-5027,200-240V,
I-R 5016-5027, 200-240V
I-R ,5016-5052,
I-R 5016-5052, 380-460V
380-460V
NEMA 1 AND NEMA
NEMA 1 AND NEMA 12 12
87
DRIVE ENCLOSURE
DISCONNECT ENCLOSURE
Exterior
DISCONNECT
INPUT
L1 L2 L3
GND
L1, L2, L3
LINE INPUT
88
DRIVE ENCLOSURE
DISCONNECT ENCLOSURE
Exterior
88
L1, L2, L3
LINE INPUT
INPUT
GND
L1 L2 L3
DISCONNECT
Fuse Disconnect
FIGURE
FIGURE 10.2410.24
I-RI-R 5032, 200 TO
5032-5052, 240V,
200 NEMA
to 240 V, 12
NEMA 12
89
DRIVE ENCLOSURE
DISCONNECT ENCLOSURE
DISCONNECT
L1, L2, L3
LINE INPUT
Fuse Disconnect
FIGURE FIGURE
10.25 10.25
I-R 5062, 380 380-460V,
I-R 5062, to 460 V,NEMA
NEM A 1 AND
1 AND NEMA
NEMA 12 12
90
DRIVE ENCLOSURE
DISCONNECT ENCLOSURE
DISCONNECT
L1, L2, L3
LINE INPUT
Fuse Disconnect
FIGURE 10.26I-R I-R
FIGURE 10.26 5072-5102,
5072-5102, 380
380 TO to 460
460V, V, 1NEMA
NEMA 1 AND
AND NEMA 12 NEMA 12
91
FUSES
DISCONNECT
92
FIGURE
FIGURE 10.28
10.28 I-RI-R5350-5500,
5350-5500, 380
380TO
to 460V,
460 V,NEMA
NEMA1 AND NEMA
1 AND 12
NEMA 12
93