Relai Arus Lebih PDF
Relai Arus Lebih PDF
FASA – FASA
FASA – TANAH
APLIKASI
PENGAMAN UTAMA
JTM ( DISTRIBUSI )
GENERATOR ( Kapasitas kecil )
TRAFO DAYA ( Kapasitas kecil )
MOTOR
• NON DIRECTIONAL
• DIRECTIONAL
• KONTROL TEGANGAN
• PENAHAN TEGANGAN
KARAKTERISTIK
@ ARAH
1. TIDAK BERARAH ( NON DIRECTIONAL )
2. BERARAH ( DIRECTIONAL )
@ ARUS – WAKTU
1. TANPA TUNDA ( MOMENT = INSTANT )
2. TUNDA WAKTU ( TIME DELAY )
# DEFINITE ( TERTENTU ) = INDEPENDEN
# INVERSE ( I – t BERBANDING TERBALIK )
= DEPENDEN
SI / NI = Standard / Normal Iverse
VI = Very Inverse
EI = Exteremely Inverse
LTI = Long Time Invers
KARAKTERISTIK INSTANT = MOMENT
t SET
I
I SET MOMENT
KARAKTERISTIK TUNDA WAKTU
TERTENTU ( DEFINITE TIME )
t SET
I SET I
KARAKTERISTIK TUNDA WAKTU
INVERSE
t SET
I SET I
KARAKTERISTIK KOMBINASI INSTANT
DENGAN TUNDA WAKTU TERTENTU
(DEFINITE TIME )
t SET
KONTAK
PLUNGER
PEGAS
BELITAN 0.6
0.8
1.0
1.2
INTI LUAR
SETTING
Fe = GAYA ELEKTROMEKANIK
Fp = GAYA PEGAS
L U L
U
2 2
KUMPARAN LAGGING
PIRINGAN
Is
KUMPARAN UTAMA
I
SETTING ARUS DAN WAKTU
TAP SETTING
KONTAK DIAM
DENGAN MENGATUR
JARAK KONTAK
TIPE RELAI STATIK
SUPLAI DC
A CT RECTIFIER
LEVEL
Vin DETECTOR
R Vo
SETTING RELAI
BANTU
V REF V IN V O 0 ( Pickup )
V REF V IN V O 0 (Re set )
BLOK DIAGRAM RELAI ARUS LEBIH STATIK
CURVE
SHAPER
FILTER
CS R F
Ia F Is
MAX
I RL
Ib GATE LD T LD
& 1 2
1
Ic RECT.
Is
INSTANT RL
LD
3
LD = LEVEL DETECTOR 3
T = TIMER
R = REGULATOR
SETTING
INSTANT
IBA DOC
HS OUTPUT
STATIC OVER CURRENT RELAY RELAY
MCGG OUTPUT
DRIVER TIME / CURRENT
OUTPUT RELAY
HS TIME
0.4/0
FULLWAVE MICRO 0.2/0
INTERPOSSING RECTIFIER COMPUTER
CT 0.2/0
0.1/0
0.05/0
INPUT
0.05/0.025
TMS SWITCH SETTING
A/D
16/0
8//0
0.2/0.1 0.4/0 0.8/0 4//0
0.2/0 0.4/0 2/0
1/0
CURRENT SETTING
HIGH SET SWITCH
SETTING
IBA DOC
RELAI
OCR / GFR
A B C E
INST INST TIPE
MCGG 82
t t NAME
I > Is I > Is PLATE
xt xt KARAK
TERISTIK
I INST I INST
Is Is
IBA DOC
PRINSIP SETTING OCR
* Is = k In In = Arus Nominal
k = Faktor pabrik ( 1 s/d 2 )
atau 0,05 s/d 2,4 dengan
step 0.05
* Plug Setting
IBA DOC
# Waktu kerja
Mps = 4 x Is x Is
IBA DOC
# Is instant ( moment )
* Is instant = k In atau
k Is
In = Arus Nominal
Is = Arus setting tunda waktu
k = Faktor pabrik
* Plug setting
IBA DOC
@ SETTING ARUS OCR /GFR DENGAN TUNDA WAKTU
I S I N
0.1 0.05
0.1 0
0.2 0
I S ARUS SETTING 0.4 0
0.4 0
I N ARUS NOMINAL RELAI 0.4 0
0.8 0
FAKTOR PABRIK
IBA DOC
# MISAL ARUS SETTING Is = 6 A.
Is = 1.2 In
POSISI SAKLAR :
0.1 0.05
0.1 0
0.2 0 Is = ( 0.1 + 0.1 + 0.2 + 0 + 0 + 0 + 0.8 ) x 5A
0.4 0 = 1,2 x 5A
0.4 0 = 6A
0.4 0
0.8 0
IBA DOC
PEMILIHAN KARAKTERISTIK
SI VI EI LTI D2 D4 D8
0 1 0 1 0 1 0
0 0 1 1 0 0 1
0 0 0 0 1 1 1
0 1 0 1
0 1 0 1
0 1 0 1
IBA DOC
KURVA / KARAKTERISTIK
0 ,14
t 0 , 02 tms
I 1
@ VERY INVERSE ( VI )
13 , 5
t tms
I 1
@ EXTREMELY INVERSE ( EI )
80
t 2 tms
I 1
@ LONG TIME INVERSE ( LTI )
120
t tms
I 1
IBA DOC
SETTING WAKTU
MISAL : KARAKTERISTIK EI
ARUS GANGGUAN 3 x Is ( I = 3 )
WAKTU KERJA = 1 DETIK
PEMILIHAN TMS :
I 2 1 32 1
tms tk 1 0,1 det ik
80 80
IBA DOC
SETTING INSTANT
IS 6 A
0 1
18
6 3
0 2
0 4
0 8
I S inst I S 0 16
0
IBA DOC
SAMBUNGAN ( WIRING )
OCR
PMT
OCR GFR
R
P1 S E
T
S1
CT OCR
S2
P2
3 Buah OCR
1 Buah GFR
IBA DOC
SAMBUNGAN ( WIRING )
PMT OCR
GFR
R
P1 E
T
S1
CT OCR
S2
P2
2 Buah OCR
1 Buah GFR
IBA DOC
PENGUJIAN RELAI ARUS LEBIH
1. PENGUJIAN INDIVIDUAL
2. PENGUJIAN FUNGSI
1. CARA SETTING
2. INTERNAL DIAGRAM RELAI
3. ALAT UJI / RANGKAIAN PENGUJIAN
4. ITEM PENGUJIAN
5. PROSEDUR PENGUJIAN
6. HASIL UJI DAN KESIMPULAN
JENIS / ITEM PENGUJIAN
3. KARAKTERISTIK INSTANTANEOUS
1. ARUS PICK UP [ ARUS AWAL / MULA ]
I pick up
I reset
I beban
t
t gangguan
PENGUJIAN INDIVIDUAL
RELAI ARUS LEBIH
21
TIMER 22
23 29
24 30
START STOP
25
26
R
220 Vac 27
28 13
A
14 Vdc
220 Vac
RANGKAIAN PENGUJIAN
(+)
KONTAK
OCR/GFR
DIAGRAM
KONTROL DC
(+)
RELAI
BANTU
RE 1
(-)
TRIP PMT
(+)
RE 2
RELAI ALARM
BANTU
RE 3
(-)
RANGKAIAN SIGNALISASI
(+)
KONTAK
RELAI
RESET
TEST LAMP
RELAI BANTU
RE
LAMPU
SIGNAL
SETTING OCR
GANGGUAN FASA – FASA [ TUNDA WAKTU
k S I max
I SEI min .....[ 1]
kD
I SET max 0 ,8 I HS 2 min ....[ 2 ]
I SET min I SET max I SET I SET min
I SET max I SET min I SET I SET max
k S 1,1 1, 2
k D 80 %
I max arusbeban max .
KOORDINASI OCR
# DEFINITE TIME
I SC I SB I SA I HS
tC t B t A
t 0 , 4 0 , 5 det
A B C
t
1,3 det
0,8 det
0,3 det
I
KOORDINASI OCR
# INVERSE TIME
A B C
TMS B TMS C
TMS A
I
SETTING ELEMEN INSTANTANEOUS
SETTING INSTANT
# INSTANTANEOUS
A B C
I SET inst . A 1, 2 I HS 3 B
I SET inst . B 1, 2 I HS 3 C
KOORDINASI DARI RELAI KOMBINASI TUNDA WAKTU
DENGAN INSTANT /
A B C
t tA
tB
t INST tC
t INST
t I
TMS B TMS C
TMS A
t INST t INST
I
SETTING GFR
[RELAI GANGGUAN TANAH ]
PERLU DIPERHATIKAN ;
I SET GFR 1, 3 3 I OR
# PADA SUTM