Anda di halaman 1dari 30

®

Sieyuan  !""#$%&'()
JIANGSU RUGAO HIGH VOLTAGE ELECTRIC APPARATUS CO., LTD.

Company Survey Company Brief


Jiangsu Rugao High Voltage Electric Apparatus Co., Ltd. a
joint venture (enterprise) between Sieyuan Electric Co., Ltd.
07
20 and Jiangsu Rugao High Voltage Electric Apparatus Factory
was established in 2002 as a high technology research and
development company specializing in high voltage
06
20 technologies. Since its foundation, the company has grown
into a company with over 800 employees and output over
5000 million in year 2006 and has passed the ISO9001: 2000
05
20 Quality Management System through SGS. The company
develops and manufactures a range of high voltage related
products that it exports from its manufacturing headquarters in
04
20 Rugao, Jiangsu province, P. R. China. The technologies from
this world leading company have been applied internationally.

03
20 Jiangsu Rugao High Voltage Electric Apparatus Co., Ltd.
mainly produces
35-220 kV SF6 Circuit Breakers,
02
20 35kV Vacuum Circuit Breakers,
35-500 kV Disconnectors, etc.
The products above-mentioned have obtained inspection and
01 Building Area:
20 examination by national authorities. The company has come
Productive Workshop: 80000m2
to be a major supplier of high voltage electric apparatus in the
Product Investment fields of energy, power system, petrochemical, metallurgy,
Registered Capital: railway in China.
RMB 146.62M
(USD 21.25M) Jiangsu Rugao High Voltage Electric Apparatus Co., Ltd. is
Total Investment: driving for becoming one of the excellent and most competi-
Increase of Employees: RMB 120M tive high technology enterprises in the field of high voltage
Total Employees: Over 800 (USD 16.37M) electric apparatus production, and providing its customers
Technical Members: Over 160 with good quality products.
Sale & Admimistration: Over 120

1 2
®
Sieyuan  !""#$%&'()
JIANGSU RUGAO HIGH VOLTAGE ELECTRIC APPARATUS CO., LTD.

Advanced Facilities

Wet Measurement Tester TCD NC Spring


Automatic Silver Plating and Oil Paint NC Machine Tool Contact Pressure Tester Testing Machine
500kV Testing Transformer
Production Line

Mechanical Characteristic Tester SF6 Halogen Tester

1000kV Power Frequency Test-


Machining Centers Switzerland Welding Machine Water Cutting Centers ing Transformer

Salt Fog Testing Machine Silver Plating Thickness Tester

600kV Power Frequency Testing 300kV Power Frequency Testing 3000kV Lightning Impulse Volt-
German Leybod Vacuum Treatment System Transformer Transformer age Generator

3 4
®
Sieyuan  !""#$%&'()
JIANGSU RUGAO HIGH VOLTAGE ELECTRIC APPARATUS CO., LTD.

Reliable Products & Quality General Customer Service


As a front runner in the field of high voltage electric apparatus, we have supplied many high voltage
ISO9000 Quality System Certificate (SGS) circuit breakers and high voltage disconnectors for many of the key projects, both in China and
overseas, with an extensive sales and service network. To provide products and services to our
customers in a timely and professional manner, we have continued to enlarge the professional service
team. Meanwhile, we can also provide timely and general services, such as technical training, product
solution, maintenance instruction, components supply and so on.

Jiangsu Rugao High Voltage Electric Apparatus Co., Ltd. is a symbol for
quality. Our goal is to be recognized by our customers as a company
Services on site
producing high quality products and providing excellent services, the
implementation of ISO9001: 2000 Quality Management System assures
us to meet our customers demands on the best customers benefit.
Our company is devoted to our customer focus oriented Total Quality
Technical Training
Management and has achieved much in our Customer Satisfaction,
Quality-related Cost Management, Supplier Management, Quality Con-
trol Circle (QCC), Statistic Process Control (SPC) and so on.

Field Erection

5 6
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

Circuit Breaker Products LW36-145/126(W)/T3150-40 self-extinguishing


high voltage SF6 circuit breaker

LW36-145/126W/T3150-40 LW36-72.5W/T3150-31.5 LW36-40.5W/T2500-31.5

 Brief introduction
 LW36-145/126(W)/T3150-40 self-energy HV AC sulfur hexafluoride circuit breaker is an outdoor product. It is used in electricity grids
with altitudes of no greater than 2000m (product designs for 3000m are available), environment temperatures of no less than -30 (low-
temperature products are suitable for -40~+40), local pollution classes of no higher than Class IV, and maximum voltage of 145/126kV
tocut off rated currents, fault currents, or switching lines in order to implement control and protection of electricity systems. It can also be used
as a connection circuit breaker.
 By adopting SF6 gas as the arc extinguisher and insulation medium, using the most advanced self-energy arc extinguishing
technology in the world, and being equipped with new-type spring actuating mechanism, this product has features such as long electrical
endurance, small operating power, low noise, and high reliability. It has a simple structure, small size, long maintenance-free cycle. In the
current trend of oil-free and high-capacity electricity equipments, it can completely replace import products in the same field.

 Structural features
LW36-145/126(W)/T3150-40 self-energy HV AC sulfur hexafluoride circuit breaker is a hard-nut science and technology problem
tacklingproject in the national "Ninth Five-year" plan. It is a new-type circuit breaker with advanced international level. Its main structure and
perfor-mance features are as follows:
Performance features  safe and reliable
 Reliable breaking performance: This circuit breaker can consecutively break 40kA short circuit current for 22 times without overhaul.
It can meet the requirement of running in the electricity grid for 25 years without replacement of component parts.
 Reliable mechanical operating performance: The mechanical life of the circuit breaker under continuous operation can reach up to
6000 times and over 10000 times after simple adjustment, which guarantees the high operating reliability of the product in its effective running
cycle (25 years).
 Reliable current-carrying function: After 3780A temperature elevation test, the temperature elevation values at all points still have
much margin.
 Reliable insulation ability: creepage distance of external insulation31mm/kV; strong pollution resistance; suitable for safe running
in hard environments with an altitude of no higher than 3000m; the insulating pulling rod can endure 250kV/5min in the air.
 Reliable sealing performance: it is guaranteed that the SF6 gas has an annual gas leakage rate of far less than 0.5%
 Strict dehumidification process for component parts of the product: the SF6 water content is far lower than similar products.
ZW39-40.5/T2000-31.5 LW8-40.5W/T2000-40  Simple structure, long overhaul cycle, convenient on-site installation and debug, safe and reliable running experience of 5 years and
more than 2000 sets by 2006; the production and sales volume of this product of our company is in the leading position of the entire country.
It can replace import products or joint-venture products.
Structural features  original and novel
 Self-energy arc extinguishing principle is adopted for the circuit breaker. The operating power is low.

9 10
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 The valve plate of the arc extinguishing compartment is made of new-type lightweight Zinc-base alloy. Compared with the traditional 2) Table of major technical parameters of the mechanism
materials adopted for similar products, this material has more stable and reliable gas feature and breaking performance.
No. Name Unit Data
 The nozzle is made of import PTFE (polyfluortetraethylene) mixed with other micro-components. It has stable breaking perfor-mance
and strong ablation resistance. 1 Auxiliary power supply V DC220 or AC220
 Xi'an Shuangjia Porcelain sleeve is adopted. It has good bending resistance, advanced production process, and strict and Opening winding voltage/current; Closing winding voltage/current DC110/4; DC220/2;
reliablequality control, which can ensure the safe running of the circuit breaker. 2 V/A
AC220/5
 Our company's unique locking-up measure is used for the insulating pulling rod of the breaker to ensure more reliable running of
Rated voltage DC220 or AC220
the breaker. V
 Spring actuating mechanism with small operating power, light weight, and low noise is adopted for zero leakage and high reliabil- 3 Power storage driver Normal working voltage range 85%~110%
ity. High-strength cast aluminum machine frame is adopted for high strength, zero welding stress, and pleasing exterior appearance. Power W 720
 The important component parts in the mechanism are forged with quality alloy steel for high strength and abrasion resistance, which 4 Number of auxiliary contact s  20
can ensure low fault rate under frequent operation of the breaker. 5 Heating voltage AC220
 Electrical units in secondary circuits and SF6 density controller are high-quality import or joint-venture products. V
6 Auxiliary switch rated voltage DC220 or AC380
 The product has a novel and lively exterior appearance and compact structure. The installation foundation frame is made of thick
steel board being overall bended. Hot zinc impregnation is adopted for the surface. The exposed fastening pieces are high-strength hot- 7 Auxiliary switch rated current A 10
galvanized bolts. The interval driving connecting rods are made of high-strength aluminum sectional material or stainless steel sectional 8 Number of auxiliary contacts 11 normally opened11 normally closed
material. The case of the mechanism is made of stainless steel. The product has excellent anti-corrosion performance.
This product is a key hard-nut science and technology problem tackling project in the national "Ninth Five-year" plan. It has gained the
title of "High and New Technology Product in Jiangsu Province" and the honor of "Gold Bull Prize" of excellent new products in Jiangsu 3) Table of product mechanical adjustment parameters
Province. It has also achieved Certificate of National Key New Product.
No. Name Unit Data
1 Clearance between pole mm 1700
 Major technical parameters 2 Opening time  40
1) Table of major parameters of the circuit breaker 3 Closing time 70  8
Serial Name Unit Data 4 Breaking time  60
No. LW36-126(W)/T3150-31.5(H) LW36-126(W)/T3150-40 5 Closing opening time ms  80 suggest to operate  80
1 Ambient temperature  Ordinary model Low-temperature model 6 Opening closing time 300
2 Rated voltage 145/126 126 7 Asynchrony of three phase opening 2
Rated power frequency To earth K.275 K.230 8 Asynchrony of three phase closing 3
3
withstand voltage (1min) Across open contacts K.315 K.(230+73)
kV
Rated lightning impulse To earth K.650 K.550
4
withstand voltage Across open contacts K.750 K.(550+103)  Instructions on placing orders
5 Rated frequency Hz 50  Model and format of the circuit breaker;
6 Rated current A 3150  Rated electrical parameters (voltage, current, breaking current, etc);
7 First pole to clear factor 1.5  Environmental conditions for using (environment temperature, altitude, and environment pollution level);
8 Rated short circuit breaking current (Ik) 40 31.5  Rated control circuit electrical parameters (power-storage electromotor rated voltage and brake separating and closing cable coil
9 Rated short - circuit marking current (peak) 100 80 rated voltage);
kA
10 Rated short circuit withstand current 40 31.5  Names and quantities of needed spare items, parts and special equipment and tools (to be otherwise ordered);
11 Rated peak value withstand current 100 80  The wire connecting direction of the primary upper terminal.
12 Rated duration of short - circuit s 4
13 Rated desynchronizing breaking current 10 8
kA
14 Short - line fault breaking current 90%Ik, 75%Ik
15 Rated line charging breaking current A 31.5
16 Rated operating sequence O-0.3s-CO-180s-CO
17 Resistance of main contact µΩ  35
18 Rated SF6 gas pressure (20 meter pressure) MPa 0.6 0.45
19 Alarm/minimum functional pressure (20 meter pressure) 0.55+/0.015/0.50+/-0.015 0.40+/0.015/0.34+/-0.015
20 SF6 gas annual leakage rate %  0.5
21 Gas water content (V/V) (20 at handover)  150
22 Mechanical life Time 10000
23 Radio interference level µv  500
Across open contacts 3906/3150
24 Creepage distance mm
To earth 3906/3150
25 Weight of SF6 gas filled in every breaker 8
kg
26 Weight of every breaker 1700
Notes: external insulation is corrected by altitude correction coefficient K: altitude 2000m, K=1.13; altitude 3000m, K=1.28.

11 12
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing


LW36-72.5(W)/T3150-31 self-energy outdoor
HV AC sulfur hexafluoride circuit breaker

 Brief introduction
LW36-72.5 self-energy outdoor HV AC sulfur hexafluoride circuit breaker is an outdoor three-phase porcelain column electrical
equipment mainly used in AC 50Hz, 72.5kV electricity systems in extremely cold regions (for electric stations in general regions and -40
extremely cold regions). This product can be operated frequently and used as a connection circuit breaker.

 Structural features
 High performance -strong rated circulating ability: strong short circuit breaking ability at 3150A, 40: 31.5kA.
 Long service life -electrical endurance: 31.5kA24times (25kA31times); mechanical life: 6000 times without maintenance and
up to 10000 after simple adjustment.
 High reliability -sharing the arc extinguishing compartment structure with LW36-126; great product internal insulation redundancy;
overall cast aluminum alloy frame adopted for the spring structure; simple structure and high reliability; suitable for frequent operations.
 Reliable breaking performance.
 Reliable sealing performance; SF6 annual gas leakage rate  0.5%
 Meeting the requirements of hard running environments -suitable for Class IV polluted places and -40  ~40 environments.
 Multi-structure forms-usually porcelain column type and handcart type.

 Major technical parameters


1) Table of major parameters of the circuit breaker
No. Name Unit Data
1 Rated voltage kV 72.5
Rated power frequency To earth, Between phases 160
2
withstand voltage (1min) Across open contacts kV 160+42 
Rated lightning impulse To earth, Between phases 350
3
withstand voltage Across open contacts 350+60 
2
LW36-126 circuit breaker, weight 1500kg, windward area 4.7m 4 Rated frequency Hz 50

13 14
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

5 Rated current A 3150  Instructions on placing orders


6 Rated short circuit breaking current 31.5  Model and format of the circuit breaker;
7 Rated short - circuit marking current (peak) 80  Rated electrical parameters (voltage, current, breaking current, etc);
8 Rated short-time withstand current 31.5  Environmental conditions for using (environment temperature, altitude, and environment pollution level);
9 Rated peak withstand current (peak value) kA 80  Rated control circuit electrical parameters (power-storage electromotor rated voltage and brake separating and closing cable coil
10 Rated desynchronizing breaking current 8 rated voltage);
 Names and quantities of needed spare items, parts and special equipment and tools (to be otherwise ordered);
11 Short - line fault breaking current 90%IK, 75%IK
 The wire connecting direction of the primary upper terminal.
12 Out-of-phase grounding fault breaking current 27.4
13 Number of breakings under rated short circuit breaking current Time 24
14 Rated duration of short - circuit s 4
 Outline and Dimensional Drawing
15 First pole to clear factor 1.5
16 Rated line charging breaking current A 10
17 Rated operating sequence O  0.3s  CO  180s  CO
Rated SF6 gas pressure/Gas refilling alarm pressure/Operation
18 MPa 0.4/0.36  0.015/0.32  0.015
lockout pressure (meter pressure, 20)
19 SF6 gas annual leakage rate %  0.5
20 SF6 gas water content (V/V) (20 at handover) V/V  150  10-6
21 Mechanical life Time 6000  10000
22 Opening time ms  40
23 Closing time ms  70 (when running)
To earth  2585
24 Creepage distance mm
Across open contacts  2248
25 Weight of SF6 gas filled used for every breaker 8
kg
26 Weight of every breaker 1300

2) Table of major technical parameters of the mechanism


No. Name Unit Data
Normal working voltage range V 85~110
1 Power  storage driver Rated voltage DC220/AC220
Rated output power W 720
2 Power storage time (at rated voltage) s  20
DC110V/4ADC220V/2A
3 Opening electromagnet rated voltage / current V/A
AC220V/5A
Rated working current A 10(DC220V)
4 Auxiliary switch
Number of auxiliary contacts: Normally opened / Normally closed Pair 10/10
Rated working current A 5(DC220V)
5 Travel switch
Number of auxiliary contacts: Normally opened / normally closed Pair 1/1
6 Continuous current that can pass through wiring terminal A 10
7 Heater and lighting circuit voltage V AC220
8 Mechanical life Time 6000~10000

3) Table of product mechanical adjustment parameters


No. Name Unit Data
1 Clearance between pole mm 1200/1000 forhandcart type
2 Opening time 40
3 Closing time 708
4 Breaking time 60
5 Closing  opening time ms 70 (when running)
6 Opening  closing time 300
7 Asynchrony of three  phase opening 2
8 Asynchrony of three  phase closing 3

15 16
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

permeability material are adopted for internally attached current mutual inductors. The accuracy of 200A and above current mutual inductors
LW36-40.5(W)/T2500-31.5 outdoor self-energy can reach up to Level 0.2 or 0.2S. Reliable electrical screening design is adopted for the cable coils of internally attached current mutual
inductors to improve the electric field distribution of the mutual inductors and promote the internal insulation of the product. It can withstand
120kV and 5min working frequency withstand voltage test, and the internal insulation is not interfered by the short circuit breaking working
HV AC sulfur hexafluoride circuit breaker conditions, which makes it safe and reliable.
For a few small-capacity electric stations, when the primary current of the mutual inductor is less than 200A but the accuracy cannot
be lower than Level 0.2, external mutual inductor structures (mounted on one side of the circuit breaker) can be an option. But this is no long-
term experience with regard to the aging resistance of outdoor cast mutual inductors, and they are more expensive than internally attached
mutual inductors, large in size, and take up a lot of room. So please carefully consider that while selecting models.
The functional parameters and service reliability of LW36-40.5 sulfur hexafluoride circuit breaker represent a revolu-tionary progress
in comparison with those of similar products in the country. It is extolled by many experts and professors in the electricity industry and
universities throughout the country as a good product "with advanced international level in similar products both home and abroad."

 Major technical parameters


1) Table of major parameters of the circuit breaker
No. Name Unit Parameters
1 Rated voltage 40.5
1 min power frequency To earth K.95
withstand voltage Across open contacts kV K.(95+23)
2 Rated insulation level
Lightning impulse To earth K.185
withstand voltage Across open contacts K.(185+33)
3 Rated frequency Hz 50
4 Rated current A 2500
5 Rated short circuit breaking current 31.5
6 Rated short - circuit marking current (peak) kA 80
7 Rated short-time withstand current 31.5
8 Rated duration of short - circuit s 4
 Brief introduction 9 Rated peak withstand current (peak value) kA 80
 LW36-40.5 outdoor self-energy HV AC sulfur hexafluoride circuit breaker is an outdoor three-phase HV AC equip-ment used in 10 Rated operating sequence O-0.3s-CO-180s-CO
electricity grids with altitudes of no greater than 3000m, environment temperatures of no less than -30, local pollution classes of no higher 11 Rated breaking current for single capacitor bank 630
A
than Class IV, and AC 50Hz with maximum voltage of 40.5kV. It is suitable for the control and protection of HV supply and transformation 12 Rated line charging breaking current 50
lines in power plants, transformer stations, and industrial and mining enter-prises. It can also be used as a connection circuit breaker. 13 Rated desynchronizing breaking current 8
kA
14 Rated out-of-phase breaking current 27.4
 Structural features 15 Mechanical life test 10000
 LW36-40.5 self-energy HV sulfur hexafluoride circuit breaker is equipped with advanced hot-expansion plus auxiliary pressure gas Time
16 Number of breakings under rated short circuit breaking current >20
self-energy arc extinguishing technology and matched with new-type spring actuating mechanism. It has features such as long electrical
endurance, small operating power, high electrical and mechanical reliability, high technical parameters, and moderate price. It is the first 17 SF6 gas rated pressure (meter pressure, 20) 0.5  0.015
choice product for current 40.5kV electricity grids. Its main perfor-mance features are as follows: SF6 gas action pressure Alarm pressure MPa 0.47  0.015
18
 High rated technical parameters: rated current 2500A and rated short circuit breaking current 31.5kA; suitable for the opening and (meter pressure, 20) Minimum functional pressure 0.45  0.015
closing of large-capacity electricity grids. 19 SF6 gas annual leakage rate %  0.5
 High electrical reliability:
20 Gas water content (V/V) (20 at handover)  150  10-6
(1) Electrical endurance 31.5kA21times (25kA31times); can meet the requirement of running for 25 years without replacing the
arc extinguishing compartment components.
(2) No restrike at opening-closing capacitor group current 630A (44193kVAr) and no heavy arcing at composite cable current 50A;
suitable for working conditions of composite capacity load and inductive load.
2) Table of major technical parameters of the mechanism
(3) Strong external insulation ability; suitable for regions with 3000m of altitude or Class IV pollution.
 High reliability of operating mechanism: No. Name Unit Parameters
(1) Mechanical life: separating and closing for 10000 times without replacing parts; can meet the user's requirement of continuous Rated voltage V DC220/AC220
running and little maintenance. 1 Power  storage driver
Rated output power W 500
(2) New type spring actuating mechanism has few components parts; overall high-strength cast aluminum frame and brake separating
and closing spring; centralized arrangement is adopted for the buffer; compact structure, reliable opera-tion, low noise, and convenient 2 Power storage time (at rated voltage) s  15
maintenance; suitable for frequent operations. 3 Manual power storage moment Nm  60
(3) Major electrical units in secondary circuits are most advanced and reliable domestic and foreign products. 4 Opening electromagnet rated voltage / current V/A DC220/1.6
 Allexposedpartsaremadeofstainlesssteelmaterialsorhot-galvanizedonthesurfaceforhighcorrosion resistance 5 Closing electromagnet rated voltage / current DC220/1.4
 Reliable sealing structure ensures the product annual leakage rate  0.5%
Rated working voltage V DC220(AC220)
 Mutual inductors can be internally or externally attached to the circuit breaker:
Four internally attached current mutual inductors for every phase can be installed on the circuit breaker. Microcrystal alloy and high 6 Auxiliary switch Rated working current A 10
Number of contacts: Normally opened / Normally closed Pair 6/6

17 18
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

Rated working voltage V DC220(AC220)


7 Limit switch Rated working current A 3
Number of contacts: Normally opened / closed Pair 1/1
8 Continuous current going through terminals A 10
9 Voltage of heater and lighting loop V AC220
10 Mechanical life Secondary 10000
11 Auxiliary loop under 1 min power frequency withstand voltage V 2000

3) Table of parameters for the mechanical adjustment of the product


No. Name Unit Parameters
1 Minimum air insulation distance mm 440
2 Three-phase opening cycle ms 2
3 Three-phase closing cycle 3
4 Resistance of main contact µΩ  60( 40 without CT)
5 Closing time 70  8
6 Opening time 35-50
7 Close-open time (Close-open time) ms  80( 8 in operation)
8 Open-close time (Automatic reclosing time) 300
9 Breaking time  65

 Outline and Dimensional Drawing

19 20
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

obtained long-term operation experience, and it also ahs a higher cost than that of the internally attached transformer, large volume, big space
ZW39-40.5 vacuum circuit breaker occupancy. The clients are kindly requested to consider these factors when selecting the types.
 In the space between the vacuum interrupter and the ceramic sleeve of this product is filled with SF6 gas (without internally attached
CT: 0.02MPawith internally attached CT: 0.2Mpa), ensuring that no internal condensation and moisture absorption will occur, and it can
also avoid sych defects of the original ZW7 serial products as that the internally filled insulation materials may easily lead to air bubbles,
penetrating discharge and difficulties in maintenance and repairs.
 Imported products or products made by joint venture manufacturers were adopted for major secondary electric components, so they
feature high reliability.
 The surface treatments for the exposed parts of this product were all hot dip galvanized or directly use high quality stainless steel
plates, which feature excellent corrosion resistance.
 This product can directly substitute SW2-35 oil-minimum breaker (with the same installation dimensions), and when provided with
transition support it can replace all types of oil-maximum breakers, so it is a rather ideal oilles breaker.

 Major technical parameters


1) Table of major parameters of the circuit breaker
No. Name Unit Data
1 Rated voltage 40.5
1 min power frequency withstand voltage (95+23)/95*(dry)
2
( Across open contacts / Between phases, to earth) kV 85*(wet)
Rated lightning impulse withstand voltage
3 185+30)/185G
(Across open contacts / Between phases, to earth)
4 Rated current A 2000
5 Rated short-circuit breaking current 31.5
kA
6 Rated short-time withstand current 31.5
7 Rated duration of short - circuit S 4
8 Rated short-circuit making current (peak) 80
kA
 Brief introduction 9 Rated peak withstand current 80
 ZW39-40.5vacuumcircuitbreakerisapplicableinthe50Hz,40.5kVthree-phaseelectricalsystemanditisusedforbreakingrated current, 10 Breaking times of rated short-circuit breaking current Time 30
failurecurrent or switching lines and realize the controlandprotectionofelectricalsystem.Thissystemcanbefrequentlyoperated and can also be 11 Rated out-of-step breaking current 8
used as used as liaison breaker. kA
12 Out-of-step grounding failure breaking current 27.4
13 Rated operating sequence O  0.3s  CO  180s  CO
 Structural features 14 Mechanical life Time 10000
StructuralFeauresZW39-40.5WT2000-31.5outdoorvacuumcircuitbreakerhassolvedthemajorproblemofdomesticproductsof similar types:
15 Rated voltage of spring energy storage motor V AC220, DC220, DC110
that is due to temperature changes the internals of the breaker will generate condensation, moisture absorption that lead to the reduction
of insulation strength. It has also solved the problem that the insulation pole may easily age due to its exposure outside, strengthened the Opening coil DC220/1.6 or DC110/3.4
16 Rated operation voltage V/A
insulation strength the internal surface of the bushings and insulating parts. In addition, this circuit breaker also has the following Close coil DC220/1.8 or DC110/2.3
characteristics: Vacuum arc chamber, with a vacuum Interceptors recently out of the factory <1.3310-3
17 Pa
 The optimized choice of vacuum interrupter contact materials keeps the breaking interception value under 4A on average, effectively degree of (TD-40.5/2000-31.5W) During the 20-year storage period <6.610-2
inhibiting operation overvoltage
18 Weight of breaker kg 750 (without CT) 1000 (with CT)
 The circuit breaker has strong breaking capacity and the breaking short-circuit current 31.5kV can reach 30 times.
 It adopts the enhanced highly reliable mechanism of CT10A and can be operated repeatedly, with a life time of more than 10000 19 Rated gas pressure of SF6 0.02 (without CT) /0.2 (with CT)
MPa
times. The major features of enhanced mechanism of CT10A(in comparison with the original CT10-A mechanism)): 20 SF6 gas superfeed pressure warning pressure (20) 0.15(with CT)
(1) The number of parts is reduced, and it adopts the structure of double half shaft featuring high reliability. 21 Water content of SF6 gas (V/V) (20, at time of transfer)  25010-6(with CT)
(2) It adopts triple sandwiched structure and the energy storage part and the switch opening and closing parts are separated, featur- 22 Annual gas leakage rate %  0.5
ing good stability.
Across open contacts  1255
(3) The design of the closing magnet is changed from the lowerpart to the upper part, which facilitates replacement and maintenance. 23 Creepage distance for outer insulation mm
(4) All the terminals are Phoenix ones. To earth  1255
 This product can meet the environment requirements for a sea level of up to 3000m; with a high insulation level, the insulation level Note: Values marked with * are the outer insulation levels and they were corrected for a sea level of 3000m, with the three values being 122kV,
at broken sections reaches 118kV. 109 kV and 237kV respectively.
 The circuit breaker may have internally or externally attached transformers.
Four internally attached transformers can be attached to each phase of the circuit beaker and the iron core of the internally attached
transformer adopts microcrystal alloy and magnetic material with high conductivity, and the electrical transformers above 200A can reach  Ordering instructions
Grade 0.2 or Grade 0.2S. The integrated structure of the circuit breaker is compact, and the binding techniques for the secondary windings
 Types and specifications of circuit breakers;
of transformers have been fully optimized, which fully ensures that after binding the coils of the transformer has regular shape, free of burrs,
 Rated electrical parameters (voltage, current and breaking current, etc.)
and they will not become loosen at baking and not deformed after they are installed into the main unit, thus ensuring even electrical field.
The internally attached CT of the circuit breaker is compact, but due to the limited space inside the circuit breaker, it cannot realize very  Ambient conditions for us (ambient temperatures, sea levels and grades of environmental contaminations);
high accuracies (for example 0.2 or 0.2S. ) at small currents (such as those below 100A), and it also has small load.In addition, the  Operating voltage and motor voltage of operating mechanism;
maintenance, capacity increase and replacement of internally attached current transformer is not convenient compared with those of the  Number, current ratios, scale order combination and secondary load of internally or externally attached transformers;
externally attached transformer, but the anti-aging problem of externally attached transformers, especially outdoor cast transformers ahs not  Spare parts and specialized tools, names and quantity of equipment (need to be ordered separately).

21 22
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing


LW8-40.5 outdoor high voltage
SF6 circuit breaker

 Brief introduction
LW8-40.5 outdoor high voltage SF6 circuit breaker is a three-phase AC 50Hz outdoor high voltage electric appliance and it uses SF6
gas as intercepting and insulating media and adopts arc chamber mechanism. With powerful breaking capacity, it can be widely used in the
electric system with a rated voltage of 40.5 V and as the open and close rated current, short-circuit current of sub-stations and power plant
and it can also be used liaison breaker and switch on/off capacitor bank; it has an internally attached current transformer for measurement
and protection.

 Structural features
As a large-capacity product developed by our Company, this product adopts arc chamber and is coupled with spring operation
mechanism. It passed all the type tests of 40kV at one time. The tests have proven that this product features excellent breaking perfor-mance,
reliable mechanical features. Its major characteristics are listed below:
 In addition to satisfying the failure protection of 40kA, this product also features powerful capacitive current inductive current and
reliable operation/
 It has reliable sealing performance, with its annual gas leakage rate being much smaller than 0.5%. So it features long mainte-nance
cycle and low maintenance fees.
 It has reliable mechanical performance and can be operated repeatedly. The option of CT-14 spring operation mechanism features
the advantages of smooth transmission and reliable operation.
 It features high insulation level: between the broken sections a 118kV industrial frequency withstand voltage,215kV lightning impulse
withstand voltage and can meet the requirements of liaison breaker. In addition, this product has been specially design to meet the
environment requirements at a sea level of 3000m.
 On both sides of the broken sections of this product current transformer CT can be attached, and the secondary windings of the
CT and the casing of the breaker are in low electric potential, so it ahs good safety and reliability and an excellent layout adaptability. The
iron core of the current transformer adopts microcrystal alloy and magnetic material with high conductivity and its accuracy grades can reach
Grade 0.2 or Grade 0.2S.
 The surface treatments for the exposed parts of this product were all hot dip galvanized or directly use high quality stainless steel
plates, which feature excellent corrosion resistance.
 Imported products or products made by joint venture manufacturers were adopted for major secondary electric components.

23 24
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Major technical parameters  Outline and Dimensional Drawing

No. Name Unit Data


1 Rated voltage 40.5
Rated lightning impulse withstand voltage (peak) kV 185
2 Rated insulation level
Power frequency withstand voltage 95
3 Rated current A 2000
4 Mechanical life Time 6000
5 Rated air pressure of SF6 gas (meter pressure at 20) 0.50
MPa
6 Warning pressure/minimum function pressure (meter pressure at 20) 0.47/0.45
7 Rated short-circuit breaking current 40
8 Rated short-circuit making current (peak) 100
9 Rated short-time withstand current (Thermal current) kA 40
10 Rated peak withstand current (Dynamic current) 100
11 Rated out-of-step breaking current 10
12 Accumulated times of breaking under rated breaking current time Time 12
13 Rated duration of short - circuit 4
14 Closing time (under rated operation voltage) s  0.1
15 Opening time (under rated operation voltage)  0.06
16 Rated operation sequence O  0.3s  CO  180s  CO
17 Rated opening / closing current for single capacitor bank A 400
18 Annual leakage rate of SF6 gas %  0.5
19 Water content of SF6 gas (V/V) (20, at time of transfer)  150  10-6
Closing winding DC220/1.7 or DC110/3.4
20 Rated operation voltage/current V/A
Opening winding DC220/2.3 or DC110/4.6
AC220, AC380
21 Energy storage motor voltage V
DC110, DC220
22 Weight of SF6 gas 8
kg
23 Weight of breaker (including operation mechanism) 1400

 Ordering instructions
 Types and specifications of circuit breakers;
 Rated electrical parameters (voltage, current and breaking current, etc.)
 Ambient conditions for us (ambient temperatures, sea levels and grades of environmental contaminations);
 Operating voltage and motor voltage of operating mechanism;
 Number, current ratios, scale order combination and secondary load of internally or externally attached transformers;
 Spare parts and specialized tools, names and quantity of equipment (need to be ordered separately).

25 26
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data
GW4A-40.5 72.5126 145D(W) Outdoor
Item Units Data
A.C. H.V. Disconnector Rated voltage kV 40.5 72.5 126 145

insulation level
1min power frequency To earth kV 95 140 230 275

Rated
withstand voltagerms Across open contacts kV 118 160 265 360
Rated lightning impulse To earth kV 185 325 550 650
withstand voltagepeak Across open contacts kV 215 375 630 770
Rated voltage Hz 50 50
Rated normal current A 630 1250 1600 2000 2000
Rated short-time withstand current kA 20 31.5 40
Rated peak withstand current kA 50 80 100
Rated short-time withstand duration DS/ES s 4/2 3
Level Straight N 750 1000 1000 1000
Rated mechanical terminal load Level Cross N 500 750 750 750
Vertical Force N 750 1000 1000 1000
Creepage distances mm 1013 1256 3150 3906 3625/4495
Mechanical endurance Times 2000 4000
Type CJ6/CJ2/CJ6
Motor mechanism Motor voltage V AC380
Control voltage V AC220AC380DC220
Opening or Closing time s 61
Manual mechanism Type CS11/CS8-6D CS14GCS17G
Control voltage VAC220DC110DC220
None ES kg 350 800 850 1000
Weight Single ES kg 400 900 950 1100
Double ES kg 450 1000 1050 1200

 Brief introduction
Type GW4A-40.5 126D(W) outdoor AC high voltage disconnector are type with three-phase alternating current rated frequency 50Hz  Order notice
outdoor high-voltage transmit electricity equipment, it is used opening-closing high voltage wiring which is in zero load, for it is easily to switch
When you place an order, please state the typerated current and voltageCreepage distancesrated short-time withstand current
high voltage wire, and changing run mode, and the overhauling generating lineBreaker and others high voltage wiring is in safe electric
of the product.
insulation.
 You must make clear the fashion of earthing switch.left ESright ESDouble ES, if you do not give clear indication of left ES or
This production shall be production center-break type, it can be install earthing switches one side or both sides. The DS adopt type
right ES, we will provide right ES.
CS14GCS17Gor CS11 manual mechanism or type CJ6 motor mechanismThe ES adopt type CS14GCS17GCS8-6D manual
 State the typenamesource voltage and Auxiliary switch contacts of the operating mechanism.
mechanism.
 Mounting meanslevel2590if you do not give clear indication of mounting means, we will provide lever setting.
This production shall be in accordance with the latest edition of GB1985-2004High-voltage alternating-current disconnectors and
If you need operating mechanism equipped with electromagnetic lock, you must state the source voltage of the electromagnetic lock.
earthing switches DL/T486-2000 Specifications for HV AC disconnectors and earthing switches and so on, it also satisfy the document
provision of order HV disconnectors which enacted by the State grid corporation of china.
This production pass the technology censor of power company of Jiang Su.

 Environmental Conditions
 Ambient temperature: -40~40
 Altitude above the sea level is not more than 2000m
 Wind speed is not more than 34m/s
 Icing depth is not more than 10mm
 Earthquake intensity is not more than 8degree
 Pollution class:  class(pollution),  class(heavy pollution)
 Radiation from sun is not more than1000W/ (fine weather, at noon)

27 28
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Main Features  Outline and Dimensional Drawing

 All electric circuits adopt stationary contact except between breaks


are sliding contact, this configuration work trustiness and contact
resistance are small.
 Electric tube are make of rectangle aluminium alloy tube, This material
are high intensitylow masscooling surface is big and anti-corrosive
property is good.

 Contact finger is made of a type of especial copper alloy. The


contact is clamped by elastic force of contact finger itself, avoiding the
increase of contact resistance and contact heat due to the corrosion of
spring and decrease of contact clamping force. The contact finger is
connected to its pedestal by bolts, which avoiding the entering of oil
contaminant and dust and the increase of contact resistance. This
structure has won national patent of practicality and new type. (Patent
NO.ZL03 2 20022.6).

 Moving parts of disconnector are designed in accordance with


requirements of maintenance free. The moving pedestal is of sealing
structure, which prevents moisture, dust and harmful gas from enter-
ing inside and keeps bearing and grease in good working conditions.
The bearing of stainless steel will never rust and MoS2 lithium base
grease can not evaporate or dry. Bearing pedestal have angular
contact thrust ball bearings inside, operation moment will not increase
when the DS circulate a long time. Moving parts adopt stainless steel
dowel and oilless automatic lubricating bearing. All ferrous metal are
treated by hot dip galvanized process.

 Mechanical interlock of DS and ES were installed on the main axes


of DS and rotational axis of ES, this interlock were immediately and
unfailingly, and we also abrogate the baroque wheel box, installation
and redressal were expediently, and even avoid the rust question of
wheel box.

qáÉJáå
 The box of mechanism are made of stainless steel plate.
 For the convenience of assembly at fieldwork the connecting pipes
of each earthing switch and the vertical connecting pipes are con-
nected by the clamps instead of pins or weld. It improves assembling
efficiency.

pí~áåäÉëë=ëíÉÉä
ãÉÅÜ~åáëã

29 30
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

31 32
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data
GW5A-40.5 72.5126D(W) Outdoor
Item Units Data
A.C. H.V. Disconnector Rated voltage kV 40.5 72.5 126

insulation level
1min power frequency To earth kV 95 140 230

Rated
withstand voltagerms Across open contacts kV 118 160 265
Rated lightning impulse To earth kV 185 325 550
withstand voltagepeak Across open contacts kV 215 375 630
Rated voltage Hz 50
Rated normal current A 630 1250 1600 2000
Rated short-time withstand current kA 20 31.5 40 40
Rated peak withstand current kA 50 80 100 100
Rated short-time withstand duration DS/ES s 4/2
Level Straight N 750 1000
Rated mechanical Level Cross N 500 750
terminal load Vertical Force N 750 1000
Creepage distances mm 10131256 18132248 31503906
Mechanical endurance times 2000
Type CJ6
Motor voltage V AC380
Motor mechanism Control voltage V AC220AC380DC220
Opening or Closing time s 61
Type CS17CS17G
Manual mechanism Control voltage V AC220DC110DC220
None ES kg 300 350 400
Weight Single ES kg 350 575 650
double ES kg 400 900 1000

 Brief introduction
Type GW5A-40.5 72.5126DWoutdoor AC high voltage disconnector are type with three-phase alternating current rated  Order notice
frequency 50Hz outdoor high-voltage transmit electricity equipment it is used opening-closing high voltage wiring which is in zero load, for
it is easily to switch high voltage wire, and changing run mode, and the overhauling generating line Breaker and others high voltage wiring  When you place an order, please state the typerated current and voltageCreepage distancesrated short-time
is in safe electric insulation. withstand current of the product.
This production shall be production center-break type, it can be install earthing switches one side or both sides. The DS and ES adopt left ES
You must make clear the fashion of earthing switch. right ES
Double ES
. if you do not give clear indication
type CS17 manual mechanism when it be 90drive. when it be 180drive, the DS adopt CJ6 motor mechanism or type CS17G manual of left ES or right ES, we will provide right ES.
mechanism; and the ES adopt type CS17G manual mechanism.  State the typenamesource voltage and Auxiliary switch contacts of the operating mechanism
This production shall be in accordance with the latest edition of GB1985-2004High-voltage alternating-current disconnectors and  Mounting mannerhorizontal mounting incline mounting 25angle and erection mounting. if you do not give clear
earthing switches DL/T486-2000 Specifications for HV AC disconnectors and earthing switches and so on, it also satisfy the document
indication of mounting manner, we will provide lever setting.
provision of order HV disconnectors which enacted by the State grid corporation of china.
 If you need operating mechanism equipped with electromagnetic lock, you must state the source voltage of the
This production pass the technology censor of power company of Jiang Su.
electromagnetic lock.

 Environmental Conditions
 Ambient temperature: JQMHQM
 Altitude above the sea level is not more than 1000m
 Wind speed is not more than 34m/s
 Icing depth is not more than 10mm
 Earthquake intensity is not more than 8degree
 Pollution class:  class(pollution),  class(heavy pollution)
 Radiation from sun is not more than1000W/ (fine weather, at noon)

33 34
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Main Features  Outline and Dimensional Drawing

 All electric circuits adopt stationary contact except between breaks are
sliding contactthis configuration work trustiness and contact resistance
are small.
 Electric tube are make of rectangle aluminium alloy tube This material
are high intensitylow masscooling surface is big and anti-corrosive
property is good.

 Contact finger is made of a type of especial copper alloy. The contact is


clamped by elastic force of contact finger itself, avoiding the increase of
contact resistance and contact heat due to the corrosion of spring and
decrease of contact clamping force. The contact finger is connected to its
pedestal by bolts, which avoiding the entering of oil contaminant and dust
and the increase of contact resistance. This structure has won national
patent of practicality and new type. (Patent NO.ZL03 2 20022.6).

 Moving parts of disconnector are designed in accordance with


requirements of maintenance free. The moving pedestal is of sealing
structure, which prevents moisture, dust and harmful gas from entering
inside and keeps bearing and grease in good working conditions. The
bearing of stainless steel will never rust and MoS2 lithium base grease can
not evaporate or dry. Bearing pedestal have angular contact thrust ball
bearings inside, operation moment will not increase when the DS circulate
a long time.

 Moving parts adopt stainless steel dowel and oilless automatic lubricating
bearing. ALL ferrous metal are treated by hot dip galvanized process.

 mechanical interlock of DS and ES were installed on the


Tie-in
main axes of DS and rotational axis of ES, this interlock were
immediately and unfailingly, and we also abrogate the baroque
wheel box, installation and redressal were expediently, and
even avoid the rust question of wheel box.

 For the convenience of assembly at fieldwork the connecting


pipes of each earthing switch and the vertical connecting Stainless steel
pipes are connected by the clamps instead of pins or weld. It mechanism
improves assembling efficiency.

35 36
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing


W
GW13-40.5 /72.5/126D neutral point Outdoor
A.C. H.V. Disconnector

Coordinating Installation drawing of Type of GW13 neutral point Outdoor AC High Voltage Disconnector and Type CJ2 Operating Mechanism
 Model explain

40.5
G W 13  72.5 (W)
126

Anti-dirt
Rated voltage
Design number
Outdoors type
Disconnector

 Production introduce
 Disconnector contain bracketbaseinsulatorcontactconnection terminal and so on. Insulator and electric part
installed on the base,The angle between two insulator is 50. Base fixup on bracket which incline mounting 25angle. The
bracket have axis which connected with the operating mechanism. It can operated by type CS17G manual mechanism or CJ6
motor mechanism.

37 38
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data
GW4C-252D(G) Outdoor A.C. H.V. Disconnector
Item Units Parameter
Rated voltage kV 252

insulation level
1min power frequency To earth kV 460

Rated
withstand voltagerms Across open contacts kV 530
Rated lightning impulse To earth kV 1050
withstand voltagepeak Across open contacts kV 1200
Rated voltage Hz 50
Rated normal current A 1600 2000 2500 3150
Rated peak withstand current kA 40 50
Rated peak withstand current kA 100 125
Rated short-time withstand duration s 3
Level Straight N 1500
Rated mechanical terminal load Level Cross N 1000
Vertical Force N 1000 1250
The Bus Transfer Current Switching Capability Of Disconnector times 300V1600A100
The Induced Current Electromagnetism inductive Current(Current/Voltage) A/kV 160/15(2) 80/2
Switching Capability Electromagnetism inductive Current(Current/Voltage) A/kV 10/15(2) 3/12
Of Earthing Switch Number of Operation times 10
The small Current Switching Capacitive Current A 1
Capability Of Disconnector Inductive Current A 0.5
Creepage distances mm 6300 7812
Mechanical endurance times 2000
Type SRCJ3
Motor voltage V AC380
Motor mechanism Control voltage V AC220
Opening or Closing time s 12  1
Angle of rotation 180
Manual operating Type SRCS1
 Brief introduction mechanism. Control voltage V AC220
None ES kg 418
Type GW4C-252DGoutdoor AC high voltage disconnector are type with three-phase alternating current rated frequency 50Hz
Weight Single ES kg 438
outdoor high-voltage transmit electricity equipmentit is used opening-closing high voltage wiring which is in zero load, for it is easily to
Double ES kg 458
switch high voltage wire, and changing run mode, and the overhauling generating line Breaker and others high voltage wiring is in safe
electric insulation. Note: 1This production pertain to type tablelandG, the test accord to 2000m height above sea level, correction factor k=1.13. If
This production shall be production three post center-break and retroflexion type, it can be install type JW10-252 earthing switches one insulation level accord to 395kVit can employ to the place which altitude above the sea level is 2800m.
side or both sides. The DS adopt type SRCJ1 motor mechanism and the ES adopt type SRCS1 manual mechanism. 2Parameter in table is the specified value of B in DL/T486-2000, and arcing device are installed. The number in bracket is the
This production shall be in accordance with the latest edition of GB1985-2004High-voltage alternating-current disconnectors and specified value of B in GB1985-2004.
earthing switches GB11022-1999DL/T593-2006Common specifications for high-voltage switchgear and controlgear standards  
DL/T486-2000Specifications for HV AC disconnectors and earthing switchesand so on, it also satisfy the documentprovision of order
HV disconnectors which enacted by the State grid corporation of china. And also pass the 9intensity aseismatic numeration and analyse.  Order notice
This production pass the national appraisal by October.2006. It is deemed toHave trait on design and the performance achieve the  When you place an order, please state the type rated current and voltageCreepage distancesrated short  time withstand
advanced level of international congener production. current of the product.
 You must make clear the mode of earthing switch.left ESright ESDouble ES . The mode of earthing switch about dual-fixed
contact disconnector (single side earthing, dual-side earthing, middle earthing , three earthing)
 Environmental Conditions  State the type, name, motor voltage ,control voltage and auxiliary switch contacts of the operating mechanism.
 Ambient temperature: -40~+40
 Altitude above the sea level is not more than 2000m
 Wind speed is not more than 34m/s
 Icing depth is not more than 20mm
 Earthquake intensity is not more than 9degree
 Pollution class:  class and less than  class
 Radiation from sun is not more than1000W/ (fine weather, at noon)

39 40
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Main Features

 Electric tube are make of tank shaped aluminium alloy tubeThis


material are high intensitylow masscooling surface is big and anti- =The base of disconnector contain steel tube and bearing pedestal
corrosive property is good. is connected with nut, high strength and zinking on the facies,
mhcorrosion resistance is good. All ferrous metal spare parts (including
above M10 fastener) are treated with zinc.

 U-contact of fixed contact is fixed on the contact support, which


forms fixed contact. The other end of conductor produces pressure by
spring pressuring the blades and spring its self-pressure. And short-
circuit current automatically increase clamping force. The contact
=Moving parts of disconnector are designed in accordance with
spring which is made of stainless material and has insulating washer.
requirements of maintenance free. The moving pedestal is of sealing
Spring is not rust and can not distribute current.
structure, which prevents moisture, dust and harmful gas from entering
U-contact fixed at one end
inside and keeps bearing and grease in good working conditions.

 Contact-head consumption is made of copper plate. During Opening


and Closing process Contact-head consumption and Contact rub a
route of travel short, operate dint small.

Arcing Stainless steel pin Stainless steel joint bearing  All the position of rotated friction takes stainless steel pin, self
 Mobile and fixed contact are fixed with arcing contact, which makes contact
lubricating bearings and stainless steel joint bearings.
diconnector has capability of the bus transfer current switching,
capacitive current and inductive current.

Polytetrafluoroethylene Composite self lubricating Supramoly


shaft liner shaft liner shaft liner

 Earthing switch takes type one pace. And its structure is simple and
convenient. Earthing switch makes effective use of electrodynamic
force clamping contact and making switch keeping closing position. So  Connect rod takes type of assembly, so which is not cutted and
it can withstands high short-circuit current and inductive current. welded. Connect rod is treated with zinc and no-sew steel pipe.

Earthing switch operating shaft


Disconnector operating shaft
 Cabinet of operating mechanism which rivet with stainless steel
Cam Sliding plate plates, do not weld. So it has a well appearance. Motor mechanism
Earthing switch operating shaft adopt orthogonal gearbox with hollow shaft and nylon gear, so which
its movement is stable and no-noise. All electric component adopt
foreign famous brand, so it works smoothly. And its closed function is
integrate.
Closed position of earthing switch (disconnector can not close) Closed position of disconnector (earthing switch can not close) Manual mechanism makes use of auxiliary relay in it to achieve
electromagnetic lock function , so interlocking is stable. The structure
 The mechanical interlocking of disconnector and earthing switch
overcomes rustiness and failure function of electromagnetic lock in
take way of cam and sliding plate, so which is stable and reliable.
china.

41 42
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing


G
GW7B-252D Outdoor A.C. H.V. Disconnector

 Brief introduction
Type GW7B-252D(G) outdoor AC high voltage disconnector are type with three-phase alternating current rated frequency 50Hz
outdoor high-voltage transmit electricity equipmentit is used opening-closing high voltage wiring which is in zero load, for it is easily to
switch high voltage wire, and changing run mode, and the overhauling generating line Breaker and others high voltage wiring is in safe
electric insulation.
This production shall be production three post center-break and retroflexion type, it can be install type JW10-252 earthing switches one
side or both sides. The DS adopt type SRCJ2 motor mechanism and the ES adopt type SRCS1 manual mechanism.
This production shall be in accordance with the latest edition of GB1985-2004High-voltage alternating-current disconnectors and
earthing switches GB11022-1999DL/T593-2006Common specifications for highvoltage switchgear and controlgear standards  
DL/T486-2000Specifications for HV AC disconnectors and earthing switchesand so on ,it also satisfy the documentprovision of order
HV disconnectors which enacted by the State grid corporation of china. And also pass the 9intensity aseismatic numeration and analyse.
This production pass the national appraisal by October .2006. It is deemed toHave trait on design and the performance achieve the
advanced level of international congener production .

 Environmental Conditions
 Ambient temperature: -40+40
 Altitude above the sea level is not more than 2000m
 Wind speed is not more than 34m/s
 Icing depth is not more than 20mm
 Earthquake intensity is not more than 9degree
 Pollution class:  class and less than  class
 Radiation from sun is not more than1000W/ (fine weat her, at noon)

43 44
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data  Main Features

Item Units Data


Rated voltage kV 252
=Disconnector adopt retroflex configuration. live blade has two steps
insulation level

1min power frequency To earth kV 460


action, which is flowing with a 70rotation of the operating insulator at the
Rated

withstand voltagerms Across open contacts kV 530


time of opening-closing, after two terminal contacting blade were coming
Rated lightning impulse To earth kV 1050
into fixed base and turned back by keeper, with a 45rotation of itself
withstand voltagepeak Across open contacts kV 1200
which the conduit is driven by overturning mechanism, touching blade and
Rated voltage Hz 50
contacting finger are reliably contact. The contact has self purging with
Rated normal current A 2000 2500 3150 4000
Overturn-close the switch, also there are not impact force to fixed insulator
Rated short-time withstand current kA 50 Sketch map about closing process
for little steering force at closing time.
Rated peak withstand current kA 125
Rated short-time withstand duration s 3
Level Straight N 1500
Rated mechanical terminal load Level Cross N 1000
=U-contact of fixed contact is fixed on the contact support , which
Vertical Force N 1250
forms fixed contact. The other end of conductor produces pressure by
The Bus Transfer Current Switching Capability Of Disconnector times 300V1600A100 U-contact
spring pressuring the blades and spring its self-pressure. And short-
The Induced Current Electromagnetism inductive Current(Current/Voltage) A/kV 160/15(2) 80/2
circuit current automatically increase clamping force. The contact
Switching Capability Of Static inductive Current(Current/Voltage) A/kV 10/15(2) 3/12
spring which is made of stainless material and has insulating washer.
Earthing Switch Number Of Operation times 10
Spring is not rust and can not distribute current.
The small Current Switching Capacitive Current A 1
Capability Of Disconnector Inductive Current A 0.5
Creepage distances mm 6300 8712
Mechanical endurance times 2000 =There is a hook plate in the fixed contact, fixed contact is locked
Arcing contact
Type SRCJ2 after CLOSE, Even if in action of bold windoscillation electric
Motor voltage V AC380 motive force, the contact is unable to come away. Mobile and fixed
Motor mechanism Control voltage V AC220 contact are fixed with arcing contact , which makes diconnector has
Opening or Closing time s 14  1 capability of the bus transfer current switching , capacitive current and Hook plate
Angle of rotation 180 inductive current
Manual mechanism Type SRCS1
Control voltage V AC220
None ES kg 630
Weight Single ES kg 650 =Earthing switch takes type one pace. And its structure is simple and
double ES kg 670 convenient. Earthing switch makes effective use of electrodynamic
force clamping contact and making switch keeping closing position. So
1This production pertain to type tablelandG, the test accord to 2000m height above sea level, correction factor k=1.13.
Note
it can withstands high short-circuit current and inductive current.
If insulation level accord to 395kVit can employ to the place which altitude above the sea level is 2800m.
2 The number of ** in table is the specified value of B in DL/T486-2000. The number in bracket is the specified value of B in
GB1985-2004.

 Order notice  Conduit is made of aluminum alloy with high strengthhigh


 When you place an order, please state the type rated current and voltageCreepage distancesrated short  time withstand conductivitycorrosion resistanceMoving contact takes type of fab-
current of the product ricated structureit make replace convenience.
 You must make clear the mode of earthing switch. left ESright ESDouble ES The mode of earthing switch about dual-fixed Reversal mechanism is airproofed by the aluminous cover, which
contact disconnector (single side earthing, dual-side earthing, middle earthing , three earthing ) can prevent raindustcorrosion.
 State the type, name, motor voltage ,control voltage and auxiliary switch contacts of the operating mechanism.

=The base of disconnector is welded with steel tube and bent


plate, high strength and zinking on the facies , mhcorrosion
resistance is good. All ferrous metal spare parts( including above
M10 fastener) are treated with zinc.

45 46
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing


=Moving parts of disconnector are designed in accordance with
requirements of maintenance free. The moving pedestal is of
sealing structure, which prevents moisture, dust and harmful gas
from entering inside and keeps bearing and grease in good
working conditions.

=All the position of rotated friction take stainless steel pin ,self
stainless steel pin stainless steel joint bearing lubricating bearings and stainless steel joint bearings.

polytetrafluoroethylene composite self lubricating supramoly


shaft liner shaft liner shaft liner

=Connect rod takes type of assembly , so which is not cutted and


welded. Connect rod is treated with zinc and no-sew steel pipe.

earthing switch disconnector earthing switch


operating shaft operating shaft operating shaft

closed position of
disconnector
(earthing switch
can not close) = The mechanical interlocking of disconnector and earthing
switch take way of cam and sliding plate, so which is stable and
cam sliding plate reliable.

closed position of
earthing switch
(disconnector can
not close)

=Cabinet of operating mechanism which rivet with stainless


steel plates, do not weld. So it has a well appearance. Motor
mechanism adopt orthogonal gearbox with hollow shaft and nylon
gear, so which its movement is stable and no-noise. All electric
component adopt foreign famous brand, so it works smoothly. And
its closed function is integrate.
Manual mechanism makes use of auxiliary relay in it to achieve
electromagnetic lock function , so interlocking is stable. The
structure overcomes rustiness and failure function of electromag-
netic lock in china.

47 48
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data
GW22B-252D(G) Outdoor AC High Voltage Disconnector
Item Units Parameter
Rated voltage kV 252
Rated 1min power frequency To earth kV 460
insulation withstand voltage(rms) Across open contacts kV 530
level Rated lightning impulse To earth kV 1050
withstand voltage(peak) Across open contacts kV 1200
Rated voltage Hz 50
Rated normal current A 1600 2000 2500 3150
Rated short-time withstand current kA 40 50
Rated peak withstand current kA 100 125
Rated short  time withstand duration s 3
Rated mechanical Level Straight N 2000
terminal load Level Cross N 1500
Vertical Force N 1250
The Bus Transfer Current Switching times 300V1600A100
Capability Of Disconnector
Electromagnetism inductive A/kV 160/15(2) 80/2
The Induced Current(Current/Voltage)
Current Switching Static inductive Current A/kV 10/15(2) 3/12
Capability Of (Current/Voltage)
Earthing Switch Number Of Operation times 10
The small Current Switching Capacitive Current A 1
Capability Of Disconnector Inductive Current A 0.5
Support lead longitudinal displacement mm 150/200Hard lead/Soft lead
Rated contact area Horizontal total drift mm 150/500Hard lead/Soft lead
Vertical excursion mm 150/250Hard lead/Soft lead
 Brief introduction Creepage distances mm 6300 7812
Type GW22B-252D(G) Outdoor AC HV disconnector are type with three-phase alternating current rated frequency 50Hz , rated voltage Mechanical endurance times 2000
252kV outdoor high-voltage transmit electricity equipment it is used opening-closing high voltage wiring which is in zero load, for it is easily Type SRCJ3
to switch high voltage wire, and changing run mode, and the overhauling generating line, Breaker and others high voltage wiring is in safe Motor voltage V AC380
electric insulation. Motor operating Control voltage V AC220
This product is of semi-pantograph type with vertical movement, it can be install JW10-252 one side or both sides. The DS adopt type mechanism Opening or Closing time s 10  1
SRCJ3 motor-operated mechanism when three poles are driving. ES adopt type SRCS1 manual operating mechanism when three poles Angle of rotation 135
are driving. Manual operating Type SRCS1
This production shall be in accordance with the latest edition of GB1985-2004High-voltage alternating-current disconnectors and mechanism Control voltage V AC220
earthing switches GBII022-1999DL/T593-2006Common specifications for high-voltage switchgear and controlgear standards DL/ None ES kg 600
T486-2000Specifications for HV AC disconnectors and earthing switchesand so on, it also satisfy the documentprovision of order H. Weight Single ES kg 630
V. disconnectorswhich enacted by the state grid corporation of china. And it passes computational analysis of withstanding earthquake 9
Note: (1) This production pertain to type tablelandG, the test accord to 2000m height above sea level, correction factor k=1.13. If
degree intensity.
insulation level accord to 395kVit can employ to the place which altitude above the sea level is 2800m.
The product has passed through an examination by experts by October 2006. It draws a conclusion: The design of product has
(2) Parameter in table is the specified value of B in DL/T486-2000, and arcing device is installed. The number in bracket is the
remarkable characteristics, and its performance attains the advanced level of international same kind product.
specified value of B in GB1985-2004.

 Environmental Conditions
=Ambient temperature: -4040  Order notice
=Altitude above the sea level is not more than 2000m =When you place an order, please state the type, rated current and voltage, creepage distances, rated short-time withstand current
=Wind speed is not more than 34m/s of the product.
=Icing depth is not more than 20mm =Whether equipped with earthing switch.
=Earthquake intensity is not more than 9 degree =The disconnector diameter of tube bus bar.
=Pollution class: beneath  class =You must make clear the mode of earthing switch(Type of portrait or landscape orientation).
=Solar radiation intensity is not more than 1000W/ (fine weather, at noon) =State the type, name , motor voltage ,control voltage and auxiliary switch contacts of the operating mechanism.

49 50
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Main Features
 Connecting shaft takes type of assembly, so which is not cutted and
welded. connecting shaft that it adopts seamless steel tubes that is
treated with hot dip galvanized.
 The disconnector forms insulation breaker after opening. And the
break is obvious, which is convenient for watching. The distance is
short, so it can be used in bus bar disconnector that it is installed just
below bus bar. It ocuppys small areas, and which economizes wires.
 Earthing switch takes type of one pace. And its structure is simple
Obviously in the dual-bus bar to side-line, it remarkbly ocuppy small
and convenient. Earthing switch makes effective use of electrody-
areas.
namic force clamping contact and making switch keeping closing
position. So it can withstands high short-circuit current and inductive
current.

 The arms are made of very strong and highly conductive aluminum
alloy tubes, which has low weight, high strength and well anti-corrosive
property.
 All the position of rotated friction take stainless steel pin, self
Stainless steel pin Stainless steel joint bearing lubricating bearings and stainless steel joint bearings. All ferrous metal
spare parts(including above M10 fastener) are treated with hot dip
galvanized.
 This product drives with transmission shaft. Comparing with type
GW16/22 which uses with bevel, the structure is simple and convenient.

Polytetrafluoroethylene Composite self Supramoly shaft


shaft liner lubricating shaft liner liner

Earthing switch
Disconnector operating shaft
operating shaft

 Conductive node adopt flexible conductors, which realizes no


movable joints for jointed position. So this structure is simple and
stable, which it realizes no-maintenance.
 The mechanical interlocking of disconnector and earthing switch
Closed position of disconnector (Earthing switch can not close) take way of cam and sliding plate, so which is stable and reliable.
Cam Sliding plate

Arcing
contact
 Type of clamp contact is equipped with arcing device, which makes
disconnector having well capability of the bus Transfer Current Switching,
capacitive current and inductive current. Below type of clamp contact is Closed position of earthing switch (Disconnector can not close)

flexible conductor, which has not movable contact. So its contact is stable Flexible conductor

and avoid excessive hot.


 Cabinet of operating mechanism which rivet with stainless steel
plates, do not weld. So it has a well appearance. Motor mechanism
adopt orthogonal gearbox with hollow shaft and nylon gear, so which
its movement is stable and no-noise. All electric component adopt
foreign famous brand, so it works smoothly. And its closed function is
 Fixed contact is equipped with adjustment wire, so adjustment is Steel wire integrated.
convenient. Manual mechanism makes use of auxiliary relay in it to achieve
And it has very small displacement up and down. electromagnetic lock function, so interlocking is very stable. The
structure overcomes rustiness and failure function of electromagnetic
lock in china.

51 52
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing


GW23B-252D(G) Outdoor AC High Voltage Disconnector

 Brief introduction
Type GW23B-252D(G) Outdoor A.C.H.V disconnector are type with three-phase alternating current rated frequency 50Hz, rated voltage 252kV
outdoor high-voltage transmit electricity equipment, it is used opening-closing high voltage wiring which is in zero load, for it is easily to switch high voltage
wire, and changing run mode, and the overhauling generating line, breaker and others high voltage wiring is in safe electric insulation.
This product is of semi-pantograph type with horizontal movement, it can install JW10-252 at one side or both sides. The DS adopt type SRCJ3 motor-
operated mechanism when three poles are driving. ES adopt type SRCS1 manual operating mechanism when three poles are driving.
High-voltage alternating-current disconnectors and earthing switches
This production shall be in accordance with the latest edition of GB1985-2004

GBII022-1999DL/T593-2006Common specifications for high-voltage switchgear and controlgear standards 
 DL/T486-2000Specifications
for HV AC disconnectors and earthing switchesand so on, it also satisfy the documentprovision of order H.V. disconnectors which enacted by the
state grid corporation of china. And it passes computational analysis of withstanding earthquake 9 degree intensity.
The product has passed through an examination by experts by October 2006. It draws a conclusion:
The design of product has remarkable characteristics ,and its performance attains the advanced level of international same kind product.

 Environmental Conditions
 Ambient temperature: -4040
 Altitude above the sea level is not more than 2000m
 Wind speed is not more than 34m/s
 Icing depth is not more than 20mm
 Earthquake intensity is not more than 9 degree
 Pollution class:  class
 Solar radiation intensity is not more than 1000 W/ (fine weather, at noon)

53 54
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data  Main characteristics

Item Units Parameter


Rated voltage kV 252
=This product is of semi-pantograph type with horizontal movement.
insulation level

1min power frequency To earth kV 460


The distance between three poles is short, and position of opening
Rated

withstand voltagerms Across open contacts kV 530


ocuppies small top space. So it is suitable for in-out line disconnector.
Rated lightning impulse To earth kV 1050
Two disconnectors form dual-contacts, this can be applied to 1.5 line
withstand voltagepeak Across open contacts kV 1200 and economizes occupied areas. This product can also be used with
Rated voltage Hz 50 transformer and others which form type of opening composite apparatus.
Rated normal current A 1600 2000 2500 3150
Rated peak withstand current kA 40 50
Rated peak withstand current kA 100 125 Type of dual-fixed contact

Rated short  time withstand duration s 3


Level Straight N 1500
=This product drives with transmission rod. Comparing with type
Rated mechanical Level Cross N 1000
GW17/23 which uses with bevel, the structure is simple and convenient.
terminal load Vertical Force N 1250
Conductive node adopt flexible conductors, which realizes no movable
The Bus Transfer Current Switching Capability Of Disconnector times 300V1600A100 joints for jointed position. So this structure is simple and stable, which
The Induced Current Electromagnetism inductive Current(Current/Voltage) A/kV 160/15(2) 80/2 realizes no-maintenance.
Switching Capability Of Electromagnetism inductive Current(Current/Voltage) A/kV 10/15(2) 3/12
Earthing Switch Number Of Operation times 10
The small Current Switching Capacitive Current A 1
=Moval contact adopt inserted type, which has self-cleaning capability. Arcing contact
Capability Of Disconnector Inductive Current A 0.5
U-contact of fixed contact is fixed on the contact base, which forms
Creepage distances mm 6300 7812
stationary contacts. The other end of conductor produces pressure by
Mechanical endurance times 2000
spring pressuring the blades and spring its self-pressure. And short-
Type SRCJ3
circuit current automatically increases clamping force. The contact
Motor voltage V AC380
spring are made of stainless material, and it has insulating washer.
Motor mechanism Control voltage V AC220
Spring is not rust, and which can not distribute current.
Opening or Closing time s 10  1
=Moval and fixed contact are fixed with arcing contact, which it makes
Angle of rotation 135
that current and inductive current diconnector has capability of the bus
Manual operating Type SRCS1
transfer current switching, capacitive current and inductive current.
mechanism. Control voltage V AC220
None ES kg 850
Weight Single ES kg 880
double ES kg 910
=Earthing switch takes type of one pace. And its structure is simple
Note: 1This production pertain to type tablelandG , the test accord to 2000m height above sea level, correction factor k=1.13. If
and convenient. Earthing switch makes effective use of electrodynamic
insulation level accord to 395kVit can employ to the place which altitude above the sea level is 2800m.
force clamping contact and making switch keeping closing position. So
2Parameter in table is the specified value of B in DL/T486-2000, and arcing device are installed. The number in bracket is the
it can withstands high short-circuit current and inductive current.
specified value of B in GB1985-2004.

 Order notice
 When you place an order, please state the type, rated current and voltage, Creepage distances, rated short-time withstand current
of the product.  All ferrous metal spare parts (including above M10 fastener) are
 You must make clear the mode of earthing switch. left ESright ESDouble ES ; The mode of earthing switch about dual-fixed treated with hot dip galvanized.
contact disconnector (single side earthing, dual-side earthing, middle earthing, three earthing)
 State the type, name, motor voltage, control voltage and auxiliary switch contacts of the operating mechanism.

55 56
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Outline and Dimensional Drawing

Stainless steel pin Stainless steel joint bearing = All the position of rotated friction takes stainless steel pin, self
lubricating bearings and stainless steel joint bearings.

fåëí~ää~íáçå=Çê~ïáåÖ=çÑ=çéÉê~íáåÖ=ãÉÅÜ~åáëãK
Polytetrafluoroethylene Composite self lubricating Supramoly
shaft liner shaft liner shaft liner

=The arms are made of very strong and highly conductive aluminum
alloy tubes, which has low weight, high strength and well anti-corrosive
property.

oÉèìáêÉãÉåí=Ñçê=Ä~ëÉêÉÑÉêÉåÅÉ

=Connecting rod takes type of assembly, so which is not cutted and NK=cáñÉÇ=Åçåí~Åí
OK=`çåí~Åí=íìÄÉ
welded. Connecting rod that it adopts seamless steel tubes is treated
PK=léÉê~íáåÖ=áåëìä~íçê
with hot dip galvanized. QK=pìééçêí=áåëìä~íçê
RK=b~êíÜáåÖ=ëïáíÅÜ
SK=jçíçêJçéÉê~íÉÇ=ãÉÅÜ~åáëã
TK=j~åì~ä=çéÉê~íáåÖ=ãÉÅÜ~åáëã
UK=qê~åëãáëëáçå=ëÜ~Ñí=çÑ=ÇáëÅçååÉÅíçê
Earthing switch operating shaft VK=`çååÉÅíáåÖ=ëÜ~Ñí=çÑ=É~êíÜáåÖ=ëïáíÅÜ
Disconnector operating shaft
`ççêÇáå~íáåÖ=fåëí~ää~íáçå=Çê~ïáåÖ=çÑ=qóéÉ=çÑ==dtOP_JOROaEdF=lìíÇççê=^`=eáÖÜ=sçäí~ÖÉ=aáëÅçååÉÅíçê
Cam Sliding plate
Earthing switch operating shaft

Closed position of disconnector (earthing switch can not close) Closed position of earthing switch (disconnector can not close)

=The mechanical interlocking of disconnector and earthing switch


take way of cam and sliding plate, so which is stable and reliable.

=Cabinet of operating mechanism which rivet with stainless steel plates, NK=qÜÉ=äáîÉ=é~êí
do not weld. So it has a well appearance. Motor mechanism adopt OK=léÉê~íáåÖ=áåëìä~íçê
orthogonal gearbox with hollow shaft and nylon gear, so which its movement PK=pìééçêí=áåëìä~íçê
QK=_~ëÉ
is stable and no-noise. All electric component adopt foreign famous brand,
RK=sÉêíáÅ~ä=ÇêáîÉ=ëÜ~Ñí
so it works smoothly. And its closed function is integrated.
SK=jçíçêJçéÉê~íÉÇ=ãÉÅÜ~åáëã
Manual mechanism makes use of auxiliary relay in it to achieve TK=j~åì~ä=çéÉê~íáåÖ=ãÉÅÜ~åáëã
electromagnetic lock function, so interlocking is stable. The structure UK=iáåâ~ÖÉ=çÑ=ÇáëÅçååÉÅíçê=àçáåí
overcomes rustiness and failure function of electromagnetic lock in china. VK=qê~åëãáëëáçå=ëÜ~Ñí=çÑ=ÇáëÅçååÉÅíçê
NMK=b~êíÜáåÖ=ëïáíÅÜ=íìÄÉ
NNK=`ççêÇáå~íáåÖ=íìÄÉ=çÑ=É~êíÜáåÖ=ëïáíÅÜ
NOK=fåíÉêäçÅâáåÖ=íê~åëãáëëáçå=ëÜ~Ñí

`ççêÇáå~íáåÖ=fåëí~ää~íáçå=Çê~ïáåÖ=çÑ=qóéÉ=çÑ==dtOP_JOROaEdFÇì~äÑáñÉÇ=Åçåí~Åí=lìíÇççê=^`=eáÖÜ=sçäí~ÖÉ=aáëÅçååÉÅíçê

57 58
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Technical Data
JW10-252(G) Outdoor AC High Voltage Earthing Switch
Item Unit Parameter
Rated voltage kV 252
Rated insula- 1min power frequency withstand voltagerms kV 460
tion level Rated lightning impulse withstand voltagepeak kV 1050
Rated voltage Hz 50
Rated short-time withstand current kA 50
Rated peak withstand current kA 125
Rated short-time withstand duration s 3
Level Straight N 1500
Rated mechanical Level Cross N 1000
terminal load Vertical Force N 125
The Induced Current Electromagnetism inductive Current(Current/Voltage) A/kV 160/15(2) 80/2
Switching Capability Of Static inductive Current(Current/Voltage) A/kV 10/15(2) 3/12
Earthing Switch Number Of Operation Time 10
Creepage distances mm 6300 7812
Mechanical endurance Time 2000
Manual operating type SRCS1
mechanism Control voltage V AC220
type SRCJ3
Motor voltage V AC380
Control voltage V AC220AC380
Motor-operated mechanism Opening or Closing time s 10  1
Angle of rotation 135
Weight kg 255
Note(1) This production pertain to type tablelandG, the test accord to 2000m height above sea level, correction factor k=1.13. If
 Brief introduction insulation level accord to 395kVit can employ to the place which altitude above the sea level is 2800m.
JW10-252(G) Outdoor AC High Voltage Earthing Switch that earthing device is independently installed . It is suitable for alternating (2) The number of ** in table is the specified value of B in DL/T486-2000, and arcing device is installed. The number in bracket
current rated frequency 50Hz , rated voltage 252kV power line . it is used to releasing load on the repairing wire and facilities. And it is used is the specified value of B in GB1985-2004.
opening-closing high voltage wiring and breaker which are in zero load, which makes wire having invisible break,ensuring repairmen safety.
Usually it is used in vertical semi-pantograph disconnector, which earth top bus bar.
Earthing switch takes type of one pace. ES adopt type SRCS1 manual operating mechanism or SRCS3 motor operating mechanism  Order notice
when three poles are driving. =When you place an order, please state the type, rated current and voltage, Creepage distances, rated short-time withstand current
This production shall be in accordance with the latest edition of GB1985-2004High-voltage alternating-current disconnectors and of the product.
earthing switches  GBII022-1999DL/T593-2006Common specifications for high-voltage switchgear and controlgear standards   =You must make clear the mode of earthing switch(Type of portrait or landscape orientation).
DL/T486-2000Specifications for HV AC disconnectors and earthing switchesand so on ,it also satisfy the documentprovision of order =State the type, name , motor voltage ,control voltage and auxiliary switch contacts of the operating mechanism.
H.V. disconnectors which enacted by the state grid corporation of china.
The product has passed an examination by experts by October 2006. It draws a conclusion: The design of product has remarkable
characteristics ,and its performance attains the advanced level of international same kind product.

 Environmental Conditions
=Ambient temperature: -40~40
=Altitude above the sea level is not more than 2000m
=Wind speed is not more than 34m/s
=Icing depth is not more than 20mm
=Earthquake intensity is not more than 9 degree
=Pollution class: beneath  class
=Solar radiation intensity is not more than 1000 W/ (fine weather, at noon)

59 60
®
Sieyuan High voltage AC circuit breaker
Professional manufacturer

 Main characteristics  Outline and Dimensional Drawing

=Earthing switch takes type of one pace. And its structure is simple
and convenient. Earthing switch makes effective use of electrody-
namic force clamping contact and making switch keeping closing
position. So it can withstands high short-circuit current and inductive
current. At the same time it has the ability to switch inductive current
that it accords with type B standard of GB1985. After adding arcing
contact, it has the ability to switch inductive current that it accord with
electric power standard of DL/T486.
Arcing contact

GB1985 type B Electromagnetism inductive current 80A/2kV


Static inductive Current 3A/12kV
DL/T486 type B Electromagnetism inductive current 160A/15kV
Static inductive Current 10A/15Kv

=All the position of rotated friction adopts stainless steel pin,self


lubricating bearings and stainless steel joint bearings. All ferrous metal
spare parts ( including above M10 fastener) are treated with hot dip
galvanized.
Stainless steel pin Stainless steel joint bearing

Polytetrafluoroethylene Composite self Supramoly


shaft liner lubricating shaft liner shaft liner

=Connecting rod takes type of assembly , so which is not cutted and


welded. Connecting rod that it adopts seamless steel tubes is treated
with hot dip galvanized.

=Cabinet of operating mechanism which rivet with stainless steel Type SRCS1 manual
plates, do not weld. So it has a well appearance. Manual mechanism operating mechanism
makes use of auxiliary relay in it to achieve electromagnetic lock
function , so interlocking is very stable. The structure overcomes
rustiness and failure function of electromagnetic lock in china.

Auxiliary relay of
AMERICA

Coordinating Installation drawing of Type of JW10-252(G) Outdoor AC High Voltage earthing switch

61 62

Anda mungkin juga menyukai