Anda di halaman 1dari 8

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8

Available online at www.sciencedirect.com

ScienceDirect
w w w . i i fi i r . o r g

journal homepage: www.elsevier.com/locate/ijrefrig

Experimental analysis of a novel cooling system


driven by liquid refrigerant pump and vapor
compressor

Gang Yan a,*, Yongbin Feng b, Leqin Peng a


a
Department of Refrigeration & Cryogenic Engineering, School of Energy and Power Engineering, Xi'an Jiaotong
University, Xi'an 710049, China
b
Hanjia Design Group CO., LTD, Xi'an Branch, Xi'an 710075, China

article info abstract

Article history: This study introduced a novel energy saving cooling system, i.e. a combined cycle coupled
Received 1 August 2014 with a traditional vapor compression cycle with a pumped liquid two-phase cooling cycle.
Received in revised form The system has two operation modes, i.e. the compression cycle mode driven by
18 September 2014 compressor and the pump cycle mode driven by refrigerant pump. A multi-purpose test
Accepted 28 September 2014 bench was constructed to experimentally evaluate the performance of the integrated cycle
Available online 7 October 2014 system under various operation conditions. The effects of cycle working condition and the
shift temperature between the two operation modes on the overall cycle performance were
Keywords: investigated in detail. It is found that the novel cycle system has a higher EER compared to
Data center the traditional compressor system when the ambient temperature is relatively low. The
Liquid refrigerant pump further experimental results and comparative annual energy saving analysis also indicated
Cooling that the proper shift temperature is about 5  C from the system EER and cooling capacity
EER point of view.
Shift temperature © 2014 Elsevier Ltd and IIR. All rights reserved.
R22

Analyse expe  rimentale d'un nouveau syste  me de


refroidissement fonctionnant gra^ ce a
 une pompe a frigorige
 ne
 un compresseur de vapeur
liquide et a
Mots cles : Centre de donne
es ; Pompe a
 frigorige
ne liquide ; Refroidissement ; Coefficient d'efficacite
energe 
tique ; Ecart de temperature ;
R22

* Corresponding author. Tel.: þ86 29 82668738; fax: þ86 29 82668725.


E-mail address: gyan@mail.xjtu.edu.cn (G. Yan).
http://dx.doi.org/10.1016/j.ijrefrig.2014.09.017
0140-7007/© 2014 Elsevier Ltd and IIR. All rights reserved.
12 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8

Nomenclature EER energy efficiency rate [-]


ho,ref refrigerant-side outlet enthalpy [kJ$kg1]
Qe,air air-side cooling capacity [kW]
hi,ref refrigerant-side inlet enthalpy [kJ$kg1]
Qe,ref refrigerant-side cooling capacity [kW]
ho,air air-side outlet enthalpy [kJ$kg1]
Qsen sensible cooling capacity [kW]
hi,air air-side inlet enthalpy [kJ$kg1]
Qcomp cooling capacity of the compression cycle mode
E energy consumption [kW$h]
[kW]
Qpump cooling capacity of the pump cycle mode [kW] Subscripts
T Temperature [ C] ref refrigerant
Ta ambient air temperature [ C] sen sensible
m_ ref refrigerant mass flow rate [kg$h1] comp compressor
m_ air air mass flow rate [kg$h1] e evaporator
Wevap evaporator fan input power [kW] a ambient air
Wcond condenser fan input power [kW] i inlet
Wpump pump input power [kW] o outlet
Wcomp compressor input power [kW] evap evaporator
SHR sensible heat rate [-] cond condenser
xe,o outlet vapor quality of evaporator [-]
Dp pressure drop [kPa]

1. Introduction experimentally evaluated a pumped liquid multiphase cool-


ing system (PLMC) to cool microprocessors (such as com-
Data centers are computer infrastructure facilities in which a puters, telecommunications, and phased array radar systems)
large number of enterprise servers, server communication and Rack-based system in data centers. They emphasized the
equipment, and cooling power equipment are contained. significant benefits of performance, cost, size, weight and
Along with the rapid development of electronics and the reliability that can be provided with the PLMC solution as
advent of cloud computing, the number of data centers is compared with existing active air cooling or simple liquid-
increased dramatically, which requires a huge amount of loop systems. They also recommended that the PLMC can be
electrical power for their normal operation. However, this has applied to military, commercial and industrial systems due to
a noticeable impact on the energy consumption and carbon its excellent thermal management capabilities. Chanwoo
footprint due to the size and number of data centers. Ac- et al. (Park et al., 2007; Crepinsek and Park, 2012) presented an
cording to an Environmental Protection Agency (EPA) report advanced Hybrid Two-Phase Loop (HTPL) technology which
on energy efficiency in data centers, the energy consumption integrated active mechanical pumping with passive capillary
of data centers in the United States was more than 100 billion pumping for electronics thermal management. The experi-
kWh by 2011, which represents an annual energy cost of mental results indicated that the hybrid loops with multi-
approximately $7.4 billion (Brown, 2008). The report empha- evaporators were able to remove high heat fluxes and the
sized that there are opportunities for data centers to improve total heat inputs govern the system temperature and pres-
their efficiencies - both on the facility and server sides of the sures. A shortcoming of the multi-evaporators loop is that
data center infrastructure. each evaporator line needs to be identical or controlled by a
The most widely used cooling strategies in computer room valve. Although there are many limitations about the tradi-
air conditioners (CRAC) is refrigerated air cooling due to its tional cooling strategies in CRAC as mentioned above, it has
high reliability, and low initial and maintenance costs. How- still attracted more attention (Mongia et al., 2006;
ever, it has several major disadvantages. One is the by-pass air Trutassanawin et al., 2006; Zhou et al., 2010). All studies
flow in the racks of servers in data centers and it cannot selected lower pressure refrigerant R134a or R600a as the
effectively participate in the cooling process of servers. working fluids and mini-compressor to drive the working fluid
Furthermore, the working liquid driven by a compressor has for the small-scale refrigeration system. Active two-phase
to be lifted to a higher condensing temperature to ensure the cooling system such as evaporative spray cooling (Glassman
safe and stable operation of the compressor at a lower outside et al., 2004; Lin et al., 2006; Silk et al., 2008; Mudawar et al.,
ambient temperature, which means a significantly amount of 2009) has been extensively investigated over the past several
energy will be consumed. The poor energetic performance of years due to advantages, such as high heat flux performance
traditional cooling strategies motivates thermal designers to and robust operation. However, it requires complex fluid
search for green thermal solutions for higher performance control due to two-phase mixed flow and flooded boiling in
servers while providing the possibility to revise the tradition the system. Ohadi et al. (2012) compared the cooling perfor-
cooling cycle to improve the overall performance. mance of electronics in data centers by using air, liquid and
Due to the performance limits of conventional cooling two-phase on-chip cooling. Advantages and disadvantages of
technologies in both military, commercial electronics and various methods were also discussed. It was concluded that
electro-optical systems, Hannemann et al. (2004) air cooling may remain a very attractive solution for locations
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8 13

where a cool air climate is available during most of the year, the vapor compressor cycle system. Such a novel cycle system
and two-phase cooling reduced thermal resistance as much as may be more effective for improving energy efficiency and
an order of magnitude less than that of air and significantly cost saving of data centers. The performance of the novel
below that of liquid cooling. Additionally, the thermal resis- cooling system driven by liquid refrigerant pump and
tance of the two-phase cooling by the force-fed manifold compressor in data centers is experimentally evaluated.
microchannels is 20 times lower than that of the liquid cooling
at 5 times lower pumping power consumption. The phase
change cooling systems will have significant competitive
advantage over conventional systems due to the lower costs 2. Experimental setup
and energy savings. Marcinichen et al. (2010, 2012) and Wu
et al. (2013) proposed three two-phase cooling cycles for Fig. 1 illustrates the integrated cooling cycle driven by a liquid
cooling data center servers and the cycles using two-phase refrigerant pump and a vapor compressor and it can be
boiling in microchannels for removing the heat from the mi- operated in two different operation modes by means of the
croprocessors and memories. The results showed that the solenoid valves (SVs) 1 to 4. The choice of the system opera-
pumping power consumption is on the order of 5 times higher tion mode depends on the cooling demand and ambient air
for the water-cooled cycle when considering the potential temperature. When the ambient air temperature is low, the
saving by implementing on-chip cooling with waste heat re- system is shifted to the pump operation mode by means of
covery. The results also showed that, when compared with opening the SVs 1 and 3, and shutting off SVs 2 and 4. In the
the traditional air-cooling systems, the energy consumption liquid pump operation cycle, a feed custom gear pump with
of the data center could be reduced by 50% when using a liquid constant speed compresses the working fluid from the satu-
pumping cycle and by 41% when using a vapor compression rated liquid state at the receiver to a subcooled liquid state at
cycle. Further investigation indicated that a PI structure and pump outlet (process 5e6). Subsequently, the subcooled fluids
simple SISO and SIMO strategies were sufficient to fulfill the absorb the data center heat in the evaporator and then change
requirements. to a saturated or superheat vapor state (process 8e1). The high
However, previous studies of two-phase cooling in data pressure and temperature vapor enters the connected pipe
centers mainly focused on the application in a microchannels between the evaporator and condenser, and then down to a
evaporator for removing the heat of on-chip cooling. In a lower pressure and temperature (process 1e2e3). Lastly, the
pump liquid two-phase cycle, the potential of energy saving heat will be rejected to the ambient in the condenser where
with lower input power feature has been already exploited, working fluid changes from the superheat state to the liquid
where it is the basis of improved cycle performance. In fact, state at the inlet of the receiver (process 3e4). The major
the two-phase cooling can be used to modify the existing function of the check valves (CVs) 1 to3 in the loop diagram is
tradition air-cooled systems in data centers considering the to ensure the proper flow direction of working fluids in
energy and cost savings, i.e. obtaining a higher system per- different operation modes. When designing a pumping sys-
formance with a lower pump input power during lower tem, it is important to prevent the phenomenon of cavitation.
ambient temperatures. For this purpose, this paper presents a Cavitation occurs when bubbles form in the liquid at the
novel hybrid cooling cycle coupled with liquid refrigerant pump inlet. In order to make the liquid pump work stable and
pump cycle and vapor compressor cycle to be used in data avoid cavitation, the 6 L receiver is lifted up to 1.5 m higher
centers. Based on existing vapor compressor cycle, a liquid than the liquid pump. The liquid refrigerant pump cycle is
refrigerant pump associated with a receiver is introduced into characterized with low condensing temperature and high

Fig. 1 e Schematic diagram of the proposed cooling cycle.


14 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8

Table 1 e Evaporator geometric parameters.


Geometric parameters Values Geometric parameters Values
Number of tube rows in air direction 4 Inner tube diameter/mm 8.85
Number of tube rows perpendicular to air direction 24 Fin thickness/mm 0.12
Transverse tube spacing/mm 25.4 Fins per inch 14
Longitudinal tube spacing/mm 22.0 Fin type Louver
Outer tube diameter/mm 9.52 Circuitry number 4

overall efficiency. This is a good operation option during the as indicated in Fig. 1. The flow rate of the working fluid was
winter season. measured using a turbine-type flow meter with an accuracy
When the ambient temperature is high, the system is of ±0.5%. One sight glass was installed downstream of the
shifted to the compressor operation mode by means of Micro Motion mass flow meter to identify the case of two-
opening SVs 2 and 4 and shutting off SVs 1 and 3. In the phase flow. The electric power output of the generator (i.e.
compressor operation cycle, a VR30KM-TFP type compressor fan, pump and compressor) was measured using a power
compresses the working fluid from the superheat state at the analyzer made by WT230, with an accuracy of ±0.02%. The
outlet of evaporator to a high temperature and pressure state air-side cooling capacity can be achieved based on data of
at the compressor outlet (process 1e2). Subsequently, the heat the airflow rate and different sensors. A steady state was
will be rejected to the ambient in the condenser where the maintained for 30 min in psychrometric lab to gather data in
working fluid passes from the superheat state to the saturate each test. During the operation, the thermodynamic prop-
state at the inlet of the receiver (process 3e4). Finally, the erties of the working fluids in cycle were calculated by
saturated or subcooled state liquid refrigerant is expanded REFPROP (Lemmon et al., 2007) using measured tempera-
through thermal expansion valve into the evaporator at a tures and pressures values. All the measurement data was
lower evaporation pressure to cool the data center (process 6- recorded and stored on a computer by using a HP 75000 se-
7-8e1). This cycle is characterized by a high condensing ries data acquisition system. For steady state performance
temperature and a medium overall efficiency when compared tests, the sampling interval was 10 s.
with the liquid refrigerant pump cycle. This is a good opera- The refrigerant enthalpy was determined by the local
tion option when the ambient temperature is high, typically pressure and temperature measurement except the two-
during the summer season. phase mixture state. The air enthalpy was determined by
During the experimental test, a 7 kW fin-tube evaporator the measured dry bulb temperature and wet bulb temperature
was designed to transfer the heat generated by the servers to at the corresponding location.
the refrigerant. The evaporator used is a cross-flow heat The refrigerant-side cooling capacity is calculated as:
exchanger and is composed of four circuits. Each circuit has a  
single inlet and outlet. The coil geometry used is summarized Qe;ref ¼ m_ ref ho;ref  hi;ref (1)
in Table 1. The condenser used is a cross-flow fin-tube heat where hi,ref is determined by the pressure and temperature
exchanger with two rows and two circuits, and each circuit ahead of the expansion device. ho,ref is determined by the
has a single inlet and outlet. pressure and temperature leaving the evaporator. It should be
Experiments were conducted in a standard psychromet- noted that the refrigerant-side cooling capacity cannot be
ric chambers with two insulated rooms to evaluate the determined when two-phase flow occurs at the exit of an
performance of the designed cycle under a range of oper- evaporator.
ating conditions. The temperature and humidity were The air-side total cooling capacity is calculated as:
independently controlled within each room to the desired  
operation conditions. The evaporator air stream was con- Qe;air ¼ m_ air ho;air  hi;air (2)
nected to an ASHRAE standard air measurement box to yield
where hi,air and ho,air are determined using the measured inlet
a measurement of the air flow rate and the evaporator air
and outlet air dry bulb and wet bulb temperature of the
flow rate was altered by a variable speed blower inside the
evaporator, respectively.
box. Two pressure transducers are used to measure the
The air-side total sensible cooling capacity is calculated as:
pressure drop across the nozzle and the pressure at the
 
nozzle inlet, respectively. Three 1000U platinum TEP series Qsen ¼ m_ air ti;air  to;air (3)
probes RTDs measure the air temperature near the inlet of
where ti,air and to,air are determined using the measured inlet
the nozzles. All temperature measurements were Type T
and outlet air dry bulb temperatures of the evaporator,
copper-constantan thermocouples, which were calibrated
respectively.
using an ice bath and boiling water to make sure the read-
Energy efficiency ratio is given as.
ings were within 0.3  C of the known values. Low pressure
transducers and high pressure transducers were installed in 
the refrigerant flow line to measure the refrigerant pres- I For compressor operation mode :
sures of the interested state points with an accuracy of (4)
Qe;air
±0.25% over the full scale range. The refrigerant tempera- EER ¼
Wcomp þ Wevap þ Wcond
tures and pressures were measured at the locations of the
inlet and outlet of each component throughout the system,
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8 15

Fig. 2 e Effect of ambient air temperature on overall system Fig. 3 e Effect of ambient air temperature on overall system
SHR and sensible capacity with the pump cycle mode. capacity with different cycle modes.

Fig. 2 shows the sensible cooling capacity and sensible heat


  Qe;air ratio (SHR) varied with the ambient air temperature in the
II For pump operation mode : EER ¼ pump cycle mode. The sensible heat ratio is the sensible
Wpump þ Wevap þ Wcond
cooling capacity divided by the total cooling capacity. The
(5)
sensible heat ratio is given as:
The quality of the experimental results was determined by
estimating the uncertainty of the test results. The un- Qsen
SHR ¼ (7)
certainties were calculated for cooling capacity and EER, given Q
by Equation (6). It can be seen that the sensible cooling capacity increases
vffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi rapidly with the decrease of ambient air temperature. How-
u  2
uX vY ever, the sensible heat ratio of the novel system decreased
UY ¼ t U2X (6)
i
vXi along with the decreased ambient air temperature in the
pump cycle mode. The sensible cooling capacity was 2.74 kW
where Xi and Y represent measured and calculated variables, when the ambient air temperature is 10  C, which is lower 51%
respectively. UX and UY are the measured and calculated un- than that of the compression cycle mode as indicated in Fig. 3.
certainties, respectively (Kline and McClintock, 1953). The total cooling capacity and the sensible cooling capacity of
The uncertainties of the dependent variables can be the novel system were 94% and 90% respectively, as compared
determined with the partial derivatives and independent with the compression cycle mode when the ambient air
uncertainties. The uncertainties of the dependent variables temperature is 5  C. Meanwhile, the system SHR was 76.63%.
air-side cooling capacity and EER in a steady-state test of the For a typical data center room, the cooling load decreased with
7 kW R22 unit are 5.38% and 6.49%, respectively. The data of the decrease of the ambient air temperature due to larger
the other steady-state tests have similar uncertainties.

3. Results and discussion

In data centers, the cooling capacity plays an essential role to


provide a proper working environment for servers. In order to
highlight the general characteristics of the novel cooling sys-
tem driven by liquid refrigerant pump and vapor compressor,
and better understand the effect of the ambient temperature
on the evaporator cooling capacity, a number of capacity tests
were conducted under a typical data center working condi-
tion. The working conditions used in the test are as below.

▪ The psychrometric indoor dry bubble temperature set as


23  C.
▪ Air inlet wet bubble temperature is 17  C, and outdoor Fig. 4 e Effect of ambient air temperature on the
ambient air temperature is from-20  C to 10  C. evaporating temperature, condensing temperature and the
▪ Working fluid used is R22. outlet quality of evaporator in the pump cycle mode.
16 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8

temperature difference between the ambient environment


and indoor room. Therefore, the novel system can nearly
reach the same level cooling capacity when compared with
the traditional compressor system.
Fig. 4 shows the effect of ambient air temperature on the
evaporating temperature, condensing temperature and the
outlet quality of evaporator in the pump cycle mode. The
evaporating temperature and condensing temperature are
corresponding to the saturation temperatures of the
measured pressure at the outlet of the evaporator and
condenser. As can be seen clearly, the evaporating tempera-
ture and condensing temperature of the novel system in the
pump operation mode decreased with the decrease of the
ambient air temperature. The evaporating and condensing
temperature were 6.73  C and 0.94  C, respectively, when the
ambient air temperature is 5  C. It can be concluded that the
condensing pressure is more sensitive to ambient air tem-
perature compared with the evaporating pressure. A higher Fig. 6 e Effect of ambient air temperature on the overall
cooling capacity can be obtained with the decrease of the system EER with different cycle modes.
ambient temperature decreased. However, it might happen
that the evaporator temperature will reach the freezing point
if no control strategy is adopted. Therefore, a condenser fan Fig. 5 shows the overall pressure drop of the pump cycle
speed control strategy is needed for the lower temperature mode decreased when the ambient air temperature varied
region but it not considered in the present study. The liquid from 20 Cto 10  C. This is because the decrease of the
refrigerant pump cycle is characterized with low condensing ambient temperature greatly affects the refrigerant thermal
temperature compared with the traditional compressor cycle. dynamic parameter (outlet quality of evaporator as seen in
The outlet vapor quality of the evaporator was calculated Fig. 4) and fluid viscosity, resulting in larger refrigerant pres-
considering equations 8e10: sure drops. For example, the percentage of the pressure drop
  for the evaporator and pipe play a significant role to the total
xe;o ¼ f he;o ; pe;o (8) pressure drop and their contributions are 35% and 45% when
the ambient air temperature is -5 C, respectively. Therefore,
Qe this means a larger connection pipe between the condenser
he;o ¼ þ he;i (9)
m_ and evaporator can decrease the system pressure drop and
  improve the cycle performance for the novel system.
he;i ¼ f pe;i ; Te;i (10) It is known that the performance of the refrigerant cycle
system always plays a significant role in influencing the en-
where xe,o,he,o are determined from Refprop software ergy consumption. As mentioned before, the novel cycle sys-
(Lemmon et al., 2007). In general, the outlet vapor quality of tem has two operation modes dependent on the ambient air
evaporator is increased along with the decreased ambient air temperature and cooling load demand. The cycle will shift to
temperature. the compression cycle mode when the ambient air

Fig. 5 e Effect of ambient air temperature on the refrigerant


side pressure drop of the overall components in the pump Fig. 7 e Effect of ambient air temperature on the overall
cycle mode. input power with different cycle modes.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8 17

temperature is higher due to the lower cooling capacity of the


pump cycle mode as indicated in Fig. 3. This compression
cycle mode commonly happens in the summer season. Along
with the decreased ambient temperature, however, the cool-
ing capacity of the pump cycle mode is increased. Thus, the
novel cycle system should be shifted to the pump cycle mode,
which commonly happens in the winter season. In this case,
there is as proper shift temperature while the two cycle modes
are shifted to each other. Figs. 6 and 7 show the overall EER
and input power of the novel system operated in the pump
cycle mode and compression cycle mode, respectively. It can
be clearly seen that the novel cycle system has a higher EER
compared with the compression cycle system when the
ambient temperature is below 7 C, which is due to the lower
input power of the pump cycle mode compared with the
compression cycle mode. The overall EER for the novel system
and compression cycle is 6.84 and 3.46, respectively, when the
ambient air temperature is 5  C. Meanwhile, the total input Fig. 9 e Effect of shift temperature on the overall system
power for the pump cycle mode is just about 50% of the energy saving with the novel hybrid cycle.
compression cycle mode. Therefore, the novel system has
better performance when compared with the traditional considering the pump cycle mode of the novel system in the
compression cycle during the lower ambient conditions. This winter season. Using the Bin method the total annual energy
means that the novel system can provide significant energy saving of the novel system can be determined using equation
savings and it also provides an alternative method to improve (11) (Liu, 1993).
the existed traditional compressor system. The experimental
Xn Xm  
results also indicated that the proper shift temperature is Esave;tot ¼ i¼1 j¼1
Eprei;j  Eposti;j (11)
about 5  C in terms of the system EER and cooling capacity.
The calculation of energy savings is an important step in where Eprei,j is the bin mode predicted hourly electricity use
the validation of the benefits of the novel system. The annual during hour (j) of day (i) in the novel hybrid cooling cycle. i is
energy saving was calculated based on the measured data the distinct day type varying from i ¼ 1 to i ¼ 365 and j is 1e24 h
using the bin method. Three typical places were selected in each day. Eposti,j is the bin mode predicted hourly electricity
during the energy saving analysis process and the bin hour use during hour (j) of day (i) in the traditional compression
distribution under different ambient temperatures is dis- cycle.
played in Fig. 8, which were generated by using EnergyPlus. It Fig. 9 shows the results of the overall system energy saving
can be seen clearly that the annual Bin hours in the low of the novel system compared with the traditional compres-
temperature region of Minneapolis is higher than that of sion cycle. It can be concluded that higher percentage of the
Washington and Atlantic. In the following analysis, the sen- lower ambient temperature is, the more energy can be saved.
sible cooling capacity is considered for both the novel hybrid There is a maximum energy saving point when the ambient
system and the traditional compressor system. The ambient air temperature is about 5  C. After the optimal shift ambient
air temperature kept in a range of 30  C to 10  C when temperature, the novel system in the pump cycle mode loses
its advantage compared with the compression cycle from the
overall energy saving point of view. The proper shift temper-
ature for the novel system is about 5  C while considering the
cooling capacity, overall EER and annual overall energy saving
simultaneously. When the shift temperature is 5  C, the
annual energy saving can reach to 1500 kW h. It provides an
alternative approach to modifying the traditional air-cooled
compressor systems by combining with a liquid pump cycle.
The novel hybrid system can be shifted to the compression
cycle mode when the ambient temperature is higher than
5  C, and turn to the pump cycle mode when the ambient
temperature is below 5  C.

4. Conclusion

A novel energy saving cooling system driven by a liquid


refrigerant pump and vapor compressor with R22 was pro-
Fig. 8 e Percentage of Bin hours' distribution under posed for the data centers. The system has two operation
different ambient temperatures. modes, i.e. one is the compression cycle mode driven by a
18 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 4 9 ( 2 0 1 5 ) 1 1 e1 8

compressor when the ambient temperature is high and the EngineeringCongress and Exposition, Anaheim, CA, USA.
other is the pump cycle mode driven by the liquid refrigerant Paper 60669.
pump when the ambient temperature is low. Based on the Kline, S.J., McClintock, F.A., 1953. Describing uncertainties in
single-sample experiments. Mech. Eng. 75, 3e8.
multi-purpose test bench, the performance of the novel
Lemmon, E.W., Huber, M.L., McLinden, M.O., 2007. NIST Standard
hybrid cooling system was experimentally evaluated under Reference Database 23: Reference Fluid Thermaldynamic and
various operation conditions and compared with the tradi- Transport Properties-REFPROP, Version 8.0. National Institute
tional compression cycle systems. The effects of the cycle of Standard and Technology. Standard Reference Data
working condition and shift temperature on the overall cycle Program.
performance were investigated. The annual overall energy Lin, L.C., Ponnappan, R., Yerkes, K., 2006. Actively pumped two-
saving was analyzed using Bin hours method based on the phase loop for spray cooling. J. Thermophy. heat Transf. 20,
107e110.
experimental test data. The results showed that the novel
Liu, Y., 1993. Measuring Retrofit Savings in Commercial Buildings
system has a higher energy efficiency ratio as compared to the with Pre-retrofit Utility Billing Data and Post-retrofit Sub-
traditional compressor system when the ambient tempera- metered Data. M.S. Thesis, Energy Systems Laboratory Report,
ture is lower due to the lower input power. The input power no. ESL-TH-93/12-04. Texas A&M University.
the novel system can be decreased by 50% when compared to Marcinichen, J.B., Thome, J.R., Michel, B., 2010. Cooling of
that of the compressor system. The experimental results also microprocessors with micro-evaporation: a novel two-phase
cooling cycle. Int. J. Refrigeration 33, 1264e1276.
indicated that the proposed novel system can obtain nearly
Marcinichen, J.B., Olivier, J.A., Thom, J.R., 2012. On-chip two-
the same cooling capacity as that of the traditional
phase cooling of datacenters: cooling system and energy
compressor system when the ambient air temperature is recovery evaluation. Appl. Therm. Eng. 41, 36e51.
5  C. The pressure drop of the connected pipe between the Mongia, R., Masahiro, K., DiStefano, E., et al., 2006. Small Scale
evaporator and condenser has a significant impact on to the Refrigeration System for Electronics Cooling within a
total system pressure drop due to the two-phase region under Notebook Computer. ITHERM, San Diego, CA.
the working conditions. The novel system EER is higher than Mudawar, I., Bharathan, D., Kelly, K., et al., 2009. Two-phase spray
cooling of hybrid vehicle electronics. IEEE Trans. Components
that of the compressor cycle when the ambient temperature is
Packag. Technol. 32, 501e512.
below 7  C. The comparative annual energy saving analysis Ohadi, M.M., Dessiatoun, S.V., Choo, K., et al., 2012. A comparison
showed that the lower annual bin temperature is, more en- analysis of air, liquid, and two phases cooling of data centers.
ergy will be saved. The proper shift temperature is about 5  C In: 28th IEEE SEMI-THERM Symposium. IEEE, pp. 58e63.
from the system EER, cooling capacity and annual overall Park, Chanwoo, Vallury, Aparna, Zuo, John, et al., 2007.
energy saving point of view. Overall, this study shows the Electronics thermal management using advanced hibrid two-
proposed novel cycle could provide a way to modify the phase loop technology. In: ASME-JSME Thermal Engineering
Summer Heat Transfer Conference, July 8e12, Vancouver,
traditional air-cooled compressor system and show strong
British Columbia, Canada. HT2007-321962.
energy saving potential for its application in green data Silk, E.A., Golliher, E.L., Selvam, R.P., 2008. Spray cooling heat
centers. transfer: technology overview and assessment of future
challenges for micro-gravity application. Energy Cover.
Manag. 49, 453e468.
references Trutassanawin, S., Groll, E.A., Garimella, S.V., et al., 2006.
Experimental investigation of a miniature-scale refrigeration
system for electronics cooling. IEEE Transact. Components
Brown, R., 2008. Report to Congress on Server and Data Center Packag. Technol. 29 (3), 267e687.
Energy Efficiency Public Law 109-431. U.S. Lawrence Berkeley Wu, D., Marcinichen, J.B., Thome, J.R., 2013. Experimental
National Laboratory. evaluation of a controlled hybrid two-phase multi-
Crepinsek, Michael, Park, Chanwoo, 2012. Experimental analysis microchannel cooling and heat recovery system driven by
of pump-assisted and capillary-driven dual-evaporators two- liquid pump and vapor compressor. Int. J. Refrigeration 36,
phase cooling loop. Appl. Therm. Eng. 38, 133e142. 375e385.
Glassman, B., Kuravi, S., Du, J., et al., 2004. A fluid management Zhou, R., Zhang, T., Catano, J., Tong, T., Chang, J., Prasher, R.,
system for a multiple nozzle array spray cooler. In: 37th AIAA Jensen, M.K., 2010. The steady-state modeling and
Thermo-physics Conference, Portland, Oregon, 2004-2574. optimization of a refrigeration system for high heat flux
Hannemann, R., Marsala, J., Pitasi, M., 2004. Pumped liquid removal. Appl. Therm. Eng. 30 (16), 2347e2356.
multiphase cooling. In: IMECEe Int. Mechanical

Anda mungkin juga menyukai