Preface
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means the death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means the light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and
to resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
l Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
l Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
l Earth
l Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
l Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
l External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
l Connection cable
Copyright
Version: CZX-22R V1.05_050743 NANJING NARI-RELAYS ELECTRIC CO., LTD.
Manual: V1.05 99 Shengtai Rd. Jiangning, Nanjing 211100,China
P/N: EN_CZXL0104.0234.1101 Tel: 86-25-52127776, Fax: 86-25-52127841
Website: www.nari-relays.com
Copyright © NR 2006. All rights reserved Email: international@nari-relays.com
Table of Contents
Preface .............................................................................................................................................. i
Table of Contents........................................................................................................................... iii
Chapter 1 Introduction............................................................................................................... 1
1.1 Application............................................................................................................................. 1
1.2 Features ................................................................................................................................. 1
1.3 Ordering Options .................................................................................................................. 1
Chapter 2 Technical Data ........................................................................................................... 3
Chapter 3 Operation Theory...................................................................................................... 5
3.1 Schemetic Digrams............................................................................................................... 5
3.1.1 Auto-Reclosing and Manual Closing Circuit ............................................................... 5
3.1.2 Phase-Segregated Closing Circuit ............................................................................. 6
3.1.3 Phase-Segregated Trip Circuit, Group 1 .................................................................... 7
3.1.4 Phase-segregated Trip Circuit, Group 2..................................................................... 8
3.1.5 Trip and Auto-reclosing Target Circuit......................................................................... 9
3.1.6 Low Pressure Blocking Circuit.................................................................................. 10
3.1.7 Output Contacts ........................................................................................................ 11
3.2 Power Supply ...................................................................................................................... 12
3.2.1 Power Supply and Its Supervision............................................................................ 12
3.2.2 Swichover on Power Supply..................................................................................... 12
3.3 Closing Circuits................................................................................................................... 13
3.3.1 Auto-reclosing Circuit................................................................................................ 13
3.3.2 Manual and Remote Closing Circuit......................................................................... 13
3.3.3 Phase-Segregated Closing Circuit ........................................................................... 13
3.4 Trip Circuit ........................................................................................................................... 14
3.4.1 Manual and Remote Trip .......................................................................................... 14
3.4.2 Three Phase Trip Signal Inputs from Protection....................................................... 14
3.4.3 Phase-Segregated Trip Circuit 1 .............................................................................. 15
3.4.4 Phase-Segregated Trip Circuit 2 .............................................................................. 16
3.5 KKJ ....................................................................................................................................... 17
3.6 Pressure Supervision ......................................................................................................... 17
3.6.1 Low Pressure to Inhibit Trip ...................................................................................... 18
3.6.2 Low Pressure to Inhibit Auto-reclosing ..................................................................... 18
3.6.3 Low Pressure to Inhibit Closing ................................................................................ 18
3.6.4 Low Pressure to Inhibit Switching............................................................................. 19
3.7 Pole Disagreement.............................................................................................................. 19
3.8 Control Circuit Failure Alarm............................................................................................. 19
3.9 Spare Relays........................................................................................................................ 19
Chapter 4 Hardware................................................................................................................ 21
4.1 Modules................................................................................................................................ 21
4.2 Mechanical Layout.............................................................................................................. 21
4.3 Front View ............................................................................................................................ 22
4.4 Terminals.............................................................................................................................. 22
Chapter 5 Settings.................................................................................................................... 25
Chapter 6 Human-Machine Interface ...................................................................................... 27
Chapter 7 Commissioning and Maintenance ........................................................................ 29
7.1 Visual Inspection................................................................................................................. 29
7.2 Storage ................................................................................................................................. 29
7.3 Installation ........................................................................................................................... 29
7.4 Commissioning Test........................................................................................................... 30
7.4.1 Visual Inspection....................................................................................................... 30
7.4.2 Choices ..................................................................................................................... 30
7.4.3 Electrical tests........................................................................................................... 30
7.5 Maintenance ........................................................................................................................ 30
Chapter 1 Introduction
1.1 Application
CZX-22R interposing relay set provides auxiliary relays for switching of circuit breaker with two
group phase-segregated trip coils and one group phase-segregated close coils. Protection,
control and other relevant equipments can trip or close circuit breaker via this relay set.
1.2 Features
The equipment is an IEC standard 4U high and 19” wide rack with modular structure. It uses an
integral faceplate and plug terminal blocks on rear panel for external connections. It has features
of compact design, high security, flexibility and convenience.
Sealed relays with high impedance and low power dissipation are used in this relay set. As a
result, the power dissipation and heating is reduced largely, moisture proof is improved, ensuring
a long life even in extreme mechanical and ambient conditions.
Seal-in current of trip and close circuit can be configured easily by jumpers on site according to
the rated current of trip and close coil.
A special relay is equipped in the relay set, which will pick up and latch when circuit breaker is
closed manually, and reset when circuit breaker is tripped manually. The contacts of this special
relay can be used by substation automation system to issue an accident signal whenever the
circuit breaker is tripped un-manually. Moreover, together with normal closed auxiliary contact of
circuit breaker (52b), the contacts of this special relay can also be used to initiate auto-reclosure in
case that circuit breaker trips especially without any trip commands from protection and manual
switch.
Terminals
Auxiliary Voltage and Binary I/O Soldering plug terminals
Power Supply
Auxiliary Voltage 250V, 220 V, 125V, 110 V,
Operating Range -20%, +15%
Per IEC60255-11, tolerable ac triple of up to 5%
Nominal Burden 25W
Power Supply Interruption Per IEC60255-11, 20ms without de-energizing
Performance
Seal-in Current of Trip & Closing Circuit 0.5A-4.0A (Configurable with a step of 0.5A)
Drop out Delay of Manual Closing Relay (21SHJ, 22SHJ, 23SHJ):
>0.4s
Drop out Delay of Low Pressure Blocking Relay for Auto-Reclosing (21YJJ, 22YJJ):
>0.3s
Drop out Delay of Low Pressure Blocking Relay for closing (3YJJ):
>0.3s
Pulse Width of Trip Relay 11BJ, 12BJ, 21BJ, 22BJ:
≈0.3S
Power Supply Burden: <25W
Pickup Voltage of Relay 55%-65% nominal voltage
Environmental Conditions
Normal Operation -10 ℃ ~ +40 ℃
Extreme Range -10 ℃ ~ +55 ℃
Storage and Transport -25 ℃ ~ +70 ℃
Ambient Humidity: Up to 95% without condensing.
Insulation
Insulation resistance >100MΩ,500V, IEC 60255-5:2000
Dielectric Strength
Between independent circuits: 2000 VAC, 1 min
Between independent circuits and ground: 2000 VAC, 1 min.
Between terminals of an open contact: 1200 VAC, 1min
Impulse: 5 kV, 1.2/50 μs, 0.5J
Mechanical Robustness
Vibration Test Per IEC 60255-21-1:1988
Response Class I
Endurance Class I
Shock and Bump Test Per IEC 60255-21-2:1988
Shock response Class I
Shock withstand Class I
Bump Class I
low pressure,
block trip
low pressure
block auto-
reclosing
low pressure
block closing
low pressure
block
switching
Post-closing position
spare
pole
disagreement
accident
signal
Group1
control circuit
annunciation c ircuit
failure
circuit breaker
open status
Group2
control circuit
a nnunciation circuit
failure
DC failure, group 1
DC failure, group 2
remote signal
trip target
circuit breaker
status
Group2
for pilot protection, auto-reclosing reclaim and initiation, and VT circuit supervision.
Some contacts are used in pole disagreement alarm and circuit failure alarm circuits, please refer
to 3.7, 3.8 and figure 3-8.
3.3.3.8 Circuit Breaker Closed State and Trip Coil Supervision circuit 1
The auxiliary relays 11HWJa, 12HWJa, 13HWJa, 11HWJb, 12HWJb, 13HWJb, 11HWJc, 12HWJc,
13HWJc are applied to supervise the closed state of circuit breaker when terminal n118, n119,
n120 are connected to the negative pole of power supply in series with normal open auxiliary
contact of each phase of circuit breaker (52a). Health of trip coils is monitored at the same time.
In figure 3-8, some contacts are provided as multiplication of 52a. Some contacts are used in pole
disagreement alarm and circuit failure alarm circuits, please refer to 3.7, 3.8 and figure 3-8.
LED 1JGa, 1JGb, 1JGc, which located on the faceplate of the equipment indicate the closed
position and health of trip coil 1 of circuit breaker.
3.3.3.13 Circuit Breaker Closed State and Trip Coil Supervision circuit 2
The auxiliary relays 21HWJa, 22HWJa, 23HWJa, 21HWJb, 22HWJb, 23HWJb, 21HWJc,
22HWJc, 23HWJc are applied to supervise the closed state of circuit breaker when terminal n127,
n128, n129 are connected to the negative pole of power supply in series with normal open
auxiliary contact of each phase of circuit breaker (52a). Health of trip coils is monitored at the
same time.
In figure 3-8, some contacts are provided as multiplication of 52a. Some contacts are used in pole
disagreement alarm and circuit failure alarm circuits, please refer to 3.7, 3.8 and figure 3-8.
LED 2JGa, 2JGb, 2JGc, which located on the faceplate of the equipment indicate the closed
position and health of trip coil 2 of circuit breaker.
3.5 KKJ
Please refer to figure 3-1. KKJ is a bistable auxiliary relay, which is called as “post-closing position
relay”. When circuit breaker is closed manually, the relay KKJ will pick up and latch. When circuit
breaker is tripped manually, the relay KKJ will reset. The contacts of this special relay can be used
by substation automation system to issue an accident signal whenever circuit breaker is tripped
un-manually. Moreover, together with normal closed auxiliary contact of circuit breaker (52b), the
contacts of this special relay can also be used to initiate auto-reclosure in case that circuit breaker
trips especially without any trip commands from protection and manual switch. The contacts of
KKJ are wired at terminal n213-n214 and n211-n212, as shown in figure 3-8.
When the relay 4YJJ picks up, it will release 11YJJ and 12YJJ to block trip. 4YJJ is a low pressure
to block switching (both trip and closing), please refer to 3.6.4 for details.
The normal open contacts of 11YJJ are used in phase-segregated closing circuit and
phase-segregated trip circuit to permit switch of circuit breaker. Please refer to 3-2, 3-3 and 3-4. If
this built-in feature is not used, just shorten the associated normal open contacts of 11YJJ.
Another normal closed contact of 11YJJ is provided via terminal n82-n76 for annunciation shown
in figure 3-8.
Another normal closed contact of 3YJJ is provided via terminal n82-n78 for annunciation shown in
figure 3-8.
Whenever there is a failure in trip coil under closed state or a failure in closing coils under open
state, an alarm will be issued via terminal n72-n74, n75, refer to figure 3-8.
Chapter 4 Hardware
The equipment is an IEC standard 4U high and 19” wide rack with modular structure. It
uses an integral faceplate and plug terminal blocks on rear panel for external connections.
It has features of compact design, high security, flexibility and convenience.
4.1 Modules
There are 14 modules plugged into chassis of CZX-22R from the front side, and then an
integrated faceplate is fastened to cover these modules. From left to right in front view,
these modules are:
308
CZX-22R
INTERPOSING RELAY SET
CZX-22R
INTERPOSING RELAY SET
4.4 Terminals
There are eight 30-pin connectors used as terminals of external connection mounted on
rear plate of the device. From right to left on the rear, they are denoted as connector A to
connector H respectively. For functions of these terminals, please refer to chapter 3.
H G F E D C B A
n211 n181 n151 n121 n91 n61 n31 n1
n212 n182 n152 n122 n92 n62 n32 n2
n213 n183 n153 n123 n93 n63 n33 n3
n214 n184 n154 n124 n94 n64 n34 n4
n215 n185 n155 n125 n95 n65 n35 n5
n216 n186 n156 n126 n96 n66 n36 n6
n217 n187 n157 n127 n97 n67 n37 n7
n218 n188 n158 n128 n98 n68 n38 n8
n219 n189 n159 n129 n99 n69 n39 n9
n220 n190 n160 n130 n100 n70 n40 n10
n221 n191 n161 n131 n101 n71 n41 n11
n222 n192 n162 n132 n102 n72 n42 n12
n223 n193 n163 n133 n103 n73 n43 n13
n224 n194 n164 n134 n104 n74 n44 n14
n225 n195 n165 n135 n105 n75 n45 n15
n226 n196 n166 n136 n106 n76 n46 n16
n227 n197 n167 n137 n107 n77 n47 n17
n228 n198 n168 n138 n108 n78 n48 n18
n229 n199 n169 n139 n109 n79 n49 n19
n230 n200 n170 n140 n110 n80 n50 n20
n231 n201 n171 n141 n111 n81 n51 n21
n232 n202 n172 n142 n112 n82 n52 n22
n233 n203 n173 n143 n113 n83 n53 n23
n234 n204 n174 n144 n114 n84 n54 n24
n235 n205 n175 n145 n115 n85 n55 n25
n236 n206 n176 n146 n116 n86 n56 n26
n237 n207 n177 n147 n117 n87 n57 n27
n238 n208 n178 n148 n118 n88 n58 n28
n239 n209 n179 n149 n119 n89 n59 n29
n240 n210 n180 n150 n120 n90 n60 n30
Chapter 5 Settings
In order to facilitate production and operation, jumpers are used for configurating trip and
closing seal-in current of this device. Schematic diagrams of related circuits are shown as
follows:
Jumpers for trip seal-in current configuration are mounted in modules #4, #5, #6 and #11,
#12, #13; jumpers for closing seal-in current configuration are mounted in modules #8, #9,
#10. Please refer to 4.1.
Note: The seal-in current can be set the same as or slight smaller than the current drawn
by the trip or closing coils when operated.
CAUTION!
The seal-in rating of trip circuit and that of closing circuit may be different. They should be
selected based on the current the trip and closing circuit drawn when operated
respectively.
All the jumpers have been configured according to the ordering information before the
WARNING!
Before removing the front panel to make a configuration the auxiliary supply must be
removed, and wait 5s for capacitors to discharge. It is also strongly recommended that the
trip and closing circuit are isolated.
DESIGNATION FUNCTION
ON: Phase a is closed, and trip coil 1 of phase a is healthy
CB A CLOSE
OFF: Phase a is open, or trip coil 1 of phase a is broken
ON: Phase b is closed, and trip coil 1 of phase b is healthy
CB B CLOSE
OFF: Phase b is open, or trip coil 1 of phase b is broken
ON: Phase c is closed, and trip coil 1 of phase c is healthy
CB C CLOSE
OFF: Phase c is open, or trip coil 1 of phase c is broken
ON: Auto-reclosure has operated to close circuit breaker through
RECLOSE this equipment.
OFF: In normal condition
ON: Protective relay has operated to trip circuit breaker phase a
TRIP A by trip coil 1 through this equipment.
OFF: In normal condition
ON: Protective relay has operated to trip circuit breaker phase b
TRIP B by trip coil 1 through this equipment.
OFF: In normal condition
ON: Protective relay has operated to trip circuit breaker phase c
TRIP C by trip coil 1 through this equipment.
OFF: In normal condition
The “RECLOSE”, “TRIP A”, “TRIP B” and “TRIP C” can be reset, please refer to 3.3.1, 3.4.4.6 and
figure 3-7.
DESIGNATION FUNCTION
ON: Phase a is closed, and trip coil 2 of phase a is healthy
CB A CLOSE
OFF: Phase a is open, or trip coil 2 of phase a is broken
ON: Phase b is closed, and trip coil 2 of phase b is healthy
CB B CLOSE
OFF: Phase b is open, or trip coil 2 of phase b is broken
ON: Phase c is closed, and trip coil 2 of phase c is healthy
CB C CLOSE
OFF: Phase c is open, or trip coil 2 of phase c is broken
ON: Protective relay has operated to trip circuit breaker phase a
TRIP A by trip coil 2 through this equipment.
OFF: In normal condition
ON: Protective relay has operated to trip circuit breaker phase b
TRIP B by trip coil 2 through this equipment.
OFF: In normal condition
ON: Protective relay has operated to trip circuit breaker phase c
TRIP C by trip coil 2 through this equipment.
OFF: In normal condition
The “RECLOSE”, “TRIP A”, “TRIP B” and “TRIP C” can be reset, please refer to 3.4.5.6 and figure
3-7.
7.2 Storage
The device shall be kept in the original package. And a dry, cool and ventilated place is required
during storage.
7.3 Installation
Please refer to 4.2 for the dimensions of this relay set.
For installation on a panel, figure 7-1 gives the cut-out and drilling.
7.4.2 Choices
Make the options according to the application specification, please refer to chapter 4.
7.5 Maintenance
It is recommended that a periodic test program be followed. Given that the intervals between
these tests vary for different types of relays and installations as well as the experience of the user
performing the tests, it is recommended that the relay is tested at least every 3 years.