Anda di halaman 1dari 2

TEST REPORT FOR

BUS PT INDURE PVT LTD

STAR ELECTRICALS
DATE: Page NO:

CLIENT M/S NTPC SHAKTINAGAR


CONTRACTOR M/S INDURE PVT LTD
PROJECT
GENERAL DATA: Location: ASH HANDLING CONVEYING MCC

MAKE UNILEC
RATED VOLTAGE 415 V
RATED FREQUENCY 50 HZ
PHASE 3

Instrument Name Make Model No. Serial NO.


Multimeter Rishab RISH Multi 14S 007305
Primary Injection Kit Shruti Electronics SE/PI/3051
LT Megger Rishab RISHI INSU 10 143950

POTENTIAL TRANSFORMER TEST : PANEL NO. 4F BUS PT-1

1. Name plate details

PHASE R Y B
Sr. No. 277576 277579 277575
Make Precise electronics
Name Ratio Class Burden
Winding Class
415/110 V 0.5 50 VA
Burden
2. Insulation Resistance Test-

Insulation Resistance
Description Test Voltage
R Y B
Primary to Earth 500V >1 GΩ >1 GΩ >1 GΩ
Secondary to Earth 500V >1 GΩ >1 GΩ >1 GΩ
Primary to Secondary 500V >1 GΩ >1 GΩ >1 GΩ

3. Polarity Check Test: As per the Scheme Drawing-

Core R Y B
Core 1 OK OK OK

TESTED BY WITNESSED BY WITNESSED BY WITNESSED BY


Company STAR INDURE PVT LTD N.T.P.C. (Erection) N.T.P.C.(commissioning)
ELECTRICALS
Signature
Name &
Designation
TEST REPORT FOR
BUS PT INDURE PVT LTD

STAR ELECTRICALS
DATE: Page NO:

4. Ratio test –

RATED RATIO 415/110 V 415/110 V 415/110 V

GIVEN (V) OBSERVED (CORE-1)


R Y B
50 V 13.36 V 13.32 V 13.35 V
100 V 26.71 V 26.75 V 27.10 V
150 V 39.83 V 39.76 V 39.78 V
200 V 53.20 V 53.31 V 53.16 V

5. Winding Resistance-

Winding R Y B
Secondary 1.16 Ω 1.18 Ω 1.12 Ω
Primary 12.56 Ω 12.58 Ω 12.62 Ω

TESTED BY WITNESSED BY WITNESSED BY WITNESSED BY


Company STAR INDURE PVT LTD N.T.P.C. (Erection) N.T.P.C.(commissioning)
ELECTRICALS
Signature
Name &
Designation

Anda mungkin juga menyukai