TeSys Protection
Components
TeSys U A4
Presentation A4/2
TeSys U
Parallel type cabling system
A4/18
Principle and components
Accessories - TeSys U
A4/35
for integration into a MCC drawer
A4/1
Presentation
TeSys U concept
102872_SE.eps
Motor circuit
breaker:
TeSys GV2 L Magnetic protection
> short-circuit protection
TeSys U
102860_SE.eps
Contactor:
TeSys D Control
> Start /Stop
Status monitoring
> signaling
> alarm monitoring
103287-SE.eps
Protection
relay:
TeSys LRD Thermal protection
> overload
DB414490.eps
A4/2
Presentation
TeSys U concept
...TeSys U starter-controller
PB105087.eps
TeSys U
TeSys U starter-controller
> All basic or advanced protection
and control functions in one block
and more...
> Overload indication and alarm
> Status report, remote control via
communication bus
TeSys U
DB414490.eps
can be used in
80 %
of motor protection
and control
applications.
A4/3
Presentation
Advantages
1 All in one
p Optimising space in enclosures.
otal coordination (No contact welding on short circuit).
pT
PB105087.eps
2 Simplicity of choice
p Controlled power.
p Protection functions ensured.
p Signaling functions, communication with PLC ensured.
TeSys U
5 Electrically simple
Basic scheme of a TeSys U starter-controller
p Protection and power control
1/L1
3/L2
5/L3
DB414491R.eps
V1 4/T2
W1 6/T3
M
3a
A4/4
Presentation
Common characteristics
Short-circuit protection
bb Isc:
vv 50 kA at y 400 V
vv 10 kA at 500 V
vv 4 kA at 690 V.
PB105087.eps
bb Up to 690 V AC.
Overload protection
bb From 0.15 to 32 A, 6 setting ranges (tripping 14.2 x I setting).
bb Test button.
bb Adjustment lock.
bb Coil choice: 24 V, 48…72 V, 110...240 V DC/AC.
3 power contacts
bb For non-reversing (reversing with reverser block).
bb Imax, for 12 A power base (direct - reversing):
vv 12 A at up to 500 V / 50 Hz
vv 9 A > 500 V, up to 690 V.
bb Imax, for 32 A power base (direct - reversing):
vv 32 A at up to 500 V / 50 Hz
TeSys U
vv 21 A > 500 V, up to 690 V.
1 NO contact
1 NC contact
bb 5 A / max. 690 V AC or 250 V CC.
Communication modules
bb Modbus,
bb Ethernet,
bb CANopen,
Motor up to bb DeviceNet,
p 7.5 kW / 1-phase 230 V / 50-60 Hz. bb Advantys stb,
p 15 kW / 3-phase 400-440 V / 50-60 Hz. bb Profibus DP,
bb Beckhoff,
p 15 kW / 3-phase 500 V / 50-60 Hz. bb AS-interface.
p 18.5 kW / 3-phase 690 V / 50-60 Hz.
p Non-reversing or reversing.
Dimensions
bb Base: b Base + reverser block:
DB416319.eps
DB416320.eps
154
224
126 45
126 45
A4/5
Presentation
The modularity principle
DB414493.eps
E
A
TeSys U
A Cavity for control unit D Cavity for additional contact block or shutter
A4/6
Presentation
Control units and modules
On/off control, 1 direction of rotation
Components overview
DB414494R.eps
1
24 5
4
E
3
A 2
11
10
B
C
9
6
8
TeSys U
19
D 7
13
22 12 16
23 15
20
14
17
21
18
Communication auxiliary
modules
11- LUFC00
Power base Auxiliary module Telefast parallel liaison Control terminal blocks
1- LUB 6- LUFN module, with RJ45 connector 19- LU9BN11
Non reversing power base - Auxiliary contacts module 12- ASILUFC5/ASILUFC51 Terminal block for imbedded
1 rotation direction AS-Interface c. m. auxiliary contacts
Load monitoring auxiliary 13- LULC031/LULC033 20- LU9BN11C
modules Modbus c. m Coil terminal block with its
Control units
7- LUFW10 14- LULC07 Profibus DP c. m connecting cable
2- LUCM Overload alarm module
15- LULC08 CANopen c. m. 21- LU9BN11L
Multifunctional control unit
8- LUFDH11 Coil terminal block with its
3- LUCB/LUCC/LUCD Overload alarm module with 16- LULC09 DeviceNET c. m. connecting cable
Advanced control units manual reset 17- LULC15 Advantys STB c. m.
4- L
UCA 9- LUFDA01/LUFAD10 Additional contacts blocks
Standard control unit Overload alarm module with Shutters 22- LUA1
5- LUCL automatic reset/remote reset 18- L
U9C 1 Additional contacts
Magnetic protection 10- LUFV2 Shutter for module cavity
control unit Motor load indication module 24- LUA8
23- Shutter for contacts
additional block cavity side-mounting additional
contacts
A4/7
Presentation
Control units and modules
On/off control, 2 directions of rotation, vertical mounting
1
6
2 3
A4/8
Presentation
Control units and modules
On/off control, 2 directions of rotation, side-mounting
TeSys U
3
Reverser block
1- LU6M B0pp
Side-mounting reverser block
A4/9
References
Components for "standard control" bb Rotation control: 1 direction - 2 directions.
bb Protection: overload + short circuits
+ main power fault.
bb Monitoring: by dry contacts.
PB105100.eps
PB105101.eps
PB108212_20.eps
PB108208_20.eps
Cial. ref.: replace dots by Standard power base Standard reversing Standard power base Standard reversing
the coil code LUB12 power base LUB32 power base
LU2B12pp LU2B32pp
Auxiliary signaling Function Indicates the open/ closed status of the protection: by NO/NC contact
contacts block Protection standby/tripped: by SD contact
To be inserted below the auxiliary module cavity (B)
DB124030.eps
A4/10
The power bases are delivered with the following items
LUB12, LUB32
12 or 32 A power base with imbedded control terminal
block and 3 blanking shutters
LU2B12, LU2B32
12 A (LUB120) or 32 A (LUB320 (1) power base without
imbedded control terminal block
+ 1 assembling connector LU9MR1C
+ 1 reverser block - vertical mounting LU2MB0pp
+ 1 control terminal block LU9M1
(1) see description next page.
TeSys U
1 terminal S2 coil
2 terminals contact NF (24 ... 250 V DC/AC, 5 A max)
Note: both LUCA and LUCL units can be used in the advanced power bases
LUB120 and LUB320.
Modules and blocks are compatible with all standard and standard inverting power
DB414501.eps
bases
E Common electrical characteristics
bb Standard operating voltage: 24…250 V AC/DC.
bb Maximum current: 5 A.
A4/11
References
Components for "advanced control" bb Rotation control: 1 direction - 2 directions.
bb Protection: overload + short circuit
+ main power fault.
bb Signaling: by dry contacts.
bb Digital display of electrical values.
bb Overload alarms.
bb Network/bus communication.
DB416347.eps
PB107387_19.eps
DB414503.eps
1
2
2 3
Advanced power base Reverser block - vertical mounting Reverser block - side mounting
Rating / Ue AC
TeSys U
DB414504.eps
of 3 phases motors 50/60 Hz
Protection type:
- overload
Lip_in - short-circuit
mounting on - Main power fault
Setting the power - alarm
400/440 V 500 V 600 V Multifunctional
range base - Rating
kW kW kW A A Class 10 Class 10 Class 20 Class 5...30
1P 3P 3P 3P 3P 1P 3P 1 - 3P
- 0.09 - - 0.15...0,6 12 and 32 LUCBX6pp LUCCX6pp LUCDX6pp LUCMX6BL
0.09 0.25 - - 0.35...1,4 12 and 32 LUCB1Xpp LUCC1Xpp LUCD1Xpp LUCM1XBL
0.55 1.5 2.2 3 1.25...5 12 and 32 LUCB05pp LUCC05pp LUCD05pp LUCM05BL
2.2 5.5 5.5 9 3...12 12 and 32 LUCB12pp LUCC12pp LUCD12pp LUCM12BL
4 7.5 9 15 4.5...18 32 LUCB18pp LUCC18pp LUCD18pp LUCM18BL
7.5 15 15 18.5 8...32 32 LUCB32pp LUCC32pp LUCD32pp LUCM32BL
Cial. ref. of the control unit: replace dots by the coil code.
Coil voltage (V) 24c 24a 48...72 c and 48a 110...220 c and 110...240a
Coil code BL B ES FU
> Selection of the modules and signaling blocks: see page A4/14
A4/12
LUB120, LUB320 - 12 or 32 A advanced power base equipped with:
One NO latching contact + one NC contact
Operation voltage 24 ... 250V AC/DC - I max 5 A
+ 2 blanking shutters
The cavity C is empty, ready for insertion of a terminal block:
for local control LU9BN11
for centralized control LU9BN11C, LU9BN11L
or insertion of an assembling connector LU9MR1C, for reverser block - vertical mounting
Inverser block: its maximum controlled power might be limited by the power base capacity
Power base interlocking control:
vertical mounting: by the assembling connector LU9MR1C
side mounting: by a LU9MR1 terminal block (to be linked to a LU9B N11 terminal block
TeSys U
in the advanced power base).
Reverse control:
Local control, to be wired on a LU9M1 terminal block
centralized control, by a LU9MRC or LU9MRL terminal block; its connector must be plugged in a
communication module, in the advanced power base.
A4/13
References
Components for "advanced control" (continued) bb Rotation control: 1 direction - 2 directions.
bb Protection: overload + short circuits
+ main power fault.
bb Signaling: by dry contacts.
bb Digital display of electrical values.
bb Overload alarms.
bb Network/bus communication.
4a- Selection of the auxiliary module and terminal block for Modicon Telefast system
Telefast system Terminal block / control cable
Module 1 direction of rotation 2 directions of rotation
DB414505.eps
DB414506.eps
DB414507.eps
TeSys U
DB414527.eps
DB414525.eps
DB414524.eps
Function Indicates the off/ready status of TeSys U: Indicates the off/ready status of the protection
by NO/NC contact
Protection on/tripped: by SD contact
To be inserted below the auxiliary module cavity (B)
Output OF and SD contacts: OF contact: NC type 2 OF contacts: NO type
NO type SD contact: NO type
Cial. reference LUA1C20 LUA1C11 LUA8E20
A4/14
bb The signaling modules with dry contacts are directly wired on indicators and electrical warning devices.
bb Contacts rating: 5 A / 24...250 V AC/DC.
bb The LUF V2 module is connected to a datalogger or any other indication device providing a 4-20 mA analog
input.
TeSys U
bb Outputs: OF / SD contacts from protection device, OF contact from the poles (to a 24 V PLC input)
bb RJ45 connector for Telefast PLC pre-wiring system:
vv Modicon TM3 (map I/O controllers for RJ45 M221, M241, M25)
vv Modicon STB modules (I/O for automation island)
vv Modicon Telefast (interfaces RJ45/HE10).
bb Must be connected to a LU9 G02 or LU9 G03 Telefast distribution box
bb Compatible exclusively with LUCppp control unit with coil code B
bb The terminal blocks + control cables provide the connection to the coil of the power base and the signal contacts.
bb Communication modules:
vv indicates the position of the control pad and the state of the poles,
vv collects the FWD, REV commands from an automation process.
bb The states and the control orders are coded according to the selected communication protocol.
bb Screw clamp terminals to the bus cable.
bb The terminal blocks + control cables provide the connection to the coil of the power base and the signal contacts.
bb Additional blocks:
vv used for wiring indicator lights or controllers.
bb Advantage:
vv the locations for these blocks are always available, regardless of the configuration of the power base.
bb Contact rating: 5 A / 24...250 V AC/DC.
Note: the indication the direction of rotation is available on the reverser block unit:
- On a LU9M R1C assembling connector
- On a LU9M R1 terminal block.
A4/15
References
Typical wiring diagrams
21 22
95 NC 96 17 NO 18
A1
33 34 43 44
NO NO
95 NC 96 17 NO 18
A1
TeSys U
A2 13 NO 14 21 NC 22
ON indication
"Motor RUN" indicator wiring "Motor starter READY" indicator wiring
DB414428.eps
DB414429.eps
READY
a
43 44
3333 3434 4343 4444 LUA8 E20
LUF N20
NO NO
33 34 43 44 33 34 43 44
95 NC 96 17 NO 18 NO NO NO NO
RUN
95 NC 96 17 NO 18 95 NC 96 17 NO 18
a A1 a
A1 A1
A2 13 NO 14 21 NC 22 A2 13 NO 14 21 NC 22
a A2 13 NO 14 21 NC 22
ALARM indication
Protection device status indicator wiring
DB432552.eps
95
33 34 43 44
NO NO
95NO
97 96
NC 98 17 NO 18
LUA1 C20
A1
33 34 43 44
A2 13 NO 14 21 NC 22
ALARM NO NO
a 97
95 NO
NC 98
96 17 NO 18
Protection OK A1
A2 13 NO 14 21 NC 22
A4/16
References
Typical wiring diagrams and contacts status
DB414431R.eps
82 81 84
1 2
33 34
A2A2 A1A1 A3A3 B1B1 B3B3
3333 3434 4343 4444
LUFN20
NO
NO NO
NO
OFF REV FW 33 34 43 44
95 NC 96 17 NO 18 33 34 43 44
a NO NO
NO NO
95 NC 96 17 NO 18
95 NC 96 17 NO 18
82 81 84
A1
A1
1 2
TeSys U
82 81 84
RUN FW
82 81 84
1 2 a
RUN REV 1 2
a
A2 A1 A3 B1 B3
A2 A1 A3 B1 B3
Ready to operate 0
Start 1
A4/17
References
Parallel-type cabling systems
Principle
Point-to-point wiring
PB105089.eps
DB416375.eps
bb The control inputs and signaling outputs of the starter are grouped in a
single socket, usually RJ45.
They are individually connected to PLC outputs and inputs.
bb The wires run in parallel in a multicore cable equipped with a multipin
connectors, RJ45 in the case of Telefast type system.
bb 3 parallel wiring systems are available:
vv Modicon TM3, based on a RJ45 I/O module for M221, M241, M25 PLC
TeSys U
A4/18
References
Parallel-type cabling systems
Modicon TM3
DB415968_Tesys U.eps
TeSys U
2
A4/19
References
Parallel-type cabling systems
Modicon Advantys STB
A4/20
References
Parallel-type cabling systems
Modicon Telefast
TeSys U
1
4 5 7
A4/21
References
Parallel-type cabling systems
Components TeSys U
Designation Reference
LUFC00
DF510918.eps
1 Parallel connection module, RJ45 output 2 coil control inputs, 3 signal outputs
2 Pre wired connector, one direction of rotation, for coil connection and one LU9BN11C
contact for emergency stop
Designation Reference
Splitter box LU9G02
TeSys U
Connection to TeSys U:
4 RJ45 connectors: for 1 to 4 TeSys U, 1 or 2 directions
4 RJ45 connectors: for 1 to 4 TeSys U, 1 direction
Connection to PLC:
1 x HE10 connector - 20 chanels, for pole status, alarms
1 x HE10 connector - 20 chanels, for control.
24 V DC auxiliary power supply required
Splitter box LU9G03
Connection to TeSys U:
8 RJ45 connectors: for 1 to 8 TeSys U, 1 or 2 directions
Connection to PLC:
LU9 G02 LU9 G03 1 x HE10 connector - 20 chanels, for pole status, alarms
1 x HE10 connector - 20 chanels, for control.
24 V DC auxiliary power supply required.
0.3 m LU9R03
1m LU9R10
3m LU9R30
5m TSXCDP503
Section: AWG 28 / 0.080 mm² (flat cable)
1m ABFH20H100
2m ABFH20H200
3m ABFH20H300
A4/22
References
Bus-type cabling systems
Principle
Many motors are scattered on the site, the process control requires individual control
to ensure safety and proper operation.
TeSys U is a suitable communicating actuator. The integration of a bus communication
module in the starter-controller saves space in the control board and simplifies wiring,
compared to solutions based on conventional components (circuit breaker + contactor).
TeSys U
bb The bus wiring interconnects TeSys U starters
DB416376.eps
A4/23
References
Bus-type cabling systems
View
Details page
A4/26
CANopen
Etoile
TeSys U
1 LUL C08
2 LU9B N11L
5
3 LU9M RL
1 1
1
2 2 3 4 TSX CAN Cppp
Bus
1 1
1
2 2 3
4 4 4
Details page
A4/27
A4/24
Network Architecture Component
references
Modbus
Etoile Bus UL C031 or
L
1
LUL C033
2 LU9B N11C
5 3 LU9M RC
1 1 1 1
2 2 3 2 2 1 VW3 A8 306Rppp
4
5 LU9 GC3
6 VW3 A8 306TF
4
6 6
TeSys U
Details page
A4/28
Advantys STB
Starter-controllers LUL C15
1
communicate
using ADVANTYS LU9B N11L
STB protocol to fit
2
into a remote I/O LU9M RL
architecture. 6
3
1
1
2 3
4 LU9 RDDppp
5 LU9 RCD
5 4
Details page 6 STB XBE1100
A4/29
Profibus-DP (Decentralized Peripherals)
is used for connecting LUL C07
5 1
actuators and sensors
to a central controller LU9B N11L
for applications in 6
2
industrial production. LU9M RL
The standard bus
3
1
provides a number of 1
2 3 U9 RPB010
L
diagnostic means 4
LU9 RPB100
c 24 V LU9 RPB400
4
5 LU9 AD7
2 LU9B N11L
3 LU9M RL
1
1
2 3
c 24 V
Details page
A4/31
A4/25
References
Bus-type cabling systems
TeSys U components for AS-Interface bus
The LULC09 communication module, combined with the power base and control unit
1 2
is used to control TeSys U starters-controllers via DeviceNet bus.
The LULC09 communication module is slave type.
PB105093.eps
Module Specifications
I/O terminal block
bb Powered by external 24 V DC (power supply not included):
vv 2 x configurable inputs for binary sensors
vv 1 x 24 V DC output - 0.5 A local auxiliary command.
Connectors
3 4 5 bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For AS-Interface bus.
1 Green LED: AS-Interface voltage present
Signaling
2 Red LED: AS-Interface or module fault
3 Outputs for starter commands
bb Module Status - Error - 24 V, by LED.
4 Black connector for connection to c 24 V
auxiliary power supply
5 Yellow connector for connection to the AS-Interface system
Tesys components
Description Mark Max number References
TeSys U
of slaves
AS-Interface communication module 1 31 ASILUFC5
62 ASILUFC51
Pre-wired connector: coil - LUB powerbase 2 - LU9BN11C
DB414635.eps
Description References
DB414636.eps
A4/26
References
Bus-type cabling systems
TeSys U components for CANopen bus
The LUL C08 communication module, combined with the power base and control
1 2 3
unit is used to control TeSys U starters-controllers via CANopen bus.
The LULC08 communication module is slave type.
PF106255.eps
Module Specifications
I/O terminal block
bb Powered by external 24 V DC (power supply not included):
vv 2 x configurable inputs for binary sensors
vv 1 x 24 V DC output - 0.5 A local auxiliary command.
4
Connectors
bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For CANopen bus.
5
Signaling
9 8 7 6 bb Module Status - Error - 24 V, by LED.
TeSys U
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter commands
Tesys components
DB414637.eps
A4/27
References
Bus-type cabling systems
TeSys U components for Modbus bus
LUL C031 LUL C033 The LULC031 and LULC032 communication modules, combined with the power
base and control unit is used to control TeSys U starters-controllers via Modbus.
1 1
Module Specifications
PB105096.eps
PB105095.eps
Tesys components
Description Item Bin. input References
DB414639.eps
Modbus hub
1 Description Length References
(m)
Modbus communication distributor - LU9GC3
2 Cables fitted with 2 x RJ45 connectors 0.3 VW3A8306R03
1 VW3A8306R10
3 VW3A8306R30
Tees derivations 0.3 VW3A8306TF03
1 VW3A8306TF10
DB414640.eps
Description References
RS 485 line terminator VW3A8306R
A4/28
References
Bus-type cabling systems
TeSys U components for Advantys STB bus
fallback positions.
Module Specifications
I/O terminal block
9 bb Powered by external 24 V DC (power supply not included):
vv 2 x configurable inputs for binary sensors (on LULC033 only)
4 vv 1 x 24 V DC output - 0.5 A local auxiliary command.
Connectors
bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For Advantys STB bus.
8 6 5
7 Signaling
bb Com - Error - 24 V, by LED.
1 Two-colour LED indicating module status
2 Fault signalling LED
3 LED indicating that c 24 V supply is ON
4 Bus connectors
TeSys U
5 c 24 V supply connection
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter commands
Tesys components
Description Item References
Advantys STB communication module 1 LULC15
Pre-wired connector: coil - LUB powerbase 2 LU9BN11L
Pre-wired connector: coil - LUB2B powerbase 3 LU9MRL
DB414641.eps
Cables
Description Length References
(m)
Cables fitted with connectors, one straight and one 0.3 LU9RCD03
elbowed 1 LU9RCD10
3 LU9RCD30
5 LU9RCD50
Cables fitted with two straight connectors 0.3 LU9RDD03
1 1 LU9RDD10
2 3 LU9RDD30
A4/29
References
Bus-type cabling systems
TeSys U components for Profidus DP bus
When used in conjunction with the power base and control unit, communication
1 2 3
module LULC07 allows TeSys U starter-controllers to be controlled via Profibus DP
(Deported Periphery) bus.
Communication module LULC07 is of the slave type.
PB105098.eps
Module Specifications
I/O terminal block
bb Powered by external 24 V DC (power supply not included):
9 vv 2 x configurable inputs for binary sensors
4 vv 1 x 24 V DC output - 0.5 A local auxiliary command.
Connectors
bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For Profibus DP bus.
8 6 5
7 Signaling
bb Com - Error - 24 V, by LED.
1 Two-colour LED indicating module status
2 Fault signalling LED
3 LED indicating c 24 V supply ON for outputs
OA1, OA3 and LO1
TeSys U
A4/30
References
Bus-type cabling systems
TeSys U components for DeviceNet bus
When used in conjunction with the power base and control unit, communication
module LULC09 allows TeSys U starter-controllers to be controlled via DeviceNet bus.
1 2 3 Communication module LUL C09 is of the slave type.
Module Specifications
PB105099.eps
TeSys U
4 DeviceNet connector for bus link
5 c 24 V supply connection
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter-controller commands
(non-reversing and reversing)
Tesys components
Description Item References
DeviceNet communication module 1 LULC09
DB414645.eps
A4/31
References
Communication gateways LUFP
Presentation
108816_SE_R.eps
Communication gateways LUF P allow connection between the Modbus serial link
and Fipio, Profibus DP or DeviceNet field buses.
Example of architecture
Configuration
of gateway TeSys U starter-controllers
by PC
DF511517.eps
LUF P
TeSys U
Fipio (1)
Profibus DP Modbus
DeviceNet
1
Communication gateway LUFP
Description Reference
Fipio / Modbus gateway LUFP1
Profidus DP / Modbus gateway LUFP7
DeviceNet / Modbus gateway LUFP9
Description
Front panel of the product
1 LED indicating :
2 - communication status of the Modbus serial links,
- gateway status,
- communication status of the Fipio, Profibus DP or DeviceNet bus.
2 Connectors for connection to Fipio, Profibus DP or DeviceNet buses.
561512.eps
Underside of product
3 RJ45 connector for connection of the Modbus serial link
4 RJ45 connector for link to a PC
5 c 24 V power supply
3
4 Software set-up
For the Fipio bus, software set-up of the gateway is performed using either PL7
Micro/Junior/Pro software or ABC Configurator software.
5 For the Profibus DP and DeviceNet buses, software set-up is performed using
ABC Configurator.
This software is included in the TeSys U user’s manual.
(1) Connection kit for PowerSuite software workshop.
A4/32
References
Current limiter blocks and accessories
PB113846.eps
To be connected in series and upstream of a TeSys U starter-controller . It increases its
ability to withstand the short circuit current from 50 kA to 100 or 130 kA under 400 V.
Principle: under the action of a short-circuit, the opening of two contacts of each
phase of the limiter creates a resistive arc. The current then decreases to a value
tolerable by a TeSys U power base.
LUA LF1
Limiter blocks and accessories
Description Breaking capacity Iq (kA) Mounting Unit reference
y 440 V 690 V
Limiter-disconnector 130 70 Direct on power base LUALB1 (1)
DB414653.eps
(1 x LUAFL1
cartridge supplied)
Limiter 100 35 Separate LA9LB920 (2)
limiter cartridge 130 70 Limiter-disconnector LUALF1
for LUALB1
(1) Must be connected to one power base only.
(2) Can be connected to multiple TeSys U power bases in parallel with limitation :
LUA LB1 LA9LB920 bb Total Ith max 63 A
bb Total nominal current 32 A from motor with simultaneous start (LA9LB920 could not
withstand higher inrush peak current)
TeSys U
Phase barrier
DB414654.eps
LU9SP0
Clip-in labels
Can be clipped on any TeSys U power base, on LU6M B0pp inverser block,
and Linergy HK busbar system.
Marking accessory
Description Sold by lot of Reference per unit
Clip-in label 8 x 18 mm 100 LAD90
The red sticker is dedicated to TeSys U LUCA, LUCB, LUCC, LUCD and LUCL
control units.
Description Reference per unit
LU9ET1S Retrofit safety-chain identification sticker LU9ET1S
A4/33
References
Handles and components for rotary control
Mounting kit
1 TeSys U Power base bracket; its horseshoe shaped sides hold the rotary
mechanism facing the original handle.
2 Mechanism, shaft and handle; the shaft enters the handle attached to the door
during closing.
Long shaft
LUA9PN21 mounting kit
bb to be cut to the required length. Equipped with a connection endpiece.
Shaft support plate for deep enclosure
bb Provides horizontal guiding of the shaft, when the door is open.
TeSys U
Handle
PB106291.eps
GVA PA1 long shaft bb Delivered as a single unit, to be fitted on a side of the enclosure.
Note: references below are suitable for TeSys U power bases after 2004.
"Safety" stickers
bb Marking: Electrical hazard, etc.
GVA PK12 shaft support plate for deep
enclosure Description Tripping Reference
indication
Mounting kit Black handle, with error status, IP54 p LU9APN21
Red handle, with error status, IP54 p LU9APN22
Red handle, without error status, IP65 - LU9APN24
DB414520.eps
A4/34
References
Handles and components for MCC control drawers
TeSys U
Mounting kit and handle for MCC drawer
Together, this provides manual control of a TeSys U starter-controller from the front
DB123404.eps
1 2 3
MCC drawer
RESET
0
A4/35
A4/36
TeSys U
Technical
TeSys U
Data for
Designers
Contents
Characteristics..................................... A4/38 to A4/45
Curves................................................. A4/46 to A4/49
Selection.............................................. A4/50 to A4/51
Dimensions.......................................... A4/52 to A4/53
Schemes.............................................. A4/54 to A4/65
TeSys U and Altistart............................ A4/66 to A4/81
A4/37
Characteristics - TeSys U
TeSys motor starters open version
TeSys U starter-controllers
Environment
Product certifications UL, CSA, CCC, GOST, ASEFA.
ABS, BV, DNV, GL, LROS.
ATEX.
Conforming to standards IEC/EN 60947-6-2, CSA C22-2 N° 14, Type E
UL 508 type E: with phase barrier LU9 SP0
Rated insulation voltage (Ui)Conforming to IEC/EN 60947-1, V 690
overvoltage category III,
degree of pollution: 3
Conforming to UL508, V 600
CSA C22-2 n°14
Rated impulse Conforming to kV 6
withstand voltage (Uimp) IEC/EN 60947-6-2
Degree of protection Front panel outside connection IP 40
Conforming to IEC/EN 60947-1 zone
(protection against Front panel and wired terminals IP 20
direct finger contact) Other faces IP 20
(At temperatures above 60°C and up to 70°C, for starter-controller LUB32, leave
a minimum gap of 9 mm between products).
Power bases and multifunction control units: -25…+60.
(At temperatures above 45 °C, leave a minimum gap of 9 mm between products.
At temperatures above 55 °C and up to 60 °C, leave a gap of 20 mm between
products.)
Maximum operating altitude m 2000
520717.eps
mounting plane 90˚ 90˚
30˚
Flame resistance Conforming to UL 94 V2
Conforming to °C 960 (parts supporting live components)
IEC/EN 60695-2-12 °C 650
TeSys U
Screwdriver Philips n° 1 or flat screwdriver: Ø5 mm
Tightening torque N.m 0.8…1.2 0.8…1.2 0.8…1.2 0.8…1.2 0.8…1.2
Control circuit characteristics
Rated voltage a 50/60 Hz V 24…240 24…240 – – –
of control circuit c V 24…220 24…220 24 24 –
Voltage limits c 24 V (1) V 20…27 20…27 20…28 20…28 –
Operation a 24 V V 20…26.5 20…26.5 – – –
a or c 48…72 V V a 38.5…72. c 38.5…93 – – –
a 110…240 V V a 88…264 a 88…264 – – –
c 110…220 V V c 88…242 c 88…242 – – –
Drop-out c 24 V V 14.5 14.5 14.5 14.5 –
a 24 V V 14.5 14.5 – – –
a or c 48…72 V V 29 29 – – –
a 110…240 V, c 110…220 V V 55 55 – – –
Typical consumption c 24 V mA 130 220 150 200 120
I max while closing a 24 V mA 140 220 – – 2360
a or c 48…72 V mA 280 280 – – 2300
a 110…240 V, c 110…220 V mA 280 280 – – 1000
I rms sealed c 24 V mA 60 80 70 75 120
a 24 V mA 70 90 – – (2)
a or c 48…72 V mA 35 45 – – (2)
A4/39
Characteristics - TeSys U
TeSys motor starters open version
TeSys U starter-controllers
Reversing power bases and auxiliary contacts
Specific characteristics of power bases LU2B and reverser blocks LU2M or LU6M
Duration of inrush phase a 50/60 Hz ms 25
c ms 15
Maximum Without change of direction ms 75
operating time With change of direction ms 150
General characteristics of auxiliary contacts
Conventional For ambient temperature θ < 70 °C A 5
thermal current (Ith)
Frequency of the operational current Hz Up to 400
Minimum switching capacity λ = 10-8 U min V 17
I min mA 5
Short-circuit protection Conforming to IEC/EN 60947-5-1 A gG fuse: 4
Mirror contact Conforming to IEC/EN 60947-1 The N/C contact fitted in each power base reliably represents the state of the power
contacts (safety scheme)
Rated operational voltage (Ue) V Up to a 690; c 250
Rated insulation voltage Conforming to IEC/EN 60947-5-1 V 690
(Ui) Conforming to UL, CSA V 600
Specific characteristics of auxiliary contacts in modules LUF N, of auxiliary contacts LUA1
and of reverser blocks LU2M and LU6M
Rated operational voltage (Ue) V Up to a 250; c 250
Rated insulation Conforming to IEC/EN 60947-5-1 V 250
voltage (Ui) Conforming to UL, CSA V 250
a.c. supply, categories AC-14 and AC-15 d.c. supply, category DC-13
Electrical durability (valid for up to 3600 operating cycles/hour) on an Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load
inductive load such as the coil of an electromagnet: making current such as the coil of an electromagnet, without economy resistor, the time constant
(cos φ 0.7) = 10 times the power broken (cos φ = 0.4) increasing with the load.
10 10
DF510594.eps
DF510595.eps
8 8
7 7 24 V
Millions of operating cycles
6
Millions of operating cycles
6
5 5 48 V
4 4 125 V
3 3
2 2 250 V
1 1
0,8 0,8
0,7 0,7
0,6 0,6
0,5 0,5
0,4 0,4
0,3 0,3
0,2 0,2
0,1 0,1
0,1 0,2 0,3 0,4 0,6 0,8 1 2 3 4 6 8 10 0,1 0,2 0,3 0,4 0,6 0,8 1 2 3 4 6 8 10
0,5 0,7 0,9 5 7 9 0,5 0,7 0,9 5 7 9
Current broken in A Current broken in A
TeSys U
protection Tripping tolerance ±20 % ±20 % ±20 %
Configuration table for protection devices and alarms on multifunction control units LUCM
Tripping Alarm Adjustment of tripping Adjustment of time before Adjustment of alarm
threshold tripping threshold
Factory setting Factory setting Range Default value Range Default value Range Default value
Cabling
Solid cable 1 conductor mm2 1.5…10
2 conductors mm2 1.5...6
Flexible cable without cable end 1 conductor mm2 1…10
2 conductors mm2 1…6
Flexible cable with cable end 1 conductor mm2 1...6
2 conductors mm2 1...6
Screwdriver Phillips n°2 or flat screwdriver Ø6 mm
Tightening torque N.m 1.9…2.5
TeSys U
Current consumption On the mA Normal operation: 25
AS-Interface bus mA Fault condition: 30
On 24 V supply mA 200
for the outputs
Auxiliary supply V c 24 ±30 %
Number of outputs 2 dedicated to starter-controller coil operation
Switching capacity of the solid state outputs 0.5 A/24 V (outputs protected against short-circuits)
Indication/diagnostics By 2 LEDs on front panel
A4/43
Characteristics - TeSys U
TeSys motor starters open version
TeSys U starter-controllers
Function modules and communication modules
Structure Physical interface 9-way SUB-D male 9-way SUB-D female “Open Style” connector
Binary rate 9600 Kbits/s…12 Mbits/s 10, 20, 50, 125, 250, 500 125…500 kbaud
and 1000 Kbits/s
(by switches)
Cables 2 shielded twisted pairs
A4/44
Characteristics - TeSys U
TeSys motor starters open version
TeSys U starter-controllers
Function modules and communication modules
Connection characteristics
Module type LUF W10, LUF V2 ASILUF C5 and ASILUF C51
LUF DH11,
LUF DA01 and Inputs and 24 V Outputs
LUF DA10 auxiliary supply
Connectors Pitch 5.08 3.81 5.08 3.81
TeSys U
Conductor size 1 conductor AWG 24… AWG 16 AWG 26… AWG 16 AWG 24… AWG 16 AWG 26… AWG 16
Conductor size 1 conductor AWG 26… AWG 16 AWG 26… AWG 16 AWG 26… AWG 16 AWG 24… AWG 16
A4/45
Curves - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
1000
562509.eps
1
100
3
10
1
TeSys U
0,1
1 2 3 4 5 6 7 8 10 12 14 20 30
x the setting current (Ir)
1000
560575.eps
1
100
2
10
0,1
1 2 3 4 5 6 7 8 10 12 14 20 30
x the setting current (Ir)
References :
page A4/12
A4/46
Curves - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
1000
100
10
TeSys U
Class 30
Class 25
Class 20
Class 15
Class 10
1 Class 5
0,1
1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 30
11 13 15 17 19
x the setting current (Ir)
References :
page A4/12
A4/47
Curves - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
1000
100
10
TeSys U
Class 30
1 Class 25
Class 20
Class 15
Class 10
Class 5
0,1
1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 30
11 13 15 17 19
x the setting current (Ir)
References :
page A4/70
A4/48
Curves - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
10 2
TeSys U
0,1
0,1 0,2 0,4 0,6 0,8 1 2 3 4 6 8 10 20 30 40 60 80 100
Prospective Isc (kA)
1
100
10
1
0,1 0,2 0,4 0,6 0,8 1 2 3 4 6 8 10 20 30 40 60 80 100
Prospective Isc (kA)
1 32 A power base
2 12 A power base
References :
pages A4/10 to A4/12
A4/49
Selection - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
LUB 12
LUB 32
10
Millions of operating cycles
520946.eps
6
5
4
1
0,8
0,6
0,5
1 2 3 4 5 6 7 8 9 10 12 32 40
Current broken in A
Ue y 440 V Ue = 690 V
LUB 12
LUB 32
LUB 12
LUB 32
10 10
520947.eps
520948.eps
Millions of operating cycles
8 8
6 6
5 5
4 4
3 3
2 2
1 1
0,8 0,8
0,6 0,6
0,5 0,5
1 2 3 4 5 6 7 8 9 10 12 32 40 1 2 3 4 5 6 7 8 9 10 12 21 32 40
Current broken in A Current broken in A
0,75
0,55
2,2
5,5
7,5
1,5
kW
230 V
0,55
0,75
7,5
1,5
2,2
5,5
15
11
4
kW
400 V
0,75
0,55
2,2
5,5
7,5
1,5
11
15
4
kW
440 V
References :
pages A4/10 to A4/12
A4/50
Selection - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
LUB 12
LUB 32
LUB 12
LUB 32
1 1
520950.eps
Millions of operating cycles
0,8 0,8
0,6 0,6
0,5 0,5
0,4 0,4
0,3 0,3
0,2 0,2
0,1 0,1
0,08 0,08
0,06 0,06
0,05 0,05
0,04 0,04
0,03 0,03
0,02 0,02
0,01 0,01
1 2 3 5 10 20 30 50 66 100 200 1 2 3 5 10 20 30 50 60 100 200
TeSys U
40 60 80 170 40 54 80 126
Current broken in A Current broken in A
References :
pages A4/10 to A4/12
A4/51
Dimensions - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Dimensions
Starter-controllers
LUB: non-reversing LU2B: reversing
Rail mounting Screw fixing Rail mounting Screw fixing
126 126 30 Ø4 (2) 29 Ø4 (2)
DF510943.eps
DF510944.eps
DF510947.eps
DF568844.eps
DF568841.eps
X1
X2
DF568843.eps
73
163…167
154
233…237
120/125
224
a (1) X2
X1
45 135 (1)
a
With Modbus module 135 45
With Advantys STB, CANopen, Profibus DP 147
or DeviceNet modules
Minimum electrical clearance:
X1 = 50 mm for Ue = 440 V and 70 mm for Ue = 500 and 690 V, X2 = 0
Reverser block for mounting separately from power base
TeSys U
DF568847.eps
DF568848.eps
104
115
113 45 113 36 Ø4
DF511518.eps
DF568851.eps
l p l
GV1 G09
18
38
95
I
GV2 G245 (2 x 45) 89
GV2 G254 (2 x 54) 98
260
DF568852.eps
l
GV2 G454 (2 x 54) 206 54
a
Number of tap-offs 5 6 7 8 I
GV2 G445 (2 x 45) 224 269 314 359 GV2 G345 (2 x 45) 134
GV2 G454 (2 x 54) 260 314 368 422 GV2 G354 (2 x 54) 152
DF568855.eps
45,5
82
38 35,5
30
79
81
45
438
452
(1) Depth with communication module.
(2) Retractable fixing lugs.
A4/52
Dimensions (continued), mounting - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Dimensions, mounting
Limiter-disconnector LUA LB1 Current limiter LA9 LB920
Disconnector LUA LB10
DF568856.eps
DB432554.eps
2ØM4
X1
93
146
103
115
154
6 51
X1
53,5
a (1) 45
TeSys U
Door interlock mechanisms
LU9 APN21, LU9 APN22, LU9 APN24 Door cut-out
16 4Ø3,5 (1) a
DB126634.eps
Ø3,5
DB127409.eps
Mini Maxi
LU9 APNpp 191 300
6
+ GV APK12
48
60
237,4
Ø22
0,5...4
= =
48
(1) For IP65 only.
43 a = =
79,5
Addressing consoles
XZ MC11 ASI TERV2
DF568860.eps
DF568861.eps
209
195
80 30 84 35
Splitter boxes
LU9 GC3 (Modbus) LU9 G02 and LU9 G03 LU9 GC7 (Profibus DP)
Rail mounting Screw fixing Rail mounting Screw fixing
Ø4 (2) Ø4 (2)
DF568862.eps
DF510945.eps
DF568867.eps
DF510946.eps
DF568865.eps
DF568863.eps
163…167
163…167
154
170
128 45 128 30
65 45 65 30
A4/53
Schemes - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
3/L2
5/L3
1/L1
3/L2
5/L3
DF568772.eps
DF568773.eps
13/NO
14/NO
21/NC
4/T2
6/T3
2/T1
4/T2
6/T3
A1
A2
Pre-wired
5 L2
DF568774.eps
Reverser
3
TeSys U
2/T1
4/T2
6/T3
A3
B3
A1
B1
A2
81
84
82
Control terminal block
13/NO
14/NO
21/NC
22/NC
Control Unit
DF568775.eps
V 6
A1
A2
A3
B3
A1
B1
A2
Reverser blocks
LU2M LU6M
Control terminal blocks
S1
1/L1
3/L2
5/L3
S2
S3
DF568777.eps
DF568776.eps
S1
S2
S3
B3
A1
B1
A2
Reverser
With pre-wired connector LU9 MRC
DF568778.eps
S1
S2
S3
4/T2
6/T3
LU9M RC
81
84
82
A3
B3
A1
B1
A2
Pre-wired coil
Control terminal block Basic scheme
A2
21
DF568779.eps
DF568780.eps
13
LU2M
22
14
A3
B3
A1
B1
A2
LU6M
S2
S1
S3
A3 Reverse
B1 Forward
A1 Forward
A2 Common
A3 Pulse reverse running
(1) Electronically operated
bistable electromagnet.
67
I O
DF568781.eps
DF568783.eps
DF568784.eps
DF568785.eps
DF568786.eps
DF568782.eps
95/NC 96/NC 97/NO 98/NO 43/NO 44/NO 31/NC 32/NC 41/NC 42/NC
58
68
A4/54
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Control units
Standard control units LUCA Advanced control units LUCB, LUCC, LUCD
Basic scheme Basic schemehd
1 2 3 4 5 6 1 2 3 4 5 6
DF568787.eps
DF568788.eps
LUCA LUCp
Power Base Power Base
Sensor Interface Sensor Interface
L1 L1
Sensor Sensor
L3 L3
Supply and Supply and Therm.overload
Thermal memory
Detection of Detection of
overload
start start
memory
sequence sequence Test
Interface module
A1
A2
A1
A2
7 8 9 10 11 12
1 and 2 Trips
TeSys U
3 and 4 Electromagnet 1 and 2 Trips
5 Power base rating 3 and 4 Electromagnet
6 N/C 5 Power base rating
6 N/C
7 Earth
8 Thermal status/Set
9 Reset mode/Reset
10 (lm/Ir)
11 Vc2
12 Vc1
Multifunction control units LUCM
Control terminal block
DF568789.eps
24 V Aux
0V
4 5 7
6 8
Basic scheme
1 2 3 4 5 6
DF568790.eps
LUCM
Power Base
Sensor Interface Display and
L1 Parameter Entry
L2 A.S.I.C.
D(B)
Sensor 4
D(A)
L3 5
RS485 +5V 7
RJ45
Supply and 0V
Thermal 8
detection of overload
start memory
sequence
Supply
24 V Aux
Interface module
A1
A2
7 8 9 10 11 12
1 and 2 Trips
3 and 4 Electromagnet
5 Power base rating
6 N/C
7 Earth
8 N/C
9 Earth
10 (lm/Ir)
11 Rx/Tx
12 Vc1
A4/55
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Function modules
Alarm Indication of motor load
LUF W10 LUF V2
4-20 mA output
DF568791.eps
DF568792.eps
LUFW 10 Alarms Module LUFV 2 Analogue output Module
4...20 mA 24 V Aux 24 V Aux
07
08
NC
DF568794.eps
LUFW 10 LUFV 2
Input interface LED Supply Input interface Supply
µP - Analogue/Digital
converter
Isolation
TeSys U
Relais bistable
Digital/Analogue
converter
07
08
Voltage/Current converter
4...20 mA
Communication modules
Communication modules ASILUF C5 and ASILUF C51
Without pre-wired coil connection With pre-wired coil connection LU9B N11C
DF568795.eps
DF568796.eps
ASILUF C5 or ASILUF C51 AS-Interface Module ASILUF C5 or ASILUF C51 AS-Interface Module
AS-i AS-i
Com
OA1
OA3
LU9B N11C
Pre-wired coil
AS-i
LU9M RC
Pre-wired coil
Basic scheme
ASILUF C5
DF568798.eps
or
ASILUF C51
Ready-Fault-Pole
DEL
A2SI
Output interface
AS-i
Com
OA1
OA3
A4/56
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
DF568800.eps
LUL C031 Modbus Module LUL C033 Modbus Module
24 V Aux 24 V 24 V
D(A)
D(B)
D(A)
D(B)
0V
Aux COM
0V
c
Com
Com
OA1
OA3
Com
LO1
OA1
OA3
LO1
LI1
LI2
4 5 8
6 4 5 8
6
With pre-wired coil connection LU9B N11C With pre-wired coil connection LU9B N11C
DF568802.eps
DF568801.eps
D(A)
D(B)
D(A)
D(B)
c Aux COM
0V
0V
Com
LO1
LO1
LI1
LI2
LU9B N11C LU9B N11C
Pre-wired coil 4 5 8
6 Pre-wired coil 4 5 8
6
TeSys U
With pre-wired coil connection LU9M RC With pre-wired coil connection LU9M RC
DF568803.eps
DF568804.eps
24 V Aux 24 V 24 V
D(A)
D(B)
D(A)
D(B)
Aux COM
0V
0V
Com
LO1
LO1
LI1
LI2
LU9M RC LU9M RC
Pre-wired coil 4 5 8 Pre-wired coil 4 5 8
x6
LUL C031 LUL C033
Input interface Control unit interface Controller
interface
D(B) D(B)
4 4
D(A) D(A)
RS485 5 Modbus RS485 5 Modbus
0V RJ45 0V RJ45
8 8
AL1 AL1
Supply Supply
Output interface AL2 Output interface I/O interface AL2
24 V 24 V
24 V Aux c Aux COM
Com
Com
Com
24 V
OA1
OA3
OA1
OA3
LO1
LO1
LI1
LI2
A4/57
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
DF568808.eps
DF568807.eps
Bus Bus
Com
Com
OA3
OA1
OA3
OA1
LO1
LO1
LI1
LI2
LI1
LI2
With pre-wired coil connection LU9B N11LC With pre-wired coil connection LU9B N11LC
DF568809.eps
DF568810.eps
LUL C07 Profibus DP Module LUL C08 Canopen Module
Bus Bus
LO1
LO1
LI1
LI2
LI1
LI2
LU9B N11L LU9B N11L
Pre-wired coil Pre-wired coil
With pre-wired coil connection LU9M RC With pre-wired coil connection LU9M RC
DF568811.eps
DF568812.eps
TeSys U
Bus Bus
LO1
LO1
LI1
LI2
LI1
LI2
LU9M RL LU9M RL
Pre-wired coil Pre-wired coil
DF568814.eps
x6 x6
LUL C07 LUL C08
Control unit interface Controller Control unit interface Controller
interface interface
AL1 AL1
Supply Supply
I/O interface AL2 I/O interface AL2
Com
Com
OA3
OA1
OA3
OA1
LO1
LO1
LI1
LI2
LI1
LI2
x6
LUL C09 DeviceNet Module
LUL C09
Bus
Control unit interface Controller
Com
OA3
OA1
LO1
LI1
LI2
interface
LI1
LI2
OA1
LO1
LI1
LI2
DF568818.eps
LI1
LI2
LU9M RL
Pre-wired coil
A4/58
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
DF568820.eps
LUL C15 Advantys STB Module LUF C00 Parallel bus Module
Bus
Com
Com
OA3
OA1
OA1
OA3
LO1
Link // RJ45
LI1
LI2
In Out 1 2 3 4 5 6 7 8
With pre-wired coil connection LU9B N11LC With pre-wired coil connection LU9B N11LC
DF568822.eps
DF568821.eps
LUL C15 Advantys STB Module LUF C00 Parallel bus Module
Bus
Link // RJ45
LO1
LI1
LI2
With pre-wired coil connection LU9M RC With pre-wired coil connection LU9M RC
DF568823.eps
DF568824.eps
TeSys U
LUL C15 Advantys STB Module LUF C00 Parallel bus Module
Bus
Link // RJ45
LO1
LU9M RC
LI1
LI2
LU9M RL
Pre-wired coil In Out Pre-wired coil 1 2 3 4 5 6 7 8
Reay-
x6 Fault-
LUL C15 Pole
Control unit interface Controller
interface RJ45
Com
OA3
OA1
Ready-Fault-Pole 1 2 3 4 5 6 7 8
LED Address
1 Forward running
OUT 2 Reverse running
3 Output common
IN 4 Selector in position
5 Pole state
AL1
Supply 6 Reserved
I/O interface AL2 7 Fault
8 Input common
Com
OA3
OA1
LO1
LI1
LI2
IN OUT
Filter
24 V Aux.
A4/59
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
N/C Reverse running Reverse running
N/C Output common Output common
D (B) – N/C N/C
D (A) + RJ45 Pole state RJ45 Pole state RJ45
N/C N/C X9 + 24 V X9
N/C Fault Fault X1 Fault Fault X1
20 19 18 17 16 15 14 13 12 1110 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 1110 9 8 7 6 5 4 3 2 1
0V +24 V Aux Fault X2 + 24 V Aux Fault X2
X2 Fault X3 Fault X3
X2 X2
Fault X4 Fault X4
Fault X5 Fault X5
X9
Fault X6 Fault X6
RJ45 N/C RJ45 RJ45
8 7 6 5 4 3 2 1
Fault X7 Fault X7
N/C
Fault X8 Fault X8
N/C
Pole state X1 Pole state X1
X3 D (B) – X3
(2) Pole state X2 X3 Pole state X2
RJ45 D (A) + (2)
Pole state X3 Pole state X3
N/C
Pole state X4 Pole state X4
24 V
RJ45 RJ45 Pole state X5 RJ45 Pole state X5
(1)
Pole state X6 Pole state X6
0V
Pole state X7 Pole state X7
X4 X4 Pole state X8 X4 Pole state X8
+ 24 V Aux + 24 V Aux
TeSys U
Com Com
RJ45 RJ45 + 24 V Aux RJ45 + 24 V Aux
Com Com
X5 X5 X5
Forward running
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
N/C X10 X10
RJ45 Commun des sorties Forward running X1
X10 Forward running X1
20 19 18 17 16 15 14 13 12 1110 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 1110 9 8 7 6 5 4 3 2 1
N/C Forward running X2 Forward running X2
Pole state RJ45 Forward running X3
RJ45
Forward running X3
X6 N/C Forward running X4
RJ45 Forward running X4
Fault Forward running X5 Forward running X5
+ 24 V Aux Forward running X6 Forward running X6
RJ45 X6 Forward running X7 Colours of X6 Forward running X7
Forward running X8 TSX CDPppp Forward running X8
Reverse running X1 connection Reverse running X1
X7 RJ45 (3) Reverse running X2 cable wires RJ45 (3) Reverse running X2
Reverse running X3 (4) Reverse running X3
Reverse running X4 Reverse running X4
1 White
RJ45 N/C Reverse running X5
X7 2 Brown X7
N/C Reverse running X6
3 Green
N/C Reverse running X7
4 Yellow
N/C
Shielding
Shielding
16 Yellow-brown
D (A) +
D (B) –
Outputs
Outputs
Inputs
Inputs
17 White-grey
Com
Com
Com
Com
0V
0V
18 Grey-brown
19 White-pink
20 Pink-brown
(1) Not connected on connectors X1 to X8. Only present on RJ45 IN and OUT connectors.
(2) 20-way HE10 input connector.
(3) 20-way HE10 output connector.
(4) Wire colours and corresponding HE10 connector pin numbers.
Gateways
LUF P1 LUF P7 LUF P9
DF568831.eps
DF568832.eps
DF568830.eps
LUF P1 Fip I/O - Modbus Gateway LUF P7 Profibus - Modbus Gateway LUF P9 DeviceNet - Modbus Gateway
D(A)
D(A)
D(B)
D(B)
D(B)
X2 Fip I/O
0V
0V
X2 DeviceNet
0v
X1 X2 Profibus X1 X1
1 2 3 4 5 6 7 8 9 4 5 8 1 2 3 4 5 6 7 8 9 4 5 8 1 2 3 4 5 4 5 8
A4/60
Schemes (continued) - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Main registers accessible with Modbus, CANopen, Advantys STB, Profibus DP and DeviceNet communication modules.
For other registers and for further information, please consult the User's Manual Communication variables on the website www.schneider-electric.com
Control unit present in the product Standard Advanced Multifunction
Marking Register 0…Register 99 Words…Bits Commercial reference, serial number, software version
Log Register 100…Register 450 Words…Bits Fault log, Operating log, Log of last 5 trips
Status Register 451…Register 464 Words…Bits Alarm signalling (bits), Fault signalling (bits)
Values Register 465…Register 473 Words Irms phase 1, phase 2, phase 3. Motor load, thermal status
Earth leakage current.
Phase imbalance and phase failure
Register 474…Register 599 Words…Bits Reserved
Configuration Register 600…Register 699 Words…Bits Protection and alarm thresholds, fallback mode and reset
mode
TeSys U
Commands Register 700…Register 714 Words…Bits Commands
Data accessible
A4/61
Basic schemes - TeSys U 1
TeSys U starter-controllers
Non-reversing
3/L2
5/L3
DF510449.eps
Control Unit
U1 2/T1
V1 4/T2
W1 6/T3
M
3
2-wire control via 2-position switch 3-wire control, pulsed start with Connection of a motor load indicator
TeSys U
DF510456.eps
DF510450.eps
DF510514.eps
07
08
07
08
LUF DA10 Automatic or remote reset LUF DA10 Automatic or remote reset
24…230 V 24…230 V
X1
X2
Z1
Z2
X1
X2
Z1
Z2
A2 A1 A2 A1
– QF1 – QF1 – S2
– S1 – S1
Control via Modbus communication module Control via Modbus communication module LUL C033
LUL C031
Without pre-wired coil connection Without pre-wired coil connection
DF510600.eps
DF510606.eps
24 V Aux 24 V 24 V
GND
GND
D(A)
D(B)
D(A)
D(B)
c Aux COM
Com
OA1
OA3
LO1
Com
Com
OA1
OA3
LO1
LI1
LI2
4 5 8
6 4 5 8
6
– S1 – S2
Modbus Modbus
A2 A1 A2 A1
A4/62
Basic schemes (continued) - TeSys U 1
TeSys U starter-controllers
Non-reversing
DF533859.eps
DF533858.eps
ASILUF C5 or ASILUF C51 AS-Interface Module ASILUF C5 or ASILUF C51 AS-Interface Module
AS-Interface AS-Interface
Com
OA1
OA3
Com
OA1
OA3
AS-Interface line AS-Interface line
Adjustment
A2 A1
Normal
A2 A1
TeSys U
With pre-wired coil connection LU9B N11C Without pre-wired coil connection
With local control
DF533860.eps
DF533861.eps
ASILUF C5 or ASILUF C51 AS-Interface Module ASILUF C5 or ASILUF C51 AS-Interface Module
AS-Interface AS-Interface
Com
LU9B N11C
OA1
OA3
OA1
OA3
A2 A1 AS-Interface line
24 V Aux
4 5 8
6
Bus Modbus
RS 485
A4/63
Basic schemes (continued) - TeSys U 1
TeSys U starter-controllers
Reversing
3/L2
5/L3
561148.eps
561149.eps
561150.eps
LU2B Reverser Motor Controller LU2B Reverser Motor Controller
A3
B3
A1
B1
A2
A3
B3
A1
B1
A2
Start
forward running
Control Unit
Stop Stop
forward running forward running forward running Start
and reverse reverse running
2/T1
4/T2
6/T3
Stop running
reverse running
Stop
reverse running
U1 2/T1
V1 4/T2
W1 6/T3
M
3
TeSys U
Control by communication modules ASILUF C5 3-wire control, pulsed start with maintaining contact and limit switches
and ASILUF C51
With pre-wired coil connection LU9M RC
With multifunction control unit LUCM
DF510955.eps
561152.eps
AS-Interface
LU9M RC A3
B3
A1
B1
A2
Pre wired coil
Stop forward
running
LUCM Multifunction Control Unit and reverse
running Limit switch Stop Start
reverse running reverse running reverse running
GND
D(A)
D(B)
24 V Aux
4 5 8
6
Bus Modbus
RS 485
OA1
OA3
A3
B3
A1
B1
A2
AS-Interface line
53 54 81 84
82
A4/64
Basic schemes (continued) - TeSys U 1
TeSys U starter-controllers
Reversing
Without pre-wired coil connection. With local control Without pre-wired coil connection. With local control
DF510607.eps
DF510601.eps
LU2B Reverser LUL C031 Modbus Module LU2B Reverser LULC 033 Modbus Module
Motor Motor
Controller Controller 24 V 24 V
GND
GND
24 V Aux
D(A)
D(A)
D(B)
D(B)
c Aux COM
Com
Com
Com
OA1
OA3
OA1
OA3
LO1
LO1
LI1
LI2
A3
B3
A1
B1
A2
A3
B3
A1
B1
A2
4 5 8
6 4 5 8
6
Modbus Modbus
Start forward
Start
Adjustment
running
Adjustment
forward running
Normal
Start reverse
Normal
running Start
reverse running
TeSys U
Reversing starter-controllers LUB + LU6M
1/L1
3/L2
5/L3
561155.eps
Control Unit
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
U1 2/T1
4/T2
W1 6/T3
V1
M
3
3-wire control, pulsed start with maintaining contact 2-wire control via 3-position switch
DF510956.eps
DF565412.eps
A1 A2 A1 A2
13 14
21 22
21 22
S1
S2
S3
S2
S3
B3
A1
B1
A2
Stop
A3
B3
A1
B1
A2
forward running
and reverse Stop Start
running forward running forward running
S5 S6 S8
forward running
Stop Start Stop
reverse running reverse running reverse running
S7 S9
A4/65
Presentation - TeSys U
Soft starters for asynchronous motors
Altistart U01 and TeSys U
Presentation
DF536566.eps
1
The Altistart U01 is a soft start/soft stop unit for asynchronous motors. It is designed
primarily for combinations with TeSys U controller-starters.
Using the Altistart U01 starter enhances the starting performance of asynchronous
motors by allowing them to start gradually, smoothly and in a controlled manner. It
prevents mechanical shocks, which lead to wear and tear, and limits the amount of
maintenance work and production downtime.
The Altistart U01 limits the starting torque and current peaks on starting, on machines
which do not require a high starting torque.
b Small cranes
b Belt-driven machines, etc.
The Altistart U01 is compact and easy to install. It complies with standards IEC/EN
60947-4-2, carries UL, CSA, C-Tick, CCC certifications and e marking.
Description
9 b Altistart U01 soft start/soft stop units are equipped with:
v A potentiometer for setting the starting time 6
v A potentiometer for setting the deceleration time 8
v A potentiometer for adjusting the start voltage threshold according to the motor
load 7
v 1 green LED 4 to indicate that the unit is switched on
v 1 yellow LED 5 to indicate that the motor is powered at nominal voltage, if it
is connected to the starter
v A connector 9:
- 2 logic inputs for Run/Stop commands
- 1 logic input for the BOOST function
- 1 logic output to indicate the end of starting
- 1 relay output to indicate the starter has a power supply fault or the motor has
reached a standstill at the end of the deceleration stage
DF536567.eps
+ 24 V LI1 LI2
b 3-wire control
The run and stop commands are controlled by 2 different logic inputs.
Stopping is achieved when logic input LI1 opens (state 0).
The pulse on input LI2 is stored until input LI1 opens.
Altistart U01 control terminals
DF536568.eps
TeSys U
+ 24 V LI1 LI2
b Starting time
Controlling the starting time means that the time of the voltage ramp applied to the
motor can be adjusted to obtain a gradual starting time, dependent on the motor load.
100%
Un
Voltage ramp
50%
Un
Initial voltage
t
200 ms
Application of a voltage boost equal to 100% of the nominal
motor voltage
b End of starting
v application function for logic output LO1
ATSU 01N2ppLT soft start/soft stop units are equipped with an open collector logic
output LO, which indicates the end of starting when the motor has reached nominal
speed.
Environmental characteristics
Type of starter ATSU 01N2ppLT
Conformity to standards Altistart U01 electronic starters have been developed to conform to the strictest
international standards and the recommendations relating to electrical industrial
control devices (IEC, EN), in particular standard IEC/EN 60947-4-2.
Electromagnetic compatibility EMC
Conducted and radiated CISPR 11 level B, IEC 60947-4-2, level B
emissions
Harmonics IEC 1000-3-2, IEC 1000-3-4
EMC immunity EN 50082-2, EN 50082-1
Electrostatic discharge IEC 61000-4-2 level 3
Immunity to radiated radio- IEC 61000-4-3 level 3
electrical interference
Immunity to electrical transients IEC 61000-4-4 level 4
Voltage/current impulse IEC 61000-4-5 level 3
Conducted and radiated IEC 61000-4-6 level 3
emissions
Immunity to conducted IEC 61000-4-11
interference caused by
radio-electrical fields
Damped oscillating waves IEC 61000-4-12 level 3
e marking The starters carry e marking in accordance with the European low voltage directives
IEC/EN 60947-4-2.
TeSys U
Electrical characteristics
Type of starter ATSU 01N2ppLT
Category of use Conforming to IEC 60947-4-2 Ac-53b
Rated operating voltage 3-phase a voltage V 200 - 10 % to 480 + 10 %
Frequency Hz 50 - 5 % to 60 + 5 %
Output voltage Maximum 3-phase voltage equal to line supply voltage
Control supply voltage 24 V c, 100 mA ±10 %
Rated operating current A 6...32
Adjustable starting time s 1...10
Adjustable deceleration time s 1...10
Starting torque % 30.... 80 % of DOL motor starting torque
Type of starter ATSU 01N206LT 01N209LT 01N212LT 01N222LT 01N232LT
Control power supply consumption 24 V c, 65 mA 24 V c, 100 mA
Power dissipated At full load at end of starting W 1.5 1.5 1.5 2.5 2.5
In transient state at 5 times the W 61.5 91.5 121.5 222.5 322.5
rated operating current
Type of starter ATSU 01N206LT to ATSU 01N222LT ATSU 01N232LT
Use
I Starting time Starting time s 1 5 10 1 5 10
Maximum number of cycles per 100 20 10 50 10 5
hour
Full voltage state or
starter at standstill
t
Operating cycle
TeSys U
Flexible wire with cable end 1 conductor mm2 1…6 10 AWG
2 conductors mm2 1…6 10 AWG
Rigid wire 1 conductor mm2 1…10 8 AWG
2 conductors mm2 1…6 10 AWG
Tightening torque N.m 1.9…2.5
The diagram opposite shows the torque/speed characteristic of a cage motor in relation to the
U
3 Tn supply voltage.
The torque varies in line with the square of the voltage at a fixed frequency. The gradual increase
0,85 U in the voltage prevents the instantaneous current peak on power-up.
2 Tn
0,6 U Tr
Tn
0 N/Ns
0 0,25 0,5 0,75 1
4 5 7.5 10 22 ATSU01N222LT
5.5 7.5 11 15
7.5 10 15 20 32 ATSU01N232LT
ATSU 01N222LT
TeSys U
1 Accessorie
DF536570.eps
ATSU 01N2ppLT (1) Standard motor power ratings, HP power ratings indicated according to standard UL 508.
(2) Depending on the configuration of the chosen TeSys U starter, replace the p with A for
standard, B for expandable, and M for multifunction.
TeSys U combination (non-reversing power base) and TeSys U combination (non-reversing or reversing power base)
ATSU 01N206LT to ATSU 01N212LT and ATSU 01N206LT to ATSU 01N212LT
Mounting on 5 (35 mm) rail with VW3 G4104 connector Side by side mounting
45 135
DF536571.eps
DF536572.eps
99
72,2
154
124
284
150
TeSys U
9
TeSys U combination (non-reversing power base) and TeSys U combination (non-reversing or reversing power base)
ATSU 01N222LT to ATSU 01N232LT and ATSU 01N222LT to ATSU 01N232LT
Mounting on 5 (35 mm) rail with VW3 G4104 connector Side by side mounting
45 135 99
DF536573.eps
DF536574.eps
72,2
154
170
314
VW3 G4104 connector
DF536575.eps
46,6
20 44,8
28
6
3/L2
5/L3
1/L1
3/L2
5/L3
DF536577.eps
DF536576.eps
– QF1 – QF1
TeSys U
TeSys U
CU CU with
reversing
TeSys U TeSys U unit
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
A1
2/T1
4/T2
6/T3
ATSU 01N2ppLT
TeSys U
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
A1
M1 ATSU 01N2ppLT
3
2/T1
4/T2
6/T3
M1
3
Compatible components
Code Description
A1 Soft start/soft stop unit
QF1 TeSys U controller-starter
CU TeSys U control unit
DF536579.eps
+ +
ATSU 01N2ppLT ATSU 01N2ppLT
17
17
BOOST
BOOST
+ 24 V
+ 24 V
18
18
COM
COM
R1C
R1A
R1C
R1A
LO1
LO1
LI1
LI2
LI1
LI2
Stop
Run
– S1 – S1
Stop
Run
A1
– QF1 – S2
A2
A1
– QF1
A2
–
Functional diagrams
Power supply Power supply
DF536580.eps
DF536581.eps
voltage voltage
Green LED
TeSys U
Green LED
Logic input LI2
Logic input LI2 Pushbutton S2
Pushbutton S1 Pushbutton S1
U1
+ +
ATSU 01N2ppLT ATSU 01N2ppLT
17
17
BOOST
+ 24 V
+ 24 V
18
18
COM
COM
R1C
R1A
R1C
R1A
LO1
LO1
LI1
LI2
LI1
LI2
– S1
– S2 – S2
14 13
13
– QF1
A1
– QF1
14
– QF1
A1
A2
– – S1
– QF1
A2
Functional diagrams
Power supply Power supply
voltage
DF536584.eps
DF536585.eps
voltage
Green LED Green LED
500 ms
Pushbutton S1 Logic input LI2
Pushbutton S2
Pushbutton S2 Logic input LI1
Pushbutton S1
Logic input LI2
Logic output LO1
Logic output LO1
Yellow LED Yellow LED
10 s 10 s
U1
DF536587.eps
LU2B p2BL ATSU 01N2ppLT LU2B p2BL ATSU 01N2ppLT
BOOST
BOOST
+ 24 V
+ 24 V
COM
COM
R1C
R1C
R1A
R1A
LO1
LO1
LI1
LI2
LI1
LI2
A3
B3
A1
B1
A2
A3
B3
A1
B1
A2
Run
Run direction 1
direction 1
Run – S1
Run – S1 direction 2
direction 2 – S2
– S2
Stop
Stop – S3
– S3
17
17
18
TeSys U
+ +
c 24 V c 24 V
– –
QF1: TeSys U controller-starter with reversing unit QF1: TeSys U controller-starter with reversing unit
A1: Soft start/soft stop unit A1: Soft start/soft stop unit
S1, S2, S3: XB4 B or XB5 B pushbuttons S1, S2, S3: XB4 B or XB5 B pushbuttons
S3: minimum depression time 500 ms
Boost on starting and end of starting signal
A1
DF536588.eps
ATSU 01N2ppLT
BOOST
+ 24 V
COM
R1C
R1A
LO1
LI1
LI2
To PLC
DF536590.eps
ATSU 01N2ppLT LUL C031 Modbus Module ATSU 01N2ppLT LUL C031 Modbus Module
BOOST
BOOST
+ 24 V
+ 24 V
D(B)
D(A)
D(B)
D(A)
Gnd
Gnd
COM
COM
COM
COM
COM
c 24 V 24 V Aux. c 24 V 24 V Aux.
R1C
OA1
OA3
R1C
R1A
R1A
LO1
LU9B N11C
LO1
LO1
LO1
LI1
LI2
LI1
LI2
Pre-wired coil + – + – 4 5 8 + – + – 4 5 8
+
13
c 24 V
+
14
c 24 V QF1
LU2B p2BL
A3
B3
A1
B1
A2
TeSys U
Function Register Bit Value Function Register Bit Value
Powering down TeSys U and ATSU Powering up TeSys U and ATSU
– 704 0 0 Forward 704 0 1
Reverse 704 1 1
Automatic control without deceleration Powering down TeSys U and ATSU
Run 700 0 1 Forward 704 0 0
Stop 704 0 0 Reverse 704 1 0
Automatic control with deceleration Automatic control without deceleration
Run 700 0 1 Run 700 0 1
Soft stop 700 0 0 Stop forward 704 0 0
Stop reverse 704 1 0
Automatic control with deceleration (forward or reverse)
Run 700 0 1
Soft stop 700 0 0
A1: Soft start/soft stop unit A1: Soft start/soft stop unit
QF1: TeSys U controller-starter with reversing unit
Automatic control with AS-Interface communication module, without deceleration
Without reversing unit With reversing unit
A1 A1
DF536591.eps
DF536592.eps
BOOST
+ 24 V
+ 24 V
COM
COM
R1C
R1C
R1A
R1A
LO1
LO1
LI1
LI2
LI1
LI2
13
QF1
ASI LUFC5 ASI LUFC5
LU2B p2BL
14
c 24 V AS-Interface
COM
Pre-wired coil + +
A3
B3
A1
B1
A2
+ +
+ +
c 24 V c 24 V
control unit LUCLpp, used in conjunction with an LUB 12 or LUB 32 power base,
provides:
vv isolation,
vv short-circuit protection of the motor starter.
(variable speed controller-based or soft start unit-based motor starters).
Note: control unit LUCL, when used in conjunction with power base LUB 12 or
LUB 32, conforms to standard IEC 60947-2.
S2 (mm2 / AWG) LUB pp LUCLpp
Installation regulations
When the length of the cable between the TeSys U starter and the variable speed
controller is more than 1.5 m, the c.s.a. of the cable between the variable speed
controller and the TeSys U starter (S2) must be equal to the c.s.a. of the cable
upstream of TeSys U (S1).
Altivar or Altistart
TeSys U
Description
PF526111.tif
3
References
4 Description Line current of the Reference
variable speed controller (1)
A4/76
Selection - TeSys U
TeSys motor starters - open version
Magnetic control unit for the protection of variable speed controllers
and soft start stop units
Operating characteristics
Control units Standard Advanced Multifunction
LUCA LUCB LUCC LUCD LUCL LUCM
Thermal overload protection
Over current protection 14.2 x the setting current 3 to 17 x the setting
current
Short-circuit protection 13 x lr max (max current setting)
Protection against phase loss
TeSys U
Protection against phase imbalance
Earth fault protection (equipment protection only)
Tripping class 10 10 20 5…30
Motor type 3-phase Single-phase 3-phase Single-phase and 3-phase
Thermal overload test function
Overtorque
No-load running
Long starting time
Reset method Manual Parameters can be set
Automatic or remote With function module, or parameters can Parameters can be set
be set via the bus with a communication Parameters can be set
module (see page 24614/2). via the bus with a
communication module
(see page 24614/2).
Integrated function Function provided with accessory
Compatibility
Compatibility of References Functions
control unit LUCLpp with
The starter-controller Yes LUB 12/LUB 32 Starter-controller (magnetic protection)
The starter No LUS 12/LUS 32 Starter without either magnetic or thermal overload protection)
Add-on contact blocks Yes LUA 1C11 Add-on contact blocks with fault signalling (1 N/O + 1 N/C)
with fault signalling LUA 1C20 Add-on contact blocks with fault signalling (2 N/O)
and auxiliary contacts
LUF N20 Auxiliary contacts (2 N/O)
LUF N11 Auxiliary contacts (1 N/O + 1 N/C)
LUF N02 Auxiliary contacts (2 N/C)
A4/77
Characteristics - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Environment
Product certifications CE
Conforming to standards When used in conjunction an LUB power base, control unit LUCL conforms to
standard 60947-2.
Rated insulation voltage (Ui) Conforming to IEC/EN 60947-1, V 690
overvoltage category III,
degree of pollution: 3
Rated impulse withstand Conforming to IEC/EN 60947-2 kV 6
voltage (Uimp)
Safety separation of circuits Conforming to IEC/EN 60947-1 V Between the control or auxiliary circuit and the main circuit: 400
SELV appendix N Between the control and auxiliary circuits: 40
Degree of protection Front panel outside connection IP 40
Conforming to IEC/EN 60947-1 zone
(protection against Front panel and wired terminals IP 20
TeSys U
DF568029.eps
mounting plane
A4/78
Characteristics - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Power bases and LUCL magnetic control unit
TeSys U
Tightening torque N.m 0.8…1.2 0.8…1.2
Control circuit characteristics
Rated control a 50/60 Hz V 24…240 24…240
circuit voltage c V 24…220 24…220
Voltage limits c 24 V (1) V 20…27 20…27
Operation a 24 V V 20…26.5 20…26.5
a or c 48…72 V V a 38.5…72. c 38.5…93 a 38.5…72. c 38.5…93
a 110…240 V V a 88…264 a 88…264
c 110…240 V V c 88…242 c 88…242
Drop-out c 24 V V 14.5 14.5
a 24 V V 14.5 14.5
a or c 48…72 V V 29 29
a 110…240 V, c 110…220 V V 55 55
Typical consumption c 24 V mA 130 220
I max while closing a 24 V mA 140 220
a or c 48…72 V mA 280 280
a 110…240 V, c 110…220 V mA 280 280
I rms sealed c 24 V mA 60 80
a 24 V mA 70 90
a or c 48…72 V mA 35 45
a 110…240 V, c 110…220 V mA 35 25
Heat dissipation W 2 3
Operating time Closing ms 24 V: 70; 48 V: 60; u 72 V: 50 24 V: 70; 48 V: 60; u 72 V: 50
Opening ms 35 35
Resistance to micro-breaks ms 3 3
Resistance to voltage dips IEC/EN 61000-4-11 At least 70 % of Uc for 500 ms
Mechanical durability In millions of operating cycles 15 15
Maximum operating rate In operating cycles per hour 3600 3600
Main pole characteristics
Number of poles 3 3
Isolation Possible Yes Yes
conforming to IEC/EN 60947-1 Padlocking 1 padlock with Ø6.9 mm shank 1 padlock with Ø6.9 mm shank
Rated thermal current A 12 32
Rated operational current Conforming Category AC-41 θ y 70 °C: 12 A θ y 70 °C: 32 A
(Ue y 440 V) to IEC/EN Category AC-43 θ y 70 °C: 12 A θ y 70 °C: 32 A
60947-2
Rated operational voltage V 690 (3) 690 (3)
Frequency limits Of the operating current Hz 40…60 40…60
Power dissipated Operational current A 3 6 9 12 18 25 32
in the power circuits Power dissipated W 0.1 0.3 0.6 1.1 2.4 4.6 7.5
in all three poles
Rated breaking capacity on short-circuit V 230 440 500 600
kA 50 50 10 4
Total breaking time ms 2 2 2
Thermal limit With Isc max on 440 V kA2s 90 120
(1) d.c. voltage with maximum ripple of ± 10 %.
(2) No consumption sealed.
(3) For 690 V, use phase barrier LU9SP0.
A4/79
Combinations - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
Coordination
The standard defines tests at different levels of current; the purpose of these tests
is to place the equipment in extreme conditions.
The standard defines 2 types of coordination, according to the condition of the
components after testing: type 1 and type 2.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter
must not present any danger to personnel or installations and must not be able to
resume operation without repair or the replacement of parts.
The product combinations given below provide type 1 coordination
PF526113-26-M.tif
PB113857.eps
+ ATV21HU15N4
A4/80
Combinations - TeSys U
TeSys motor starters - open version
TeSys U starter-controllers
TeSys U
7.5 LUB32 + LUCL32 ATV31HU75N4
A4/81
A4/82