Polytechnic
University
Collage of Engineering and Technology
Department of Civil and Architectural Engineering
Reinforced
Concrete
II
Dr. Nasr Younis Abboushi
2013-2014
Reinforced Concrete II Dr. Nasr Abboushi
CONTENTS
II - iii
Reinforced Concrete II Dr. Nasr Abboushi
II - iv
Reinforced Concrete II Dr. Nasr Abboushi
Structural concrete slabs are constructed to provide flat surfaces, usually horizontal, in
building floors, roofs, bridges, and other types of structures. The slab may be supported by
walls, by reinforced concrete beams usually cast monolithically with the slab, by structural
steel beams, by columns, or by the ground. The depth of a slab is usually very small
compared to its span.
185
Reinforced Concrete II Dr. Nasr Abboushi
form fillers (pans), which may be used many times. In some ribbed slabs, the spaces
between ribs may be filled with permanent fillers to provide a horizontal slab.
3. Two-way floor systems: When the slab is supported on four sides and the ratio of
the long side to the short side is less than ( ), the slab will deflect in
double curvature in both directions. The floor load is carried in two directions to the four
beams surrounding the slab. Other types of two-way floor systems are flat plate floors, flat
slabs, and waffle slabs. This chapter deals only with one-way floor systems.
187
Reinforced Concrete II Dr. Nasr Abboushi
In statically determinate structures, such as simple-span beams, the deflected shape and
the moments and shears depend only on the type and magnitude of the loads and the
dimensions of the member. In contrast, inspection of the statically indeterminate structures
shows that the deflection curve of any member depends not only on the loads but also on
the joint rotations, whose magnitudes in turn depend on the distortion of adjacent, rigidly
connected members.
Continuous beams and frames can be analyzed using approximate methods or computer
programs, which are available commercially. Other methods, such as the displacement and
force methods of analysis based on the calculation of the stiffness and flexibility matrices,
may also be adopted. Slope deflection and moment-distribution methods may also be used.
These methods are explained in books dealing with the structural analysis of beams and
frames. However, the ACI Code, Section 8.3, gives approximate coefficients for calculating
the bending moments and shear forces in continuous beams and slabs. These coefficients
were given in Section 8.3 of this Chapter. The moments obtained using the ACI coefficients
will be somewhat larger than those arrived at by exact analysis. The limitations stated in the
use of these coefficients must be met.
In the structural analysis of continuous beams, the span length is taken from center to
center of the supports, which are treated as knife-edge supports. In practice, the supports
are always made wide enough to take the loads transmitted by the beam, usually the
moments acting at the face of supports. To calculate the design moment at the face of the
support, it is quite reasonable to deduct a moment equal to from the factored
moment at the centerline of the support, where is the factored shear and is the column
width.
According to ACI Code Section 8.9 – Span Length:
8.9.1 — Span length of members not built integrally with supports shall be considered as the
clear span plus the depth of the member, but need not exceed distance between
centers of supports.
8.9.2 — In analysis of frames or continuous construction for determination of moments,
span length shall be taken as the distance center-to-center of supports.
8.9.3 — For beams built integrally with supports, design on the basis of moments at faces of
support shall be permitted.
8.9.4 — It shall be permitted to analyze solid or ribbed slabs built integrally with supports,
with clear spans not more than 3 m, as continuous slabs on knife edge supports
with spans equal to the clear spans of the slab and width of beams otherwise
neglected.
The individual members of a structural frame must be designed for the worst combination of
loads that can reasonably be expected to occur during its useful life. Internal moments,
shears, and thrusts are brought about by the combined effect of dead and live loads, plus
other loads, such as wind and earthquake. While dead loads are constant, live loads such as
floor loads from human occupancy can be placed in various ways, some of which will result
in larger effects than others.
188
Reinforced Concrete II Dr. Nasr Abboushi
For structural analysis of continuous beam or rib to obtain the shear and moment diagrams,
it shall be permitted according to ACI code, 8.11.2, to assume that the arrangement of live
load is limited to combinations of:
a. Factored dead load on all spans with full factored live load on two adjacent
spans; and
b. Factored dead load on all spans with full factored live load on alternate spans.
LL
DL
LL
DL
LL LL
DL
LL
DL
189
Reinforced Concrete II Dr. Nasr Abboushi
190
Reinforced Concrete II Dr. Nasr Abboushi
8.3 ANALYSIS AND DESIGN OF ONE-WAY SOLID SLABS. ACI CODE LIMITATIONS.
If the concrete slab is cast in one uniform thickness without any type of voids, it can be
referred to as a solid slab. In a one-way stab nearly all the loading is transferred in the short
direction, and the slab may be treated as a beam. A unit strip of slab, usually 1 m at right
angles to the supporting girders, is considered a rectangular beam. The beam has a unit
width with a depth equal to the thickness of the slab and a span length equal to the distance
between the supports. A one-way slab thus consists of a series of rectangular beams placed
side by side.
If the slab is one span only and rests freely on its supports, the maximum positive moment
for a uniformly distributed load of is , where is the span length
between the supports. If the same slab is built monolithically with the supporting beams or
is continuous over several supports, the positive and negative moments are calculated by
structural analysis or by moment coefficients as for continuous beams. The ACI Code,
Section 8.3, permits the use of moment and shear coefficients in the case of two or more
approximately equal spans.
The maximum positive and negative moments and shears are computed from the following
expressions:
191
Reinforced Concrete II Dr. Nasr Abboushi
( )
( )
where and are moment and shear coefficients given in table below and figure (page
193).
For all positive midspan moments, all shears and the negative moment at exterior
supports, , is for the span under consideration. For the negative moment at interior
supports, , shall be taken as ( ) as defined in the figure above.
192
Reinforced Concrete II Dr. Nasr Abboushi
193
Reinforced Concrete II Dr. Nasr Abboushi
The conditions under which the moment coefficients for continuous beams and slabs should
be used can be summarized as follows:
1. Spans are approximately equal: Longer span (shorter span).
2. Loads are uniformly distributed.
3. The ratio (live load/dead load) is less than or equal to .
4. For slabs with spans less than or equal to , negative bending moment at
face of all supports is ( )
5. For an unrestrained discontinuous end, the coefficient is at end support and
( ) at midspan.
6. Shear force at C is and at the face of all other support is ( ) .
7. The members are prismatic.
When these conditions are not satisfied, structural analysis is required. In structural analysis,
the negative bending moments at the centers of the supports are calculated. The value that
may be considered in the design is the negative moment at the face of the support, ACI
8.9.2, 8.9.3.
194
Reinforced Concrete II Dr. Nasr Abboushi
For structural slabs and of uniform thickness, in the direction of the span shall be the
same as that required by 7.12.2.1 for temperature and shrinkage reinforcement (see section
8.5).
195
Reinforced Concrete II Dr. Nasr Abboushi
Maximum spacing of this reinforcement shall not exceed three times the thickness, nor
.
To limit the widths of flexural cracks in beams and slabs, ACI Code Section 10.6.4 defines
upper limit on the center-to-center spacing between bars in the layer of reinforcement
closest to the tension face of a member. The spacing limit is:
( )
but
( )
Concrete shrinks as the cement paste hardens, and a certain amount of shrinkage is usually
anticipated. If a slab is left to move freely on its supports, it can contract to accommodate
the shrinkage. However, slabs and other members are joined rigidly to other parts of the
structure, causing a certain degree of restraint at the ends. This results in tension stresses
known as shrinkage stresses. A decrease in temperature and shrinkage stresses is likely to
cause hairline cracks. Reinforcement is placed in the slab to counteract contraction and
distribute the cracks uniformly. As the concrete shrinks, the steel bars are subjected to
compression.
Reinforcement for shrinkage and temperature stresses normal to the principal
reinforcement should be provided in a structural slab in which the principal reinforcement
extends in one direction only.
The ACI Code, Section 7.12.2, specifies that: area of shrinkage and temperature
reinforcement shall provide at least the following ratios of reinforcement area to gross
concrete area, but not less than :
For slabs in which grade 280 ( ) or 350 ( ) deformed bars
are used, .
For slabs in which grade 420 ( ) deformed bars or welded bars or
welded wire fabric are used, .
For Slabs where reinforcement with yield stress exceeding measured at a
×
yield strain of percent is used, 𝜌
𝑓𝑦
Shrinkage and temperature reinforcement shall be spaced not farther apart than five times
the slab thickness, nor farther apart than .
196
Reinforced Concrete II Dr. Nasr Abboushi
For temperature and shrinkage reinforcement, the whole concrete depth exposed to
shrinkage shall be used to calculate the steel area.
In continuous one-way slabs, the steel area of the main reinforcement is calculated for all
critical sections, at midspans, and at supports. The choice of bar diameter and detailing
depends mainly on the steel areas, spacing requirements, and development length. Two bar
systems may be adopted.
In the straight-bar system: straight bars are used for top and bottom reinforcement
in all spans. The time and cost to produce straight bars is less than that required to
produce bent bars; thus, the straight-bar system is widely used in construction.
In the bent-bar, or trussed, system: straight and bent bars are placed alternately in
the floor slab. The location of bent points should be checked for flexural, shear, and
development length requirements. For normal loading in buildings, the bar details at
the end and interior spans of one-way solid slabs may be adopted as shown in
figures.
197
Reinforced Concrete II Dr. Nasr Abboushi
198
Reinforced Concrete II Dr. Nasr Abboushi
199
Reinforced Concrete II Dr. Nasr Abboushi
Example:
Design a simply supported one-way solid slab, span of , subjected to service live load
( ). Dead Load – own weight only. and .
𝑚
𝑚 𝑠𝑡𝑟𝑖𝑝
Solution:
Minimum thickness (deflection requirements). For simply supported one-way solid
slab:
Loads calculation:
𝑚𝑚
𝑚𝑚
s 𝑚𝑚
Cover
( √ ) ( √ )
Provide
Use then
200
Reinforced Concrete II Dr. Nasr Abboushi
Take .
Step ( ) is the smallest of:
1. ×
2.
( ) ( )
( ) ( )
( )
Take .
Step ( ) is the smallest of:
1. ×
2.
–
𝑚𝑚
𝑚𝑚
Example:
The cross-section of a continuous one-way solid slab in a building is shown below. The slabs
are supported by beams that span between simple supports. The dead load on the
slabs is that due to self-weight plus ; the live load is . Design the
continuous slab and draw a detailed section. Given: and .
201
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
Minimum thickness (deflection requirements).
( )
( )
Loads calculation:
202
Reinforced Concrete II Dr. Nasr Abboushi
× ×
√ √
- for shear.
×
Even, if for solid slabs, the thickness of the slab will be enough.
( )
Location
C ( )
D ( )
( √ ) ( √ )
203
Reinforced Concrete II Dr. Nasr Abboushi
Use then
Take .
Step ( ) is the smallest of:
1. ×
2.
( ) ( )
( ) ( )
–
Midspan section E:
( √ ) ( √ )
Use then
Take .
–
Slab Design for the negative moments:
Note that the second support has two values of moments by analysis, at section C and
section D. In construction, the provided reinforcement will be the same bar diameters on
opposite sides of the support, so the design may be done for the maximum moment of the
two moments at C and D (Only one design for Support section C).
204
Reinforced Concrete II Dr. Nasr Abboushi
Support section C:
( √ ) ( √ )
Use then
Take .
–
( √ ) ( √ )
Use then
Take .
–
205
Reinforced Concrete II Dr. Nasr Abboushi
Support section A:
( √ ) ( √ )
Provide
Use then
Take .
–
Temperature and shrinkage reinforcement.
( )
Take .
Step ( ) is the smallest of:
1. ×
2.
–
Required Provided
Location Reinforcement
A 3.3 ( )
B 3.3 ( )
C and first
3.3 ( )
interior D
Interior D 3.3 ( )
E 3.3 ( )
Temperature and shrinkage
reinforcement ( )
206
Reinforced Concrete II Dr. Nasr Abboushi
Example:
Design the one-way solid slab, which plan is shown below. The dead load on the slabs is that
due to self-weight plus weight of:
• Tiles, .
• Mortar, .
• Sand, .
• Plaster, .
• Partitions, .
The live load is .
Given:
and .
𝑚
𝑚 𝑚 𝑚
Solution:
Minimum thickness
(deflection requirements).
From the maximum span
length for one-end
continuous, we get
𝑚 𝑚
Loads calculation:
207
Reinforced Concrete II Dr. Nasr Abboushi
Quality Density
Material
Tiles ×
mortar ×
Sand ×
Reinforced Concrete solid slab ×
Plaster ×
Partitions
Total Dead Load
208
Reinforced Concrete II Dr. Nasr Abboushi
√ √
- for shear.
( √ ) ( √ )
× ×
Use then
Take .
Step ( ) is the smallest of:
1. ×
2.
( ) ( )
( ) ( )
( ) ( )
210
Reinforced Concrete II Dr. Nasr Abboushi
( √ ) ( √ )
Use then
Take
–
( √ ) ( √ )
Use then
Take
–
211
Reinforced Concrete II Dr. Nasr Abboushi
Take .
Step ( ) is the smallest of:
1. ×
2.
–
A one-way joist floor system consists of hollow slabs with a total depth greater than that of
solid slabs. The system is most economical for buildings where superimposed loads are small
and spans are relatively large, such as schools, hospitals, and hotels. The concrete in the
tension zone is ineffective; therefore, this area is left open between ribs or filled with
lightweight material to reduce the self-weight of the slab.
212
Reinforced Concrete II Dr. Nasr Abboushi
The design procedure and requirements of ribbed slabs follow the same steps as those for
rectangular and T-sections explained in Chapter 4. The following points apply to design of
one-way ribbed slabs:
1. Ribs are usually tapered and uniformly spaced at about . Voids are
usually formed by using pans (molds) wide and deep,
depending on the design requirement. The standard increment in depth is 50 mm.
2. The ribs shall not be less than wide and must have a depth of not more than
times the width. Clear spacing between ribs shall not exceed (ACI Code,
Section 8.13).
213
Reinforced Concrete II Dr. Nasr Abboushi
3. Shear strength, , provided by concrete for the ribs may be taken greater than
that for beams. This is mainly due to the interaction between the slab and the closely
spaced ribs (ACI Code, Section 8.13.8).
4. The thickness of the slab on top of the ribs is usually and contains
minimum reinforcement (shrinkage reinforcement). This thickness over permanent
fillers shall not be less than ( ) of the clear span between ribs or (ACI Code,
Section 8.13.5.2). When removable forms or fillers are used slab thickness shall be
not less than ( ) of the clear distance between ribs, nor less than . (ACI
Code, Section 8.13.6.1)
5. The ACI coefficients for calculating moments in continuous slabs can be used for
continuous ribbed slab design.
If the live load on the ribbed slab is less than and the span of ribs exceeds ,
a secondary transverse rib (distribution rib) should be provided at midspan (its direction is
perpendicular to the direction of main ribs) and reinforced with the same amount of steel as
the main ribs. Its top reinforcement shall not be less than half of the main reinforcement in
the tension zone. These transverse ribs act as floor stiffeners. If the live load exceeds
and the span of ribs varies between and , one traverse rib must be provided,
as indicated before. If the span exceeds , at least two transverse ribs at one-third span
must be provided with reinforcement, as explained before.
214
Reinforced Concrete II Dr. Nasr Abboushi
215
Reinforced Concrete II Dr. Nasr Abboushi
Reinforcement for the joists usually consists of two bar in the positive bending region, with
one bar discontinued where no longer needed or bent up to provide a part of the negative
steel requirement over supporting girder. According to ACI Code section 7.13.2 at least one
bottom bar must be continuous over the support, or at non continuous supports, terminated
in a standard hook, as a measure to improve structural integrity in the event of major
structural damage.
The minimum thickness of beams or ribbed one way slabs depending on the support
conditions can be determined according to ACI Code 9.5.2. (see table 9.5(a), page 194).
216
Reinforced Concrete II Dr. Nasr Abboushi
Quality Density
Material
Tiles
mortar
Sand
Reinforced Concrete
Hollow Block
Plaster
Partitions
217
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
Rib 2 800 mm
800 mm
Beam 1
Beam 4
Beam 3
Beam 2
Beam 6
Beam 5
Rib 1
218
Reinforced Concrete II Dr. Nasr Abboushi
The maximum span length for both-ends continuous (for ribs): then
The maximum span length for one-end continuous (for Beams): then
The maximum span length for both-ends continuous (for Beams): then
Topping Design.
𝑤𝑢 𝐷 𝐿
Topping in One way ribbed slab can be
considered as a strip of 1 meter width and
span of hollow block length with both end
fixed in the ribs. 𝑐𝑚
219
Reinforced Concrete II Dr. Nasr Abboushi
√ √ ×
( ) ( )
( ) ( )
𝑏𝑤 𝑚𝑚
From the Geometry of T-section:
220
Reinforced Concrete II Dr. Nasr Abboushi
The Effective Flange width ( ) According to ACI 8.12.2 (see page 220):
is the smallest of:
( )
( )
( )
Take .
Structural Analysis of Rib 1. The envelope shear and moment diagrams (for all load
combinations).
Using the structural analysis and design programs, we obtain the Envelope Moment diagram
for Rib1.
221
Reinforced Concrete II Dr. Nasr Abboushi
222
Reinforced Concrete II Dr. Nasr Abboushi
̅ ( ) ( )×
( √ ) ( √ )
Check for
Use with
Check for strain:
( ) ( )
Usually, no reinforcement less than can be used. So, for all spans with positive
moments equal or less than , use for each rib span.
223
Reinforced Concrete II Dr. Nasr Abboushi
According to ACI 8.9.3 — for beams built integrally with supports, design on the basis of
moments at faces of support shall be permitted.
The maximum negative moment at the face of support
×
( √ ) ( √ )
Check for
Use with
( ) ( )
Usually, no reinforcement less than can be used. So, for all supports with negative
moments equal or less than , use for each rib support.
The maximum shear force at the distance from the face of support
Shear strength, , provided by concrete for the ribs may be taken greater than that for
beams. This is mainly due to the interaction between the slab and the closely spaced ribs
(ACI Code, Section 8.13.8).
224
Reinforced Concrete II Dr. Nasr Abboushi
( )× √ × √
Minimum shear reinforcement is required except for concrete joist construction. So, No
shear reinforcement is provided.
The distributed Dead and Live loads acting upon the Beam 4 can be defined from the
support reactions of the rib 1 and rib 2.
Beam 4
225
Reinforced Concrete II Dr. Nasr Abboushi
Assume the width of the beam , then the own weight of the beam and the weight
of the floor layers within the beam width can be calculated:
Important NOTE:
The dead and live loads acting within the beam width have been calculated twice actually.
That because the support reactions of ribs from the dead and live loads acting over the ribs
were calculated for full span of the ribs, measured center to center, which include the whole
beam width.
More accurately calculations to determine the loads on the beam could be done by taking
the loads that transfer from the rib to the beam which could be calculated as the sum of
shear values of the ribs at the face of support (beam) from each side and then adding the
dead and live loads acting directly on the beam within the beam width.
From the next envelope shear diagrams, the shear values at the face of beam 4 are:
From dead load: from the left, and from the right) which means
that the total dead load that transfers to the beam 4 is
The uniformly distributed dead load over the beam from the ribs only is
226
Reinforced Concrete II Dr. Nasr Abboushi
From live load: from the left, and from the right) which means
that the total live load that transfers to the beam 4 is
The uniformly distributed live load over the beam from the ribs only is
Beam 4
Beam 4
227
Reinforced Concrete II Dr. Nasr Abboushi
I’ v h h f h h f l l .I’ f l
to calculate the loads more accurate specially when the beam section is wide and the spans
are large. We can use the first method for simplicity, especially in this stage of calculations,
when the dimensions of the beam are not known yet.
Structural Analysis of Beam 4. The envelope shear and moment diagrams (for all load
combinations).
The Beam 4 is loaded from the ribs 1 (first two spans) and ribs 2 (last span). The load
transferred from ribs 1 to Beam 4 is calculated before. The load transferred from rib 2 to
Beam 4 will be obtained by analyzing the rib 2 as continuous beam as follows:
Beam 4
228
Reinforced Concrete II Dr. Nasr Abboushi
Using the structural analysis and design programs, we obtain the Envelope Moment diagram
for Beam 4.
229
Reinforced Concrete II Dr. Nasr Abboushi
The width of the Beam 4 can be defined from the maximum factored moment.
The maximum factored moment in Beam 4
Note that according to ACI 8.9.3 — for beams built integrally with supports, design on the
basis of moments at faces of support shall be permitted. Here the design will be done for the
moments at the center of supports.
Take f fl - ll
Assume .
230
Reinforced Concrete II Dr. Nasr Abboushi
Take ( )
( ) ( )
( ) ( )
𝑐𝑚
Check whether the section will be act as singly or
doubly reinforced section:
Maximum nominal moment strength from strain
𝑐𝑚
condition
( ) ( )×
( √ ) ( √ )
231
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( )
× × ×
√ √
√ √
√
232
Reinforced Concrete II Dr. Nasr Abboushi
√ √
Check for :
( √ )
√ √
( )
( )
Or
𝑚𝑚
𝑚𝑚
25 cm
𝑚𝑚
100 cm
233
Reinforced Concrete II Dr. Nasr Abboushi
Design the other beam sections for flexure (for positive and negative moments and caculate
the area of steel for each section).
Note that for shear design, it is obvious that, the stirrups cannot be less than two U-shape
stirrups and the step for all sections where stirrups are reqired.
So, for all sections the design for shear will be as the previous section ( 2 U-shape
).
An alternative design for the Beam 4 can be done on the basis of drop beam section, not as a
hidden beam as in the previous design.
234
Reinforced Concrete II Dr. Nasr Abboushi
9.1 INTRODUCTION
When the slab is supported on all four sides and the length, , is less than twice the width,
, the slab will deflect in two directions, and the loads on the slab are transferred to all four
supports. This slab is referred to as a two-way slab. The bending moments and deflections in
such slabs are less than those in one-way slabs; thus, the same slab can carry more load
when supported on four sides. The load in this case is carried in two directions, and the
bending moment in each direction is much less than the bending moment in the slab if the
load were carried in one direction only.
235
Reinforced Concrete II Dr. Nasr Abboushi
4. Two-Way Ribbed Slabs and the Waffle Slab System: This type of slab consists of a
floor slab with a length-to-width ratio less than 2. The thickness of the slab is usually
5 to 10 cm and is supported by ribs (or joists) in two directions. The ribs are arranged
in each direction at spacings of about , producing square or
rectangular shapes. The ribs can also be arranged at or from the centerline
of slabs, producing architectural shapes at the soffit of the slab. In two-way ribbed
slabs, different systems can be adopted:
a. A two-way rib system with voids between the ribs, obtained by using special
removable and usable forms (pans) that are normally square in shape. The ribs are
supported on four sides by girders that rest on columns. This type is called a two-
way ribbed (joist) slab system.
b. A two-way rib system with permanent fillers between ribs that produce horizontal
slab soffits. The fillers may be of hollow, lightweight or normal-weight concrete or
any other lightweight material. The ribs are supported by girders on four sides,
which in turn are supported by columns. This type is also called a two-way ribbed
(joist) slab system or a hollow-block two-way ribbed system.
c. A two-way rib system with voids between the ribs with the ribs continuing in both
directions without supporting beams and resting directly on columns through solid
panels above the columns. This type is called a waffle slab system.
236
Reinforced Concrete II Dr. Nasr Abboushi
Various types of floor systems can be used for general buildings, such as residential, office,
and institutional buildings. The choice of an adequate and economic floor system depends
on the type of building, architectural layout, aesthetic features, and the span length
between columns. In general, the superimposed live load on buildings varies between 4 and
. A general guide for the economical use of floor systems can be summarized as
follows:
1. Flat Plates: Flat plates are most suitable for spans of and live loads
between and . The advantages of adopting flat plates include low-
cost formwork, exposed flat ceilings, and fast construction. Flat plates have low
shear capacity and relatively low stiffness, which may cause noticeable
deflection. Flat plates are widely used in buildings either as reinforced or
prestressed concrete slabs.
237
Reinforced Concrete II Dr. Nasr Abboushi
2. Flat Slabs: Flat slabs are most suitable for spans of and for live loads of
. They need more formwork than flat plates, especially for column
capitals. In most cases, only drop panels without column capitals are used.
3. Waffle Slabs: Waffle slabs are suitable for spans of and live loads of
. They carry heavier loads than flat plates and have attractive
exposed ceilings. Formwork, including the use of pans, is quite expensive.
4. Slabs on Beams: Slabs on beams are suitable for spans beiween and and
live loads of . The beams increase the stiffness of the slabs,
producing relatively low deflection. Additional formwork for the beams is
needed.
5. One-Way Slabs on Beams: One-way slabs on beams are most suitable for spans
of and a live load of . They can be used for larger spans
with relatively higher cost and higher slab deflection. Additional formwork for
the beams is needed.
6. One-Way Joist Floor System: A one-way joist floor system is most suitable for
spans of and live loads of . Because of the deep ribs, the
concrete and steel quantities are relatively low, but expensive formwork is
expected. The exposed ceiling of the slabs may look attractive.
The ACI Code, Section 9.5.3, specifies a minimum slab thickness in two-way slabs to control
deflection. The magnitude of a slab's deflection depends on many variables, including the
flexural stiffness of the slab, which in turn is a function of the slab thickness, . By increasing
the slab thickness, the flexural stiffness of the slab is increased, and consequently the slab
deflection is reduced. Because the calculation of deflections in two-way slabs is complicated
and to avoid excessive deflections, the ACI Code limits the thickness of these slabs by
adopting the following three empirical limitations, which are based on experimental
research. If these limitations are not met, it will be necessary to compute deflections.
1. For
( )
( )
but not less than .
2. For
( )
3. For
238
Reinforced Concrete II Dr. Nasr Abboushi
where
clear span in the long direction measured face to face of columns (or face to face of
beams for slabs with beams).
the ratio of the long to the short clear spans.
the average value of for all beams on the sides of a panel.
the ratio of flexural stiffness of a beam section to the flexural stiffness of the slab
, bounded laterally by the centerlines of the panels on each side of the beam.
where , and are the moduli of elasticity of concrete in the beam and the slab,
respectively, and
the gross moment of inertia of the beam section about the centroidal axis (the beam
section includes a slab length on each side of the beam equal to the projection of the
beam above or below the slab, whichever is greater, but not more than four times the
slab thickness)
the moment of inertia of the gross section of the slab.
However, the thickness of any slab shall not be less than the following:
1. For slabs with then thickness
2. For slabs with then thickness
If no beams are used, as in the case of flat plates, then and . The ACI Code
equations for calculating slab thickness, , take into account the effect of the span length,
the panel shape, the steel
reinforcement yield stress,
, and the flexural stiffness
of beams. When very stiff
beams are used, Eq. ( )
may give a small slab
thickness, and Eq. ( ) may
control. For flat plates and
flat slabs, when no interior
beams are used, the
minimum slab thickness
may be determined directly
from Table 9.5(c) of the ACI
Code, which is shown here.
239
Reinforced Concrete II Dr. Nasr Abboushi
Placement Sequence.
In a flat plate or flat slab, the moments are larger in the slab strips spanning the long
direction of the panels. As a result, the reinforcement for the long span generally is placed
closer to the top and bottom of the slab than is the short-span reinforcement. This gives the
larger effective depth for the larger moment. For slabs supported on beams having
greater than about , the opposite is true, and the reinforcing pattern should be reversed.
If a particular placing sequence has been assumed in the reinforcement design, it should be
shown or noted on the drawings. It also is important to maintain the same arrangements of
layers throughout the entire floor, to avoid confusion in the field. Thus, if the east–west
reinforcement is nearer the top and bottom surfaces in one area, this arrangement should
be maintained over the entire slab, if at all possible.
Concrete Cover.
ACI Code Section 7.7.1 specifies the minimum clear cover to the surface of the
reinforcement in slabs as for and smaller bars, provided that the slab is not
exposed to earth or to weather.
ACI Code Section 13.3.4 requires that all negative-moment steel perpendicular to an edge be
bent, hooked, or otherwise anchored in spandrel beams, columns, and walls along the edge
to develop in tension. If there is no edge beam, this steel still should be hooked to act as
torsional reinforcement and should extend to the minimum cover thickness from the edge of
the slab.
ACI 318 - Fig. 13.3.8 — Minimum extensions for reinforcement in slabs without beams. (See 12.11.1 for
reinforcement extension into supports).
ACI Code Section 13.3.6 requires that at exterior corners of slabs supported by edge walls or
where one or more edge beams have a value of greater than , top and bottom slab
reinforcement shall be provided at exterior corners in accordance with 13.3.6.1 through
13.3.6.4.
13.3.6.1 — Corner reinforcement in both top and bottom of slab shall be sufficient to
resist a moment per unit of width equal to the maximum positive moment per unit width in
the slab panel.
13.3.6.2 — The moment shall be assumed to be about an axis perpendicular to the
diagonal from the corner in the top of the slab and about an axis parallel to the diagonal
from the corner in the bottom of the slab.
13.3.6.3 — Corner reinforcement shall be provided for a distance in each direction
from the corner equal to one-fifth the longer span.
242
Reinforced Concrete II Dr. Nasr Abboushi
13.3.6.4 — Corner reinforcement shall be placed parallel to the diagonal in the top of
the slab and perpendicular to the diagonal in the bottom of the slab. Alternatively,
reinforcement shall be placed in two layers parallel to the sides of the slab in both the top
and bottom of the slab.
In a two-way floor system, the slab must have adequate thickness to resist both bending
moments and shear forces at the critical sections. To investigate the shear capacity of two-
way slabs, the following cases should be considered.
243
Reinforced Concrete II Dr. Nasr Abboushi
If no shear reinforcement is provided, the shearing force at a distance from the face of the
beam, , must be equal to
√
where
( )
244
Reinforced Concrete II Dr. Nasr Abboushi
column, and the slab is considered as a wide beam spanning between supports, as in the
case of one-way beams. The shear capacity of the concrete section is √ .
( ) √
( ) √
𝑑 𝑑 𝑑
248
Reinforced Concrete II Dr. Nasr Abboushi
An exact analysis of forces and displacements in a two-way slab is complex, due to its highly
indeterminate nature; this is true even when the effects of creep and nonlinear behavior of
the concrete are neglected. Numerical methods such as finite elements can be used, but
249
Reinforced Concrete II Dr. Nasr Abboushi
simplified methods such as those presented by the ACI Code are more suitable for practical
design. The ACI Code, Chapter 13, assumes that the slabs behave as wide, shallow beams
that form, with the columns above and below them, a rigid frame. The validity of this
assumption of dividing the structure into equivalent frames has been verified by analytical
and experimental research. It is also established that factored load capacity of two-way slabs
with restrained boundaries is about twice that calculated by theoretical analysis, because a
great deal of moment redistribution occurs in the slab before failure. At high loads, large
deformations and deflections are expected; thus, a minimum slab thickness is required to
maintain adequate deflection and cracking conditions under service loads.
The ACI Code specifies two methods for the design of two-way slabs:
1. The direct design method. DDM (ACI Code, Section 13.6), is an approximate
procedure for the analysis and design of two-way slabs. It is limited to slab systems
subjected to uniformly distributed loads and supported on equally or nearly equally
spaced columns. The method uses a set of coefficients to determine the design
moments at critical sections. Two-way slab systems that do not meet the limitations
of the ACI Code, Section 13.6.1, must be analyzed by more accurate procedures.
2. The equivalent frame method, EFM (ACI Code, Section 13.7), is one in which a three-
dimensional building is divided into a series of two-dimensional equivalent frames by
cutting the building along lines midway between columns. The resulting frames are
considered separately in the longitudinal and transverse directions of the building
and treated floor by floor, as will be shown later.
The systems that do not meet the requirements permitting analysis by the "direct design
method" of the present code, has led many engineers to continue to use the design method
of the 1963 ACI Code (The coefficient method) for the special case of two-way slabs sup-
ported on four sides of each slab panel by relatively deep, stiff, edge beams. It has been
used extensively here since 1963 for slabs supported at the edges by walls, steel beams, or
monolithic concrete beams having a total depth not less than about 3 times the slab
thickness. While it was not a part of the 1977 or later ACI Codes, its continued use is
permissible under the current code provision (ACI Code 13.5.1) that a slab system may be
designed by any procedure satisfying conditions of equilibrium and geometric compatibility,
if it is shown that the design strength at every section is at least equal to the required
strength, and that serviceability requirements are met.
The coefficient method makes use of tables of moment coefficients for a variety of
conditions. These coefficients are based on elastic analysis but also account for inelastic
redistribution. In consequence, the design moment in either direction is smaller by an
appropriate amount than the elastic maximum moment in that direction. The moments in
the middle strips in the two directions are computed from
250
Reinforced Concrete II Dr. Nasr Abboushi
and
The method provides that each panel be divided in both directions into a middle strip whose
width is one-half that of the panel and two edge or column strips of one-quarter of the panel
width (see figure below). The moments in both directions are larger in the center portion of
the slab than in regions close to the edges. Correspondingly, it is provided that the entire
middle strip be designed for the full, tabulated design moment. In the edge strips this
moment is assumed to decrease from its full value at the edge of the middle strip to one-
third of this value at the edge of the panel. This distribution is shown for the moments in
the short span direction in figure below. The lateral variation of the long span moments
is similiar.
The discussion so far has been restricted to a single panel simply supported at all four edges.
An actual situation is shown in next figure, in which a system of beams supports a two-way
slab. It is seen that some panels, such as , have two discontinuous exterior edges, while the
other edges are continuous with their neighbors. Panel has one edge discontinuous and
three continuous edges, the interior panel has all edges continuous, and so on. At a
continuous edge in a slab, moments are negative, just as at interior supports of continuous
beams. Also, the magnitude of the positive moments depends on the conditions of
continuity at kall four edges.
251
Reinforced Concrete II Dr. Nasr Abboushi
252
Reinforced Concrete II Dr. Nasr Abboushi
253
Reinforced Concrete II Dr. Nasr Abboushi
254
Reinforced Concrete II Dr. Nasr Abboushi
255
Reinforced Concrete II Dr. Nasr Abboushi
256
Reinforced Concrete II Dr. Nasr Abboushi
𝑚
Find the required slab thickness and Corner
reinforcement for the corner panel shown. Panel
Solution:
( )
257
Reinforced Concrete II Dr. Nasr Abboushi
Interior beam:
( )
Short direction
( )
Long direction
( )
Short direction
Long direction
258
Reinforced Concrete II Dr. Nasr Abboushi
𝛼𝑓
𝛼𝑓 𝛼𝑓
𝑚
Corner
Panel
𝛼𝑓
∑
( ) ( )
2. Loads calculation:
Quality Density
Material
Tiles
mortar
Sand
Reinforced Concrete solid slab
Plaster
Partitions
Total Dead Load
259
Reinforced Concrete II Dr. Nasr Abboushi
3. Moments calculations:
𝑚
Discontinuous Edge
𝑚 𝑚 𝑚
𝑚
Column strip - short
Discontinuous Edge
Continuous Edge
𝑚
Case 4
𝑚
middle strip - short
𝑚
Column strip - short
and
The moment calculations will be done for the slab middle strip.
Negative moments at continuous edges (Table 1):
( ) and ( )
( ) ( )
( ) and ( )
( ) ( )
( ) and ( )
( ) ( )
( ) and ( )
( ) ( )
260
Reinforced Concrete II Dr. Nasr Abboushi
( ) and ( )
( ) ( )
( ) and ( )
( ) ( )
𝑎 short direction
Moments
𝐾𝑁 𝑚 𝑚
long direction
𝑚
𝑏
261
Reinforced Concrete II Dr. Nasr Abboushi
4. Slab reinforcement:
Short direction:
Assume bar diameter for main reinforcement.
Midspan:
( √ ) ( √ )
Provide
Use then
Take
Note that in the edge strips the positive moment, and the corresponding steel reinforcement
area, is assumed to decrease from its full value at the edge of the middle strip to one-third of
this value at the edge of the panel, which will not be provided.
Continuous edge:
Assume bar diameter for main reinforcement.
( √ ) ( √ )
262
Reinforced Concrete II Dr. Nasr Abboushi
Provide
Use then
Take
Discontinuous edge.
The negative moment at the discontinuous edge is one-third the positive moment in the
span.
Provide
Take
Long direction.
Design for positive and negative moment as in the short direction.
Note that the effective depth for the long direction will be
( ) and ( )
( ) ( )
( ) and ( )
( ) ( )
The reactions of the slab are calculated from Table 4, which indicates that of the load is
transmitted in the short direction and in the long direction.
The total load on the panel being
The load per meter on the long beam is , and
The load per meter on the short beam is .
The shear to be transmitted by the slab to these beams is numerically equal to these beam
loads, reduced to a critical section a distance from the beam face. The shear strength of
the slab is
263
Reinforced Concrete II Dr. Nasr Abboushi
√ √
- for shear.
Example:
A monolithic reinforced concrete solid slab is to be composed of rectangular bays as shown.
Beams of width and depth are provided on all column lines. The floor is to be
designed to carry a service live load and a dead load on the slab due to self-
weight plus weight of:
• Tiles, .
• Mortar, .
• Sand, .
• Plaster, .
• Partitions, .
Given: and .
Find the required slab thickness and reinforcement for the solid slab shown.
Solution:
1. Minimum thickness (deflection requirements):
For slabs of this type the first trial thickness is often taken equal to
( )
264
Reinforced Concrete II Dr. Nasr Abboushi
𝑙𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏
B 15 (60 x 60 cm)
B 18 (60 x 60 cm)
B 21 (60 x 60 cm)
B 24 (60 x 60 cm)
𝐶𝑎 𝐷 𝐶𝑎 𝐷 𝐶𝑎 𝐷
𝐶𝑏 𝐷 𝐶𝑏 𝐷 𝐶𝑏 𝐷
8.1 m
7.5 m
𝐶𝑎 𝐿 𝐶𝑎 𝐿 𝐶𝑎 𝐿
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑏 𝐿 𝐶𝑏 𝐿 𝐶𝑏 𝐿
𝑙𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏
B 14 (60 x 60 cm)
B 17 (60 x 60 cm)
B 20 (60 x 60 cm)
B 23 (60 x 60 cm)
𝐶𝑎 𝐷 𝐶𝑎 𝐷 𝐶𝑎 𝐷
8.1 m
7.5 m
𝐶𝑏 𝐷 𝐶𝑏 𝐷 𝐶𝑏 𝐷
𝐶𝑎 𝐿 𝐶𝑎 𝐿 𝐶𝑎 𝐿
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑏 𝐿 𝐶𝑏 𝐿 𝐶𝑏 𝐿
𝛼
𝑙𝑎 𝑙𝑏 𝑙 𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏
B 13 (60 x 60 cm)
B 16 (60 x 60 cm)
B 19 (60 x 60 cm)
B 22 (60 x 60 cm)
𝐶𝑎 𝐷 𝐶𝑎 𝐷 𝐶𝑎 𝐷
8.6 m
8.0 m
𝐶𝑏 𝐷 𝐶𝑏 𝐷 𝐶𝑏 𝐷
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝐿 𝐶𝑎 𝐿 𝐶𝑎 𝐿
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑏 𝐿 𝐶𝑏 𝐿 𝐶𝑏 𝐿
𝛼
265
Reinforced Concrete II Dr. Nasr Abboushi
Interior beam:
( )
Short direction
( )
Long direction
( )
Short direction
Long direction
( )
266
Reinforced Concrete II Dr. Nasr Abboushi
𝛼𝑓
𝑚
𝛼𝑓 𝛼𝑓
𝑚
Corner
Panel
𝛼𝑓
∑
( ) ( )
2. Loads calculation:
Quality Density
Material
Tiles
mortar
Sand
Reinforced Concrete solid slab
Plaster
Partitions
Total Dead Load
267
Reinforced Concrete II Dr. Nasr Abboushi
3. Moments calculations:
and
All negative and positive coefficients are shown on the slab plane (page 265).
Negative moments at Discontinuous edges ( ):
6.0 m 6.0 m 6.0 m
5.4
5.4
3.8
42.4 44.5 42.4
B 15 (60 x 60 cm)
B 18 (60 x 60 cm)
B 21 (60 x 60 cm)
B 24 (60 x 60 cm)
44.5
+11.5
+16.2
+16.2
8.1 m
7.5 m
8.4 8.4
27.1
15.9
38.3
25.2
B 17 (60 x 60 cm)
B 20 (60 x 60 cm)
B 23 (60 x 60 cm)
38.8
+12.2
+15.3
+15.3
8.1 m
7.5 m
7.2 7.2
38.3
25.2
14.9
25.5
B 16 (60 x 60 cm)
B 19 (60 x 60 cm)
B 22 (60 x 60 cm)
+14.9
+14.9
+9.6
8.6 m
8.0 m
9.2 9.2
5
5
4. Slab reinforcement:
Assume bar diameter .
Find corresponding to :
( ) ( )
( ) ( )
Take
Assume bar diameter .
( ) ( )
( ) ( )
Take
Assume bar diameter .
( ) ( )
( ) ( )
Take
10@15 cm c/c
10@15 cm c/c
10@15 cm c/c
L=300 cm
L=300 cm
L=300 cm
T 10@15 cm c/c T 12@15 cm c/c T 12@15 cm c/c T 10@15 cm c/c
L=300 cm L=500 cm L=500 cm L=300 cm
T
T
B 10@15 cm c/c B 10@15 cm c/c
B 10@15 cm c/c
L=750 cm L=750 cm
8.1 m
7.5 m
L=750 cm
10@15 cm c/c
10@15 cm c/c
10@15 cm c/c
L=900 cm
L=900 cm
L=900 cm
12@15 cm c/c
10@15 cm c/c
12@15 cm c/c
B
B
L=600 cm
L=600 cm
L=600 cm
T
T
T 10@15 cm c/c T 12@15 cm c/c T 12@15 cm c/c T 10@15 cm c/c
L=300 cm L=500 cm L=500 cm L=300 cm
7.5 m
10@15 cm c/c
10@15 cm c/c
10@15 cm c/c
L=900 cm
L=900 cm
L=900 cm
B
B
12@15 cm c/c
10@15 cm c/c
12@15 cm c/c
L=600 cm
L=600 cm
L=600 cm
T
8.0 m
10@15 cm c/c
10@15 cm c/c
10@15 cm c/c
L=950 cm
L=950 cm
L=950 cm
10@15 cm c/c
10@15 cm c/c
10@15 cm c/c
B
B
B
L=300 cm
L=300 cm
L=300 cm
T
√ √
- for shear.
Another way (simply supported strip) to calculate the shear at distance from the face
of support
( ) ( )
Even, if for solid slabs, the thickness of the slab will be enough.
For the two methods of calculating the thickness of the slab is adequate enough.
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
B 16 B 17 B 18
8.6 m 8.1 m 8.1 m
271
8.6 m 8.1 m 8.1 m
45°
3.0 m 3.0 m 3.0 m 3.0 m 3.0 m 3.0 m
6.6 m
6.0 m
Reinforced Concrete II
45°
272
6.6 m
6.0 m
2.0 m
1.5 m 1.5 m
45°
45°
3.0 m 3.0 m 3.0 m 3.0 m 3.0 m 3.0 m
6.6 m
6.0 m
2.0 m
45°
45°
1.5 m 1.5 m
Dr. Nasr Abboushi
Using software programs such as BEAMD to analyze the beam and to get shear and moment
8.0 m 7.5 m 7.5 m
Reinforced Concrete II Dr. Nasr Abboushi
273
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
1. Minimum thickness (deflection requirements): Assume the thickness for the shown
ribbed slab
Check for the minimum thickness of the slab (for the shaded corner slab):
All Exterior and Interior beams have rectangular section of 60 cm width and 52 cm
depth:
The moment of inertia for the ribbed slab is the sum of moment of inertia of T-section ribs
within a distance ( )
was defined as in one-way ribbed
slab design ( )
274
Reinforced Concrete II Dr. Nasr Abboushi
B 18 (60x52 cm)
B 21 (60x52 cm)
B 24 (60x52 cm)
8.1 m
7.5 m
B7 (60x52 cm) B8 (60x52 cm) B9 (60x52 cm)
B 14 (60x52 cm)
B 17 (60x52 cm)
B 20 (60x52 cm)
B 23 (60x52 cm)
8.1 m
7.5 m
B4 (60x52 cm) B5 (60x52 cm) B6 (60x52 cm)
B 13 (60x52 cm)
B 16 (60x52 cm)
B 19 (60x52 cm)
B 22 (60x52 cm)
8.1 m
7.5 m
275
Reinforced Concrete II Dr. Nasr Abboushi
Short direction
Long direction
Short direction
( ) ( )
Long direction
( ) ( )
𝛼𝑓
7.5 m
𝛼𝑓 𝛼𝑓
6m
Corner
Panel
𝛼𝑓
∑
( ) ( )
( )
276
Reinforced Concrete II Dr. Nasr Abboushi
2. Loads calculation:
Quality Density
Material
Tiles
mortar
Sand
Reinforced Concrete Topping
Reinforced Concrete Rib
Concrete Block
Plaster
Partitions
Total Dead Load,
3. Moments calculations:
and
All negative and positive coefficients are shown on the slab plane (page 278).
Negative moments at Discontinuous edges ( ):
277
Reinforced Concrete II Dr. Nasr Abboushi
𝑙𝑎 𝑙𝑏 𝑙 𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏
𝐶𝑎 𝐷 𝐶𝑎 𝐷 𝐶𝑎 𝐷
𝐶𝑏 𝐷 𝐶𝑏 𝐷 𝐶𝑏 𝐷
8.1 m
7.5 m
𝐶𝑎 𝐿 𝐶𝑎 𝐿 𝐶𝑎 𝐿
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑏 𝐿 𝐶𝑏 𝐿 𝐶𝑏 𝐿
𝑙𝑎 𝑙𝑏 𝑙 𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏
𝐶𝑎 𝐷 𝐶𝑎 𝐷 𝐶𝑎 𝐷
8.1 m
7.5 m
𝐶𝑏 𝐷 𝐶𝑏 𝐷 𝐶𝑏 𝐷
𝐶𝑎 𝐿 𝐶𝑎 𝐿 𝐶𝑎 𝐿
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑏 𝐿 𝐶𝑏 𝐿 𝐶𝑏 𝐿
𝑙𝑎 𝑙𝑏 𝑙 𝑎 𝑙𝑏 𝑙𝑎 𝑙𝑏
8.1 m
7.5 m
𝐶𝑎 𝐷 𝐶𝑎 𝐷 𝐶𝑎 𝐷
𝐶𝑏 𝐷 𝐶𝑏 𝐷 𝐶𝑏 𝐷
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝑛𝑒𝑔
𝐶𝑎 𝐿 𝐶𝑎 𝐿 𝐶𝑎 𝐿
𝐶𝑏 𝐿 𝐶𝑏 𝐿 𝐶𝑏 𝐿
Note that all moments and are for strip. For one rib ( )
278
Reinforced Concrete II Dr. Nasr Abboushi
2.95
2.95
2.09
23.23
B 15 (60 x 60 cm)
B 18 (60 x 60 cm)
B 21 (60 x 60 cm)
B 24 (60 x 60 cm)
23.23 24.54 24.54
+6.26
+8.84
+8.84
8.1 m
7.5 m
4.57 4.57
14.82
14.82
8.69
20.96
13.8
18 21.27 18
B 14 (60 x 60 cm)
B 17 (60 x 60 cm)
B 20 (60 x 60 cm)
B 23 (60 x 60 cm)
21.27
+6.61
+8.32
+8.32
8.1 m
7.5 m
3.91 3.91
20.96
13.8
14.82
23.23 24.54
B 13 (60 x 60 cm)
B 16 (60 x 60 cm)
B 19 (60 x 60 cm)
B 22 (60 x 60 cm)
24.54 23.23
+6.26
+8.84
+8.84
8.1 m
7.5 m
4.57 4.57
2.95
2.95
Moments, 𝐾𝑁 𝑚 𝑟𝑖𝑏
279
Reinforced Concrete II Dr. Nasr Abboushi
4. Slab reinforcement:
The design can be done directly for the negative moment or through section analysis with
assumed bar diameter and step.
( √ ) ( √ )
Check for
Use with
Check for strain:
( ) ( )
280
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( )
( ) ( )
Take
All panels will be reinforced with bottom bars in both directions except for the middle
panel in the short direction where will be used bottom bars as shown in the next
figure.
( ) ( )
Check for strain :
( ) ( )
Take
( ) ( )
Check for strain :
( ) ( )
Take
281
Reinforced Concrete II Dr. Nasr Abboushi
6.0 m 6.0 m 6.0 m
L=300 cm
L=300 cm
L=300 cm
T 2 10
T 2 10
T 2 10
T 2 10 T 2 14 T 2 14 T 2 10
L=300 cm L=500 cm L=500 cm L=300 cm
B 2 10 B 2 10
B 2 10
L=750 cm L=750 cm
8.1 m
7.5 m
L=750 cm
L=900 cm
L=900 cm
L=900 cm
B 2 10
B 2 10
B 2 10
L=600 cm
L=600 cm
L=600 cm
T 2 12
T 2 12
T 2 12
T 2 10 T 2 12 T 2 12 T 2 10
L=300 cm L=500 cm L=500 cm L=300 cm
B 2 10 B 2 10
B 2 12
L=750 cm L=750 cm
L=750 cm
8.1 m
7.5 m
L=900 cm
L=900 cm
L=900 cm
B 2 10
B 2 10
B 2 10
L=600 cm
L=600 cm
L=600 cm
T 2 12
T 2 12
T 2 12
T 2 10 T 2 14 T 2 14 T 2 10
L=300 cm L=500 cm L=500 cm L=300 cm
B 2 10 B 2 10
B 2 10
8.1 m
7.5 m
L=750 cm L=750 cm
L=750 cm
L=900 cm
B 2 10
L=900 cm
L=900 cm
B 2 10
B 2 10
L=300 cm
L=300 cm
L=300 cm
T 2 10
T 2 10
T 2 10
24 cm
2 10
40 cm 12 cm
( ) ( )
( ) ( )
Take
√ √
- for shear.
( )
1.5 m
Design the rib for shear assuming that the critical shear
3m
in the rib is .
3m 3m
283
Reinforced Concrete II Dr. Nasr Abboushi
( )
Provide minimum shear reinforcement.
Use for stirrups
( ) ( )
The tributary load area for beams 16, 17, 18 from ribbed slab is as shown (shaded area). In
addition to factored load acting on the beam from the ribbed slab, the own weight of the
beam must be added.
Load calculation for the beams 16-17-18:
Material
Tiles
mortar
Sand
Plaster
Partitions
Total Dead Load,
1.5 m 1.5 m
45°
3.0 m 3.0 m 3.0 m 3.0 m 3.0 m 3.0 m
6.6 m
6.0 m
Reinforced Concrete II
45°
B1 (60x52 cm)
B4 (60x52 cm)
B7 (60x52 cm)
B10 (60x52 cm)
1.5 m
285
6.6 m
6.0 m
B2 (60x52 cm)
B5 (60x52 cm)
B8 (60x52 cm)
B11 (60x52 cm)
6.6 m
6.0 m
B3 (60x52 cm)
B6 (60x52 cm)
B9 (60x52 cm)
B12 (60x52 cm)
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
𝑚 𝑚 𝑚
Using software programs such as BEAMD to analyze and design the beams and to get
reinforcement details.
The tributary load area for beams 7, 8, 9 from ribbed slab is as shown (shaded area). In
addition to factored load acting on the beam from the ribbed slab, the own weight of the
beam must be added.
Load calculation for the beams 7-8-9:
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
Using software programs such as BEAMD to analyze and design the beams and to get
reinforcement details.
286
Reinforced Concrete II Dr. Nasr Abboushi
The tributary load area beams 22, 23, 24 from ribbed slab is as shown (shaded area). In
addition to factored load acting on the beam from the ribbed slab, the own weight of the
beam must be added and the load of the RC wall ( thick, height).
Load calculation for the beams 22-23-24:
Note here that the width of the beam for the floor materials and live load on the beam will
be smaller because of the thickness of the exterior wall ( )
Material
Tiles
mortar
Sand
Plaster
Partitions
Total Dead Load,
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚 𝐷𝐿 𝐾𝑁 𝑚
𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚 𝐿𝐿 𝐾𝑁 𝑚
𝑚 𝑚 𝑚
Using software programs such as BEAMD to analyze and design the beams and to get
reinforcement details.
287
Reinforced Concrete II Dr. Nasr Abboushi
288
Reinforced Concrete II Dr. Nasr Abboushi
289
Reinforced Concrete II Dr. Nasr Abboushi
290
Reinforced Concrete II Dr. Nasr Abboushi
291
Reinforced Concrete II Dr. Nasr Abboushi
292
Reinforced Concrete II Dr. Nasr Abboushi
293
Reinforced Concrete II Dr. Nasr Abboushi
The direct-design method also could have been called “the direct-analysis method,” because
this method essentially prescribes values for moments in various parts of the slab panel
without the need for a structural analysis. The reader should be aware that this design
method was introduced in an era when most engineering calculations were made with a
slide rule and computer software was not available to do the repetitive calculations required
to analyze a continuous-floor slab system. Thus, for continuous slab panels with relatively
uniform lengths and subjected to distributed loading, a series of moment coefficients were
developed that would lead to safe flexural designs of two-way floor systems.
The direct-design method is easier to use than the equivalent-frame method, but can be
applied only to fairly regular multipanel slabs. The limitations, given in ACI Code Section
13.6.1, include the following:
1. There must be a minimum of three continuous spans in each direction. Thus, a
ninepanel structure ( ) is the smallest that can be considered. If there are fewer
than three panels, the interior negative moments from the direct-design method
tend to be too small.
2. Rectangular panels must have a long-span/short-span ratio that is not greater than .
One-way action predominates as the span ratio reaches and exceeds .
3. Successive span lengths in each direction shall not differ by more than one third of
the longer span. This limit is imposed so that certain standard reinforcement cutoff
details can be used.
4. Columns may be offset from the basic rectangular grid of the building by up to 0.1
times the span parallel to the offset. In a building laid out in this way, the actual
column locations are used in determining the spans of the slab to be used in
calculating the design moments.
5. All loads must be due to gravity only and uniformly distributed over an entire panel.
The direct-design method cannot be used for unbraced, laterally loaded frames,
foundation mats, or prestressed slabs.
6. The service (unfactored) live load shall not exceed two times the service dead load.
Strip or checkerboard loadings with large ratios of live load to dead load may lead to
moments larger than those assumed in this method of analysis.
7. For a panel with beams between supports on all sides, the relative stiffness of the
beams in the two perpendicular directions given by ( ) ( ) shall not be less
than or greater than . The term was defined in the prior section, and and
are the spans in the two directions.
Limitations and do not allow use of the direct-design method for slab panels that
transmit load as one-way slabs.
294
Reinforced Concrete II Dr. Nasr Abboushi
295
Reinforced Concrete II Dr. Nasr Abboushi
296
Reinforced Concrete II Dr. Nasr Abboushi
297
Reinforced Concrete II Dr. Nasr Abboushi
9.9.5 Lateral Distribution of Moments (between Column Strips and Middle Strips)
Having distributed the moment to the positive and negative-moment sections as just
described, the designer still must distribute these design moments across the width of the
critical sections. For design purposes, it is convenient to consider the moments constant
within the bounds of a middle strip or column strip unless there is a beam present on the
column line. In the latter case, because of its greater stiffness, the beam will tend to take a
larger share of the column-strip moment than the adjacent slab. The distribution of total
negative or positive moment between slab middle strips, slab column strips, and beams
depends upon the ratio , the relative stiffness of the beam and the slab, and the degree
of torsional restraint provided by the edge beam.
A convenient parameter defining the relative stiffness of the beam and slab spanning in
either direction is
in which and are the moduli of elasticity of the beam and slab concrete (usually the
same) and and are the moments of inertia of the effective beam and the slab.
Subscripted parameters and are used to identify computed for the directions of
, and , respectively.
The flexural stiffnesses of the beam and slab may be based on the gross concrete section,
neglecting reinforcement and possible cracking, and variations due to column capitals and
drop panels may be neglected. For the beam, if present, and for the slab, are
defined as in Section 9.4.
The relative restraint provided by the torsional resistance of the effective transverse edge
beam is reflected by the parameter , defined as
where , as before, is calculated for the slab spanning in direction , and having width
bounded by panel centerlines in the direction. The constant pertains to the torsional
rigidity of the effective transverse beam, which is defined according to ACI Code 13.7.5 as
the largest of the following:
1. A portion of the slab having a width equal to that of the column, bracket, or capital in
the direction in which moments are taken,
2. The portion of the slab specified in 1 plus that part of any transverse beam above and
below the slab,
3. The transverse beam defined as in Section 9.4.
The constant is calculated by dividing the section into its component rectangles, each
having smaller dimension and larger dimension , and summing the contributions of all
the parts by means of the equation
∑( )
With these parameters defined, ACI Code 13.6.4 distributes the negative and positive
moments between column strips and middle strips, assigning to the column strips the
percentages of positive and negative moments shown in the next table. Linear interpolations
are to be made between the values shown.
An interior panel of a flat-plate floor in an apartment building shown below. The slab
thickness is . The slab supports a design live load of and a superimposed
dead load of for partitions. The columns and slab have the same strength of
concrete. The story height is . Compute the column-strip and middle-strip moments
in the short direction of the panel.
Solution:
The column strip extends the smaller of or on each side of the column
centerline (ACI Code Section 13.2.1). Thus, the column strip extends on each
side of column centerline. The total width of the column strip is . Each half-middle strip
extends from the edge of the column strip to the centerline of the panel. The total width of
two half-middle strips is .
299
Reinforced Concrete II Dr. Nasr Abboushi
(b) Compute .
(c) Divide into negative and positive moments. From ACI Code Section 13.6.3.2,
Negative moment
Positive moment
This process is illustrated in the figure (a) below, and the resulting distribution of total
moments is shown in figure (b).
300
Reinforced Concrete II Dr. Nasr Abboushi
(d) Divide the moments between the column and middle strips.
Negative moments: From Table (page 299) for ( because there
are no beams between columns and in this panel),
These calculations are illustrated in figure (a) below. The resulting distributions of moments
in the column strip and middle strip are summarized in figure (c).
301
Reinforced Concrete II Dr. Nasr Abboushi
In the next figure, the moments in each strip have been divided by the width of that strip.
3. Compute the moments in the long span of the slab. Although it was not asked for in
this example, in a slab design, it now would be necessary to repeat steps 2(a) to 2(d)
for the long span.
4. Design the middle and the column strips for these moments and find the
reinforcement area for each strip.
The ACI Code presents two general methods for calculating the longitudinal distribution of
moments in two-way slab systems. These are the direct-design method (presented in the
previous section) and equivalent-frame methods, which are presented in this section.
Equivalent-frame methods are intended for use in analyzing moments in any practical slab–
column frame. Their scope is thus wider than the direct-design method, which is subject to
the limitations presented in Section 9.9.1 (ACI Code Section 13.6.1). In the direct-design
method, the statical moment, is calculated for each slab span. This moment is then divided
between positive- and negative-moment regions using arbitrary moment coefficients, which
are adjusted to reflect pattern loadings. For equivalent-frame methods, a stiffness analyses
of a slab–column frame is used to determine the longitudinal distribution of bending
moments, including possible pattern loadings. The transverse distribution of moments to
column and middle strips, as defined in the prior section, is the same for both methods.
The design requirements can be explained as follows.
1. Description of the equivalent frame: An equivalent frame is a two-dimensional
building frame obtained by cutting the three-dimensional building along lines
midway between columns (see the figure below). The resulting equivalent frames are
considered separately in the longitudinal and transverse directions of the building.
302
Reinforced Concrete II Dr. Nasr Abboushi
For vertical loads, each floor is analyzed separately, with the far ends of the upper
and lower columns assumed to be fixed. The slab-beam may be assumed to be fixed
at any support two panels away from the support considered, because the vertical
loads contribute very little to the moment at that support. For lateral loads, the
equivalent frame consists of all the floors and extends for the full height of the
building, because the forces at each floor are a function of the lateral forces on all
floors above the considered level. Analysis of frames can also be made using
computer programs.
2. Load assumptions: When the ratio of the service live load to the service dead load is
less than or equal to , the structural analysis of the frame can be made with the
factored dead and live loads acting on all spans instead of a pattern loading. When
the ratio of the service live load to the service dead load is greater than , pattern
loading must be used, considering the following conditions:
303
Reinforced Concrete II Dr. Nasr Abboushi
a. Only of the full-factored live load may be used for the pattern loading
analysis.
b. The maximum negative bending moment in the slab at the support is
obtained by loading only the two adjacent spans.
c. The maximum positive moment near a midspan is obtained by loading only
alternate spans.
d. The design moments must not be less than those occurring with a full-
factored live load on all panels (ACI Code, Section 13.7.6).
e. The critical negative moments are considered to be acting at the face of a
rectangular column or at the face of the equivalent square column having
the same area for nonrectangular sections.
3. Slab-beam moment of inertia: The ACI Code specifies that the variation in moment
of inertia along the longitudinal axes of the columns and slab beams must be taken
into account in the analysis of frames. The critical region is located between the
centerline of the column and the face of the column, bracket, or capital. This region
may be considered as a thickened section of the floor slab. To account for the large
depth of the column and its reduced effective width in contact with the slab beam,
the ACI Code, Section 13.7.3.3, specifies that the moment of inertia of the slab beam
between the center of the column and the face of the support is to be assumed equal
to that of the slab beam at the face of the column divided by the quantity
— , where is the column width in the transverse direction and is the
width of the slab beam. The area of the gross section can be used to calculate the
moment of inertia of the slab beam.
4. Column moment of inertia: The ACI Code, Section 13.7.4, states that the moment of
inertia of the column is to be assumed infinite from the top of the slab to the bottom
of the column capital or slab beams.
304
Reinforced Concrete II Dr. Nasr Abboushi
∑ ∑
where ∑ is the sum of the stiffness of the upper and lower columns at their ends,
∑
( )
∑( )
Stirrups:
ACI Code Section 11.11.3 allows the use of single-leg, multiple-leg and closed stirrups,
provided there are longitudinal bars in all corners of the stirrups.
Stirrups are allowed in slabs with effective depths, , that exceed the larger of or
16 times the stirrup diameter. The precision required to bend and place either the closed
stirrups or the multiple-leg stirrups makes these types of shear reinforcement labor-
intensive and expensive. As a result, shear reinforcement consisting of stirrups or bent
reinforcement is not used widely.
305
Reinforced Concrete II Dr. Nasr Abboushi
placement of the shear studs and to anchor the lower ends of the studs, they generally are
shop-welded to flat steel bars at the desired spacing. The vertical rods are referred to as
headed shear reinforcement or headed shear studs. The assembly of studs plus the bar is
called a stud rail.
ACI Section 11.11.5 — Headed shear stud reinforcement, placed perpendicular to the plane
of a slab or footing, shall be permitted in slabs and footings in accordance with 11.11.5.1
through 11.11.5.4. The overall height of the shear stud assembly shall not be less than the
thickness of the member less the sum of:
(1) the concrete cover on the top flexural reinforcement;
(2) the concrete cover on the base rail; and
(3) one-half the bar diameter of the tension flexural reinforcement.
Where flexural tension reinforcement is at the bottom of the section, as in a footing, the
overall height of the shear stud assembly shall not be less than the thickness of the member
less the sum of:
(1) the concrete cover on the bottom flexural reinforcement;
(2) the concrete cover on the head of the stud; and
(3) one-half the bar diameter of the bottom flexural reinforcement.
11.11.5.1 — For the critical section defined in 11.11.1.2, shall be computed using
Eq. (11-2) ( ), with and not exceeding √ and √ ,
respectively. shall be calculated using Eq. (11-15) ( ) with equal to the cross-
sectional area of all the shear reinforcement on one peripheral line that is approximately
parallel to the perimeter of the column section, where is the spacing of the peripheral
lines of headed shear stud reinforcement. shall not be less than √ .
11.11.5.2 — The spacing between the column face and the first peripheral line of
shear reinforcement shall not exceed . The spacing between peripheral lines of shear
reinforcement, measured in a direction perpendicular to any face of the column, shall be
constant. For prestressed slabs or footings satisfying 11.11.2.2, this spacing shall not exceed
; for all other slabs and footings, the spacing shall be based on the value of the shear
stress due to factored shear force and unbalanced moment at the critical section defined in
11.11.1.2, and shall not exceed:
(a) where maximum shear stresses due to factored loads are less than or
equal to √ ;
(b) where maximum shear stresses due to factored loads are greater than
√ .
11.11.5.3 — The spacing between adjacent shear reinforcement elements, measured
on the perimeter of the first peripheral line of shear reinforcement, shall not exceed .
11.11.5.4 — Shear stress due to factored shear force and moment shall not exceed
√ at the critical section located outside the outermost peripheral line of shear
reinforcement.
307
Reinforced Concrete II Dr. Nasr Abboushi
Example (Checking One-Way and Two-Way Shear at an Interior Column in a Flat Plate):
The figure below shows an interior column in a large uniform flat-plate slab. The slab is
thick. An average effective depth, , as shown, normally is used in shear strength
calculations for two-way slabs. Both one-way and two-way punching shear usually is checked
near columns where top reinforcement is used in both principal directions to resist negative-
bending moments. ACI Code Section 7.7.2(c) states that the minimum clear cover for slab
reinforcement is . Thus, assuming
bars are used as flexural reinforcement, the
average value for determining shear strength
of the slab is
Solution:
1. Determine the factored uniform load.
2. Check the one-way shear. One-way shear is critical at a distance from the face of
the column. Thus, the critical sections for one-way shear are A–A and B–B.
The loaded areas causing shear on these sections are cross hatched. Their outer boundaries
are lines of symmetry on which Because the tributary area for section A–A is larger,
this section will be more critical.
(c) Compute at section A–A.
309
Reinforced Concrete II Dr. Nasr Abboushi
√ √
– the slab is OK in one-way shear.
3. Check the two-way punching shear. Punching shear is critical on a rectangular section
located at away from the face of the column. The load on the cross-hatched area
causes shear on the critical perimeter. Once again, the outer boundaries of this area
are lines of symmetry, where is assumed to be zero.
(b) Compute for the critical section. The length of the critical perimeter is
( )√ ( ) ( )
( )√ ( ) ( )
310
Reinforced Concrete II Dr. Nasr Abboushi
( )√ √
So
Because exceeds the slab is OK in two-way shear.
Solution:
The design shear strength of the concrete alone at the critical section from the face of
the column, is the smallest of the following:
( )√ ( ) ( )
( )√ ( ) ( )
where
√ √
This is less than , indicating that shear reinforcement is required. The effective
depth just satisfies the minimum allowed to use stirrup reinforcement, as
described in the beginning of this Section.
In this case, the maximum design strength allowed by the ACI Code is
√ √
satisfactorily above the actual . When shear is resisted by combined action of concrete and
bar reinforcement, the concrete contribution is reduced to
√ √
311
Reinforced Concrete II Dr. Nasr Abboushi
The vertical closed hoop stirrups will be used since must be times the stirrup
diameter ( ) and arranged along four integral beams as shown below.
Thus, the provided is at the first critical section, a distance
from the column face, and the required spacing can be found from:
√ √
from which the minimum perimeter . Using this value of in the other
equations for :
( )√ ( )√
( )√ ( )√
( √ ) ( )
√
( )
√
( √ )
which exceeds the requirement.
Note: the projection distance can be
calculated from the face of the column and assuming that is the column width.
( √ )
312
Reinforced Concrete II Dr. Nasr Abboushi
Four longitudinal bars will be provided inside the corners of each closed hoop stirrup,
as shown, to provide for proper anchorage of the shear reinforcement.
Note that the approach taken here is somewhat conservative because the portion of the slab
load applied inside the perimeter of the critical section does not act on that section and can
thus be subtracted from the factored load of .
Solution:
1. Select the critical section for two-way shear around the column. At this stage in the
calculations, the designer does not know whether shear reinforcement will be
required.
We will assume it is not and will redo the calculations if we are wrong. Assuming
flexural reinforcement, the average effective depth of the slab is
The inner critical shear section for two-way shear in a flat plate extends around the column
at from the face of the column, as shown in the figure below.
The length of one side of the critical shear section around the column is
giving a shear perimeter
2. Compute the shear acting on the critical shear section. The load combinations from
ACI Code Section 9.2 will be used to compute the total factored dead and live loads.
The basic combination for gravity load is
( )√ ( ) ( )
( )√ ( ) ( )
√ √
So
Because less than , shear reinforcement is required at
the critical shear section. Using shear studs as shear reinforcement results in
√ √
This gives
√ √
3. Lay out the punching shear reinforcement. Rows of shear studs welded to bars will
be placed parallel and perpendicular to the main slab reinforcement to cause the
least disruption in the placement of the main slab steel. Using a trial and error
process:
Try eight stud rails, each with seven -diameter studs ( ) with
-diameter heads, and (typical for shear studs).
The spacing to the first set of shear studs, , is to be taken less than or equal to . Thus,
select (see figure). Before proceeding to layout the subsequent rows of shear
studs, the shear strength should be checked at the inner critical section. In Equation
, the area provided by the inner row of shear studs is
314
Reinforced Concrete II Dr. Nasr Abboushi
Try eight stud rails with the first stud located at from the column face.
Subsequent studs are at a spacing of with seven -diameter headed shear
studs per rail.
The outermost studs are at from the face of the column, and the
outer critical section is from the face of the column.
315
Reinforced Concrete II Dr. Nasr Abboushi
The outer critical-shear section is a series of straight line segments passing through points
located outside the outer shear studs, as shown in the figure. The perimeter of this
peripheral line is
( √ )
4. Check the shear stresses on the outer critical section. The factored shear force on the
concrete at the outer critical section is
and
√ √
Because this is larger than , the design is OK.
316
Reinforced Concrete II Dr. Nasr Abboushi
CHAPTER 10 STAIRS
10.1 INTRODUCTION
Stairs must be provided in almost all buildings, either low-rise or high-rise, even if adequate
numbers of elevators are provided. Stairs consist of rises, runs (or treads), and landings. The
total steps and landings are called a staircase. The rise is defined as the vertical distance
between two steps, and the run is the depth of the step. The landing is the horizontal part of
the staircase without rises.
317
Reinforced Concrete II Dr. Nasr Abboushi
318
Reinforced Concrete II Dr. Nasr Abboushi
4. Cantilever stairs: Cantilever stairs are used mostly in fire-escape stairs, and they are
supported by concrete walls or beams. The stairsteps may be of the full-flight type,
projecting from one side of the wall, the half-flight type, projecting from both sides of
the supporting wall, or of the semispiral type. In this type of stairs, each step acts as a
cantilever, and the main reinforcement is placed in the tension side of the run and
the bars are anchored within the concrete wall. Shrinkage and temperature
reinforcement is provided in the transverse direction.
320
Reinforced Concrete II Dr. Nasr Abboushi
Another form of a cantilever stair is that using open-riser steps supported by a central beam,
as shown below. The beam has a slope similar to the flight of stairs and receives the steps on
its horizontally prepared portions. In most cases, precast concrete steps are used, with
special provisions for anchor bolts that fix the steps into the beam.
5. Precast flights of stairs: The speed of construction in some projects requires the use
of precast flights of stairs. The flights may be cast separately and then fixed to cast-
in-place landings. In other cases, the flights, including the landings, are cast and then
placed in position on their supporting walls or beams. They are designed as simply
supported one-way slabs with the main reinforcement at the bottom of the stair
waist. Adequate reinforcement must be provided at the joints.
Provisions must be made for lifting and handling the precast stair units by providing lifting
holes or inserting special lifting hooks into the concrete. Special reinforcement must be
provided at critical locations to account for tensile stresses that will occur in the stairs from
the lifting and handling process.
321
Reinforced Concrete II Dr. Nasr Abboushi
6. Free-standing staircase: In this type of stairs, the landing projects into the air without
any support at its end. The stairs behave in a springboard manner, causing torsional
stresses in the slab.
322
Reinforced Concrete II Dr. Nasr Abboushi
Three systems of loading must be considered in the design of this type of stairs, taking into
consideration that torsional moments will develop in the slab in all cases:
a. When the live load acts on the upper flight and half the landing only (Case 1), the
upper flight slab will be subjected to tensile forces in addition to bending moments,
whereas the lower flight will be subjected to compression forces, which may cause
buckling of the slab.
b. When the live load acts on the lower flight and half the landing only (Case 2), the
upper flight slab will be subjected to tensile forces, whereas the lower flight will be
subjected to bending moment and compression forces.
c. When the live load acts on both upper and lower flights, the loading of one flight will
cause the twisting of the other. The torsional stresses developed in the stairs require
adequate reinforcement in both faces of the stair slabs and the landing. Transverse
reinforcement in the slab and the landing must be provided in both faces of the
concrete in the shape of closed U-bars lapping at midwidth of the stairs. Typical
reinforcement details are shown in the figure below.
323
Reinforced Concrete II Dr. Nasr Abboushi
This type of stairs is favored by architects and sometimes called a pliers-shaped staircase or
jackknife staircase.
For practical design, the parameters may be chosen as follows: flight width between
and , horizontal span between and , total (light height between and
, and slab thickness between and .
The above information is a guide to help the designer to choose the right parameters for an
economical design.
7. Run-riser stairs: Run-riser stairs are stepped underside stairs that consist of a number
of runs and risers rigidly connected without the provision of the normal waist slab.
This type of stairs has an elegant appearance and is sometimes favored by architects.
The structural analysis of run-riser stairs can be simplified by assuming that the effect of
axial forces is negligible and that the load on each run is concentrated at the end of the run
324
Reinforced Concrete II Dr. Nasr Abboushi
(see next figure). For the analysis of a simply supported flight of stairs, consider a simple
flight of two runs, , subjected to a concentrated load at . Because joints and
are rigid, the moment at joint is equal to the moment at , or
where is the width of the run. The moment in rise, , is constant and is equal to .
When the rise is absent, the stairs, , act as a simply supported beam, and the maximum
bending moment occurs at midspan with value
For a flight of stairs that consists of a number of runs and risers, the same approach can be
used; the bending moment diagram is shown below. The moment in is constant and is
equal to the moment at joint , or . Similarly, , and
325
Reinforced Concrete II Dr. Nasr Abboushi
The stairs may be supported at some edges within adjacent walls or may be designed as a
free-standing helical staircase, which is most popular. The structural analysis of helical
staircases is complicated. Design charts for helical stairs are also prepared. Under load, the
flight slab will be subjected to torsional stresses throughout. The upper landing will be
subjected to tensile stresses, whereas compressive stresses occur at the bottom of the flight.
The forces acting at any section may consist of vertical moment, lateral moment, torsional
moment, axial force, shearing force across the waist of the stairs, and radial horizontal
shearing force. The main longitudinal reinforcement consists of helical bars placed in the
concrete waist of the stairs and runs from the top landing to the bottom support. The
transverse reinforcement must be in a closed stirrup form to resist torsional stresses or in a
U-shape lapped at about the midwidth of the stairs.
Based on many studies, the possible practical dimensions may be chosen as follows: Total
subtended arc between and , stair width between and , stairs slab
thickness between and and stair height between and .
The above information can be used as a guide to achieve a proper and economical design of
helical staircase.
326
Reinforced Concrete II Dr. Nasr Abboushi
An alternative method of providing a helical stair is to use a central helical girder located at
the midwidth of the stairs and have the steps project equally on both sides of the girder.
Each step is analyzed as a cantilever, and the reinforcement bars extend all along the top of
the run. Precast concrete steps may be used and can be fixed to specially prepared
horizontal faces at the top surfaces of the girder.
In the second and third types (slab type stairs), the main supporting element could be the
slab itself. The flight could be supported on the landing, which is in turn supported on the
supporting beams. From the structural point of view, it is better that the main supporting
element is spanning in the short direction. However, this depends on the surrounding
beams. If the beams exist around the perimeter of the stair well or at least along the long
sides, solution A in the figure below is more economical. If the supporting beams are only at
the short side, solution B is the only valid structural system.
Since the landing and the stairs are not straight, internal forces are generated in these
sloped elements. The two tensile forces and generated at the kink, producing a third
outward force as shown in the next figure. This force tends to cause splitting cracks if the
produced stresses exceed concrete tensile strength. Thus, tension reinforcement should be
extended from each side so that no outward force is generated.
327
Reinforced Concrete II Dr. Nasr Abboushi
328
Reinforced Concrete II Dr. Nasr Abboushi
Example
Design the staircase shown below, which carries a uniform live load of . Assume a
rise of and a run of . Use and .
Solution
1. Structural system: If no stringer beam is used, one of the four possible solutions
shown in figure (page 318) may be adopted. When no intermediate supports are
used, the flight of stairs will be supported at the ends of the upper and lower
landings. This structural system will be adopted in this example.
2. Minimum slab thickness for deflection is (for a simply supported one-way solid slab)
In the case presented here, where the slab ends are cast with the supporting beams and
additional negative reinforcement is provided, minimum thickness can be assumed to be
Take .
3. Loads: The applied live loads are based on the plan area (horizontal projection), while
the dead load is based on the sloped length. To transform the dead load into
horizontal projection the figure below explains how.
Flight Dead Load computation:
( ) ( )
𝑞 𝐾𝑁 𝑚
𝐿𝑜
𝑤 𝐾𝑁 𝑚
𝑤∙𝐿 𝑞 ∙ 𝐿𝑜
𝐿𝑜 𝑞
𝑤 𝑞∙
𝐿 cos 𝜃
329
Reinforced Concrete II Dr. Nasr Abboushi
Quality Density
Material
Tiles ( )
mortar ( )
Stair steps ( )
Reinforced Concrete
solid slab cos
Plaster
cos
Total Dead Load,
Quality Density ∙ ∙
Material
Tiles
mortar
Reinforced Concrete solid slab
Plaster
Total Dead Load 8.01
Live Load:
Total factored Load:
∙ ∙
∙ ∙
Because the load on the landing is carried into two directions, only half the load will be
considered in each direction .
330
Reinforced Concrete II Dr. Nasr Abboushi
√ ∙√ ∙ ∙ ∙
- for shear.
∙
( ) ∙ ∙( ) ∙ ∙ ∙
∙ ∙
( √ ) ( √ )
∙ ∙
∙ ∙
Use then
Take .
Step ( ) is the smallest of:
1.
2.
331
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( ) ∙
( ) ( )
s s –
Take .
Step ( ) is the smallest of:
1.
2.
s s –
If the slab will be cast monolithically with its supporting beams, additional reinforcement
must be provided at the top of the upper and lower landings. Details of stair reinforcement
are shown in the figure (page 333).
7. Design of landings: Considering a 1-m length of the landing, the load on the landing is
shown in the next figure. The middle will carry a full load, whereas the two
1.5-m lengths on each side will carry half the ultimate load.
( ) ∙ ∙( ) ∙ ∙ ∙
332
Reinforced Concrete II Dr. Nasr Abboushi
333
Reinforced Concrete II Dr. Nasr Abboushi
Assume bar diameter for main reinforcement. Because the bars in the landing will be
placed on top of the main stair reinforcement
∙
∙ ∙
∙ ∙
( √ ) ( √ )
∙ ∙
∙ ∙
then provide
Use then
Take .
Step ( ) is the smallest of:
1.
2.
( ) ( ) ∙
( ) ( )
s s –
8. The transverse beams at the landing levels must be designed to carry loads from
stairs ( ) in addition to their own weight and the weight of the wall
above.
334
Reinforced Concrete II Dr. Nasr Abboushi
Example
Design the staircase shown below, which carries a uniform live load of . Assume a
rise of and a run of . Use and .
Solution
1. Minimum slab thickness for deflection is (for a simply supported one-way solid slab)
Take .
2. Loads:
Flight Dead Load computation:
( ) ( )
Quality Density
Material
Tiles ( )
mortar ( )
Stair steps ( )
Reinforced Concrete
solid slab cos
Plaster
cos
Total Dead Load,
335
Reinforced Concrete II Dr. Nasr Abboushi
Quality Density ∙ ∙
Material
Tiles
mortar
Reinforced Concrete solid slab
Plaster
Total Dead Load 8.01
Live Load:
Total factored Load:
∙ ∙ ∙
∙ ∙ ∙
3. Design of slab S1:
Slab S1 is supported at the centerline of slabs S2 and S3.
√ ∙√ ∙ ∙ ∙
- for shear.
∙
336
Reinforced Concrete II Dr. Nasr Abboushi
( ) ∙
∙ ∙
( √ ) ( √ )
∙ ∙
∙ ∙
Use then
Take .
Step ( ) is the smallest of:
1.
2.
( ) ( ) ∙
( ) ( )
s s –
Take .
Step ( ) is the smallest of:
1.
2.
s s –
or
( )
338
Reinforced Concrete II Dr. Nasr Abboushi
√ ∙√ ∙ ∙ ∙
- for shear.
∙
( ) ∙
∙ ∙
( √ ) ( √ )
∙ ∙
∙ ∙
Use then
Take .
Step ( ) is the smallest of:
1.
339
Reinforced Concrete II Dr. Nasr Abboushi
2.
( ) ( ) ∙
( ) ( )
s s –
Take .
Step ( ) is the smallest of:
1.
2.
s s –
Design the slab S3 for flexure and shear as for slabs S1 and S2.
340
Reinforced Concrete II Dr. Nasr Abboushi
11.1 INTRODUCTION.
Reinforced concrete footings are structural members used to support columns and walls and
to transmit and distribute their loads to the soil. The design is based on the assumption that
the footing is rigid, so that the variation of the soil pressure under the footing is linear.
Uniform soil pressure is achieved when the column load coincides with the centroid of the
footing. Although this assumption is acceptable for rigid footings, such an assumption
becomes less accurate as the footing becomes relatively more flexible. The proper design of
footings requires that
1. The load capacity of the soil is not exceeded.
2. Excessive settlement, differential settlement, or rotations are avoided.
3. Adequate safety against sliding and/or overturning is maintained.
The most common types of footings used in buildings are the single footings and wall
footings. When a column load is transmitted to the soil by the footing, the soil becomes
compressed. The amount of settlement depends on many factors, such as the type of soil,
the load intensity, the depth below ground level, and the type of footing. If different footings
of the same structure have different settlements, new stresses develop in the structure.
Excessive differential settlement may lead to the damage of nonstructural members in the
buildings or even failure of the affected parts.
Vertical loads are usually applied at the centroid of the footing. If the resultant of the applied
loads does not coincide with the centroid of the bearing area, a bending moment develops.
In this case, the pressure on one side of the footing will be greater than the pressure on the
other side.
341
Reinforced Concrete II Dr. Nasr Abboushi
If the bearing soil capacity is different under different footings—for example, if the footings
of a building are partly on soil and partly on rock—a differential settlement will occur. It is
usual in such cases to provide a joint between the two parts to separate them, allowing for
independent settlement.
The depth of the footing below the ground level is an important factor in the design of
footings. This depth should be determined from soil tests, which should provide reliable
information on safe bearing capacity at different layers below ground level. Soil test reports
specify the allowable bearing capacity to be used in the design. In cold areas where freezing
occurs, frost action may cause heaving or subsidence. It is necessary to place footings below
freezing depth to avoid movements.
Different types of footings may be used to support building columns or walls. The most
common types are as follows:
1. Wall footings are used to support structural walls that carry loads from other floors
or to support nonstructural walls. They have a limited width and a continuous length
under the wall. Wall footings may have one thickness, be stepped, or have a sloped
top.
2. Isolated, or single, footings are used to support single columns. They may be square,
rectangular, or circular. Again, the footing may be of uniform thickness, stepped, or
have a sloped top. This is one of the most economical types of footings, and it is used
when columns are spaced at relatively long distances. The most commonly used are
square or rectangular footings with uniform thickness.
342
Reinforced Concrete II Dr. Nasr Abboushi
3. Combined footings usually support two columns or three columns not in a row. The
shape of the footing in plan may be rectangular or trapezoidal, depending on column
loads. Combined footings are used when two columns are so close that single
footings cannot be used or when one column is located at or near a property line.
4. Cantilever, or strap, footings consist of two single footings connected with a beam or
a strap and support two single columns. They are used when one footing supports an
eccentric column and the nearest adjacent footing lies at quite a distance from it.
This type replaces a combined footing and is sometimes more economical.
5. Continuous footings support a row of three or more columns. They have limited
width and continue under all columns.
6. Raft, or mat, foundations consist of one footing, usually placed under the entire
building area, and support the columns of the building. They are used when:
a. The soil-bearing capacity is low.
b. Column loads are heavy.
c. Single footings cannot be used.
d. Piles are not used.
e. Differential settlement must be reduced through the entire footing system.
2. Pile caps are thick slabs used to tie a group of piles together and to support and
transmit column loads to the piles.
The figure below shows a footing supporting a single column. When the column load, P, is
applied on the centroid of the footing, a uniform pressure is assumed to develop on the soil
surface below the footing area. However, the actual distribution of soil pressure is not
uniform but depends on many factors, especially the composition of the soil and the degree
of flexibility of the footing. For example, the distribution of pressure on cohesionless soil
(sand) under a rigid footing is shown. The pressure is maximum under the center of the
footing and decreases toward the ends of the footing. The cohesionless soil tends to move
from the edges of the footing, causing a reduction in pressure, whereas the pressure
343
Reinforced Concrete II Dr. Nasr Abboushi
increases around the center to satisfy equilibrium conditions. If the footing is resting on a
cohesive soil such as clay, the pressure under the edges is greater than at the center of the
footing. The clay near the edges has a strong cohesion with the adjacent clay surrounding
the footing, causing the nonuniform pressure distribution.
The allowable bearing soil pressure, , is usually determined from soil tests. The allowable
values vary with the type of soil, from extremely high in rocky beds to low in silty soils.
Maximum allowable
Class of Material
soil pressure [ ]
of ultimate
Rock
crushing strength
Compact coarse sand, compact fine sand,
hard clay, or sand clay
Loose sand
The figure below shows a -thick spread footing with a column at its center and with its
top surface located below the ground surface. There is no column load at this stage.
The total downward load from the weights of the soil and the footing is . This is
balanced by an equal, but opposite, upward pressure. As a result, the net effect on the
concrete footing is zero. There are no moments or shears in the footing due to this loading.
When the column load is added, the pressure under the footing increases by . The
total soil pressure is . This is referred to as the gross soil pressure and must
not exceed the allowable soil pressure, . When moments and shears in the concrete
footing are calculated, the upward and downward pressures of cancel out,
leaving only the net soil pressure, , to cause internal forces in the footing.
In design, the area of the footing is selected so that the gross soil pressure does not exceed
the allowable soil pressure. The flexural reinforcement and the shear strength of the footing
are then calculated by using the net soil pressure. Thus, the area of the footing is selected to
be
344
Reinforced Concrete II Dr. Nasr Abboushi
where and refer to the unfactored service dead and live loads.
Once the area of the footing is known, the rest of the design of the footing is based on soil
stresses due to the factored loads.
345
Reinforced Concrete II Dr. Nasr Abboushi
Once the area is determined, a factored soil pressure is obtained by dividing the factored
load, , by the area of the footing. This is required to design the footing
by the strength design method.
The allowable soil pressure, , is obtained from soil test and is based on service load
conditions.
For footings with bending action in one direction, the critical section is located at a distance
from the face of the column. The diagonal tension at section m-m in the figure of one way
shear can be checked as was done before in beams. The allowable shear in this case is equal
to
√ √
where width of section m-m. The factored shear force at section m-m can be
calculated as follows:
346
Reinforced Concrete II Dr. Nasr Abboushi
( )
If no shear reinforcement is to be used, then can be determined, assuming :
Two-way shear is a measure of the diagonal tension caused by the effect of the column load
on the footing. Inclined cracks may occur in the footing at a distance from the face of
the column on all sides. The footing will fail as the column tries to punch out part of the
footing.
The ACI Code, Section 11.11.2 allows a shear strength, , in footings without shear
reinforcement for two-way shear action, the smallest of
( ) √
( ) √
For shapes other than rectangular, is taken to be the ratio of the longest dimension of the
effective loaded area in the long direction to the largest width in the short direction
(perpendicular to the long direction).
perimeter of the critical section taken at from the loaded area.
effective depth of footing.
for normal-weight concrete.
is assumed to be:
for interior columns,
for edge columns, and
for corner columns.
Based on the preceding three values of , the effective depth, , required for two-way
shear is the largest obtained from the following formulas assuming ):
( ) √
( ) √
348
Reinforced Concrete II Dr. Nasr Abboushi
maximum spacing of steel bars in the direction of bending shall be as required for shrinkage
and temperature reinforcement (see section 8.4, 8.5 page 195).
The reinforcement in one-way footings
and two-way footings must be
distributed across the entire width of
the footing. In the case of two-way
rectangular footings, the ACI Code,
Section 15.4.4, specifies that in the long
direction, a portion of the total
reinforcement distributed
uniformly along the width of the
footing. In the short direction, a certain
ratio of the total reinforcement in this
direction must be placed uniformly
within a bandwidth equal to the length
of the short side of the footing
according to
The bandwidth must be centered on the centerline of the column. The remaining
reinforcement in the short direction must be uniformly distributed outside the bandwidth.
This remaining reinforcement percentage shall not be less than that required for shrinkage
and temperature.
When structural steel columns or masonry walls are used, then the critical sections for
moments in footings are taken at halfway between the middle and the edge of masonry
walls and halfway between the face of the column and the edge of the steel base place (ACI
Code, Section 15.4.2).
349
Reinforced Concrete II Dr. Nasr Abboushi
Generally, the column bars stop at the bottom of the column, and dowels are used to
transfer forces across the column–footing joint. Dowels are used because it is awkward to
embed the column steel in the footing, due to its unsupported height above the footing and
the difficulty in locating it accurately. The above figure a shows an column
with and bars. The column is supported on a footing made of
concrete. There are Grade-420 dowels in the connection. The dowels
extend into the footing a distance equal to the compression development length of a
bottom bar in concrete ( ) and into the column a distance equal to the
greater of
1. the compression lap-splice length for a bar in concrete ( ), and
2. the compression development length of a bar in concrete ( ).
350
Reinforced Concrete II Dr. Nasr Abboushi
The total capacity of the column for pure axial load is , of which is carried
by the steel and the rest by the concrete, as shown in the previous figure b. At the joint, the
area of the dowels is less than that of the column bars, and the force transmitted by the
dowels is , where is the area of the dowels and is that for tied columns. As a
result, the load carried by the concrete has increased. In the above figure, the dowels are
hooked so that they can be supported on and tied
to the mat of footing reinforcement when the
footing concrete is placed. The hooks cannot be
used to develop compressive force in the bars
(ACI Code Section 12.5.5).
The maximum bearing load on the concrete is
defined in ACI Code Section 10.14 as
. If the load combinations from ACI
Code Section 9.2 are used, ACI Code Section
9.3.2.4 gives for bearing and is the
area of the contact surface.
When the supporting surface is wider on all sides
than the loaded area, the maximum bearing load
may be taken as
351
Reinforced Concrete II Dr. Nasr Abboushi
If no moments are transmitted, or if the eccentricity falls within the kern of the column,
there will be compression over the full section. The total force transferred by bearing is
then calculated as times the smaller of the bearing stresses allowed on the
column or the footing, where is total area of the column and is the area of the bars
or dowels crossing the joint. Any additional load must be transferred by dowels.
If moments are transmitted to the footing, bearing stresses will exist over part, but not all,
of the column cross section. The number of dowels required can be obtained by considering
the area of the joint as an eccentrically loaded column with a maximum concrete stress
equal to the smaller of the bearing stresses allowed on the column or the footing. Sufficient
reinforcement must cross the interface to provide the necessary axial load and moment
capacity. Generally, this requires that all the column reinforcement or similar-sized dowel
bars must cross the interface. This steel must be spliced in accordance with the
requirements for column splices.
Practical Aspects
Three other aspects warrant discussion prior to the examples. The minimum cover to the
reinforcement in footings cast against the soil is (ACI Code Section 7.7.1). This
allows for small irregularities in the surface of the excavation and for potential
contamination of the bottom layer of concrete with soil. Sometimes, the bottom of the
excavation for the footing is covered with a lean concrete seal coat, to prevent the bottom
from becoming uneven after rainstorms and to give a level surface for placing
reinforcement.
The minimum depth of the footing above the bottom reinforcement is for footings
on soil and for footings on piles (ACI Code Section 15.7). ACI Code Section 10.6.4,
covering the distribution of flexural reinforcement in beams and one-way slabs, does not
apply to footings.
352
Reinforced Concrete II Dr. Nasr Abboushi
Spread footings are square or rectangular pads that spread a column load over an area of
soil large enough to support the column load. The soil pressure causes the footing to deflect
upward, causing tension in two directions at the bottom. As a result, reinforcement is placed
in two directions at the bottom.
weight of soil:
353
Reinforced Concrete II Dr. Nasr Abboushi
√ √
Take
Depth of footing and shear design:
( ) ( )
Let
√ √
( ) √
Assume cover 75 mm, and steel bars of
Generally, the thickness of aspread footing is governed by two-way shear. The shear will be
checked on the critical perimeter at from the face of the column and, if necessary, the
thickness will be increased or decreased. Because there is reinforcement in both directions,
the average will be used:
354
Reinforced Concrete II Dr. Nasr Abboushi
Let
( )
( )
( )√ ( ) ( )
( )√ ( ) ( )
Take √ √
Try
( )
( )
√ √
355
Reinforced Concrete II Dr. Nasr Abboushi
( √ ) ( √ )
Take with
Using bars of instead of as assumed before makes the effective depth larger.
So no need to check for .
1.
2.
356
Reinforced Concrete II Dr. Nasr Abboushi
( √ ) ( √ )
Take with
Using bars of instead of as assumed before makes the effective depth larger.
So no need to check for .
357
Reinforced Concrete II Dr. Nasr Abboushi
𝑚
0.55 m
𝑚
𝑚
Check for the development length as will be discussed later (see chapter 12.)
358
Reinforced Concrete II Dr. Nasr Abboushi
pyramid or cone as defined earlier. ACI Code Section 9.3.2.4 defines equal to 0.65 for
bearing.
2.8 m
Thus, the maximum load that can be transferred by bearing is , and dowels are
NOT needed.
The minimum area of dowels
Note: If dowels are needed, the required area of dowels
Where has been used. This is the value from ACI Code Sections 9.3.2.2(b) for
compression-controlled tied columns and 9.3.2.4 for bearing.
Use or use the same reinforcement as in the column if larger.
The dowels must extend into the footing a distance equal to the compression-development
length ( and concrete). The bars will be extended down to the level of the
main footing steel and hooked . The hooks will be tied to the main steel to hold the
dowels in place. The dowels must extend into the column a distance equal to the greater of
a compression splice for the dowels or the compression development length of the column
bars. Dowel each corner bar.
359
Reinforced Concrete II Dr. Nasr Abboushi
A wall footing cantilevers out on both sides of the wall as shown. The soil pressure causes
the cantilevers to bend upward, and as a result, reinforcement is required at the bottom of
the footing. The critical sections for design for flexure and anchorage are at the face of the
wall (section A–A). One-way shear is critical at a section a distance from the face of the
wall (section B–B).
The presence of the wall prevents two-way shear.
Solution:
Estimate the size of the footing and the factored net pressure. Consider a 1- strip of
footing and wall. Allowable soil pressure is . Because the thickness of the
footing is not known at this stage, it is necessary to guess a thickness for a first trial.
Try a - -thick footing.
Therefore,
and we have:
Take .
Depth of footing and shear design:
360
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( )
Let
√ √
( ) √
Assume cover , and steel bars of
( √ ) ( √ )
Or Take with
Using bars of instead of as assumed before makes the effective depth larger.
So no need to check for .
Step is the smallest of:
1.
361
Reinforced Concrete II Dr. Nasr Abboushi
2.
362
Reinforced Concrete II Dr. Nasr Abboushi
When a column transmits axial loads only, the footing can be designed such that the load
acts at the centroid of the footing, producing uniform pressure under the footing. However,
in some cases, the column transmits an axial load and a bending moment, as in the case of
the footings of fixed-end frames. The pressure q that develops on the soil will not be uniform
and can be evaluated from the following equation:
where
vertical load, positive in compression,
area of the contact surface between the soil and the footing,
moment of inertia of this area,
moment about the centroidal axis
of the footing area
distance from the centroidal axis to
the point where the stresses are being
calculated.
The moment, , can be expressed as
, where is the eccentricity of the
load relative to the centroidal axis of the
area . The maximum eccentricity for
which the previous equation applies is
that which first causes at some
point. Larger eccentricities will cause a
portion of the footing to lift off the soil,
because the soil – footing interface
cannot resist tension. For a rectangular
footing, this occurs when the
eccentricity exceeds
. If the load acts through the kern point, at one side and at the
other. If the load falls outside the kern point, the resultant upward load is equal and
opposite to the resultant downward load, as shown in next figure (d). Generally, such a
pressure distribution would not be acceptable, because it makes inefficient use of the
footing concrete, tends to overload the soil, and may cause the structure to tilt.
364
Reinforced Concrete II Dr. Nasr Abboushi
( )
( )
Example:
Determine the dimensions of an isolated footing subjected to the loads:
𝑃 𝐾𝑁 𝑃 𝐾𝑁
𝑚
𝑀 𝐾𝑁 𝑚
𝑚 𝑚 𝑚
𝑚𝑚
Use
Use
𝑚𝑚
𝑚 𝑚
No tension zone.
365
Reinforced Concrete II Dr. Nasr Abboushi
. Take
Assume
Example:
Determine the dimension of an isolated footing subjected to the loads:
( )
𝑚
Take
( ) ( )
𝐾𝑁 𝑚
𝑥 𝑚
𝑒 𝑚
366
Reinforced Concrete II Dr. Nasr Abboushi
Example (Design a Rectangular Footing for a Column Subjected to Axial Load and Bending):
The rectangular footing has a width of and it will be supporting a column
that is carrying the following loads.
Service surcharge
Permissible (allowable) soil pressure
Soil density ( soil depth
2. Estimate footing length and depth. Estimate the overall thickness, , of the footing to
be between 1.5 and 2.0 times the size of the column, so select .
The net permissible bearing pressure is:
Assume the soil pressure distribution at the base of the footing is trapezoidal (no tension
zone). Assuming a footing width, , and a footing length, , an expression for the maximum
bearing pressure under the footing is:
Setting we can use the following expression to solve for the required footing
length, .
or
3. Calculate factored soil pressures. (Note: In the prior step the acting loads were used
with the allowable soil bearing pressure to select the size of the footing. Now, the
factored loads will be used to determine the soil pressures that will subsequently be
used to determine the factored moment and shear used for the design of the
footing.)
367
Reinforced Concrete II Dr. Nasr Abboushi
4. Check for one-way shear. The critical section for checking one-way shear strength is
shown. To simplify this check, it is conservative to assume that the maximum
factored soil pressure of acts on the entire shaded region. Thus, the
factored shear force to be resisted at the critical section is (Take steel bars of ):
( )
Let
√ √
5. Check footing thickness for two-way shear. The critical shear perimeter is located
away from each column face, as shown. Assume the average effective depth for
the footing is (Take steel bars of ):
Thus, each side of the critical shear perimeter has a length of . Using the average
factored shear stress inside the critical perimeter
( ) the net factored shear to be transferred across
the critical perimeter is:
369
Reinforced Concrete II Dr. Nasr Abboushi
( )√ ( ) ( )
( )√ ( ) ( )
Take √ √
Thus, the footing depth satisfies the strength requirement for the net shear force.
370
Reinforced Concrete II Dr. Nasr Abboushi
( √ ) ( √ )
Take with
Using bars of instead of as assumed before makes the effective depth larger.
So no need to check for .
1.
2.
The design procedure for flexural reinforcement in the transverse direction would be Similar.
For the arrangement of the bars in the transverse direction (ACI Code Section 15.4.4.2).
371
Reinforced Concrete II Dr. Nasr Abboushi
Combined footings are used when it is necessary to support two columns on one footing.
When an exterior column is so close to a property line that a spread footing cannot be used,
a combined footing is often used to support the edge column and an interior column.
The shape of the footing is chosen such that the centroid of the area in contact with soil
coincides with the resultant of the column loads supported by the footing.
Sometimes, a combined footing will be designed as two isolated pads joined by a strap or
stiff beam. Here, the exterior footing acts as a wall footing, cantilevering out on the two
sides of the strap. The interior footing can be designed as a two-way footing. The strap is
designed as a beam and may require shear reinforcement in it.
372
Reinforced Concrete II Dr. Nasr Abboushi
The soil pressure is assumed to act on longitudinal beam strips, A–B–C. These transmit the
load to hypothetical cross beams, A–D and B–E, which transmit the upward soil reactions to
the columns. For the column placement shown, the longitudinal beam strips would deflect
as shown, requiring the reinforcement shown.
373
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
𝑃𝐷 𝐾𝑁 𝑃 𝐷 𝐾𝑁
𝑃𝐿 𝐾𝑁 𝑃 𝐿 𝐾𝑁
𝑐𝑚 𝑐𝑚
𝑐𝑜𝑙 𝑐𝑜𝑙
𝑞
𝑃 𝐾𝑁
Footing dimensions.
𝑐𝑚 𝑐𝑚
𝑚 𝑚
𝑐𝑜𝑙 𝑐𝑜𝑙
𝑚
𝑚 𝑚 𝑚
374
Reinforced Concrete II Dr. Nasr Abboushi
𝑃𝑢 𝐾𝑁 𝑃 𝑢 𝐾𝑁
𝑐𝑚 𝑐𝑚
𝑚 𝑚
𝑐𝑜𝑙 𝑐𝑜𝑙
𝑚
𝑚 𝑚 𝑚
𝐾𝑁 𝑚
𝑥 𝑚
𝑀𝑚𝑎𝑥 𝐾𝑁
375
Reinforced Concrete II Dr. Nasr Abboushi
√ √
At column 1 :
At column 2 :
At column 1, :
( )
( )
( )√ ( ) ( )
( )√ ( ) ( )
√ √
376
Reinforced Concrete II Dr. Nasr Abboushi
At column 2, :
( )
( )
( )√ ( ) ( )
( )√ ( ) ( )
√ √
Now, we can design the footing for flexure. By calculating the negative and positive
moments or by analyzing the combined footing using BeamD software we plot the moment
diagram. The moment diagram is plotted for the full 3.3 m width of the footing.
377
Reinforced Concrete II Dr. Nasr Abboushi
( √ ) ( √ )
Provide
Take with
Using bars of instead of as assumed before makes the effective depth larger.
So no need to check for .
1.
2.
( )
378
Reinforced Concrete II Dr. Nasr Abboushi
( √ ) ( √ )
Take with
( )
( √ ) ( √ )
Take with
379
Reinforced Concrete II Dr. Nasr Abboushi
Example
A continuous footing supports three columns carrying a service dead load and a
service live load as shown. The length of the footing is . The allowable net soil bearing
pressure is .
Design the footing, assuming that and .
𝑃𝐷 𝐾𝑁 𝑃𝐷 𝐾𝑁 𝑃𝐷 𝐾𝑁
𝑃𝐿 𝐾𝑁 𝑃𝐿 𝐾𝑁 𝑃𝐿 𝐾𝑁
𝑐𝑚 𝑐𝑚 𝑐𝑚
𝑚 𝑚
𝑐𝑜𝑙 𝑐𝑜𝑙 𝑐𝑜𝑙
𝑚 𝑚 𝑚 𝑚
380
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
1. Footing width.
𝑃𝐷 𝐾𝑁 𝑃𝐷 𝐾𝑁 𝑃𝐷 𝐾𝑁
𝑃𝐿 𝐾𝑁 𝑃𝐿 𝐾𝑁 𝑃𝐿 𝐾𝑁
𝑐𝑚 𝑐𝑚 𝑐𝑚
𝑚 𝑚
𝑐𝑜𝑙 𝑐𝑜𝑙 𝑐𝑜𝑙
𝑚 𝑚 𝑚 𝑚
𝐾𝑁 𝑚
𝐾𝑁 𝑚
381
Reinforced Concrete II Dr. Nasr Abboushi
𝐾𝑁 𝑚
𝐾𝑁 𝑚
√ √
At column 1, :
at distance from the face of support:
( )
At column 2, :
at distance from the Left face of support:
( )
at distance from the Right face of support:
( )
Or from the right:
( )
At column 3, :
382
Reinforced Concrete II Dr. Nasr Abboushi
( )
At column 1, :
( )
( ) ( )
( )√ ( ) ( )
( )√ ( ) ( )
√ √
( )
383
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( )
√ √
At column 2, :
( )
( )√ ( ) ( )
( )√ ( ) ( )
√ √
At column 3, :
( )
384
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( )
( )√ ( ) ( )
( )√ ( ) ( )
√ √
Now, we can design the footing for flexure. By calculating the negative and positive
moments or by analyzing the combined footing using BeamD software we plot the moment
diagram. The moment diagram is plotted for the full width of the footing.
1 2 3 4 5
1 2 3 4
A A A A
A A A A
0.3 0.3 1.7 0.3 1.7 0.3 0.3
0.45 2. 2. 0.45
-2127.7
-2070.5 -2070.5 -1816.3 -1816.3 -1562.1 -1562.1
-1504.9
0.45 2. 2. 0.45
-482.3
-387.7
0.14 0.51
0.46 0.13
-15.9 -25.4
95.2
213.5 154.3 68.3
506.4 527.2
816.2
385
Reinforced Concrete II Dr. Nasr Abboushi
When the bearing capacity of the soil is low, isolated footings are replaced by a raft
foundation. In such a case, a solid reinforced concrete rigid slab is constructed under the
entire building as shown below. Structurally, raft foundations resting directly on soil act as a
flat slab or a flat plate, upside down, i.e., loaded upward by the bearing pressure and
downward by the concentrated column reactions. The raft foundation develops the
maximum available bearing area under the building. If the bearing capacity of the soil is so
low that even this large bearing capacity is insufficient, deep foundations such as piles must
be used. Apart from developing large bearing areas, another advantage of raft foundations is
that their continuity and rigidity that helps in reducing differential settlement of individual
columns relative to each other, which might be caused by local variations in the quality of
subsoil, or other causes.
The design of raft foundations may be carried out by one of two methods:
• T conv ntional igid m t od and;
• T finit l m nt m t od utilizing comput p og ams.
The conventional method is easy to apply and the computations can be carried out using
hand calculations. However, the application of the conventional method is limited to rafts
with relatively regular arrangement of columns.
In contrast, the finite element method can be used for the analysis of raft regardless of the
column arrangements, loading conditions, and existence of cores and shear walls.
Commercially available computer programs can be used. The user should, however, have
sufficient background and experience.
Where
area of the raft
moment of inertia of the raft about axis
387
Reinforced Concrete II Dr. Nasr Abboushi
To draw the shear and moment diagrams we can divide the raft into several strips in the
direction (B1, B2, B3) and in the direction (B4, B5, B6, B7). The soil pressure at the
center-line of the strip is assumed constant along the width of the strip.
Design each strip for shear and flexure as in the continuous footing design.
Example
Design the mat foundation, assuming that and . The allowable
net soil bearing pressure is . Columns dimensions are .
388
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
Y
A B C D
0.9 m
445 KN 801 KN 845 KN 489 KN
267 KN 534 KN 534 KN 311 KN
(712) KN (1335) KN (1379) KN (800) KN
(961) KN (1816) KN (1868) KN (1084) KN
9m
E F G H
9m
I J K L
K
845 KN 1779 KN 1957 KN 890 KN
578 KN 1068 KN 1334 KN 534 KN
(1423) KN (2847) KN (3291) KN (1424) KN
(1939) KN (3844) KN (4483) KN (1922) KN
9m
0.6 m 0.6 m
389
Reinforced Concrete II Dr. Nasr Abboushi
A B D
𝑒𝑦 𝑚
𝑒𝑥 𝑚
M N P
390
Reinforced Concrete II Dr. Nasr Abboushi
The maximum soil pressure ill b at point “P” and is l ss t allo abl soil
pressure .
Check
( )
391
Reinforced Concrete II Dr. Nasr Abboushi
𝐾𝑁 𝐾𝑁 𝐾𝑁 𝐾𝑁
F J
B N
𝑚 𝑚 𝑚 𝑚 𝑚
𝐾𝑁 𝑚
𝐾𝑁 𝑚
The mat foundation will be divided into several strips in both directions. The stress
distribution will be defined for each strip as was done for the previous strip.
Each strip will be treated as continuous footing with flexure along the strip only. Analysis and
design of the strip will be analoge to the analysis an design of continuous footing.
392
Reinforced Concrete II Dr. Nasr Abboushi
12.1 INTRODUCTION
( ) ( )
And taking ( ) gives
393
Reinforced Concrete II Dr. Nasr Abboushi
If we consider a length of beam between two cracks, as shown in the above figures, the
moments acting at the two cracks are and . If the beam is reinforced with one bar of
diameter , the forces on the bar are as shown. Summing horizontal forces gives
( )
( )
( )
( )
If there is more than one bar, the bar perimeter is replaced with the sum of the perimeters
∑ , giving
∑
The last two equations give the average bond stress between two cracks in a beam. The
actual bond stresses vary from point to point between the cracks.
A smooth bar embedded in concrete develops bond by adhesion between the concrete and
the bar and by a small amount of friction. Both of these effects are quickly lost when the bar
is loaded in tension, particularly because the diameter of the bar decreases slightly, due to
Poisson’s ratio. For this reason, smooth bars are generally not used as reinforcement. In
cases where smooth bars must be embedded in concrete (anchor bolts, stirrups made of
small diameter bars, etc.), mechanical anchorage in the form of hooks, nuts, and washers on
the embedded end (or similar devices) are used.
Although adhesion and friction are present when a deformed bar is loaded for the first time,
these bond-transfer mechanisms are quickly lost, leaving the bond to be transferred by
bearing on the deformations of the bar as shown in figure (a). Equal and opposite bearing
stresses act on the concrete, as shown in figure (b). The forces on the concrete have both a
longitudinal and a radial component (figures c and d). The latter causes circumferential
tensile stresses in the concrete around the bar. Eventually, the concrete will split parallel to
the bar, and the resulting crack will propagate out to the surface of the beam. The splitting
394
Reinforced Concrete II Dr. Nasr Abboushi
cracks follow the reinforcing bars along the bottom or side surfaces of the beam,
as shown in figure below. Once these cracks develop, the bond transfer drops rapidly unless
reinforcement is provided to restrain the opening of the splitting crack.
395
Reinforced Concrete II Dr. Nasr Abboushi
Because the actual bond stress varies along the length of a bar anchored in a zone of
tension, the ACI Code uses the concept of development length rather than bond stress. The
development length, , is the shortest length of bar in which the bar stress can increase
from zero to the yield strength, . If the distance from a point where the bar stress equals
to the end of the bar is less than the development length, the bar will pull out of the
concrete. The development lengths are different in tension and compression, because a bar
loaded in tension is subject to in-and-out bond stresses and hence requires a considerably
longer development length. Also, for a bar in compression, bearing stresses at the end of the
bar will transfer part of the compression force into the concrete.
The development length can be expressed in terms of the ultimate value of the average
bond stress by setting in equation for equal to :
1. Tension-Development Lengths
shown by the larger circles in the previous figure. Splitting is assumed to occur when the
maximum stress in the concrete is equal to the tensile strength of the concrete, . For
equilibrium in the vertical direction in a prism of length equal to
( )
where is the ratio of the average tensile stress to the maximum tensile stress and equals
for the triangular stress distribution shown in figure “c” below. Rearranging gives
( )
If the forces shown in the figures b and c on page (395) are assumed to act at , the
average bond stress, , at the onset of splitting is equal to . Taking √ gives
√ ( )
The length of bar required to raise the stress in the bar from zero to is called the
development length,
√ ( )
Arbitrarily taking (for the reasons to be given in the derivation of Equations for
Development Lengths later in the chapter) and rearranging yields
√
Basic Tension-Development Equation.
The ACI Code simplified the design expressions, in two stages as will be explained later. First,
a basic expression was developed for the development length, given in ACI Code Section
12.2.3 as
( )
√ ( )
397
Reinforced Concrete II Dr. Nasr Abboushi
where the confinement term ( ) is limited to 2.5 or smaller, to prevent pull-out bond
failures, and the length is not taken less than . Also,
is the development length, .
is the bar diameter, .
is a bar-location factor given in ACI Code Section 12.2.4.
is an epoxy-coating factor given in ACI Code Section 12.2.4.
is a bar-size factor given in ACI Code Section 12.2.4.
is the lightweight concrete factor defined in ACI Code Section 12.2.4(d).
is the smaller of:
(a) the smallest distance measured from the surface of the concrete to the center of a
bar being developed, and
(b) one-half of the center-to-center spacing of the bars or wires being developed.
is a transverse reinforcement factor given in ACI Code Section 12.2.3.
Values for these factors will be presented later.
The second stage in the derivation of the basic expression for was to substitute common
values of and into the basic expression for (equation ( )) as described next.
Other cases √ √
( ) ( )
- The length computed using these equations shall not be taken less than .
398
Reinforced Concrete II Dr. Nasr Abboushi
Bar-Spacing Factor,
The factor is the smaller of two quantities:
1. In the first definition, is the smallest distance from the surface of the concrete to the
center of the bar being developed. (See figure (a) on page 397).
ACI Code Section 7.7.1(c) gives the minimum cover to principal reinforcement as .
For a beam stem not exposed to weather, with bars enclosed in stirrups or ties,
will be
( ) ( )
2. In the second definition, is equal to one-half of the center-to-center spacing of the
bars.
ACI Code Section 7.6.1 gives the minimum clear spacing of parallel bars in a layer as , but
not less than . For bars, the diameter is , giving the center-to-center
spacing of the bars as and
The smaller of the two values discussed here is . The minimum
stirrups or ties given in ACI Code Sections 7.10.5, 11.4.5, and 11.4.6.3 correspond to
between and , depending on a wide range of factors. Thus, for this case,
( ) . Substituting this and the appropriate bar size factor, , into equation
( ) gives equations ( ) and ( ) in the above table.
For Case 2 in the table, consider a slab with clear cover to the outer layer of bars of and a
clear spacing between the bars of . It is assumed that splitting in the cover will be
restrained by bars perpendicular to the bars being developed. As a result, is governed by
the bar spacing. If the clear spacing is , the center-to-center spacing is . Thus,
. Substituting this into Eq. ( ) and taking gives Eqs. ( ) or ( ) in
the previous Table.
For the situation where the minimum clear cover to the bar being developed is and
the minimum clear spacing is is the smaller of and . Substituting and
into Eq. ( ), assuming that gives Eqs. ( ) and ( ), which apply to
cases other than 1 and 2, as shown in the Table.
Typically, is about for to bottom bars and about for and
larger bottom bars.
399
Reinforced Concrete II Dr. Nasr Abboushi
coating factor
Epoxy-coated bars or wires with cover less than or clear spacing less
than ....................................................................................................... 1.5
All other epoxy-coated bars or wires........................................................... 1.2
Uncoated and galvanized reinforcement .................................................... 1.0
The product of ( ) need not be taken greater than 1.7.
bar-size factor
and smaller bars and deformed wires .............................................. 0.8
and larger bars.................................................................................... 1.0
Comparison of equation ( ) with a large collection of bond and splice tests showed that a
shorter development length was possible for smaller bars.
lightweight-aggregate-concrete factor
When any lightweight-aggregate concrete is used ................................... 0.75
However, when the splitting tensile strength is specified, shall be
permitted to be taken as √ but not more than.......................... 1.0
When normal-weight concrete is used ........................................................1.0
where
total cross-sectional area of all transverse
reinforcement within the spacing , which
crosses the potential plane of splitting along
the reinforcement being developed within
the development length, .(illustrated in
right figure).
maximum center-to-center spacing of transverse reinforcement within ,
number of bars or wires being developed or spliced along the plane of splitting.
ACI Code Section 12.2.3 allows to be taken equal to zero to simplify the calculations,
even if there is transverse reinforcement.
400
Reinforced Concrete II Dr. Nasr Abboushi
IMPORTANT. The basic rule governing the development and anchorage of bars is as follows:
The calculated tension or compression in reinforcement at each section of reinforced
concrete members shall be developed on each side of that section by embedment length,
hook, headed deformed bar, or mechanical anchorages, or a combination thereof. (ACI Code
Section 12.1)
Example:
A 400-mm-wide cantilever beam frames into the edge of a 400-mm-thick wall similar to
figure below. To reach , the three bars at the top of the beam are stressed to their
yield strength at point at the face of the wall. Compute the minimum embedment of the
bars into the wall and the development length in the beam. The concrete is sand/low-
density concrete with a strength of . The yield strength of the flexural reinforcement
is . Construction joints are located at the bottom and top of the beam, as shown.
The beam has closed stirrups with at a spacing of throughout
its length. (The stirrups are not shown.) The cover is 40 mm to the stirrups. The three
bars are inside vertical steel in each face of the wall.
@ 𝑚𝑚
O.C.
A
Construction joint
387.5mm
450 mm
𝑙𝑑
B
Construction joint
Wall 1.5 m
400 mm
Solution:
Anchorage of a traight bar (in a wall).
We shall do this problem twice, first using ACI Code Section 12.2.2 (Table – page 398) and
then using ACI Code Section 12.2.3, Eq. ( ).
1. Find the spacing and confinement case for bars anchored in wall. The clear side
cover to the bars in the wall is ( ). The clear spacing of
the bars is
Because the clear spacing between the bars is not less than and the clear cover to the
bars exceeds , this is Case 2, and for bars, Eq. ( ) applies
2. Compute the development length. From Eq. ( ),
401
Reinforced Concrete II Dr. Nasr Abboushi
√
where
because there will be more than 300 mm of fresh concrete under the bar when
the concrete in the beam covers the bars ( ).
because the bars are not epoxy coated.
because the concrete has low-density aggregates
√
The bars must extend 2184 mm into the wall to develop the full yield strength.
Extend the bars 2.2 m into the wall.
3. Compute the development length for bars in the beam using Eq. ( ).
√ ( )
Where and are the same as in step 2. For a bar, . is the smaller of:
(a) the distance from the center of the bar to the nearest concrete surface; measuring
from the side face to the center of the bar is , and
(b) half the center-to-center spacing of the bars; ( )
Thus, .
The transverse reinforcement index is:
where
is the spacing of transverse reinforcement along the development length,
which is equal to in this example (vertical steel bars in each
face of the wall).
The number of bars being anchored.
is the area of transverse reinforcement crossing the
potential splitting plane within the spacing (one vertical bar @ 300
mm in each face of the wall). Thus,
Then,
√ ( )
402
Reinforced Concrete II Dr. Nasr Abboushi
Thus, and the bars must extend 1310 mm into the wall. Extend the bars 1.35
m into the wall.
In this case, there is a large difference between the computed from equation ( ) and
the computed from equation ( ). This is because equation ( ) was derived by using
( ) equal to 1.5. In this case it is actually equal to 2.5.
The cantilever extends 1.5 m from the face of the wall. The bars shown are stressed to their
yield strength at the face of the wall. Is there adequate development length for bars in
the span? If not, what is the largest-size bar that can be used?
The point of maximum bar force occurs at the face of the wall (point A). The bar must be
developed on each side of this point. To accomplish this, the bar must extend a minimum of
into the support (previous solution) and a minimum into the span.
1. Find the spacing and confinement case. From the previous example, the clear
spacing between the bars in the beam is . for the 175-mm stirrup
spacing, the minimum area of stirrups, by section 11.4.6.3, is
√ √
1. Find the spacing and confinement case for bars anchored in the beam. The clear side
cover to the bars in the beam is ( ). The clear spacing
of the bars is
Since the stirrups exceed the ACI Code minimum and the clear spacing between the bars is
not less than and the clear cover to the bars exceeds , this is Case 1, and for
bars, Eq. ( ) applies
403
Reinforced Concrete II Dr. Nasr Abboushi
√ √
The bars must extend 1258 mm into the beam. Since , bars can
be developed whithout hooks at the free end. Use bars.
ACI Section 12.2.5 allows the development length to be reduced by multiplying by the
ration ( ) ( ) . We will not take advantage of
this, because the reduced anchorage length will not allow the bars to be used for their full
capacity in the event of a change in use of structure.
Compression-Development Lengths
√
where the constant has units of . The development length in compression
may be reduced by multiplying by the applicable modification factors given in ACI Code:
Section 12.3.3 for excess reinforcement……………………………. ( )
Reinforcement enclosed within spiral reinforcement……………………………………....( )
The resulting development length shall not be less than .
Example:
Determine the required development length of column steel reinforcements which are
embedded in a footing a s shown below in the figure.
Take , .
Solution:
√
𝑚𝑚
404
Reinforced Concrete II Dr. Nasr Abboushi
OR
405
Reinforced Concrete II Dr. Nasr Abboushi
A hook loaded in tension develops forces in the manner shown in the figure below. The
stress in the bar is resisted by the bond on the surface of the bar and by the bearing on the
concrete inside the hook. The hook
moves inward, leaving a gap between
it and the concrete outside the bend.
Because the compressive force inside
the bend is not collinear with the
applied tensile force, the bar tends to
straighten out, producing compressive
stresses on the outside of the tail.
Failure of a hook almost always
involves crushing of the concrete inside
the hook. If the hook is close to a side
face, the crushing will extend to the
surface of the concrete, removing the
side cover. Occasionally, the concrete
outside the tail will crack, allowing the
tail to straighten.
406
Reinforced Concrete II Dr. Nasr Abboushi
( )
√
where for epoxy-coated bars or wires and 1.0 for galvonized and uncoated
reinforcement, and is the lightweight-aggregate factor given in ACI Code Section 12.2.4(d).
ACI Code Section 12.5.4 states that for bars being developed by a standard hook at
discontinuous ends of members with both side cover and top (or bottom) cover over a hook
of less than 65 mm the hooked bar shall be (must be) enclosed within ties or stirrups
perpendicular to the bar being developed, spaced not greater than along the
development length of the hook, . In this case, the factors of ACI Code Section 12.5.3(b)
and (c) shall not apply. ACI Code Section 12.5.4 applies at such points as the ends of simply
supported beams (particularly if these are deep beams), at the free ends of cantilevers, and
at the ends of members that terminate in a joint with less than 65 mm of both side cover
407
Reinforced Concrete II Dr. Nasr Abboushi
and top (or bottom) cover over the hooked bar. Hooked bars at discontinuous ends of slabs
are assumed to have confinement from the slab on each side of the hook; hence, ACI Code
Section 12.5.4 is not applied.
2. Anywhere,
12.5.3(a) Any Not required
The previous Figures (page 408) shows the meaning of the words “ties or stirrups parallel
to” or “perpendicular to the bar being developed” in ACI Code Sections 12.5.3(b) and (c), and
12.5.4. In ACI Code Sections 12.5.3 and 12.5.4, is the diameter of the hooked bar, and the
first tie or stirrup shall enclose the bent portion of the hook, within of the outside of the
bend.
If a hook satisfies more than one of the cases in ACI Code Section 12.5.3, from Equation
is multiplied by each of the applicable factors. Thus, if a hook satisfies both the covers
from ACI Code Section 12.5.3(a) and the stirrups from 12.5.3(b), is the length from the
409
Reinforced Concrete II Dr. Nasr Abboushi
first part of Equation for multiplied by from 12.5.3(a) and 0.8 from 12.5.3(b), making
the total reduction
Finally, the length of the hook, shall not be less than or ,
whichever is greater, after all the reduction factors have been applied.
Hooks may not be used to develop bars in compression, because bearing on the outside of
the hook is not efficient.
410
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
Compute the development length for hooked beam bars. The basic development length for a
hooked bar is
√
Therefore,
√
Assume that the four bars will extend into the column inside the vertical column bars,
as shown in the above figure. ACI Code Section 11.10.2 requires minimum ties in the joint
area. The required spacing of closed ties by ACI Code Section 11.10.2 (Except for
connections not part of a primary seismic load-resisting system that are restrained on four
sides by beams or slabs of approximately equal depth, connections shall have lateral
reinforcement not less than that required by Eq. (11-13) within the column for a depth not
less than that of the deepest connection of framing elements to the columns. See also 7.9.) is
computed as:
( )
This exceeds 65 mm and is therefore O.K. The top cover to the lead-in length in the joint
exceeds 65 mm because the joint is in the column.
The cover on the bar extension beyond the hook (the tail of the hook) is
12.5.3.2(a): The side cover exceeds 65 mm, and the cover on the bar extension is equal to
50 mm; therefore, the 0.7 reduction factor could be used. Note, if we used ties in the
joint, the cover on the bar extension after the hook would be less than 50 mm, and thus, the
multiplier = 1.0.
ACI Code Section 12.5.4 does not apply because the side cover and top cover both exceed
65 mm. Therefore, only the minimum ties required by ACI Section 11.10.2 are required:
ties at 300 mm. These are spaced farther apart than therefore,
ACI Code Section 12.5.3(b) does not apply, and so the multiplier is 1.0. Thus,
Take
The hook-development length available is
411
Reinforced Concrete II Dr. Nasr Abboushi
Because 600 mm exceeds 350 mm, the hook development length is O.K.
Check the vertical height of a standard hook on a bar. From Fig. a (page 410), the
vertical height of a standard hook is . This will
fit into the joint.
Therefore, anchor the four bars into the joint, as shown in the previous figure.
In reinforced concrete, reinforcement is provided near the tensile face of beams to provide
the tension component of the internal resisting couple. A continuous beam and its moment
diagram are shown below. At midspan, the moments are positive, and reinforcement is
required near the bottom face of the member. The opposite is true at the supports. For
economy, some of the bars can be terminated or cut off where they are no longer needed.
Generally speaking, bar cut offs should be kept to a minimum to simplify design and
construction, particularly in zones where the bars are stressed in tension.
In the following sections, the location of theoretical cut-off points for flexure, referred to as
flexural cut-off points, is discussed. This is followed by a discussion of how these flexural
cut-off locations must be modified to account for shear, development, and constructional
requirements to get the actual cut-off points used in construction.
The calculation of the flexural cut-off points will be illustrated with the simply supported
beam shown next. At midspan, this beam has reinforcing bars, shown in section
(figure c). At points and two of these bars are cut off, leaving bars in the end
portions of the beam, as shown in figure b.
The beam is loaded with a uniform factored load of including its selfweight, which
gives the diagram of ultimate moments, , shown in figure d. This is referred to as the
required-moment diagram, because, at each section, the beam must have a reduced
nominal strength, at least equal to . The maximum required moment at midspan is
414
Reinforced Concrete II Dr. Nasr Abboushi
The three bars that extend into the supports are cut off at points and . At and ,
these bars are undeveloped, and as a result, the moment capacity is at and .
At points and the bars are fully developed, and the moment capacity
In figure g, the moment-capacity diagram from figure f and the required moment diagram
from figure d are superimposed. Because the moment capacity is greater than or equal to
the required moment at all points, the beam has adequate capacity for flexure, neglecting
the effects of shear.
The ACI Code does not explicitly treat the effect of shear on the tensile force. Instead, ACI
Code Section 12.10.3 arbitrarily requires that longitudinal tension bars be extended a
minimum distance equal to the greater of or past the
theoretical cut-off point for flexure.
Development of Bars at Points of Maximum Bar Force. For reinforcement and concrete to
act together, each bar must have adequate embedment on both sides of each section to
develop the force in the bar at that section. In beams, this is critical at
1. Points of maximum positive and negative moment, which are points of maximum bar
stress.
2. Points where reinforcing bars adjacent to the bar under consideration are cut off or
bent (ACI Code Section 12.10.2).
Thus, bars must extend at least a development length, , each way from such points or be
anchored with hooks or mechanical anchorages.
ACI Code 12.10 requires special precautions, specifying that no flexural bar shall be
terminated in a tension zone unless one of the following conditions is satisfied:
1. The shear is not over two-thirds of the design strength .
( )
2. Stirrups in excess of those normally required are provided over a distance along each
terminated bar from the point of cutoff equal to . These "binder" stirrups shall
provide an area . In addition, the stirrup spacing shall not exceed
, where is the ratio of the area of bars cut off to the total area of bars
at the section.
3. The continuing bars, if or smaller, provide twice the area required for flexure at
that point, and the shear does not exceed three-quarters of the design strength
( )
415
Reinforced Concrete II Dr. Nasr Abboushi
416
Reinforced Concrete II Dr. Nasr Abboushi
417
Reinforced Concrete II Dr. Nasr Abboushi
The concept of requiring the development of reinforcement on both sides of a section where
the bars are to be fully stressed may also be applied to the continuation of positive moment
tension reinforcement beyond either the centerline of a simple support or a point of
inflection.
Simple Supports
Referring to the next figure, consider the point A on the factored moment curve near a
simple support, where the factored moment equals the moment capacity of the
bars continuing into the support. The distance from point A to the end of the bars must be at
least equal to the required development length as computed from ACI-12.2. This
requirement given in ACI-12.11.3 is that the available embedment length must equal or
exceed , or
( )
In the next figure, the area of the shaded portion of the shear diagram equals the change in
moment between the center of support and point A; thus the ordinate on the factored
moment diagram at A is
Thus, the distance between the point A and the centerline of support is approximately
equal to
( )
or
The factor accounts for the fact that bars extending into a simple support have less
tendency to cause splitting when confined by a compressive reaction. When the beam is
supported in such a way that there are no bearing stresses above the support, the factor
becomes (as eq. ( )) [The ACI Code allows a increase in the value of or in
such cases [see Eq. ( )].
418
Reinforced Concrete II Dr. Nasr Abboushi
Inflection Points
Since an inflection point is a point of zero moment located away from a support (refer to the
next figures), bars in that region are not confined by a compressive reaction; therefore the
factor is interpreted as not to apply. In this case, the embedment length that must
exceed the required development length ; (ACI-12.11.3) may be stated as
[ ] ( )
where and refer to the nominal flexural strength and the factored shear at the point
of inflection.
419
Reinforced Concrete II Dr. Nasr Abboushi
The consequence of these special requirements at the point of zero moment is that, in some
cases, smaller bar sizes must be used to obtain smaller , even though requirements for
development past the point of maximum stress are met.
ACI Code 12.11.1 requires that at least one-third the positive moment reinforcement in
simple members and one-fourth the positive moment reinforcement in continuous members
shall extend along the same face of member into the support. In beams, such reinforcement
shall extend into the support at least .
420
Reinforced Concrete II Dr. Nasr Abboushi
Example
Check the Code requirement of development length at support of the beam shown.
Take .
Solution:
𝐾𝑁 𝑚
𝑚𝑚
𝑚𝑚
𝑚𝑚
𝑚𝑚 𝑚
421
Reinforced Concrete II Dr. Nasr Abboushi
( )
Using equation ( ) from the table on page 398 (Case 1 with minimum stirrups).
√ √
According to ACI Code 12.12, at least one-third of the total reinforcement provided for
negative moment at the support must be extended beyond the extreme position of the
point of inflection a distance not less than one-sixteenth the clear span ( ), or , or
, whichever is greatest.
Requirements for bar cutoff or bend point locations are summarized in the next figure. If
negative bars are to be cut off, they must extend a full development length beyond the
face of the support. In addition, they must extend a distance or beyond the
theoretical point of cutoff defined by the moment diagram. The remaining negative bars
(at least one-third of the total negative area) must extend at least beyond the theoretical
point of cutoff of bars and in addition must extend , , or (whichever is
greatest) past the point of inflection of the negative-moment diagram.
If the positive bars are to be cut off, they must project past the point of theoretical
maximum moment, as well as or beyond the cutoff point from the positive-moment
diagram. The remaining positive bars must extend past the theoretical point of cutoff of
bars and must extend at least into the face of the support.
422
Reinforced Concrete II Dr. Nasr Abboushi
When bars are cut off in a tension zone, there is a tendency toward the formation of
premature flexural and diagonal tension cracks in the vicinity of the cut end. This may result
in a reduction of shear capacity and a loss in overall ductility of the beam.
As an alternative to cutting off the steel, tension bars may be anchored by bending them
across the web and making them continuous with the reinforcement on the opposite face.
Although this leads to some complication in detailing and placing the steel, thus adding to
construction cost, some engineers prefer the arrangement because added insurance is
423
Reinforced Concrete II Dr. Nasr Abboushi
provided against the spread of diagonal tension cracks. In some cases, particularly for
relatively deep beams in which a large percentage of the total bottom steel is to be bent, it
may be impossible to locate the bend-up point for bottom bars far enough from the support
for the same bars to meet the requirements for top steel. The theoretical points of bend
should be checked carefully for both bottom and top steel.
It may be evident from review of the previous sections that the determination of cutoff or
bend points in flexural members is complicated and can be extremely time-consuming in
design. It is important to keep the matter in perspective and to recognize that the overall
cost of construction will be increased very little if some bars are slightly longer than
absolutely necessary, according to calculation, or as dictated by ACI Code provisions. In
addition, simplicity in construction is a desired goal, and can, in itself, produce compensating
cost savings. Accordingly, many engineers in practice continue all positive reinforcement into
the face of the supports the required 150 mm and extend all negative reinforcement the
required distance past the points of inflection, rather than using staggered cutoff points.
Example
Locate the flexural cut-off for the beam shown below.
Take .
𝐾𝑁 𝑚
𝑚𝑚
𝑚𝑚
𝑚𝑚
𝑚𝑚 𝑚
Solution:
( )
( ) ( )
424
Reinforced Concrete II Dr. Nasr Abboushi
𝑤 𝐾𝑁 𝑚
𝑀𝑢
𝐴𝑦 𝐾𝑁 𝑉
√ 𝑥
𝑑 𝑚𝑚
𝑚𝑚 𝑚
𝑥 𝑚 𝑚
For :
( )
√ √
Take
For :
𝐵𝐵 𝐿
𝐵𝐵 𝐿
The primary purpose for both the continuity and structural-integrity reinforcement
requirements is to tie the structural elements together and prevent localized damage from
spreading progressively to other parts of the structure. However, because of the limited
amount of calculations required to select and detail this reinforcement, structures satisfying
these requirements cannot be said to have been designed to resist progressive collapse.
Continuity Reinforcement
Requirements for continuity reinforcement in continuous beams are given in ACI Code
Sections 12.11.1 and 12.11.2 for positive-moment (bottom) reinforcement and in ACI Code
Sections 12.12.1 through 12.12.3 for negative-moment (top) reinforcement.
These requirements are summarized in next figures for positive-moment reinforcement and
for negative-moment reinforcement respectively.
426
Reinforced Concrete II Dr. Nasr Abboushi
ACI Code Section 12.11.1 requires that at least one-third of the positive-moment
reinforcement used at midspan for simply supported members and at least one-fourth of the
positive-moment reinforcement used at midspan for continuous members shall be
continued at least 150 mm into the supporting member (Fig. a). Further, if the beam under
consideration is part of the primary lateral load-resisting system, ACI Code Section 12.11.2
requires that the bottom reinforcement must be continuous through interior supports and
fully anchored at exterior supports (Fig. b).
ACI Code Section 12.12.1 requires that negative-moment reinforcement must be continuous
through interior supports and fully anchored at exterior supports (next figure).
ACI Code Section 12.12.2 requires that all of the negative-moment reinforcement must
extend the development length, , into the span before being cut off. Finally, ACI Code
Section 12.12.3 requires that at least one-third of the negative-moment reinforcement
provided at the face of the support shall be extended beyond the point of inflection a
distance greater than or equal to the largest of , , and . Theoretically, no top
steel should be required beyond the point of inflection, where the beam moment changes
from negative to positive. The minimum extension given by the ACI Code accounts for
427
Reinforced Concrete II Dr. Nasr Abboushi
possible shifts in the theoretical point of inflection due to changes in the loading and for the
effect of shear on longitudinal steel requirements.
Structural-Integrity Reinforcement
Requirements for structural-integrity reinforcement in continuous floor members first
appeared in the 1989 edition of the ACI Code. These requirements, which are given in ACI
Code Section 7.13, were clarified and strengthened in the 2002 and 2008 editions of the ACI
Code. The structural-integrity requirements are supplemental to the continuity
requirements discussed previously and were added to better tie the structural members
together in a floor system and to provide some resistance to progressive collapse. Because
the ACI Code Committee was concerned that a significant number of structural engineers
using Chapter 12 were not aware of the structural-integrity requirements, ACI Code Section
12.1.3 was added in 2008 to specifically direct the designer’s attention to the need to satisfy
ACI Code Section 7.13 when detailing reinforcement in continuous beams. Structural-
integrity requirements for reinforced concrete (nonprestressed) continuous slabs are given
in ACI Code Chapter 13, for precast construction in Code Chapter 16, and for prestressed
two-way slab systems in Code Chapter 18. Those requirements will not be discussed here.
The structural-integrity requirements in ACI Code Section 7.13 can be divided into
requirements for joists, perimeter beams, and interior beams framing into columns. For joist
construction, as defined in ACI Code Sections 8.13.1 through 8.13.3, ACI Code Section
7.13.2.1 requires that at least one bottom bar shall be continuous over all spans and through
428
Reinforced Concrete II Dr. Nasr Abboushi
interior supports and shall be anchored to develop at the face of exterior supports.
Continuity of the bar shall be achieved with either a Class B tension lap splice or a
mechanical or welded splice satisfying ACI Code Section 12.14.3. Class B lap splices are
defined in ACI Code Section 12.15.1 as having a length of (but not less than ).
The value for the development length, , is to be determined in accordance with ACI Code
Section 12.2, which has been given previously ( see pages 397 and 398 ). When determining
, the minimum does not apply, and the reduction for excessive reinforcement
cannot be applied.
ACI Code Section 7.13.2.2 states that perimeter beams must have continuous top and
bottom reinforcement that either passes through or is anchored in the column core, which is
defined as the region of the concrete bounded by the column longitudinal reinforcement.
The continuous top reinforcement shall consist of at least one-sixth of the negative-moment
(top) reinforcement required at the face of the support, but shall not be less than two bars.
The continuous bottom
reinforcement shall
consist of at least one-
fourth of the positive-
moment (bottom)
reinforcement required at
midspan, but not less than
two bars. At
noncontinuous supports
(corners), all of these bars
must be anchored to
develop at the face of
the support. Also, all of
the continuous
longitudinal bars must be
enclosed by closed
transverse reinforcement
429
Reinforced Concrete II Dr. Nasr Abboushi
(ACI Code Section 7.13.2.3), as specified for torsional transverse reinforcement in ACI Code
Sections 11.5.4.1 and 11.5.4.2, and placed over the full clear span at a spacing not exceeding
. As before, reinforcement continuity can be achieved through either the use of Class B
tension lap splices or a mechanical or welded splice.
For interior beams framing between columns, ACI Code Section 7.13.2.5 defines two ways to
satisfy the structural-integrity requirements for continuous longitudinal reinforcement. If
closed transverse reinforcement is not present, then structural integrity must be achieved by
continuous bottom reinforcement similar to that required for perimeter beams (see next
Figure a). As before, this reinforcement must pass through or be fully anchored in the
column core, and reinforcement continuity can be achieved through either a Class B tension
lap splice or a mechanical or welded splice. For interior beams that are not part of the
primary system for resisting lateral loads, the bottom reinforcement does not need to be
continuous through interior supports or fully anchored at exterior supports, and structural
integrity can be achieved by a combination of bottom and top steel that is enclosed by
closed transverse reinforcement (Fig. b). The top steel must satisfy the requirements of ACI
Code Section 12.12 and must be continuous through the column core of interior supports or
fully anchored in the column core of exterior supports. The bottom steel must satisfy the
requirements given in ACI Code Section 12.11.1. The closed transverse reinforcement (not
shown in Fig. b) must satisfy ACI Code Sections 11.5.4.1 and 11.5.4.2 and must be provided
over the full clear span at a spacing not exceeding . How continuity and structural-
integrity requirements affect the selection of cut-off points and longitudinal reinforcement
detailing are given in the examples.
430
Reinforced Concrete II Dr. Nasr Abboushi
Example
The beam shown below is constructed of normal-weight concrete, , and Grade-
420 reinforcement, . It supports a factored dead load of and a
factored live load of . The cross sections at the points of maximum positive and
negative moment, as given in figures below, are shown next.
431
Reinforced Concrete II Dr. Nasr Abboushi
Solution:
1. Locate flexural cut offs for positive-moment reinforcement. The positive moment in
span AB is governed by the loading case in
Fig. a below .From a free-body analysis of a
part of span AB (Fig. d), the equation for
at a distance from A is
( )
( ) ( )
432
Reinforced Concrete II Dr. Nasr Abboushi
Thus or from A. These flexural cut-off points are shown in figure c for
bending moment diagram and figure a for location of positive moment cut-off points. They
will be referred to as theoretical flexural cut-off points E and F. In a similar fashion, by
setting the flexural cut-off point G is found to be from A or from B.
Because the bar spacing exceeds for both the and bars, and because the beam
has minimum stirrups, the bars satisfy Case 1 in the Table on page 398.
√ √
3. Locate actual cut-off points for positive-moment reinforcement. The actual cut-off
points are determined from the theoretical flexural cut-off points using rules stated
earlier. Because the location of cut offs G and D are affected by the locations of cut
offs E and F, the latter are established first, starting with F. Because the beam is
simply supported it is not included in the ACI Code listing of members that are
susceptible to actions requiring structural integrity.
a) Cutoff F. Two bars are cut off. They must satisfy rules for anchorage, extension
of bars into the supports and effect of shear on moment diagrams.
Extension of bars into the supports. At least one-third of the positive-moment
reinforcement, but not less than two bars, must extend at least into the
supports. We shall extend two bars into each of the supports A and B.
Effect of shear. Extend the bars by the larger of or
. Therefore, the first trial position of the actual cutoff is
at from the center of the support at A, say, . (see point
F’ in next Fig. b).
Anchorage. Bars must extend at least past the points of maximum bar stress. For
the bars cut off at F’, the maximum bar stress occurs near midspan, at from
A. The distance from the point of maximum bar stress to the actual bar cutoff is
. for the bars is . The distance available is
more than —therefore OK. Cut off two bars at from A (shown as point
F’ in Fig. b).
433
Reinforced Concrete II Dr. Nasr Abboushi
b) Cutoff G. Two bars are cut off; we must consider the same three items as
covered in step (a), plus we must check the anchorage at a point of inflection using
Eq. ( ) on page 419.
Extension of bars into simple supports. In step (a), we stated the need to extend two
bars into support B. Thus, G’ is at .
Effects of shear. Because the cut off is at the support, we do not need to extend the
bars further.
Anchorage. Bars must extend at least past actual cut offs of adjacent bars. for
bottom bar . Distance from F’ to G’
. Bar does not extend , therefore extend the bars to
say, .
Anchorage at point of inflection. Must satisfy Eq. ( ) on page 419 at point of
inflection (point where the moment is zero). Therefore, at G, . The
point of inflection is from the support (see figure c). At this point is
(Fig. b) and the moment strength for the bars in the beam at the point
of inflection (two bars) is
c) Cutoff E. Two bars are cut off; we must check for the effect of shear and
development length (anchorage).
Effects of shear, positive moment. Extend the bars past the flexural
cutoff point. Therefore, the actual cutoff E’ is at
from A.
Anchorage, positive moment. The distance from the point of maximum moment to
the actual cutoff exceeds therefore OK. Cut off two bars at
from A (point E’ in Fig. b; note that this is changed later).
d) Cutoff D. Two bars are cut off; we must consider extension into a support,
extension beyond the cut-off point and development of bars at a simple support
using Eq. ( ) on page 418.
Extension into simple support. This was done in step (a).
Bars must extend from the actual cutoff E’, where ( bars).
The maximum possible length available is . Because
this is less than , we must either extend the end of the beam, hook the ends of the
434
Reinforced Concrete II Dr. Nasr Abboushi
bars, use smaller bars, or eliminate the cutoff E’. We shall do the latter. Therefore,
extend all four bars 150 mm past support A.
Development of bars at simple support. We must satisfy Eq. ( ) on page 418 at the
support.
( )
( ) ( )
Because this exceeds , development at the simple support is satisfied. The actual cut-off
points are illustrated in figure below.
Over the support at B, the reinforcement is two bars plus two bars. The two
bars are no longer required when the moment is less than
(strength of the beam with two bars).
So, between A and B,
from A.
Therefore, the theoretical flexural cut-off point for two top bars in span AB is at
from A. Finally, between B and C,
from C
Therefore, the theoretical flexural cut-off point for
two top bars in span BC is at from C.
The flexural cut-off points for the negative-
moment steel are shown in the figure a below and
are lettered H, J, K, and L.
436
Reinforced Concrete II Dr. Nasr Abboushi
Anchorage of negative-moment steel. The bars must extend from the point of
maximum bar stress. For the two top bars, the maximum bar stress is at B. The
actual bar extension is . This exceeds therefore OK.
Cut off two bars at from B (point J’ in Fig. b).
c) Cutoff K. Two bars are cut off. The theoretical flexural cut off is at from C
( from B).
Effect of shear. Extend bars . The end of the bars is at
from B, say, .
Anchorage. Extend past B. for a top bar . The extension of
is thus not enough. Try extending the top bars past B to point K’.
Therefore, cut off two bars at from B (point K’ in Fig. b). Note that this is
changed in the next step.
437
Reinforced Concrete II Dr. Nasr Abboushi
7. Check whether extra stirrups are required at cutoffs. ACI Code Section 12.10.5
prohibits bar cutoffs in a tension zone, unless
12.10.5.1: at actual cutoff ( ) at that point, or
12.10.5.2: Extra stirrups are provided at actual cut-off point, or
12.10.5.3: The continuing flexural reinforcement at the flexural cutoff has twice the required
and ( ).
Because we have determined the theoretical cut-off points on the basis of the continuing
reinforcement having 1.0 times the required it is unlikely that we could use ACI Code
Section 12.10.5.3, even though the actual bar cut-off points were extended beyond the
theoretical cut-off points. Further, because we only need to satisfy one of the three sections
noted, we will concentrate on satisfying ACI Code Section 12.10.5.1.
As indicated from the beam section in Fig. b on page 432, the initial shear design was to use
double-leg stirrups throughout the length of the beam. We can determine the value
for
( )
√ √
( )
a) Cutoff F’. This cutoff is at from B, which is in a flexural tension zone for the
bottom reinforcement. From Fig. b (page 432), for load Case 1, the shear at F’ is:
where the sign simply indicates the direction of the shear force. This value for exceeds
so we must either decrease the spacing for the stirrups or change
to a larger ( ) stirrup. We will try stirrups at a spacing:
and then,
438
Reinforced Concrete II Dr. Nasr Abboushi
( )
This value exceeds so the modified stirrup design is OK. This tighter spacing should start at
the cut-off point and extend at least a distance toward the maximum positive-moment
region. For simplicity, use a stirrup spacing from the center of support B for 1.65
in. toward midspan of span A–B (see next Figure).
b) Cutoff J’. The cutoff is located at from B. The flexural tension that occurs in
these bars is due to load Case 2 (Figure on page 437). By inspection, at J’ is
considerably less than . Therefore, no extra stirrups are required
at this cut off.
The final reinforcement details are shown in next figure. For nonstandard beams such as this
one, a detail of this sort should be shown in the contract drawings.
The calculations just carried out are tedious, and if the underlying concepts are not
understood, the detailing provisions are difficult to apply. Several things can be done to
simplify these calculations. One is to extend all of the bars past their respective points of
inflection so that no bars are cut off in zones of flexural tension. This reduces the number of
cutoffs required and eliminates the need for extra stirrups, on one hand, while requiring
more flexural reinforcement, on the other. A second method is to work out the flexural cut-
off points graphically.
Example
Design the simply supported beam shown below. The dead load is not
including the weight of the beam. The live load consist of a concentrated load of at
midspan.
Take .
Use @ for vertical stirrups. Assume for self-weight.
439
Reinforced Concrete II Dr. Nasr Abboushi
𝑚𝑚
𝑚𝑚
𝑐𝑚
𝑚
Solution:
( ) .
( ) .
Take
At midspan ( )
( )
( ) ( )
( )
For ( )
( )
( ) ( )
( )
440
Reinforced Concrete II Dr. Nasr Abboushi
For :
√ ( )
(a) , and
(b) half the center-to-center spacing of the bars; one bar only (no spacing)
Thus, .
( ) ( ) ( )
√
For :
(a) , and
(b) half the center-to-center spacing of the bars;
( )
Thus, .
( ) ( ) ( )
441
Reinforced Concrete II Dr. Nasr Abboushi
𝑚
𝑚𝑚
𝑙𝑑 𝑚𝑚
𝑑 𝑚𝑚
𝑙𝑑 𝑚𝑚
𝑥 𝑚 𝑚
For :
Take
For :
𝐵𝐵 𝐿
𝐵𝐵 𝐿
442
Reinforced Concrete II Dr. Nasr Abboushi
Example 𝑐𝑚
Design the beam shown below. The total factored load is
Take .
𝑐𝑚
Stirrups @
𝑐𝑚 𝑐𝑚
𝑚 𝑚
𝑤𝑢 𝐾𝑁 𝑚
𝐴𝑦 𝐾𝑁 𝐵𝑦 𝐾𝑁
𝐾𝑁 𝑚
𝐾𝑁 𝑚
Solution:
443
Reinforced Concrete II Dr. Nasr Abboushi
For ( ) ( )
( )
( ) ( )
For ( )
( )
( ) ( )
Development length:
√ ( )
For :
(c) , and
(d) half the center-to-center spacing of the bars; one bar Splitting plane
only (no spacing)
Thus, .
( ) ( ) ( )
444
Reinforced Concrete II Dr. Nasr Abboushi
√
For
For :
(c) , and
Splitting plane
(d) half the center-to-center spacing of the bars;
( )
Thus, .
( ) ( ) ( )
(a) , and
(b) half the center-to-center spacing of the bars;
Splitting plane
( )
Thus, .
( ) ( ) ( )
445
Reinforced Concrete II Dr. Nasr Abboushi
𝑤𝑢 𝐾𝑁 𝑚
𝐴𝑦 𝐾𝑁 𝐵𝑦 𝐾𝑁
𝑚 𝑚
𝐾𝑁 𝑚
𝑚
𝑑 𝑚 𝑑 𝑚
𝐾𝑁 𝑚
𝑙𝑑 𝑚
𝐾𝑁 𝑚
𝑙𝑑 𝑚 𝑙𝑑 𝑚 𝑙𝑑 𝑚
𝑇𝐵 𝐿
𝑐𝑚
𝐵𝐵 𝐿
𝐵𝐵 𝐿
The final length of bars will be calculated and checked as discussed in the example
(page 431). These bars are illustrated in the above figure.
446
Reinforced Concrete II Dr. Nasr Abboushi
Frequently, reinforcement in beams and columns must be spliced. There are four types of
splices: lapped splices, mechanical splices, welded splices, and end-bearing splices. All four
types of splices are permitted, as limited in ACI Code Sections 12.14, 12.15, and 12.16.
As shown in Fig. b, large transverse cracks occur at the discontinuities at the ends of the
spliced bars. Transverse reinforcement in the splice region delays the opening of the splitting
cracks and hence improves the splice capacity.
ACI Code Section 12.15 distinguishes between two types of tension lap splices, depending on
the fraction of the bars spliced in a given length and on the reinforcement stress at the
splice. Table R12.15.2 of the ACI Commentary is reproduced below. The splice lengths for
each class of splice are as follows:
Class A splice:
Class B splice:
447
Reinforced Concrete II Dr. Nasr Abboushi
Because the stress level in the bar is accounted for in Table above, the reduction in the
development length for excess reinforcement allowed in ACI Code Section 12.2.5 is not
applied in computing for this purpose.
The center-to-center distance between two bars in a lap splice cannot be greater than one-
fifth of the splice length, with a maximum of . (ACI Code Section 12.14.2.3). Bars
larger than cannot be lap spliced, except for compression lap splices at footing-to-
448
Reinforced Concrete II Dr. Nasr Abboushi
column joints (ACI Code Section 15.8.2.3). Lap splices should always be enclosed within
stirrups, ties, or spirals, to delay or prevent the complete loss of capacity indicated in the
previous photo. As indicated in ACI Code Sections 12.2.2 and 12.2.3, the presence of
transverse steel may lead to shorter and hence shorter splices. ACI Code Section 21.5.2.3
requires that tension lap splices of flexural reinforcement in beams resisting seismic loads be
enclosed by hoops or spirals.
For lap splices of slab and wall reinforcement, effective clear spacing of bars being spliced at
the same location is taken as the clear spacing between the spliced bars (R12.15.1). This
clear spacing criterion is illustrated in (a). Spacing for noncontact lap splices (spacing
between lapped bars not greater than ( ) lap length nor ) should be considered
the same as for contact lap splices. For lap splices of column and beam bars, effective clear
spacing between bars being spliced will depend on the orientation of the lapped bars; see
Fig. (b) and (c), respectively.
The designer must specify the class of tension lap splice to be used. The class of splice
depends on the magnitude of tensile stress in the reinforcement and the percentage of total
reinforcement to be lap spliced within any given splice length as shown in Table above. If the
area of tensile reinforcement provided at the splice location is more than twice that required
for strength (low tensile stress) and or less of the total steel area is lap spliced within the
required splice length, a Class A splice may be used. Both splice conditions must be satisfied,
otherwise, a Class B splice must be used. In other words, if the area of reinforcement
449
Reinforced Concrete II Dr. Nasr Abboushi
provided at the splice location is less than twice that required for strength (high tensile
stress) and/or more than 1/2 of the total area is to be spliced within the lap length, a Class B
splice must be used.
but not less than . For less than , the required lap is increased by one-
third. When bars of different size are lap-spliced in compression, the splice length is to be
the larger of the development length of the larger bar and the splice length of the smaller
bar. In exception to the usual restriction on lap splices for large-diameter bars, and
bars may be lap-spliced to and smaller bars.
End-Bearing Splices
Direct end bearing of the bars has been found by test and experience to be an effective
means for transmitting compression. In such a case, the bars must be held in proper
alignment by a suitable device.
Section 12.16.4 specifies the requirements for end-bearing compression splices. End-bearing
splices are only permitted in members containing closed ties, closed stirrups or spirals
(12.16.4.3). Section R12.16.4.1 cautions the engineer in the use of end-bearing splices for
bars inclined from the vertical. End-bearing splices for compression bars have been used
almost exclusively in columns and the intent is to limit use to essentially vertical bars
because of the field difficulty of getting adequate end bearing on horizontal bars or bars
significantly inclined from the vertical. Mechanical or welded splices are also permitted for
compression splices and must meet the requirements of 12.14.3.2 or 12.14.3.4, respectively.
Column Splices
Lap splices, butt-welded splices, mechanical connections, or end-bearing splices may be used
in columns, with certain restrictions. Reinforcing bars in columns may be subjected to
compression or tension, or, for different load combinations, both tension and compression.
Accordingly, column splices must conform in some cases to the requirements for
compression splices only or tension splices only or to requirements for both. ACI Code 12.17
450
Reinforced Concrete II Dr. Nasr Abboushi
requires that a minimum tension capacity be provided in each face of all columns, even
where analysis indicates compression only. Ordinary compressive lap splices provide
sufficient tensile resistance, but end-bearing splices may require additional bars for tension,
unless the splices are staggered.
Type of lap splice to be used will depend on the bar stress at the splice location, compression
or tension, and magnitude if tension, due to all factored load combinations considered in the
design of the column. Type of lap splice to be used will be governed by the load combination
producing the greatest amount of tension in the bars being spliced. The design requirements
for lap splices in column bars can be illustrated by a typical column load-moment strength
interaction as shown.
Bar stress at various locations along the strength interaction curve define segments of the
strength curve where the different types of lap splices may be used. For factored load
combinations along the strength curve, bar stress can be readily calculated to determine
type of lap splice required. However, a design dilemma exists for load combinations that do
not fall exactly on the strength curve (below the strength curve) as there is no simple exact
method to calculate bar stress for this condition.
A seemingly rational approach is to consider factored load combinations below the strength
curve as producing bar stress of the same type, compression or tension, and of the same
approximate magnitude as that produced along the segment of the strength curve
intersected by radial lines (lines of equal eccentricity) through the load combination point.
451
Reinforced Concrete II Dr. Nasr Abboushi
This assumption becomes more exact as the factored load combinations being investigated
fall nearer to the actual strength interaction curve of the column. Using this approach, zones
of “bar stress” can be established as shown in the previous figure.
For factored load combinations in Zone 1, all column bars are considered to be in
compression. For load combinations in Zone 2 of the figure, bar stress on the tension face of
the column is considered to vary from zero to in tension. For load combinations in
Zone 3, bar stress on the tension face is considered to be greater than in tension. Type
of lap splice to be used will then depend on which zone, or zones, all factored load
combinations considered in the design of the column are located. The designer need only
locate the factored load combinations on the load-moment strength diagram for the column
and bars selected in the design to determine type of lap splice required. Use of load-moment
design charts in this manner will greatly facilitate the design of column bar splices. For
example, if factored gravity load combination governed design of the column, say Point A in
the figure above, where all bars are in compression, but a load combination including wind,
say Point B, produces some tension in the bars, the lap splice must be designed for a Zone 2
condition (bar stress is tensile but does not exceed in tension).
The design requirements for lap splices in columns are summarized in the Table below. Note
that the compression lap splice permitted when all bars are in compression (see 12.17.2.1)
considers a compression lap length adequate as a minimum tensile strength requirement.
For lap splices, where the bar stress due to factored loads is compression, column lap splices
must conform to the requirements presented in the previous section for compression
splices. Where the stress is tension and does not exceed , lap splices must be Class B if
more than one-half the bars are spliced at any section, or Class A if one-half or fewer are
spliced and alternate lap splices are staggered by . If the stress is tension and exceeds
then lap splices must be Class B, according to ACI Code.
If lateral ties are used throughout the splice length having an area of at least in
both directions, where is the spacing of ties and is the overall thickness of the
member, the required splice length may be multiplied by but must not be less than
452
Reinforced Concrete II Dr. Nasr Abboushi
. If spiral reinforcement confines the splice, the length required may be multiplied
by but again must not be less than .
End-bearing splices, as described above, may be used for column bars stressed in
compression, if the splices are staggered or additional bars are provided at splice locations.
The continuing bars in each face must have a tensile strength of not less than times
the area of reinforcement in that face.
As mentioned in before, column splices are commonly made just above a floor. However, for
frames subjected to lateral loads, a better location is within the center half of the column
height, where the moments due to lateral loads are much lower than at floor level. Such
placement is mandatory for columns in "special moment frames" designed for seismic loads.
Example
Compute the minimum lap length of the reinforcement at the retaining wall joints shown
below.
Take .
Solution:
@ 𝑐𝑚 𝑐 𝑐
Clear cover
(a) , and
(b) half the center-to-center spacing
𝑙𝑠
of the bars;
Thus, .
( ) ( ) ( )
454
Reinforced Concrete II Dr. Nasr Abboushi
Example
An axially loaded reinforced concrete column of dimension with six bars of
is intended to lapped at a floor level. Determine the lap length of the reinforcement.
Take .
Ties @
Solution:
𝑙𝑠
√ RC Slab
√
𝑚𝑚
𝑚𝑚
In the 300 mm direction:
Take
455
Reinforced Concrete II Dr. Nasr Abboushi
Example
Design the tension lap splices for the grade beam shown below.
Take .
Dimensions of the Beam section .
bars top and bottom (continuous).
Stirrups @ (entire span)
Bending moments @ @
IMPORTANT: Preferably, splices should be located away from zones of high tension. For a typical
grade beam, top bars should be spliced under the columns, and bottom bars about midway between
columns. Even though in this example the splice at A is not a preferred location, the moment at A is
relatively small. Assume for illustration that the splices must be located as shown.
Solution:
(c) , and
(d) half the center-to-center spacing of the bars; ( )
Thus, .
456
Reinforced Concrete II Dr. Nasr Abboushi
√ ( )
Lap Splice of Bottom Reinforcement at Section B
( ) ( ) ( )
( ) ( )
( √ ) ( √ )
( @ )
( )
Note: Even if lap splices were staggered ( ), a Class B splice must be used
with ( )
Class B Splice
It is better practice to stagger alternate lap splices. As a result, the clear spacing between
spliced bars will be increased with a potential reduction of development length.
Clear spacing
Center-to-center spacing of bars being developed
Distance from center of bar to concrete surface
Thus,
457
Reinforced Concrete II Dr. Nasr Abboushi
( ) ( ) ( )
√
Class B Splice
Use 1.1 m lap splice @ B and stagger alternate lap splices.
( ) ( )
( √ ) ( √ )
( @ )
( )
If alternate lap splices are staggered at least a lap length (As spliced = 50%):
Class A splice may be used
If all bars are lap spliced at the same location (within required n lap length):
Class B splice must be used
Assuming splices are staggered, the top bar multiplier will be 1.3.
Class A splice
Use 1.1 m lap splice @ A also, and stagger alternate lap splices.
458
Reinforced Concrete II Dr. Nasr Abboushi
Example
Design the lap splice for the tied column detail shown.
Continuing bars from column above ( )
Offset bars from column below ( )
Take .
Dimensions of the column section
.
bars (above and below floor level)
Ties @
Solution:
1. Determine type of lap splice required.
Type of lap splice to be used depends on the bar stress at
the splice location due to all factored load combinations
considered in the design of the column. For design
purposes, type of lap splice will be based on which zone, or
459
Reinforced Concrete II Dr. Nasr Abboushi
zones, of bar stress all factored load combinations are located on the column load-moment
strength diagram. The load-moment strength diagram (column design chart) for the
column with bars is shown above, with the three factored load
combinations considered in the design of the column located on the interaction strength
diagram.
Note that load combination (2) governed the design of the column (selection of
bars).
For load combination (1), all bars are in compression (Zone 1), and a compression lap splice
could be used. For load combination (2), bar stress is not greater than (Zone 2), so a
Class B tension lap splice is required; or, a Class A splice may be used if alternate lap splices
are staggered. For load combination (3), bar stress is greater than (Zone 3), and a Class
B splice must be used.
Lap splice required for the bars must be based on the load combination producing
the greatest amount of tension in the bars; for this example, load combination (3) governs
the type of lap splice to be used.
√ ( )
( ) ( ) ( )
√
Class B splice
Use lap splice for the bars at the floor level indicated.
461