Electrical Distribution
Solutions
Ground fault monitoring
on an ungrounded,
three-wire circuit
operating properly, plant personnel were
The problem concerned that the high voltages to ground
would cause insulation failures and catastrophic
In this issue, A US-based automotive manufacturer was in the electrical faults.
start-up phase of a new production plant. The
we discuss
electrical system serving the new equipment was This issue of PowerLogic Solutions describes
ground fault a 480 V three-wire, ungrounded (delta) circuit. ground fault monitoring and neutral instability,
monitoring All of the new production equipment - air and recommends a way to measure ground
with the compressors, motors, conveyors, lights - was faults on ungrounded systems with the
operating fine. During final commissioning PowerLogic Circuit Monitor from Square D
PowerLogic of the electrical system, however, electricians Company.
Circuit measured unusual voltages.
Monitor The PowerLogic Circuit Monitor is designed to
Their readings showed that phase-to-phase perform metering functions; it is not a protective
voltages were about 480 V on all three phases. relay designed to provide circuit protection. Think
Phase-to-ground readings, however, measured of the circuit monitor as device used for ground
130 V, 550 V, and 690 V on the three conductors fault detection, not protection. Alarm/relay
(normal voltages to ground on a 480 V functions are included with the Circuit Monitor
ungrounded system are approximately 277 V). to provide alarm annunciation and, in cases like
Detection devices at the main switchgear this application, to be used in conjunction with
showed there was a ground fault (see sidebar on existing ground fault protection systems.
page 4) somewhere in the new plant, but an
exhaustive investigation proved fruitless.
Electricians added to the puzzle by discovering Key concepts and Terms
that the strange phase-to-ground voltage
readings returned to normal when the ground Neutral Instability
fault detection system was removed from Neutral instability, a form of ferroresonance,
service. Even though plant equipment was is a rare problem. It occurs on three-phase
ungrounded circuits that are equipped with
ground fault monitoring through voltage
transformers (VTs, previously called potential
transformers, or PTs) connected phas
to ground. The term itself seems to be
a misnomer because a three-phase, three-wire
circuit has no neutral conductor. Neutral in
neutral instability refers to the single imaginary
point in a delta (three-phase, three-wire) circuit
at which all three phases measure equal
voltages. This point in a delta circuit is typically
at ground potential, except during a ground fault
or neutral instability (see figure 2).
Imaginary Imaginary
Neutral Point Neutral Point
A
Imaginary
Neutral Point
C
From-To Normal Ground Fault Neutral Instability
A–B 480 480 480
B–C 480 480 480
C– A 480 480 480
Figure 2: Typical voltage readings from an ungrounded circuit under normal, ground fault, and neutral instability conditions.
The solution
Ground Fault Monitoring with the Transformers and resistors must be properly
Circuit Monitor sized to ensure metering accuracy and neutral
stability.
As stated earlier, the Circuit Monitor accurately
meters electricity parameters, but should not be
Circuit Monitors should be configured for
used to replace overcurrent devices or ground
system 40, as if monitoring a four-wire circuit.
fault protection systems. However, the Circuit
Line-to-ground readings will actually be
Monitor can be used to monitor and alarm when
represented as line-to-neutral values. Since line-
ground faults occur.
to-ground voltages drop to zero on the grounded
Ground fault monitoring can be accomplished as
phase and increase to line-to-line values on the
shown in figure 3. The resistors in the circuit
ungrounded phases, over- or undervoltage
serve to stabilize the voltage transformers
triggers. Circuit Monitor alarms can easily be set
connected to ground and eliminate the VTs
to indicate ground fault conditions.
as a source of neutral instability.
The resistors in figure 4 can be off-the-shelf
heating elements, sized to meet the
requirements. The resistors provide damping
load to reduce the adverse effects of neutral
instability. To ensure metering accuracy, the
voltage transformers should be instrument
transformers, not control power transformers.
Control power transformers can introduce 5%
metering error, plus several degrees of phase
shift.
Ungrounded Source
Voltage
Transformers
R CM-2000
Va
R Vb
Vc
Vn
R = Resistors
IG
IG (small) IG (large)
{
{
Figure 4: Ungrounded systems are used because inadvertent ground faults do not trip
overcurrent devices and shut down critical processes.
ENMED199035EN
Schneider Electric Centre Merlin Gerin This paper was originally published as a part of the series PowerLogic This document has been
F - 38050 Grenoble cedex Solutions, copyright Square D Company 1998. Used with permission. printed on ecological paper.
Industries SA
France
Tel.: +33 (0)4 76 57 60 60 Published by: Schneider Electric SA
Fax: +33 (0)4 76 57 73 62 Design and layout by: Insign’
http://www.schneiderelectric.com Printed by:
service-commc4@mail.schneider.fr
ART.28268 09/1999