1 2 3 4 5 6 7 8 CAPACIDAD
CALIBRE NUMERO ÁREA DIÁMETRO ESPESOR DIÁMETRO ÁREA RESISTENCIA DE CORRIENTE CAIDA DE TENSIÓN
AWG ó MCM HILOS (mm2) CONDUCTOR AISLAMIENTO CON CON DC A 20 ºc TW (60 ºC) THW (75 ºC) XHHW (90 ºC)
rIL
(mm) (mm) AISLAMIENTO AISLAMIENTO Ohm/Km Nota 1 Nota 2 Nota 1 Nota 2 Nota 1 Nota 2 E
(mm) (mm2) A A A A A A
1000
14 1 2.08 1.63 0.76 3.23 8.19 8.29 25 20 30 20 r = valor columna 8
12 1 3.31 2.05 0.76 3.65 10.46 5.21 30 25 35 25 I = Corriente del Circuito
10 1 5.26 2.59 0.76 4.19 13.79 3.28 40 30 50 35
8 1 8.37 3.26 1.14 5.64 24.98 2.06 60 40 70 50 L= Longitud del circuito,
6 1 13.3 4.12 1.52 7.29 41.74 1.3 80 55 95 65 Cuando es monofásico se
4 1 21.15 5.19 1.52 8.36 54.89 0.815 105 70 125 85 toma L = 2 x distancia
14 7 2.08 1.79 0.76 3.39 9.03 8.45 25 20 30 20 35 25
12 7 3.31 2.25 0.76 3.85 11.64 5.31 30 25 35 25 40 30 ∆E Permitido: 3% - 5%
10 7 5.26 2.85 0.76 4.45 15.55 3.34 40 30 50 35 55 40
8 7 8.37 3.59 1.14 5.97 27.99 2.1 60 40 70 50 80 55
6 7 13.3 4.52 1.52 7.69 46.45 1.32 80 55 95 65 105 75
4 7 21.15 5.71 1.52 8.88 61.93 0.831 105 70 125 85 140 95
2 7 33.63 7.2 1.52 10.37 84.46 0.523 140 95 170 115 190 130
1 19 42.41 7.9 2.03 12.08 114.61 0.415 165 110 195 130 220 150
NTC2050 310-16
3/0 19 85.03 11.19 2.03 15.37 185.54 0.207 260 165 310 200 350 225 TW THW
AMBIENTE (ºC)
4/0 19 107.2 12.56 2.03 16.75 220.35 0.164 300 195 360 230 405 260
21 - 25 1,08 1,05
250 37 126.7 14.18 2.41 19.15 288.02 0.139 340 215 405 255 455 290 26 - 30 1,00 1,00
300 37 152 15.52 2.41 20.49 329.74 0.116 375 240 455 285 505 320 31 - 35 0,91 0,94
350 37 177.3 16.78 2.41 21.75 371.54 0.0992 420 260 505 310 570 350 36 - 40 0,82 0,88
41 - 45 0,71 0,82
400 37 202.7 17.94 2.41 22.91 412.23 0.0868 455 280 545 335 615 380 46 - 50 0,58 0,75
500 37 253.4 20.04 2.41 25.01 491.27 0.0694 515 320 620 380 700 430 51 - 55 0,41 0,67
600 61 304 22 2.79 27.75 604.81 0.0578 575 355 690 420 780 475 56 - 60 0,58
700 61 354.7 23.75 2.79 29.50 683.49 0.0496 630 385 755 460 855 520
750 61 380 24.59 2.79 30.35 723.45 0.0463 655 400 785 475 885 535
FACTOR DE CORRECCIÓN POR
Instructor:
Orlando Castañeda Alvarez
orcastan@misena.edu.co
AREA EFECTIVA DE LOS DUCTOS EN PVC PARA EL CALCULO DE CONDUCTORES POR DUCTO
Instructor:
ORLANDO CASTAÑEDA ALVAREZ
orcastan@misena.edu.co