2 EXTINGUISHER AGENT HFC-227ea 3 DESIGN CONCENTRATION 0.07 4 FLOODING FACTOR 0.5483 Kg/m3 5 DESIGN TEMP 21 C 6 MAX EXPECTED TEMP 35 C 7 AVE CIL PRESSURE 25 BAR @ 21C 8 TYPE OF FIRE HAZARD ELECTRICL 9 TYPE OF APPLICATION TOTAL FLOODING 10 MAXIMUM DISCHARGE TIME 10 SEC DESIGN DATA TABULATION ENCLOUSURE INFORMATION TYPE ROOM VOID CELING VOID FLOOR VOID WIDTH 20 7.18 7.18 ;ENGTH 8.98 8.98 8.98 HIGHT 2.75 0.8 0.45 NON-PERMABLE VOLUME 5.03 1.46 0.83 TOTAL VOLUME 488.87 50.12112 28.18438 CALCULATION RESULT MIN AGENT REQUIRED 310.98 TOTAL AGENT REQUIRED 342.078 754.15200036 TOTAL DISCHARGE TIME 10 SEC CYLINDER CAPACITY 1000
SCHEDULE OF FOUNDATION SIZE & FLOOR LOADS
CYILINDER CYILINDER CYILINDER CYILINDER CAPACITY DIAMETER HEIGHT HEIGHT 60 Ib 237 mm 711.2 mm 375x375x100 100 Ib 237 mm 984.3 mm 375x375x100 150 Ib 508 mm 600.1 mm 600x600x100 215 Ib 508 mm 733.3 mm 600x600x100 375 Ib 508 mm 1079.5 mm 600x600x100 650 Ib 610 mm 1286 mm 700x700x100 1000 Ib 610 mm 1778 mm 700x700x100